Pipe-mountable Liquid Level Detection Fiber
Other
Products
FT-Z8Y
Chemical-resistant
FD-F4/F9
FD-F8Y
EX-F1
Liquid Leak / Liquid Level Sensing
SENSORS FOR
SEMICONDUCTOR INDUSTRY
FD-F4/F9
Reliable liquid level
detection from outside
the pipe
Widely applicable FD-F41/F91 released
Easily mountable and adjustable
Durable up to 100 C 212 F
FD-F41/F91 can reliably detect the
liquid level inside a pipe made of, not
only, PVC, but also, acrylic or glass.
The range of applicable pipes has
been increased by this addition to
FD-F4/F9 (for 1 mm 0.039 in thick PFA
pipe).
Just attach it on a pipe with the tying
bands. The position can be easily
changed with the release lever even
after mounting, so that there is no
need to cut tying bands.
FD-F4 /F9 can operate under an
ambient temperature of 40 to 100 C
40 to 212 F. Hence, even hot
liquids can be safely detected.
Release lever
Position
adjustable
Applicable pipe "6 to "26 mm "0.236 to "1.024 in
Compact body
FD-F4/F9 can be mounted on a
wide range of pipe diameters from "6
to "26 mm "0.236 to "1.024 in.
The body is just 13 mm 0.512 in thick
so that multi-level detection by
adjacent mounting at 13 mm 0.512 in
pitch is possible.
5 m 16.404 ft fiber cable length type is available
FD-F9 is attached with a 5 m 16.404 ft
long fiber cable. Hence, even if it is
used in an explosive area, the amplifier
can be installed outside the explosive
area.
Principle of detection
When the pipe is empty, the beam is
reflected from the inner surface of the pipe
wall and returns to the beam-receiving
part, since the difference in the refractive
indexes of the pipe and air is large.
When there is liquid in the pipe, the beam
enters the liquid through the wall and does
not return to the beam-receiving part,
since the difference in the refractive
indexes of the pipe and the liquid is small.
The beam reflected from
the inner surface of the
pipe wall returns to the
beam-receiving part.
612
The beam passes
through the wall
into the liquid.
Ramco Innovations - 1207 Maple Street, West Des Moines IA USA 50265 - 800-280-6933 - www.ramcoinnovations.com
APPLICATIONS
Detecting liquid level in a tank
SENSORS FOR
SEMICONDUCTOR INDUSTRY
FD-F4/F9
Liquid Leak / Liquid Level Sensing
FD-F4/F9
FD-F8Y
EX-F1
FD-F41
ORDER GUIDE
Fibers
Outer dia "6 to "26 mm
"0.236 to "1.024 in
transparent pipe
PVC, fluorine resin, polycarbonate,
acrylic, glass, wall thickness
1 to 3 mm 0.039 to 0.118 in
For PFA pipe,
wall thickness
1mm 0.039 in
Liquid (Note 1)
Fiber cable length Allowable
bending
:
radius
Free-cut
FD-F41
2m
6.562 ft
5m
16.404 ft
Model No.
Chemical-resistant
FT-Z8Y
Sensing object Applicable pipe diameter (Note 2)
FD-F91
R10 mm
R0.394 in
Outer dia "6 to "26 mm
"0.236 to "1.024 in
transparent pipe
2m
6.562 ft
FD-F4
PFA (fluorine resin) or equivalently
transparent pipe, wall thickness
1 mm 0.039 in
5m
16.404 ft
FD-F9
Other
Products
Appearance
Standard
Type
Notes: 1) Unclear or highly viscous liquid may not be detected stably.
Notes: 2) Liquid in an opaque pipe cannot be detected correctly.
Amplifiers
Appearance
Model No.
Emitting
element
Output
FX-301
NPN open-collector transistor
FX-301P
PNP open-collector transistor
FX-302
NPN open-collector transistor
FX-302P
PNP open-collector transistor
High-functional
digital
Digital
Type
Quick-connection cable is not supplied with the amplifier. Please order it separately.
