FP0
Programmable Controllers
ARCT1B164E
0
ZERO
Suitable for Installation
Virtually Anywhere
Actual size:
W30 × H90 × D60 (mm)
W1.181 × H3.543 × D2.362 (inch)
These materials are printed on ECF pulp.
These materials are printed with earth-friendly vegetable-based (soybean oil) ink.
Please contact ..........
Matsushita Electric Works, Ltd.
Automation Controls Business Unit
Head Office: 1048, Kadoma, Kadoma-shi, Osaka 571-8686, Japan
Telephone: +81-6-6908-1050
Facsimile: +81-6-6908-5781
http://www.nais-e.com/
I/O 10 points/14 points
Relay output,
terminal block type
(
) (
I/O 16 points
Transistor
output type
) (
I/O 32 points
Transistor
output type
)
All Rights Reserved © 2006 COPYRIGHT Matsushita Electric Works, Ltd.
Specifications are subject to change without notice.
Printed in Japan.
Excellent space-saving
design!
25 mm
105 mm
.984 inch
4.134 inch
Control unit
Expansion unit
Expansion unit
Expansion unit
Actual size
image
A terminal block type and a connector type are
available. Both can be detached for easy wiring.
● Terminal block
● Connector
● MIL connector
Terminal block type
(European type, made
by Phoenix Contact):
Installation of electric
wires having a cross
section of 0.2 to 1.25
mm2 is possible without
crimp terminals.
Connector type (made
by Molex): Ideal for
installation during mass
production.
Installation of electric
wires having a cross
section of 0.2 to 0.75
mm2 is available
Wire-press sockets are
attached to the units with
16 or 32 I/O points.
Installation of electric
wires having a cross
section of 0.2 to 0.3 mm2
is possible without
stripping the wire cover.
Available for:
FP0-C10RS, C10CRS,
C14RS, C14CRS, E8RS,
E8YRS, E16RS
Available for:
FP0-C10RM, C10CRM,
C14RM, C14CRM, E8RM,
E16RM
Available for:
FP0-C16T, C16CT, C32T,
C32CT, T32CT, E8X, E8YT,
E16X, E16YT, E16T,E32T
Wide variety of intelligent units
● Analog unit
● Thermocouple unit
Analog I/O, A/D conversion, and D/A
conversion units are available. Up to
three units can be connected,
allowing multi-channel analog
control.
Total accuracy: ± 0.8 °C (K/J/T
range). Two types are available:
4-ch/8-ch types. Up to three units
can be connected, allowing highaccuracy multi-point temperature
control of a maximum of 24
channels.
90 mm
3.543 inch
Input/Output terminals
Control unit with 14
I/O points
Control unit with 32 I/O points
+ 3 expansion units with
32 I/O points = 128 I/O points
(Maximum allowable number
of I/O points)
EEPROM is used as the program memory.
Program rewriting is possible even when running!
Tool port
Communications with the "Control FPWIN GR"
software for programming from a personal
computer is possible with only one cable.
Available for:
FP0-A21, FP0-A80, FP0-A04V, FP0-A04I
Available for:
FP0-TC4, FP0-TC8
● CC-Link slave unit
● I/O link unit
Supports CC-Link, which is an open
network. Reading/Writing of fourword data through a maximum of 16
input and 16 output points.
A link unit to enable FP0 to serve as
a slave station of MEWNET-F
(remote I/O system).
Available for:
FP0-CCLS
Available for:
FP0-IOL
● S-LINK control unit
● Power supply unit
Can be directly connected to the SLINK wire-saving system and control
up to 64 input and 64 output points.
* S-LINK is a trademark of SUNX Limited.
A power supply unit having the same
height and depth as that of FP0.
Input: 100 to 240 V AC universal.
Output: 24 V AC up to 0.7 A
Available for:
FP0-SL1
Available for:
FP0-PSA4
● Rewriting in RUN mode
Programs can be rewritten for debugging or activation
adjustments during the operation of FP0.
● No backup battery required
From 10
I/O points
EEPROM is used as the program memory. Programs and
device data can be stored without backup batteries, ensuring
safe use in mass-produced machines.
Up to 128
I/O points
The control unit width is only 25 mm .984 inch*.
Only 105 mm 4.134 inch even in combination with
expansion units having a maximum of 128 I/O points
* The width of the control unit with 32 I/O points and the S-LINK control unit is 30 mm 1.181 inch.
The control unit can fit in your pocket: W 25 × H 90 × D 60 mm W .984 ×
H 3.543 × D 2.362 inch
The number of I/O points can be expanded up to 128. Even with the
maximum expansion, the size is only W 105 × H 90 × D 60 mm W 4.134 ×
H 3.543 × D 2.362 inch. The ultra-compact body size and installation area
beyond comparison with the conventional compact PLCs facilitate the
miniaturization of target machines, equipment, and control panels.
● Three selectable installation methods
● Password protection
Program rewriting can be password-protected. Program
rewriters can be limited, enhancing maintenance reliability.
Up to three expansion units can be directly
connected without connection cables.
The expansion units can be directly connected to the control unit
with a simple operation using the expansion connector and lock
lever on the unit side. Dedicated cables or motherboards are not
necessary for expansion.
High-speed operation of 0.9 µs per basic
instruction meets the need for a quick response.
● High-speed operation
Each basic instruction can be operated in 0.9 µs. A 500-step
program can be scanned in approx. 1 ms. The highest
processing speed in this class of controller has been
achieved.
● Pulse catch function
Can read pulses as short as 50 µs. Ideal for sensor input.
● Interrupt input function
Reliable processing is available without being affected by the
scan time.
DIN rail
2
Slim type mounting
plate
Flat type mounting plate*
* Cannot be used for
Control
unit
Expansion
unit
Expansion
unit
Expansion
unit
to 3 units
(Up
can be added. )
3
Excellent space-saving
design!
25 mm
105 mm
.984 inch
4.134 inch
Control unit
Expansion unit
Expansion unit
Expansion unit
Actual size
image
A terminal block type and a connector type are
available. Both can be detached for easy wiring.
● Terminal block
● Connector
● MIL connector
Terminal block type
(European type, made
by Phoenix Contact):
Installation of electric
wires having a cross
section of 0.2 to 1.25
mm2 is possible without
crimp terminals.
Connector type (made
by Molex): Ideal for
installation during mass
production.
Installation of electric
wires having a cross
section of 0.2 to 0.75
mm2 is available
Wire-press sockets are
attached to the units with
16 or 32 I/O points.
Installation of electric
wires having a cross
section of 0.2 to 0.3 mm2
is possible without
stripping the wire cover.
Available for:
FP0-C10RS, C10CRS,
C14RS, C14CRS, E8RS,
E8YRS, E16RS
Available for:
FP0-C10RM, C10CRM,
C14RM, C14CRM, E8RM,
E16RM
Available for:
FP0-C16T, C16CT, C32T,
C32CT, T32CT, E8X, E8YT,
E16X, E16YT, E16T,E32T
Wide variety of intelligent units
● Analog unit
● Thermocouple unit
Analog I/O, A/D conversion, and D/A
conversion units are available. Up to
three units can be connected,
allowing multi-channel analog
control.
Total accuracy: ± 0.8 °C (K/J/T
range). Two types are available:
4-ch/8-ch types. Up to three units
can be connected, allowing highaccuracy multi-point temperature
control of a maximum of 24
channels.
90 mm
3.543 inch
Input/Output terminals
Control unit with 14
I/O points
Control unit with 32 I/O points
+ 3 expansion units with
32 I/O points = 128 I/O points
(Maximum allowable number
of I/O points)
EEPROM is used as the program memory.
Program rewriting is possible even when running!
Tool port
Communications with the "Control FPWIN GR"
software for programming from a personal
computer is possible with only one cable.
Available for:
FP0-A21, FP0-A80, FP0-A04V, FP0-A04I
Available for:
FP0-TC4, FP0-TC8
● CC-Link slave unit
● I/O link unit
Supports CC-Link, which is an open
network. Reading/Writing of fourword data through a maximum of 16
input and 16 output points.
A link unit to enable FP0 to serve as
a slave station of MEWNET-F
(remote I/O system).
Available for:
FP0-CCLS
Available for:
FP0-IOL
● S-LINK control unit
● Power supply unit
Can be directly connected to the SLINK wire-saving system and control
up to 64 input and 64 output points.
