ÒZNRâÓ Arrester Blocks (Type S)
ÒZNRâÓ Arrester Blocks
Type:
S
ZNR Arrester Block is mounted in the lightning arresters
or the lightning protection devices in high voltage power
distribution and protects the power distribution apparatus
from lightning or switching surges.
ZNR Arrester Block is a high voltage block improved
in its material and manufacturing process to secure
the long term stability.
n Recommended Application
n Features
l Lightning arrester
l Lightning arrester in power apparatus (transformers,
primary cutout switches, insulators, disconnectors,
switches)
l Simplified lightning arrester
l No series gap is required because of the excellent
voltage-current characteristics
l Low clamping voltage and excellent protection level
l Fast response to the fast steep transient voltage
l No follow current
l Large withstanding surge current capability
Note: Contact our sales office or factory for “Precautions
for Handling of the Type S”
n Explanation of Part Numbers
E
R
Z
S
K
n Application Notes (Type S)
1) ZNR arrester blocks shall be kept in dry air after
the package open.
2) ZNR arrester blocks shall be handled with care
because mechanical shock such as dropping or
crashing each other may cause chipping or cracking.
3) Sweat on the side surface of ZNR arrester block
degrades its characteristic, and therefore handling
with bare hand shall not be allowed.
4) Electrical contact to ZNR arrester block shall be
done by pressing the external metal electrode.
5) ZNR arrester block shall be kept dry in the lightning
arrester or device housing.
6) If you have any questions on its application, please
contact and ask our office.
ÒZNRâÓ Arrester Blocks (Type S)
Series B, Type S
n Ratings and Characteristics
l Operating Temperature Range: Ð25 to 70 ûC
l Storage Temperature Range: Ð25 to 100 ûC
l Temperature Coefficient of Varistor Voltage: 0 to Ð0.05 %/ûC
Characteristics
Application
ERZB28SK602
ERZB32SK602
ERZB40SK602
Class 2.5 kA Lightning Arrester Class 2.5 kA Lightning Arrester Class 5 kA Lightning Arrester
Maximum Continuous Operating Voltage
AC 3 kV
AC 3 kV
AC 3 kV
Applied Voltage Ratio]
80 %
80 %
80 %
Varistor Voltage V1 mA (DC)
6 kV±10 %
6 kV±10 %
6 kV±10 %
Clamping Voltage
V2.5 kA: 12 kV max.
V2.5 kA: 12 kV max.
V5 kA: 12 kV max.
Short Duration (4/10 µs)
Maximum
Peak Current
Standard Test Long Duration (2 ms)
10 kA
10 kA
20 kA
75 A
150 A
250 A
Maximum Peak Current Special Test (4/10 µs)
20 kA
50 kA
65 kA
MCOV ´ Ã2
´ 100(%)
V1 mA
MCOV: Maximum Continuous Operating Voltage (RMS)
l Varistor voltage other than 6 kV is available.
Block configuration other than culumn is available on request.
] Applied Voltage Ratio =
Maximum Peak Current Special Test (4/10 µs)
n Dimensions in mm (not to scale)
Part No.
D
T
ERZB28SK602 29±1 31±1
ERZB32SK602 33±1 31±1
ERZB40SK602 40±1 31±1
很抱歉,暂时无法提供与“ERZB32SK602F”相匹配的价格&库存,您可以联系我们找货