High speed
digital
NPN open-collector transistor
FX-303P
PNP open-collector transistor
Manually set
Red LED
FX-303
FX-311
NPN open-collector transistor
FX-311P
PNP open-collector transistor
Ramco Innovations - 1207 Maple Street, West Des Moines IA USA 50265 - 800-280-6933 - www.ramcoinnovations.com
613
SENSORS FOR
SEMICONDUCTOR INDUSTRY
FD-F4/F9
ORDER GUIDE
Quick-connection cables Quick-connection cable is not supplied with the amplifier. Please order it separately.
Main cable
Main cable
Sub cable
Model No.
Description
CN-73-C1
Length: 1 m
3.281 ft
CN-73-C2
Length: 2 m
6.562 ft
CN-73-C5
Length: 5 m
16.404 ft
CN-71-C1
Length: 1 m
3.281 ft
CN-71-C2
Length: 2 m
6.562 ft
CN-71-C5
Length: 5 m
16.404 ft
End plates
• CN-73-C1
• CN-73-C2
• CN-73-C5
0.15 mm2 3-core cabtyre cable, with connector on one end
Cable outer diameter: "3.0 mm "0.118 in.
Sub cable
• CN-71-C1
• CN-71-C2
• CN-71-C5
0.15 mm2 1-core cabtyre cable, with connector on one end
Cable outer diameter: "3.0 mm "0.118 in.
End plates are not supplied with the amplifier. Please order it separately when the amplifiers are mounted in cascade.
Appearance
Other
Products
FT-Z8Y
Chemical-resistant
FD-F4/F9
FD-F8Y
EX-F1
Liquid Leak / Liquid Level Sensing
Type
Model No.
MS-DIN-E
Description
When cascading multiple amplifiers, or when it moves
depending on the way it is installed on a DIN rail, these end
plates ensure that all amplifiers are mounted together in a
secure and fully connected manner.
Two pcs. per set
Accessories
• FX-CT2
(Fiber cutter)
614
• MS-DIN-2
(Amplifier mounting bracket)
• FX-AT4
("1 mm "0.039 in fiber attachment)
Ramco Innovations - 1207 Maple Street, West Des Moines IA USA 50265 - 800-280-6933 - www.ramcoinnovations.com
SPECIFICATIONS
Refer to p.77/p.119/p.138/p.166 for amplifier specifications.
Fibers
For PFA pipe, wall thickness 1 mm 0.039 in
FD-F41
Model No.
FD-F91
Applicable amplifiers
FD-F4
FD-F9
FX-301(P), FX-302(P), FX-303(P), FX-311(P)
Sensing object
Liquid (Note 1)
Outer dia "6 to "26 mm "0.236 to "1.024 in transparent pipe Outer dia "6 to "26 mm "0.236 to "1.024 in transparent pipe
Applicable pipe diameter (Note 2)
(PVC, fluorine resin, polycarbonate, acrylic, glass, wall thickness 1 to 3 mm 0.039 to 0.118 in) [PFA (fluorine resin) or equivalently transparent pipe, wall thickness 1 mm 0.039 in]
Repeatability
1 mm 0.039 in or less (for water)
Allowable bending radius
R10 mm R0.394 in or more
Fiber cable length
2 m 6.562 ft free-cut
5 m 16.404 ft free-cut
2 m 6.562 ft free-cut
5 m 16.404 ft free-cut
40 to100 C 40 to212 F (No dew condensation or icing allowed), Storage:40 to100 C 40 to212 F
Ambient temperature (Note 3)
Ambient humidity
35 to 85 % RH, Storage: 35 to 85 % RH
Material
Fiber head: Polyetherimide, Fiber core: Acrylic, Fiber sheath: Polypropylene, Tying band: Nylon, Anti-slip tube: Silicone
Weight
6 g approx.
11 g approx.
6 g approx.
11 g approx.
Chemical-resistant
FT-Z8Y
Tying band: 4 pcs. Anti-slip tube: 2 pcs. FX-CT2 (Fiber cutter): 1 pc.
FX-AT4 ("1 mm "0.0.39 in fiber attachment): 1set (Note 4)
Accessories
Notes: 1) Unclear or highly viscous liquid may not be detected stably.
Notes: 2) Liquid in an opaque pipe cannot be detected correctly.
Notes: 3) Liquid being detected should also be kept within the rated ambient temperature range.