* S-LINK is a trademark of SUNX Limited.
A power supply unit having the same
height and depth as that of FP0.
Input: 100 to 240 V AC universal.
Output: 24 V AC up to 0.7 A
Available for:
FP0-SL1
Available for:
FP0-PSA4
● Rewriting in RUN mode
Programs can be rewritten for debugging or activation
adjustments during the operation of FP0.
● No backup battery required
From 10
I/O points
EEPROM is used as the program memory. Programs and
device data can be stored without backup batteries, ensuring
safe use in mass-produced machines.
Up to 128
I/O points
The control unit width is only 25 mm .984 inch*.
Only 105 mm 4.134 inch even in combination with
expansion units having a maximum of 128 I/O points
* The width of the control unit with 32 I/O points and the S-LINK control unit is 30 mm 1.181 inch.
The control unit can fit in your pocket: W 25 × H 90 × D 60 mm W .984 ×
H 3.543 × D 2.362 inch
The number of I/O points can be expanded up to 128. Even with the
maximum expansion, the size is only W 105 × H 90 × D 60 mm W 4.134 ×
H 3.543 × D 2.362 inch. The ultra-compact body size and installation area
beyond comparison with the conventional compact PLCs facilitate the
miniaturization of target machines, equipment, and control panels.
● Three selectable installation methods
● Password protection
Program rewriting can be password-protected. Program
rewriters can be limited, enhancing maintenance reliability.
Up to three expansion units can be directly
connected without connection cables.
The expansion units can be directly connected to the control unit
with a simple operation using the expansion connector and lock
lever on the unit side. Dedicated cables or motherboards are not
necessary for expansion.
High-speed operation of 0.9 µs per basic
instruction meets the need for a quick response.
● High-speed operation
Each basic instruction can be operated in 0.9 µs. A 500-step
program can be scanned in approx. 1 ms. The highest
processing speed in this class of controller has been
achieved.
● Pulse catch function
Can read pulses as short as 50 µs. Ideal for sensor input.
● Interrupt input function
Reliable processing is available without being affected by the
scan time.
DIN rail
2
Slim type mounting
plate
Flat type mounting plate*
* Cannot be used for
Control
unit
Expansion
unit
Expansion
unit
Expansion
unit
to 3 units
(Up
can be added. )
3
FP0 Features
FP0
Equipped with 2-axis independent positioning, high-speed counter and
PWM output
Can be directly connected to the S-LINK wire-saving system (SUNX Ltd.).
● Pulse output function (For transistor output type only)
● High-speed counter function
The FP0 comes equipped with 2 channels of pulse output up to
10 kHz (5 kHz during 2-channel output). Since these two
channels can be separately controlled, the FP0 is also suitable
for 2-axis independent positioning. Setting for automatic
trapezoid control, automatic return to home position and JOG
operation are very easy, by using special instructions.
The high-speed counter is prepared for 4
channels in single phase, and 2 channels
in 2-phase. In single phase, the 4-channel
total is 10 kHz, and in 2-phase the 2channel total is 2 kHz total speed, making
the unit suitable for inverter control, and
so forth.
Feeder roller
Y0
Y2
Y1
Y3
FP0
S-LINK Control unit
W30 × H90 × D60
W1.181 × H3.543 × D2.362
Cutter
Pulse output
Motor
driver 1
cw/ccw
Stepping motor
Servo motor
Pulse output
Inverter
cw/ccw
(300 m sec)
(300 m sec)
● High speed
(7 kHz)
R0
F0
MV
H102, DT0
Control code
F0
MV
K500, DT1
Initial speed (500 Hz)
F0
MV
K7000, DT2
F0
MV
K300, DT3
F1
DMV K300000, DT4
F0
MV
F168 SPD1
● Initial speed
(500 Hz)
High speed (7 kHz)
Deceleration/Acceleration time (300 m sec)
START/
STOP signal
Encoder
Stepping motor
Servo motor
Motor
driver 2
Cutter blade
control signal
Input encoder
output into the
high-speed counter
T-branch multi
drop wiring
(For transistor output type only)
Its PWM output (Pulse Width Modulation
output) function makes it possible to
provide temperature control with a single
compact FP0 unit.
● When pulse width values are increased...
● Output pulse count
(300,000)
Output pulse count (300,000)
Pulse output starts from Y0
2 signal wires
2 power
supply wires
● PWM output function
Heater power up
K0, DT6
DT0, K0
Maximum length: 200 m 656.168 ft.
Max. 128 points
Lead wire and
tape
Motor
Position control is a breeze with the auto trapezoid control
instruction F168!
● Acceleration time ● Acceleration time
DF
The FP0 S-Link control unit makes sensor wiring and control panel simple by using easy T-shape connectability and
4-wire cable. It can control up to 128 input/output of S-Link I/O devices. Adding up to three FP0 Expansion units you
can have flexible I/O configuration capability.
● When reduced...
● Simply set the values
for each point
Surveillance possible of FP0 operation status from a Web browser using
FP Web-Server Unit
Connecting an FP0 to the FP Web-Server unit
with an RS232C cable and then setting up using
the dedicated software (FP Web Configurator
Tool) makes surveillance possible of the FP0
running conditions from a PC Web browser.
Ethernet
Heater power down
FP Web-Server
Unit
RS232C port enables serial communications. (Product No. C10CR, C14CR, C16CT, C32CT, T32CT, SL1)
The RS232C port allows the direct connection to
computers and operation display panels. Also, bidirectional data communication with bar-code readers and
other RS232C devices is made easy.
FP0
● For connecting to computers and operation
display panels
* The port block is connected by three S.R.G. terminals. Operation display panels can also be
connected using the tool port.
* RS232C port is equipped on the control units for both relay types and transistor output types.
Host computer
(Personal computer)
Operation
display panel
By using C-NET, you can use multiple FP0s as data collection terminals.
● For data communication with RS232C devices
FP0
RS-232C
POWER
COM COM D2
READY
MODE
A
FLASH
D1
D4
D3
D6
D5
D8
D9
D7 READY
MICRO-IMAGECHECKER
KEY PAD
B
M100
C
Matsuhita Electronic Works, Ltd.
CAMERA
MONITOR
24VDC
START ACK IN1
IN3
IN5
COM COM IN2 IN4
COM
Image checker
Bar-code reader
Serial printer
Wide variety of analog units available
● PCWAY
Pressure
sensor
Inverter
RUN
MODE
PROG
1
2
3
4
5
ERROR
ALARM
RUN
OFF ON
PROG.
V0
I 0
IN COM
V1
I 1
V
Laser analog
sensor
OUT
I
COM
FP0 - A21
Even with compact body, the following analog units are
available.
FP0-A21 (AFP0480)
: 2 input, 1 output
FP0-A80 (AFP0401)
: 8 input
FP0-A04V (AFP04121) : Voltage 4 output
FP0-A04I (AFP04123) : Current 4 output
FP0-TC4 (AFP0420)
: Thermocouple 4 input
FP0-TC8 (AFP0421)
: Thermocouple 8 input
By using the C-NET network and exclusive adapters, you
can connect multiple FP0s by multi-drop connection with 2wire cables. You can use computers for distributed control or
have network terminals for a centralized management
system.
Potentio meter
The Excel add-in software ìPCWAYî is
available for data collection of the
networked PLCs. PLC status and data
registers value can be simply shown
and managed on Excel worksheets,
which also makes it possible to
transmit Email when malfunctions
occur or to make status inquiries.
PCWAY
C-NET
adapter
to 200 V AC : AFP8536
( 100
24 V DC
: AFP8532 )
Max. 32 units
Max. 1,200 m
3,937.008 ft.
C-NET
adapter
S2 type
(AFP15402)
FP0
Thermocouple
4
5
FP0 Features
FP0
Equipped with 2-axis independent positioning, high-speed counter and
PWM output
Can be directly connected to the S-LINK wire-saving system (SUNX Ltd.).
● Pulse output function (For transistor output type only)
● High-speed counter function
The FP0 comes equipped with 2 channels of pulse output up to
10 kHz (5 kHz during 2-channel output). Since these two
channels can be separately controlled, the FP0 is also suitable
for 2-axis independent positioning. Setting for automatic
trapezoid control, automatic return to home position and JOG
operation are very easy, by using special instructions.
The high-speed counter is prepared for 4
channels in single phase, and 2 channels
in 2-phase. In single phase, the 4-channel
total is 10 kHz, and in 2-phase the 2channel total is 2 kHz total speed, making
the unit suitable for inverter control, and
so forth.
Feeder roller
Y0
Y2
Y1
Y3
FP0
S-LINK Control unit
W30 × H90 × D60
W1.181 × H3.543 × D2.362
Cutter
Pulse output
Motor
driver 1
cw/ccw
Stepping motor
Servo motor
Pulse output
Inverter
cw/ccw
(300 m sec)
(300 m sec)
● High speed
(7 kHz)
R0
F0
MV
H102, DT0
Control code
F0
MV
K500, DT1
Initial speed (500 Hz)
F0
MV
K7000, DT2
F0
MV
K300, DT3
F1
DMV K300000, DT4
F0
MV
F168 SPD1
● Initial speed
(500 Hz)
High speed (7 kHz)
Deceleration/Acceleration time (300 m sec)
START/
STOP signal
Encoder
Stepping motor
Servo motor
Motor
driver 2
Cutter blade
control signal
Input encoder
output into the
high-speed counter
T-branch multi
drop wiring
(For transistor output type only)
Its PWM output (Pulse Width Modulation
output) function makes it possible to
provide temperature control with a single
compact FP0 unit.
● When pulse width values are increased...
● Output pulse count
(300,000)
Output pulse count (300,000)
Pulse output starts from Y0
2 signal wires
2 power
supply wires
● PWM output function
Heater power up
K0, DT6
DT0, K0
Maximum length: 200 m 656.168 ft.
Max. 128 points
Lead wire and
tape
Motor
Position control is a breeze with the auto trapezoid control
instruction F168!
● Acceleration time ● Acceleration time
DF
The FP0 S-Link control unit makes sensor wiring and control panel simple by using easy T-shape connectability and
4-wire cable. It can control up to 128 input/output of S-Link I/O devices. Adding up to three FP0 Expansion units you
can have flexible I/O configuration capability.
● When reduced...
● Simply set the values
for each point
Surveillance possible of FP0 operation status from a Web browser using
FP Web-Server Unit
Connecting an FP0 to the FP Web-Server unit
with an RS232C cable and then setting up using
the dedicated software (FP Web Configurator
Tool) makes surveillance possible of the FP0
running conditions from a PC Web browser.
Ethernet
Heater power down
FP Web-Server
Unit
RS232C port enables serial communications. (Product No. C10CR, C14CR, C16CT, C32CT, T32CT, SL1)
The RS232C port allows the direct connection to
computers and operation display panels. Also, bidirectional data communication with bar-code readers and
other RS232C devices is made easy.
FP0
● For connecting to computers and operation
display panels
* The port block is connected by three S.R.G. terminals. Operation display panels can also be
connected using the tool port.
* RS232C port is equipped on the control units for both relay types and transistor output types.
Host computer
(Personal computer)
Operation
display panel
By using C-NET, you can use multiple FP0s as data collection terminals.
● For data communication with RS232C devices
FP0
RS-232C
POWER
COM COM D2
READY
MODE
A
FLASH
D1
D4
D3
D6
D5
D8
D9
D7 READY
MICRO-IMAGECHECKER
KEY PAD
B
M100
C
Matsuhita Electronic Works, Ltd.
CAMERA
MONITOR
24VDC
START ACK IN1
IN3
IN5
COM COM IN2 IN4
COM
Image checker
Bar-code reader
Serial printer
Wide variety of analog units available
● PCWAY
Pressure
sensor
Inverter
RUN
MODE
PROG
1
2
3
4
5
ERROR
ALARM
RUN
OFF ON
PROG.
V0
I 0
IN COM
V1
I 1
V
Laser analog
sensor
OUT
I
COM
FP0 - A21
Even with compact body, the following analog units are
available.
FP0-A21 (AFP0480)
: 2 input, 1 output
FP0-A80 (AFP0401)
: 8 input
FP0-A04V (AFP04121) : Voltage 4 output
FP0-A04I (AFP04123) : Current 4 output
FP0-TC4 (AFP0420)
: Thermocouple 4 input
FP0-TC8 (AFP0421)
: Thermocouple 8 input
By using the C-NET network and exclusive adapters, you
can connect multiple FP0s by multi-drop connection with 2wire cables. You can use computers for distributed control or
have network terminals for a centralized management
system.
Potentio meter
The Excel add-in software ìPCWAYî is
available for data collection of the
networked PLCs. PLC status and data
registers value can be simply shown
and managed on Excel worksheets,
which also makes it possible to
transmit Email when malfunctions
occur or to make status inquiries.
PCWAY
C-NET
adapter
to 200 V AC : AFP8536
( 100
24 V DC
: AFP8532 )
Max. 32 units
Max. 1,200 m
3,937.008 ft.
C-NET
adapter
S2 type
(AFP15402)
FP0
Thermocouple
4
5
FP0 Unit list
FP0
■ Control units
10 points: Input: 6, Relay output: 4
● Units having 10 to 32 I/O points are
available depending on the output type.
● A model having an RS232C port has been
added to each type.
● A type that can be directly connected to
the S-LINK wire-saving system (SUNX
Ltd.) is also available.
● A 10-k step type with a calendar timer
function and an RS232C port is also
available.
● Precautions for selection
PNP transistor output type is also
available.
Replace "4" in the second last digit of
Product No. with "5" to order the PNP
output type.
The price is the same.
90
3.543
90
3.543
90
3.543
60
2.362
25
.984
Terminal block type
FP0-C10RS
AFP02123
25
.984
60
2.362
Connector type
FP0-C10RM
AFP02113
16 points: Input: 16
14 points: Input: 8, Relay output: 6
90
3.543
90
3.543
60
2.362
25
.984
Terminal block type
FP0-C14RS
AFP02223
25
.984
60
2.362
25
.984
10 points (with RS232C): Input: 8, Relay output: 6
90
3.543
90
3.543
60
2.362
16 points: Input: 8, Transistor output: 8
25
.984
60
2.362
25
.984
Terminal block type
FP0-C10CRS
AFP02123C
25
.984
60
2.362
Connector type
FP0-C10CRM
AFP02113C
32 points: Input: 16, Transistor output: 16
MIL connector
FP0-E32T
AFP03543
8 points: Relay output: 8
8 points: Transistor output: 8
16 points: Transistor output: 16
90
3.543
90
3.543
60
2.362
Terminal block type
FP0-C14CRS
AFP02223C
25
.984
25
.984
60
2.362
60
2.362
60
2.362
25
.984
Terminal block
FP0-E8YRS
AFP03020
Connector type
FP0-C14CRM
AFP02213C
S-LINK: Input: 64, Output: 64 (S-LINK section)
60
2.362
25
.984
MIL connector
FP0-E16YT
AFP03340
MIL connector
FP0-E8YT
AFP03040
■ Intelligent units
● Addition of the analog I/O unit to the lineup enabled analog control by FP0.
Analog I/O unit
A/D converter unit
D/A converter unit
D/A converter unit
Input: 2 ch, Output: 1 ch
Input: 8 ch
Voltage output: 4 ch
Current output: 4 ch
90
3.543
90
3.543
Thermocouple unit
90
3.543
60
2.362
60
2.362
60
2.362
30
1.181
30
1.181
25
.984
60
2.362
25
.984
90
3.543
25
.984
90
3.543
90
3.543
60
2.362
MIL connector
FP0-E16T
AFP03343
90
3.543
90
3.543
90
3.543
MIL connector
FP0-E16X
AFP03303
Connector type
FP0-C14RM
AFP02213
10 points (with RS232C): Input: 6, Relay output: 4
32 points: Input: 16, Transistor output: 16
90
3.543
E.g.: AFP02543 → AFP02553
The last character of the product number
for the NPN output type is "T", and that for
the PNP output type is "P".