Notes: 4) Fiber attachments provided include FX-AT4, made for the FX-301/302/303/311 series, and conventional amplifier attachments.
PRECAUTIONS FOR PROPER USE
Refer to p.1135l for general precautions and p.90/p.121/p.141/p.168l for amplifier precautions.
This product is not a safety sensor. Its use is not
intended or designed to protect life and prevent body
injury or property damage from dangerous parts of
machinery. It is a normal object detection sensor.
Mounting
• Mount the fiber on a pipe with the attached tying bands
and anti-slip tubes as shown in the figure below.
Make sure that the release lever is retracted (position as
shown in the figure) before mounting.
Fasten two tying bands, as shown, and cut off the excess
portions.
Position adjustment
• In case of mounting on the pipe with tying bands, the fiber
position can be easily adjusted.
Adjustment
Release lever
1 Unlock the release lever (in the
direction of the arrow).
Loosen
2 Press the movable center holders
forward to loosen the tying bands
and adjust the position.
Position
adjustable
Press
3 Lock the release lever to its
original place.
Anti-slip tube
Upper side
Release lever
Tying band
Lower side
Release lever
2-"3.2 mm 0.126 in mounting holes
• If other tying bands are to be used, the dimension @
shown in the figure below should be 2.5 mm 0.098 in or
less.
Notes: 1) Whenever the mounting position is changed, adjust the sensitivity
again.
Notes: 2) The lever mechanism must be used only to adjust the position, and
not for tightening the tying bands. If tying bands are tightened while
the lever is open, and then the lever is locked, the fiber may be
damaged.
@
• In case of mounting using the two mounting holes, use M3
screws, plain washers, and spring washers.
The tightening torque should be 0.5 N m or less.
Please arrange the M3 screws, plain washers, and
spring washers separately.
(
Liquid Leak / Liquid Level Sensing
FD-F4/F9
FD-F8Y
EX-F1
Item
Standard
2 m 6.562 ft fiber cable length 5 m 16.404 ft fiber cable length 2 m 6.562 ft fiber cable length 5 m 16.404 ft fiber cable length
)
Ramco Innovations - 1207 Maple Street, West Des Moines IA USA 50265 - 800-280-6933 - www.ramcoinnovations.com
615
Other
Products
Type
SENSORS FOR
SEMICONDUCTOR INDUSTRY
FD-F4/F9
SENSORS FOR
SEMICONDUCTOR INDUSTRY
FD-F4/F9
FD-F8Y
EX-F1
Liquid Leak / Liquid Level Sensing
FD-F4/F9
PRECAUTIONS FOR PROPER USE
Refer to p.1135l for general precautions and p.90/p.121/p.141/p.168l for amplifier precautions.
Fiber attachment (FX-AT4)
• When the beam-emitting and beam-receiving fibers are
inserted into the fiber sensor amplifier (FX-301/302/303/311
series etc.), the enclosed fiber attachment for
FX-301/302/303/311 series facilitates insertion of the fibers
and reduces the possibility of incorrect fiber insertion.
For conventional amplifier
1 Thread the fiber cable through the gland and holder
separately, and screw the gland into the holder
clockwise.
Screw it clockwise
Cautions
• Take care that fiber attachment for
FX-301/302/303/311 series cannot be
used with fiber sensor amplifiers having
a pitch, between the beam-emitting and
the beam-receiving fibers, other than
7 mm 0.276 in. In case of fiber sensor
amplifiers having a pitch other than
7 mm 0.276 in, please use attachments
for conventional amplifier.
7.0 mm
0.276 in
2 Insert the fiber cables one by one into the holes for
"1.0 mm "0.039 in or "1.3 mm "0.051 in fiber cable
of the fiber cutter (FX-CT2) from the direction shown in
the figure below.
(
At this time, insert the attachment to a position at
which it stops. The fiber cables will be cut at a
position approx. 0.5 mm 0.020 in from the holder.
(
Mounting of fiber attachments
For FX-301/302/303/311 series
Other
Products
FT-Z8Y
Chemical-resistant
1 Mount the holders on the gland lightly
Holder
For "1.0 mm "0.039 in or
"1.3 mm "0.051 in fiber cables
Gland
Note: If both long holders and short holders are enclosed with the fiber, use
the short holders.