NPN output type: FP0-C16T
→ PNP output type: FP0-C16P
16 points: Input: 8, Transistor output: 8
MIL connector
FP0-C16T
AFP02343
MIL connector
FP0-C32T
AFP02543
4-wire S-LINK cable
* with an RS232C port
FP0-SL1
AFP02700
16 points (with RS232C): Input: 8, Transistor output: 8
32 points (with RS232C): Input: 16, Transistor output: 16
32 points (with RS232C) 10-k step type:
Input: 16, Transistor output: 16
90
3.543
90
3.543
60
2.362
60
2.362
25
.984
60
2.362
25
.984
Terminal block
FP0-A21
AFP0480
90
3.543
60
2.362
25
.984
Terminal block
FP0-A80
AFP0401
60
2.362
25
.984
Terminal block
FP0-A04V
AFP04121
Terminal block
FP0-A04I
AFP04123
25
.984
4ch
FP0-TC4
AFP0420
8ch
FP0-TC8
AFP0421
■ Link/communication units
90
3.543
90
3.543
25
.984
FP0 CC-Link slave unit
90
3.543
60
2.362
60
2.362
30
1.181
MIL connector
FP0-C32CT
AFP02543C
MIL connector
FP0-T32CT
AFP02643C
90
3.543
90
3.543
■ Expansion units
16 points: Input: 8, Relay output: 8
8 points: Input: 8
I/O link unit
FP0-IOL
AFP0732
25
.984
60
2.362
Terminal block type
FP0-E8RS
AFP03023
6
90
3.543
25
.984
60
2.362
Connector type
FP0-E8RM
AFP03013
90
3.543
25
.984
60
2.362
Terminal block type
FP0-E16RS
AFP03323
60
2.362
Adapter to link with a host computer
With a 30-cm 1.181-inch dedicated cable.
No power supply required.
AFP15402
25
.984
FP-WEB
AFP0610
■ Power supply unit and others
Power supply Input: 100 to 240 V AC,
Output: 24 V DC, 0.7 A
90
3.543
90
3.543
25
.984
FP0-CCLS
AFP07943
● The input-only and output-only types added to the lineup enhance the flexibility of I/O expansion.
90
3.543
FP Web-Server unit
60
2.362
60
2.362
25
.984
8 points: Input: 4, Relay output: 4
C-NET adapter S2 type
60
2.362
30
1.181
MIL connector
FP0-C16CT
AFP02343C
I/O link unit
FP memory loader
90
3.543
25
.984
90
3.543
60
2.362
Connector type
FP0-E16RM
AFP03313
60
2.362
25
.984
MIL connector
FP0-E8X
AFP03003
60
2.362
35
1.378
FP0-PSA4
AFP0634
Data clear type/Data hold type
AFP8670/AFP8671
7
FP0 Unit list
FP0
■ Control units
10 points: Input: 6, Relay output: 4
● Units having 10 to 32 I/O points are
available depending on the output type.
● A model having an RS232C port has been
added to each type.
● A type that can be directly connected to
the S-LINK wire-saving system (SUNX
Ltd.) is also available.
● A 10-k step type with a calendar timer
function and an RS232C port is also
available.
● Precautions for selection
PNP transistor output type is also
available.
Replace "4" in the second last digit of
Product No. with "5" to order the PNP
output type.
The price is the same.
90
3.543
90
3.543
90
3.543
60
2.362
25
.984
Terminal block type
FP0-C10RS
AFP02123
25
.984
60
2.362
Connector type
FP0-C10RM
AFP02113
16 points: Input: 16
14 points: Input: 8, Relay output: 6
90
3.543
90
3.543
60
2.362
25
.984
Terminal block type
FP0-C14RS
AFP02223
25
.984
60
2.362
25
.984
10 points (with RS232C): Input: 8, Relay output: 6
90
3.543
90
3.543
60
2.362
16 points: Input: 8, Transistor output: 8
25
.984
60
2.362
25
.984
Terminal block type
FP0-C10CRS
AFP02123C
25
.984
60
2.362
Connector type
FP0-C10CRM
AFP02113C
32 points: Input: 16, Transistor output: 16
MIL connector
FP0-E32T
AFP03543
8 points: Relay output: 8
8 points: Transistor output: 8
16 points: Transistor output: 16
90
3.543
90
3.543
60
2.362
Terminal block type
FP0-C14CRS
AFP02223C
25
.984
25
.984
60
2.362
60
2.362
60
2.362
25
.984
Terminal block
FP0-E8YRS
AFP03020
Connector type
FP0-C14CRM
AFP02213C
S-LINK: Input: 64, Output: 64 (S-LINK section)
60
2.362
25
.984
MIL connector
FP0-E16YT
AFP03340
MIL connector
FP0-E8YT
AFP03040
■ Intelligent units
● Addition of the analog I/O unit to the lineup enabled analog control by FP0.
Analog I/O unit
A/D converter unit
D/A converter unit
D/A converter unit
Input: 2 ch, Output: 1 ch
Input: 8 ch
Voltage output: 4 ch
Current output: 4 ch
90
3.543
90
3.543
Thermocouple unit
90
3.543
60
2.362
60
2.362
60
2.362
30
1.181
30
1.181
25
.984
60
2.362
25
.984
90
3.543
25
.984
90
3.543
90
3.543
60
2.362
MIL connector
FP0-E16T
AFP03343
90
3.543
90
3.543
90
3.543
MIL connector
FP0-E16X
AFP03303
Connector type
FP0-C14RM
AFP02213
10 points (with RS232C): Input: 6, Relay output: 4
32 points: Input: 16, Transistor output: 16
90
3.543
E.g.: AFP02543 → AFP02553
The last character of the product number
for the NPN output type is "T", and that for
the PNP output type is "P".
NPN output type: FP0-C16T
→ PNP output type: FP0-C16P
16 points: Input: 8, Transistor output: 8
MIL connector
FP0-C16T
AFP02343
MIL connector
FP0-C32T
AFP02543
4-wire S-LINK cable
* with an RS232C port
FP0-SL1
AFP02700
16 points (with RS232C): Input: 8, Transistor output: 8
32 points (with RS232C): Input: 16, Transistor output: 16
32 points (with RS232C) 10-k step type:
Input: 16, Transistor output: 16
90
3.543
90
3.543
60
2.362
60
2.362
25
.984
60
2.362
25
.984
Terminal block
FP0-A21
AFP0480
90
3.543
60
2.362
25
.984
Terminal block
FP0-A80
AFP0401
60
2.362
25
.984
Terminal block
FP0-A04V
AFP04121
Terminal block
FP0-A04I
AFP04123
25
.984
4ch
FP0-TC4
AFP0420
8ch
FP0-TC8
AFP0421
■ Link/communication units
90
3.543
90
3.543
25
.984
FP0 CC-Link slave unit
90
3.543
60
2.362
60
2.362
30
1.181
MIL connector
FP0-C32CT
AFP02543C
MIL connector
FP0-T32CT
AFP02643C
90
3.543
90
3.543
■ Expansion units
16 points: Input: 8, Relay output: 8
8 points: Input: 8
I/O link unit
FP0-IOL
AFP0732
25
.984
60
2.362
Terminal block type
FP0-E8RS
AFP03023
6
90
3.543
25
.984
60
2.362
Connector type
FP0-E8RM
AFP03013
90
3.543
25
.984
60
2.362
Terminal block type
FP0-E16RS
AFP03323
60
2.362
Adapter to link with a host computer
With a 30-cm 1.181-inch dedicated cable.
No power supply required.
AFP15402
25
.984
FP-WEB
AFP0610
■ Power supply unit and others
Power supply Input: 100 to 240 V AC,
Output: 24 V DC, 0.7 A
90
3.543
90
3.543
25
.984
FP0-CCLS
AFP07943
● The input-only and output-only types added to the lineup enhance the flexibility of I/O expansion.
90
3.543
FP Web-Server unit
60
2.362
60
2.362
25
.984
8 points: Input: 4, Relay output: 4
C-NET adapter S2 type
60
2.362
30
1.181
MIL connector
FP0-C16CT
AFP02343C
I/O link unit
FP memory loader
90
3.543
25
.984
90
3.543
60
2.362
Connector type
FP0-E16RM
AFP03313
60
2.362
25
.984
MIL connector
FP0-E8X
AFP03003
60
2.362
35
1.378
FP0-PSA4
AFP0634
Data clear type/Data hold type
AFP8670/AFP8671
7
FP0 Unit combinations
FP0
■ Unit combination limitations
■ Expansion method
● Up to three expansion or intelligent units can be added to
one control unit.
● There is no limitation on the type or the order of units to
be added.
● A mixed combination of the relay output type and the
transistor output type is also possible.
● Additional cables are not necessary for expansion
because the units can be directly connected to one
another using the expansion connector and lock lever on
the unit side.
Control
unit
Expansion
unit
Expansion
unit
)+(
Expansion unit 3
Expansion
unit
● Relay output type combinations
(
Total number of
I/O points
=
Input 6
Output 6
=
Input 8
Output 8
=
Input 6
Output 10
=
Input 8
Output 12
=
Input 6
=
Input 6
=
Input 8
=
Input 8
=
Input 6
=
Input 6
=
Input 8
=
Input 8
18
Input 10
22
Input 12
26
Input 14
30
Input 16
Output 14
34
Input 18
Output 16
38
Input 20
Output 18
42
Input 22
Output 20
8
Output 4
Output 4
14
Output 6
14
Output 6
10
Output 4
10
Output 4
14
Output 6
14
Output 6
10
Input 6
Output 4
10
Input 8
Output 24
=
Input 6
Output 26
=
Input 8
Output 28
=
Input 6
Output 30
=
Input 8
62
Input 32
Output 6
10
=
58
Input 30
Output 4
10
Input 8
54
Input 28
X40 - / Y40 -
X60 - / Y60 -
)
of
( TotalI/Onumber
) = ( Control unit ) + (Expansion unit 1) + ( Expansion unit 2 ) + ( Expansion unit 3 )
points
X20 - / Y20 -
16
=
Input 8
Output 16
=
Input 16
=
Input 8
=
Input 16
=
Input 8
=
Input 8
=
Input 16
Output 4
=
Input 16
Output 4
=
Input 8
=
Input 8
=
Input 16
=
Input 16
=
Input 8
=
Input 8
=
Input 16
Output 4
=
Input 16
Output 4
=
Input 8
=
Input 16
=
Input 8
=
Input 16
32
Input 16
Output 4
14
Output 6
14
Output 6
10
Output 4
14
Output 6
10
Output 4
14
Output 6
8
+
Input 4
+
Input 4
+
Input 8
+
Input 4
+
Input 8
+
Input 4
+
Input 8
+
Input 4
+
Input 8
+
Input 4
+
Output 4
48
8
Input 24
Output 4
Output 24
16
Output 8
8
Output 4
+
8
Input 4
Output 4
16
8
Output 8
+
Input 4
Output 4
+
Input 4
Output 8
+
Input 4
Output 4
+
Input 4
16
8
16
Output 8
16
Input 8
+
Input 8
+
Input 8
+
Input 8
+
Input 8
+
Input 8
+
Input 8
Output 8
16
Output 8
16
Output 8
16
Output 8
16
Output 8
16
Output 8
16
Output 8
+
Output 32
8
Input 4
8
+
Input 32
+
Output 4
16
Input 8
64
Output 8
8
8
Output 4
+
8
Input 4
Output 4
8
80
Output 4
8
Output 4
Input 40
+
Output 40
8
Input 4
Output 4
16
Input 8
Output 8
8
+
Input 4
+
Input 8
+
Input 4
+
Input 8
+
Input 8
+
Input 8
+
Input 8
Output 4
+
8
Input 4
Output 4
16
96
Output 8
8
Output 4
16
Output 8
16
Output 8
16
Output 8
16
Output 8
Input 48
Output 48
8
+
Input 4
+
Input 4
+
Input 4
+
Input 8
+
Input 8
8
8
112
Output 4
Input 56
Output 56
16
Output 8
16
Output 8
128
Input 64
Output 64
X40 - / Y40 -
X60 - / Y60 -
16
Output 8
Input 8
Output 6
14
=
50
Input 26
X20 - / Y20 -
Output 4
10
Input 6
Output 22
Expansion unit 2
14
=
46
Input 24
=
)+(
Expansion unit 1
10
Output 4
14
Input 8
● Transistor output type combinations
) = ( Control unit ) + (
10
Input 6
Up to 3 units
can be added.
Output 8
32
Output 16
16
Output 8
32
Output 16
16
Output 8
16
Output 8
32
Output 16
32
Output 16
16
Output 8
16
Output 8
32
Output 16
32
Output 16
16
Output 8
16
Output 8
32
Output 16
32
Output 16
16
Output 8
32
Output 16
16
Output 8
32
Output 16
16
+
Input 8
+
Input 8
+
Input 16
+
Input 8
+
Input 16
+
Input 8
+
Input 16
+
Input 8
+
Input 16
+
Input 8
+
Input 16
+
Input 16
+
Input 16
+
Input 16
+
Input 16
+
Input 16
+
Input 16
+
Input 16
Output 8
16
Output 8
32
Output 16
16
Output 8
16
+
Input 8
+
Input 8
+
Input 8
+
Input 8
+
Input 8
+
Input 8
+
Input 16
+
Input 8
+
Input 16
+
Input 8
+
Input 16
+
Input 16
+
Input 16
+
Input 16
Output 8
32
Output 16
16
Output 8
32
Output 16
16
Output 8
32
Output 16
16
Output 8
32
Output 16
32
Output 16
32
Output 16
32
Output 16
32
Output 16
32
Output 16
32
Output 16
32
Output 16
16
Output 8
16
Output 8
16
Output 8
16
+
Input 8
+
Input 8
+
Input 8
+
Input 8
+
Input 8
+
Input 8
+
Input 16
+
Input 16
Output 8
16
Output 8
16
Output 8
16
Output 8
32
Output 16
16
Output 8
16
Output 8
32
Output 16
16
Output 8
32
Output 16
32
Output 16
32
Output 16
32
Output 16
16
Output 8
16
Output 8
16
Output 8
32
Output 16
32
Output 16
9
FP0 Unit combinations
FP0
■ Unit combination limitations
■ Expansion method
● Up to three expansion or intelligent units can be added to
one control unit.
● There is no limitation on the type or the order of units to
be added.
● A mixed combination of the relay output type and the
transistor output type is also possible.
● Additional cables are not necessary for expansion
because the units can be directly connected to one
another using the expansion connector and lock lever on
the unit side.
Control
unit
Expansion
unit
Expansion
unit
)+(
Expansion unit 3
Expansion
unit
● Relay output type combinations
(
Total number of
I/O points
=
Input 6
Output 6
=
Input 8
Output 8
=
Input 6
Output 10
=
Input 8
Output 12
=
Input 6
=
Input 6
=
Input 8
=
Input 8
=
Input 6
=
Input 6
=
Input 8
=
Input 8
18
Input 10
22
Input 12
26
Input 14
30
Input 16
Output 14
34
Input 18
Output 16
38
Input 20
Output 18
42
Input 22
Output 20
8
Output 4
Output 4
14
Output 6
14
Output 6
10
Output 4
10
Output 4
14
Output 6
14
Output 6
10
Input 6
Output 4
10
Input 8
Output 24
=
Input 6
Output 26
=
Input 8
Output 28
=
Input 6
Output 30
=
Input 8
62
Input 32
Output 6
10
=
58
Input 30
Output 4
10
Input 8
54
Input 28
X40 - / Y40 -
X60 - / Y60 -
)
of
( TotalI/Onumber
) = ( Control unit ) + (Expansion unit 1) + ( Expansion unit 2 ) + ( Expansion unit 3 )
points
X20 - / Y20 -
16
=
Input 8
Output 16
=
Input 16
=
Input 8
=
Input 16
=
Input 8
=
Input 8
=
Input 16
Output 4
=
Input 16
Output 4
=
Input 8
=
Input 8
=
Input 16
=
Input 16
=
Input 8
=
Input 8
=
Input 16
Output 4
=
Input 16
Output 4
=
Input 8
=
Input 16
=
Input 8
=
Input 16
32
Input 16
Output 4
14
Output 6
14
Output 6
10
Output 4
14
Output 6
10
Output 4
14
Output 6
8
+
Input 4
+
Input 4
+
Input 8
+
Input 4
+
Input 8
+
Input 4
+
Input 8
+
Input 4
+
Input 8
+
Input 4
+
Output 4
48
8
Input 24
Output 4
Output 24
16
Output 8
8
Output 4
+
8
Input 4
Output 4
16
8
Output 8
+
Input 4
Output 4
+
Input 4
Output 8
+
Input 4
Output 4
+
Input 4
16
8
16
Output 8
16
Input 8
+
Input 8
+
Input 8
+
Input 8
+
Input 8
+
Input 8
+
Input 8
Output 8
16
Output 8
16
Output 8
16
Output 8
16
Output 8
16
Output 8
16
Output 8
+
Output 32
8
Input 4
8
+
Input 32
+
Output 4
16
Input 8
64
Output 8
8
8
Output 4
+
8
Input 4
Output 4
8
80
Output 4
8
Output 4
Input 40
+
Output 40
8
Input 4
Output 4
16
Input 8
Output 8
8
+
Input 4
+
Input 8
+
Input 4
+
Input 8
+
Input 8
+
Input 8
+
Input 8
Output 4
+
8
Input 4
Output 4
16
96
Output 8
8
Output 4
16
Output 8
16
Output 8
16
Output 8
16
Output 8
Input 48
Output 48
8
+
Input 4
+
Input 4
+
Input 4
+
Input 8
+
Input 8
8
8
112
Output 4
Input 56
Output 56
16
Output 8
16
Output 8
128
Input 64
Output 64
X40 - / Y40 -
X60 - / Y60 -
16
Output 8
Input 8
Output 6
14
=
50
Input 26
X20 - / Y20 -
Output 4
10
Input 6
Output 22
Expansion unit 2
14
=
46
Input 24
=
)+(
Expansion unit 1
10
Output 4
14
Input 8
● Transistor output type combinations
) = ( Control unit ) + (
10
Input 6
Up to 3 units
can be added.