2 Insert the fiber cables into the holders, in condition 1.
3 Tighten the holders to fix the fiber cables at the desired
length.
4 Insert the fiber cables, in condition 3, into the holes for
"1.0 mm "0.039 in or "1.3 mm "0.051 in fiber cables
of the fiber cutter (FX-CT2) from direction shown in the
figure below.
Holder
Gland
For "1.0 mm "0.039 in or
"1.3 mm "0.051 in fiber cables
5 Cut both fiber cables simultaneously. (At this time, insert
the attachment to a position at which it stops. The fiber
cables will be cut at a position approx. 0.5 mm 0.020 in
from the holder.)
6 After cutting, insert the fiber cables to the fiber sensor
amplifier immediately.
616
Ramco Innovations - 1207 Maple Street, West Des Moines IA USA 50265 - 800-280-6933 - www.ramcoinnovations.com
Cutting procedure
• To cut the fiber cables, insert them from the direction
shown below.
(Fiber cable insertion direction)
Free-cut fiber
without FX-AT
attachment
Free-cut fiber
with FX-AT
attachment
How to use fiber cutter (FX-CT2)
1 Slide part @ of the fiber cutter fully upward till it stops.
2 Insert the fiber cables, mounted in the attachment, till
they stop.
Take care that there are separate fiber cable insertion
holes for "2.2 mm "0.087 in and "1.0 mm "0.039 in
or "1.3 mm "0.051 in fiber cables.
3 Slide part @ of the fiber cutter down to cut the fiber cables.
Part@
For "1.0 mm "0.039 in or
"1.3 mm "0.051 in fiber cables
Notes: 1) The fiber cables should be cut in one stroke.
2) Once a fiber cable is cut off at a hole, do not use the hole again, if
used, it degrades the cut surface quality and the detectability may
deteriorate.
3) The blade cannot be replaced. Please purchase an additional fiber
cutter, if required.
4) Note that the sensing range may be reduced by up to 20 %
depending on the cut condition. Hence, decide the setting distance
by taking sufficient margin.
Others
• Liquid in a pipe which is not transparent cannot be sensed
correctly.
• Unclear or highly viscous liquid may not be sensed.
• Fit the fiber head to the pipe securely, otherwise the
operation may be erroneous.
• Take care that no dew condenses on the pipe’s sensing
surface or the pipe’s inside wall and that no bubble
attaches on the pipe’s inside wall, since it can affect the
operation.
• If a liquid drop flows down across the sensing point or an
air bubble sticks on the wall at the sensing point, the
operation may be erroneous. Make sure that no bubble
arises in the liquid, and that no dew or liquid drop is
present on either surface of the pipe wall.
• Neither FD-F4 or FD-F9 is waterproof or chemicalresistant. Installation should be avoided at any place
where it could come in direct contact with water or
chemicals.
• Do not apply excessive tensile force to the fiber cable.
• Bending radius of the fiber cable must be R10 mm
R0.394 in or more. If the bending radius is smaller than
the specified value, the sensing performance may
deteriorate.
• Do not use the fiber at places having intense vibrations, as
this can cause malfunction.
• Keep the fiber head surface intact.
If it is scratched or spoiled, the detectability will
deteriorate.
• Do not expose the fiber cable to any organic solvents.
• Ensure that any strong extraneous light is not incident on
the receiving face of the fiber head.
• Take care that the sensor is not directly exposed to
fluorescent light from a rapid-starter lamp or a high
frequency lighting device as it may affect the sensing
performance.
Ramco Innovations - 1207 Maple Street, West Des Moines IA USA 50265 - 800-280-6933 - www.ramcoinnovations.com
617
SENSORS FOR
SEMICONDUCTOR INDUSTRY
Fiber cutter
• The fiber cables should be cut off at the ends with the fiber
cutter before insertion into the amplifier.
Liquid Leak / Liquid Level Sensing
FD-F4/F9
FD-F8Y
EX-F1
Refer to p.1135l for general precautions and p.90/p.121/p.141/p.168l for amplifier precautions.