Output 8
32
Output 16
16
Output 8
32
Output 16
16
Output 8
16
Output 8
32
Output 16
32
Output 16
16
Output 8
16
Output 8
32
Output 16
32
Output 16
16
Output 8
16
Output 8
32
Output 16
32
Output 16
16
Output 8
32
Output 16
16
Output 8
32
Output 16
16
+
Input 8
+
Input 8
+
Input 16
+
Input 8
+
Input 16
+
Input 8
+
Input 16
+
Input 8
+
Input 16
+
Input 8
+
Input 16
+
Input 16
+
Input 16
+
Input 16
+
Input 16
+
Input 16
+
Input 16
+
Input 16
Output 8
16
Output 8
32
Output 16
16
Output 8
16
+
Input 8
+
Input 8
+
Input 8
+
Input 8
+
Input 8
+
Input 8
+
Input 16
+
Input 8
+
Input 16
+
Input 8
+
Input 16
+
Input 16
+
Input 16
+
Input 16
Output 8
32
Output 16
16
Output 8
32
Output 16
16
Output 8
32
Output 16
16
Output 8
32
Output 16
32
Output 16
32
Output 16
32
Output 16
32
Output 16
32
Output 16
32
Output 16
32
Output 16
16
Output 8
16
Output 8
16
Output 8
16
+
Input 8
+
Input 8
+
Input 8
+
Input 8
+
Input 8
+
Input 8
+
Input 16
+
Input 16
Output 8
16
Output 8
16
Output 8
16
Output 8
32
Output 16
16
Output 8
16
Output 8
32
Output 16
16
Output 8
32
Output 16
32
Output 16
32
Output 16
32
Output 16
16
Output 8
16
Output 8
16
Output 8
32
Output 16
32
Output 16
9
FP0
FP0 Specifications
■ Performance specifications
■ Input specification (As for the limitation on the number of simultaneous ON points, please refer to the manual.)
C10 series
C14 series
C16 series
C32 series
(Relay output type only) (Relay output type only) (Transistor output type only) (Transistor output type only)
Programming method / Control method
No expansion
(control unit only)
Relay symbol / Cyclic operation
10 points
14 points
16 points
32 points
[Input: 6, NPN Output: 4] [Input: 8, NPN Output: 6] [Input: 8, NPN Output: 8] [Input: 16, NPN Output: 16]
Number of
W/expansion 1
I/O points * Same type of control and expansion units
W/expansion 2
* Mix type of relay and transistor units
Max. 58 points
Max. 62 points
Max. 112 points
Max. 128 points
Max. 106 points
Max. 110 points
Max. 112 points
Max. 128 points
Program memory
Program capacity
2.7 k steps
Basic
High-level
Operation speed (central value/step)
Internal relay (R)
Operation Relay
Timer/Counter (T/C)
memory
Memory Data register (DT)
points
area
Index register (IX,IY)
Master control relay points (MCR)
Number of labels (JMP and LOOP)
Differential points
Number of step ladder
Number of subroutines
Number of
instructions
High speed counter
Special
functions
1,660 words
−
PWM output
−
0.15 Hz to 1 kHz
Pulse catch input/interrupt input
Interrupt program
10 k steps
Item
Rated input voltage
Operating voltage range
Rated input current
Input impedance
Input points per common
Min. ON voltage/ON current
Max. OFF voltage/OFF current
Response OFF → ON
time
16,384 words
Note 1) Since the response time of X0 to X5 is very fast (for high-speed counter input) the FP0 happens to chattering noise as an input signal.
To prevent this, it is recommended that the timer should be put in the ladder program.
■ Output specification
255 labels
−
−
−
−
7 programs (external 6 points, internal 1 point)
1 program
(internal 1 point)
704 stages
100 subroutines
Available (same as
32 points series)
Available (same as
32 points series)
Available (same as
32 points series)
Available (same as
32 points series)
Available (same as
32 points series)
1. Relay output type
Item
Output type
Rated control capacity
Response OFF → ON
time
ON → OFF
Mechanical
Life time
Electrical
Surge absorber
Operating indicator
Stored fixed area in EEP-ROM
Counter: 4 points
Internal relay: 32 points
Data register: 8 words
Self-diagnostic function
Clock/Calender function
Other functions
Stored fixed area in EEP-ROM
Counter: 16 points
Internal relay: 128 points
Data register: 32 words
Watchdog timer, program syntax check
−
Runtime editing, password setting
Item
Output type
Rated load voltage
Load voltage allowable
range
Description
Open collector
NPN type: 5 to 24 V DC, PNP type: 24 V DC
NPN type: 4.75 to 26.4 V DC
PNP type: 21.6 to 26.4 V DC
Max. load current
Max. inrush current
OFF state leakage current
ON state voltage drop
Response OFF → ON
time
ON → OFF
Voltage range for external
power supply
0.1 A/point (1 A/common)
0.3 A
100 µA or less
1.5 V or less
1 ms or less
(50 µs or less at Y0 and Y1 only)
Surge absorber
Zener diode
21.6 to 26.4 V DC
8 points/common (C16T, C16P, C16CT,
C16CP, E16T, E16P, E8YT, E8YP)
16 points/common (C32T, C32P, C32CT,
C32CP, E32T, E32P, E16YT, E16YP)
Photocoupler
Output points per common
Insulation method
Backup is provided by
secondary battery. The
holding range for the
timers, counters internal
relays, and data registers are specified with
the programming tool.
■ I/O circuit diagram
Relay output
Transistor output (NPN)
Transistor output (PNP)
Input
5.6 kΩ
X0
Input
5.6 kΩ X0
Available
* For the limitations while operating units, see the manual.