Chemical-resistant
FT-Z8Y
PRECAUTIONS FOR PROPER USE
Other
Products
FD-F4/F9
PRECAUTIONS FOR PROPER USE
Refer to p.1135l for general precautions and p.90/p.121/p.141/p.168l for amplifier precautions.
Teaching
When using in combination with the FX-301(P), the FX-302(P) and the FX-303(P)
• The threshold values can be set by either 2-level teaching or limit teaching, when the MODE indicator / TEACH
(yellow) lights up.
• This is the method of setting the threshold value by
teaching two levels, corresponding to the liquid present
and liquid absent conditions. Normally, setting is done
by this method.
Step
Description
• This is the method of setting the threshold value by teaching
only the liquid absent condition (stable incident light condition).
Step
Display
Press MODE key to light up
MODE indicator / TEACH
1 (yellow).
Press jog switch in the liquid absent condition.
If the teaching is accepted, the read incident light
intensity blinks in the display.
Display
Press MODE key to light up
MODE indicator / TEACH
1 (yellow).
Description
Liquid absent
2
Fiber
Pipe
Press jog switch in the liquid absent condition.
If the teaching is accepted, the read incident light
intensity blinks in the digital display.
3
If jog switch is turned to the ‘ ’ side, ‘
’ scrolls
(twice) the display from left to right, and the
threshold level is shifted to a
value approx. 15 % lower (higher
sensitivity) than that set at 2.
(Note 1)
Liquid absent
2
MODE indicator / TEACH (yellow) blinks.
Turn jog switch to the ‘ ’ side.
Fiber
High
Pipe
OFF
4
Threshold
value
SENSORS FOR
SEMICONDUCTOR INDUSTRY
FD-F4/F9
FD-F8Y
EX-F1
Liquid Leak / Liquid Level Sensing
FT-Z8Y
Chemical-resistant
Other
Products
FD-F4/F9
MODE indicator / TEACH (yellow) blinks.
Press jog switch in the liquid present condition.
100 %
Incident light
intensity with
liquid absent
15 %
Threshold
value
ON
Low
Liquid present
Turn to ‘’ side
3
5
If the teaching is accepted, the read incident light
intensity blinks in the digital display and the
threshold value is set at the mid-value between the
incident light intensities in the liquid present and the
4 liquid absent conditions. After this, the judgment on
the stability of sensing is displayed.
• In case stable sensing is possible: ‘
’ is
displayed. Stability indicator (green) blinks.
• In case stable sensing is not possible: ‘
’ is
displayed. Stability indicator (green) is off.
5 The threshold value is displayed.
6 ‘
7
0
’ blinks in the digital display.
The incident light intensity appears in the digital
display and the setting is complete.
After this, the judgment on whether the setting shift
amount can be shifted or not is displayed.
• In case shifting is possible: ‘
’ is displayed.
’ is displayed.
• In case shifting is not possible: ‘
6 The threshold value is displayed.
7 ‘
8
’ blinks in the digital display.
The incident light intensity appears in the digital
display and the setting is complete.
Notes: 1) The approx. 15 % amount of shift is the initial value. The amount of
shift can be changed in the PRO mode from approx. 5 to 80 %
(5 % step). Refer to ‘Fiber Sensor Guide Book’ or ‘SUNX fiber
sensor homepage’ (http://www.fiber-sensor.com) for details of the
setting method.
Notes: 2) Do not move or bend the fiber cable after the sensitivity setting.
Detection may become unstable.
Note: Do not move or bend the fiber cable after the sensitivity setting.
Detection may become unstable.
618
Ramco Innovations - 1207 Maple Street, West Des Moines IA USA 50265 - 800-280-6933 - www.ramcoinnovations.com
Step
When combining with the FX-311(P)
• Adjust the sensitivity,
: Lights up
: Lights off
observing the operation Sensing condition
MODE
Operation indicator
indicator (orange).
Light
L-ON (ON when liquid absent)
However, since the con- ( liquid )
absent D-ON (ON when liquid present)
dition for lighting up of
L-ON (ON when liquid absent)
the indicator depends on Dark
liquid
the combination of the ( present ) D-ON (ON when liquid present)
sensing condition and
selected operation for
L/D-ON, verify it from the table on the right.