5.6 kΩ
Internal
circuit
Internal
circuit
Internal
circuit
Xn
Xn
Description
24 V DC
21.6 to 26.4 V DC
5 ms (at 21.6 V), 10 ms (at 24 V)
10 ms (at 21.6 V / 24 V)
0 to +55 °C 32 to +131 °F
ñ20 to +70 °C ñ4 to +158 °F
30 to 85% RH (non-condensing)
30 to 85% RH (non-condensing)
Between input/output terminals and power/ground terminals: 500 V AC for 1 minute (for the relay output type, 1500 V AC for 1 minute)
Between input terminals and output terminals: 500 V AC for 1 minute (for the relay output type, 1500 V AC for 1 minute)
Insulation resistance
Between input/output terminals and power/ground terminals: Over 100 MΩ (using a 500V DC megger)
Between input terminals and output terminals: Over 100 MΩ (using a 500V DC megger)
Vibration resistance
Shock resistance
Noise immunity
Operating condition
10 to 55 Hz, 1 sweep/min. Double amplitude of 0.75 mm .030 inch, 10 min. on 3 axes
98 m/s2 or more , 4 times on 3 axes
1,000 V (p-p) with pulse widths 50 ns and 1 µs (using a noise simulator)
Free from corrosive gasses and excessive dust
Internal
circuit
Internal
circuit
Input
X0
(* Note 1)
Xn
■ General specifications
10
Description
1a (1 form A, normally open)
2 A 250 V AC, 2 A 30 V DC (4.5 A/common)
Approx. 10 ms
Approx. 8 ms
Min. 2 × 107 operations
Min. 105 operations
None
LED display
Stored program and system register in EEP-ROM
Maintenance
Breakdown voltage
2. Transistor output type
One RS232C port is mounted on each of the models FP0- C10CR, C14CR, C16CT, C16CP, C32CT, C32CP,
T32CT, T32CP and SL1 type (3P terminal block)
Transmission speed (Baud rate): 300 to 19,200 bits/s, Transmission distance: 3 m 9.843 ft
Communication method: half duplex
Operation memory
Rated voltage
Operating voltage range
Allowed momentary 10 points, 14 points type
power off time
16 points, 32 points, S-LINK type
Ambient temperature
Storage temperature
Ambient humidity
Storage humidity
19.2 V / 3 mA
2.4 V / 1 mA
50 µs or less (at X0, X1) Note 1) (at 24V DC and under the ambient temperature of 25 °C 77 °F)
100 µs or less (at X2 to X5) Note 1) (at 24 V DC and under the ambient temperature of 25 °C 77 °F)
2 ms or less (at X6 onward)
Same as above
Photocoupler
0.5 ms to 30 s
Available
Program and system
register
Item
Description
24 V DC
21.6 to 26.4 V DC
Approx. 4.3 mA (at 24 V DC)
Approx. 5.6 kΩ
±common, 4 points/common (E8RS/E8RM), 6 points/common (C10RS/C10RM), 8 points/common (C14RS/C14RM, C16T, E16T,
E16R, E8X), 16 points/common (C32T/E32T/E16X)
ON → OFF
Insulation method
6 points (with high speed counter)
Periodical interrupt
Constant scan
32 points
[Input: 16, NPN Output: 16]
Expansion section: Max. 128 points
Max. 96 points
Max. 128 points
1 phase/4 points (10 kHz in total) or 2 phases/2 points (2 kHz in total)*
Pulse output
RS232C port
S-LINK section:
max. 128 points
[Input: 64, NPN Output: 64]
EEP-ROM (no back up battery required)
5 k steps
83
115
0.9 µs/step (for basic instructions)
1,008 points
114 points
6,144 words
2 words
32 points
64 labels
Unlimited number of points
128 stages
16 subroutines
2 points (10 kHz* in total), enable to
control 2 channels individually*
Memory
back up
S-LINK type
Internal
circuit
COM
(* Note 1)
Model
T32 series
(Transistor output type only)
24 V DC
COM
COM
Output (ñ)
Output
Output
Y0
L
Internal
circuit
Y0
L
Internal
circuit
Y0
L
Internal
circuit
(+)
Yn
L
Internal
circuit
COM
Internal
Internal
circuit
Yn
L
Internal
circuit
(ñ)
Source
Internal
Yn
(+)
Internal
L
24 V DC
(Load voltage
and external
power supply)
Note: For transistor
output types,
make sure that the
externally supplied
voltage between
the (+) and (-)
terminal is
between 21.6 and
26.4 V DC.
11
FP0
FP0 Specifications
■ Performance specifications
■ Input specification (As for the limitation on the number of simultaneous ON points, please refer to the manual.)
C10 series
C14 series
C16 series
C32 series
(Relay output type only) (Relay output type only) (Transistor output type only) (Transistor output type only)
Programming method / Control method
No expansion
(control unit only)
Relay symbol / Cyclic operation
10 points
14 points
16 points
32 points
[Input: 6, NPN Output: 4] [Input: 8, NPN Output: 6] [Input: 8, NPN Output: 8] [Input: 16, NPN Output: 16]
Number of
W/expansion 1
I/O points * Same type of control and expansion units
W/expansion 2
* Mix type of relay and transistor units
Max. 58 points
Max. 62 points
Max. 112 points
Max. 128 points
Max. 106 points
Max. 110 points
Max. 112 points
Max. 128 points
Program memory
Program capacity
2.7 k steps
Basic
High-level
Operation speed (central value/step)
Internal relay (R)
Operation Relay
Timer/Counter (T/C)
memory
Memory Data register (DT)
points
area
Index register (IX,IY)
Master control relay points (MCR)
Number of labels (JMP and LOOP)
Differential points
Number of step ladder
Number of subroutines
Number of
instructions
High speed counter
Special
functions
1,660 words
−
PWM output
−
0.15 Hz to 1 kHz
Pulse catch input/interrupt input
Interrupt program
10 k steps
Item
Rated input voltage
Operating voltage range
Rated input current
Input impedance
Input points per common
Min. ON voltage/ON current
Max. OFF voltage/OFF current
Response OFF → ON
time
16,384 words
Note 1) Since the response time of X0 to X5 is very fast (for high-speed counter input) the FP0 happens to chattering noise as an input signal.
To prevent this, it is recommended that the timer should be put in the ladder program.
■ Output specification
255 labels
−
−
−
−
7 programs (external 6 points, internal 1 point)
1 program
(internal 1 point)
704 stages
100 subroutines
Available (same as
32 points series)
Available (same as
32 points series)
Available (same as
32 points series)
Available (same as
32 points series)
Available (same as
32 points series)
1. Relay output type
Item
Output type
Rated control capacity
Response OFF → ON
time
ON → OFF
Mechanical
Life time
Electrical
Surge absorber
Operating indicator
Stored fixed area in EEP-ROM
Counter: 4 points
Internal relay: 32 points
Data register: 8 words
Self-diagnostic function
Clock/Calender function
Other functions
Stored fixed area in EEP-ROM
Counter: 16 points
Internal relay: 128 points
Data register: 32 words
Watchdog timer, program syntax check
−
Runtime editing, password setting
Item
Output type
Rated load voltage
Load voltage allowable
range
Description
Open collector
NPN type: 5 to 24 V DC, PNP type: 24 V DC
NPN type: 4.75 to 26.4 V DC
PNP type: 21.6 to 26.4 V DC
Max. load current
Max. inrush current
OFF state leakage current
ON state voltage drop
Response OFF → ON
time
ON → OFF
Voltage range for external
power supply
0.1 A/point (1 A/common)
0.3 A
100 µA or less
1.5 V or less
1 ms or less
(50 µs or less at Y0 and Y1 only)
Surge absorber
Zener diode
21.6 to 26.4 V DC
8 points/common (C16T, C16P, C16CT,
C16CP, E16T, E16P, E8YT, E8YP)
16 points/common (C32T, C32P, C32CT,
C32CP, E32T, E32P, E16YT, E16YP)
Photocoupler
Output points per common
Insulation method
Backup is provided by
secondary battery. The
holding range for the
timers, counters internal
relays, and data registers are specified with
the programming tool.
■ I/O circuit diagram
Relay output
Transistor output (NPN)
Transistor output (PNP)
Input
5.6 kΩ
X0
Input
5.6 kΩ X0
Available
* For the limitations while operating units, see the manual.