• The sensitivity adjuster is a 12-turn
Pointer
potentiometer. The maximum sensitivity
is obtained by turning it fully clockwise.
• The pointer shows the present sensitivity
level.
4
6
8
Sensing method
Make sure that the
operation selection
switch is set to LON (Light-ON).
In case ‘assist Turn the sensitivity adjuster
function’ is to be fully counterclockwise.
1
used, switch the (Minimum sensitivity)
operation selection
switch in the order
of L-ON (Light-ON)
n D-ON (Dark-ON)
n L-ON (Light-ON).
Liquid absent
Fiber
2
Pipe
• This product incorporates an ‘assist
function’, which helps to easily search
the optimum sensitivity position by
blinking of the pointer.
• In order to make ‘assist function’ effective, switch the operation selection
switch in the order L-ON (Light-ON) n
D-ON (Dark-ON) n L-ON (Light-ON).
0
Sensitivity
indicator
Operation
MAX
Liquid present
3
Notes: 1) ‘Assist function’ turns off automatically once the sensitivity
adjustment has been completed.
Notes: 2) In case ‘assist function’ is not to be used, set the operation
selection switch to D-ON (Dark-ON) and wait for 2 sec., or more, to
make ‘assist function’ ineffective.
In the liquid absent condition,
slowly turn the adjuster
clockwise and find the point
@ where the sensor is
switched ON. The pointer
blinks once at the point @.
(Note 1)
In the liquid present condition,
slowly turn the adjuster further
clockwise until the sensor goes
into the ON state again. Once it
is switched on, turn the adjuster
counterclockwise a little and
find the point b where it is
switched OFF. The pointer
blinks twice at the point b.
(Note 2)
If the sensor does not go into
the ON state, MAX is the point
b.
(
4
0
MAX
ON
A
0
MAX
OFF
B
0
MAX
ON
)
Turn the adjuster towards
the point @ from the point
b slowly. The pointer starts
blinking when it approaches
the optimum sensitivity point
and blinks faster at the
optimum sensitivity point for
3 sec. This point is the
optimum sensitivity point.
(Note 2)
Optimum point
B
A
0
MAX
5 Select either L-ON (Light-ON) or D-ON (Dark-ON) according to your
application.
Notes: 1) When ‘assist function’ is not used, the pointer does not blink.
Notes: 2) When ‘assist function’ is not used, the middle point of @ and b is
regarded as the optimum sensitivity point.
Notes: 3) In order to protect the mechanism, the sensitivity adjuster idles
when over turned, which may result in a backlash of 1 to 2
divisions.
Notes: 4) Depending upon the sensing conditions, stable sensing may be
possible at a position which is slightly shifted from the optimum
sensitivity point.
Notes: 5) Do not move or bend the fiber cable after the sensitivity
adjustment. Detection may become unstable.
The CAD data in the dimensions can be downloaded from the SUNX website: http://www.sunx.co.jp/
Refer to p.102/p.127/p.143/p.170 for amplifier dimensions.
DIMENSIONS (Unit: mm in)
FD-F41 FD-F91
FD-F4 FD-F9
8
0.315
13.5
25 0.531
0.984
Free-cut
With FX-AT4
20
0.787
5
0.197
2-"3.2 "0.126 mounting holes
6 0.236
("3)("0.118) Model No. tube (PVC)
"1 "0.0392
14
0.551
14
0.551
(20)
(0.787)
2,000 78.740
(FD-F9: 5,000 196.850)
10 4 0.157
13
0.512 0.394
Ramco Innovations - 1207 Maple Street, West Des Moines IA USA 50265 - 800-280-6933 - www.ramcoinnovations.com
619
SENSORS FOR
SEMICONDUCTOR INDUSTRY
Sensitivity adjustment
Liquid Leak / Liquid Level Sensing
FD-F4/F9
FD-F8Y
EX-F1
Refer to p.1135l for general precautions and p.90/p.121/p.141/p.168l for amplifier precautions.
Chemical-resistant
FT-Z8Y
PRECAUTIONS FOR PROPER USE
Other
Products
FD-F4/F9