5.6 kΩ
Internal
circuit
Internal
circuit
Internal
circuit
Xn
Xn
Description
24 V DC
21.6 to 26.4 V DC
5 ms (at 21.6 V), 10 ms (at 24 V)
10 ms (at 21.6 V / 24 V)
0 to +55 °C 32 to +131 °F
ñ20 to +70 °C ñ4 to +158 °F
30 to 85% RH (non-condensing)
30 to 85% RH (non-condensing)
Between input/output terminals and power/ground terminals: 500 V AC for 1 minute (for the relay output type, 1500 V AC for 1 minute)
Between input terminals and output terminals: 500 V AC for 1 minute (for the relay output type, 1500 V AC for 1 minute)
Insulation resistance
Between input/output terminals and power/ground terminals: Over 100 MΩ (using a 500V DC megger)
Between input terminals and output terminals: Over 100 MΩ (using a 500V DC megger)
Vibration resistance
Shock resistance
Noise immunity
Operating condition
10 to 55 Hz, 1 sweep/min. Double amplitude of 0.75 mm .030 inch, 10 min. on 3 axes
98 m/s2 or more , 4 times on 3 axes
1,000 V (p-p) with pulse widths 50 ns and 1 µs (using a noise simulator)
Free from corrosive gasses and excessive dust
Internal
circuit
Internal
circuit
Input
X0
(* Note 1)
Xn
■ General specifications
10
Description
1a (1 form A, normally open)
2 A 250 V AC, 2 A 30 V DC (4.5 A/common)
Approx. 10 ms
Approx. 8 ms
Min. 2 × 107 operations
Min. 105 operations
None
LED display
Stored program and system register in EEP-ROM
Maintenance
Breakdown voltage
2. Transistor output type
One RS232C port is mounted on each of the models FP0- C10CR, C14CR, C16CT, C16CP, C32CT, C32CP,
T32CT, T32CP and SL1 type (3P terminal block)
Transmission speed (Baud rate): 300 to 19,200 bits/s, Transmission distance: 3 m 9.843 ft
Communication method: half duplex
Operation memory
Rated voltage
Operating voltage range
Allowed momentary 10 points, 14 points type
power off time
16 points, 32 points, S-LINK type
Ambient temperature
Storage temperature
Ambient humidity
Storage humidity
19.2 V / 3 mA
2.4 V / 1 mA
50 µs or less (at X0, X1) Note 1) (at 24V DC and under the ambient temperature of 25 °C 77 °F)
100 µs or less (at X2 to X5) Note 1) (at 24 V DC and under the ambient temperature of 25 °C 77 °F)
2 ms or less (at X6 onward)
Same as above
Photocoupler
0.5 ms to 30 s
Available
Program and system
register
Item
Description
24 V DC
21.6 to 26.4 V DC
Approx. 4.3 mA (at 24 V DC)
Approx. 5.6 kΩ
±common, 4 points/common (E8RS/E8RM), 6 points/common (C10RS/C10RM), 8 points/common (C14RS/C14RM, C16T, E16T,
E16R, E8X), 16 points/common (C32T/E32T/E16X)
ON → OFF
Insulation method
6 points (with high speed counter)
Periodical interrupt
Constant scan
32 points
[Input: 16, NPN Output: 16]
Expansion section: Max. 128 points
Max. 96 points
Max. 128 points
1 phase/4 points (10 kHz in total) or 2 phases/2 points (2 kHz in total)*
Pulse output
RS232C port
S-LINK section:
max. 128 points
[Input: 64, NPN Output: 64]
EEP-ROM (no back up battery required)
5 k steps
83
115
0.9 µs/step (for basic instructions)
1,008 points
114 points
6,144 words
2 words
32 points
64 labels
Unlimited number of points
128 stages
16 subroutines
2 points (10 kHz* in total), enable to
control 2 channels individually*
Memory
back up
S-LINK type
Internal
circuit
COM
(* Note 1)
Model
T32 series
(Transistor output type only)
24 V DC
COM
COM
Output (ñ)
Output
Output
Y0
L
Internal
circuit
Y0
L
Internal
circuit
Y0
L
Internal
circuit
(+)
Yn
L
Internal
circuit
COM
Internal
Internal
circuit
Yn
L
Internal
circuit
(ñ)
Source
Internal
Yn
(+)
Internal
L
24 V DC
(Load voltage
and external
power supply)
Note: For transistor
output types,
make sure that the
externally supplied
voltage between
the (+) and (-)
terminal is
between 21.6 and
26.4 V DC.
11
FP0
FP0
■ Analog unit specifications
1. Analog input specifications
Description
Item
FP0-A21
8 channels/unit (Number of input points
can be changed 2, 4, 6 and 8 channels.)
0 to 5 V(K 0 to K 4000) Note 1)/-10 to +10 V
-100 to +100 mV (K -2000 to K +2000) Note 1)
2 channels/unit
Voltage range 0 to 5 V(K 0 to K 4000) Note 1)/
-10 to +10 V (K -2000 to K +2000) Note 1)
Current range
0 to 20 mA (K 0 to K 4000) Note 1)
1/4000 (12 bits)
1 ms/channel Note 2)
±1% FS or less (0 to 55 °C), ±0.6% F.S or less (25 °C)
1 MΩ or more
250 Ω
±15 V
±30 mA
Resolution
Conversion speed
Overall precision
Input
Voltage range
impedance Current range
Absolute
Voltage range
maximum input Current range
Between analog input terminal and FP0 internal
circuit: optical coupler insulation (non-insulated
between channels)
Between analog input terminal and I/O unit external
power supply: based on insulation-type DC/DC
converter
Between analog input terminal and analog output
terminal: based on insulation-type DC/DC converter
Insulation method
Number of I/O contact points
Averaging function
None
Between analog output terminal and FP0 internal
circuit: optical coupler insulation (non-insulated
between channels)
Between analog output terminal and D/A converter
unit external power supply: based on insulationtype DC/DC converter
32 input contact points
Can be switched on and off.
Notes
1) If the analog input value exceeds the upper or lower limit, the digital value will preserve the upper or
lower limit.
2) The number for the input contact point being used varies depending on the expansion position.
FP0-A21
FP0-A21
Output range
0V
Analog
input
1 ms
K0
WX2
Refresh
standby
-10 to +10 V range (K -2000 to K +2000) Note 1)
Voltage range
Current range 0 to 20 mA (K 0 to K 4000) Note 1)
Resolution
Conversion speed
Overall precision
Output impedance Voltage range
Absolute output load resistance Voltage range
Max. output current Current range
0.5 Ω or less
±10 mA
30 Ω or less
1000 Ω or less
Between analog output terminal and FP0
internal circuit: optical coupler insulation
Between analog output terminal and
analog I/O unit extenal power supply:
based on insulation-type DC/DC
converter
Between analog output terminal and
analog input terminal: based on
insulation-type DC/DC converter
Insulation method note 2)
Number of I/O contact points
0V
Analog
input
WX2
Conversion
time
Waiting for
processing
K0
Conversion
time
10 V
0V
Analog output
Refresh
1 ms × No. of
0 ms to
1 ms to
scan time expansions
Note 4)
1 ms × number of
input channels × ( Number of input channels )
2
Note 3)
K0
Between analog output terminal and FP0 internal circuit:
optical coupler insulation (non-insulated between channels)
Between analog output terminal and D/A converter unit
external power supply: based on insulation-type DC/DC
converter
K2000
WX2
1 ms × number
0 ms to
scan time of expansions
Refresh
standby
500 Ω or less
16 output contact points 16 input contact points, 32 output contact points Note 3)
Refresh
10 V
FP0-A80
Transmission line
Notes
1) If the digital input value exceeds the upper or lower limit, D/A conversion will not take place.
(Analog output will remain as the previous data.)
2) The number for the output contact point being used varies depending on the expansion position.
K2000
1 ms × number
of expansions
0 ms to
scan time
500
µs
K2000
FP0-A04V, FP0-04 I
K2000
K0
WX2
0V
Analog output
Conversion
time
0 ms to
scan time
Waiting for
processing
1 ms × mumber
of expansions
Conversion
time
500 µs/1CH
1 ms/2CH
10 V
3) Settings value switch for the number of input channels.
4) With each one scan of the control unit, the data for two channels will be loaded into it. In other words,
if the input channel number switch is set to 8-channel, the data in the control unit will be updated once
every four scans.
3) The data for two channels will be output to the D/A converter unit with one scan of the control unit.
■ Thermocouple unit specifications
■ CC-Link slave unit specifications
Item
Input points
Input range
Digital output
Description
4-channel, 8-channel
(The number of input points can be changed 2, 4, 6 and 8 channels.)
Thermocouple types K and J
-100.0 to 500.0 °C/-148.0 to 790.0 °F Note 1)
Thermocouple type T
Thermocouple type R
-100.0 to 400.0 °C/-148.0 to 752.0 °F
0.0 to 1500.0 °C/32.0 to 1590.0 °F Note 1)
K and J (when using °C): K -1000 to K 5000
K and J (when using °F): K -1480 to K 7900 Note 1)
(When range over using °C: K-1001, K 5001 or K 8000)
(When range over using °F: K-1481, K 7901 or K 8000)
(When the thermocouple broken: K 8000) Note 2)
(Until the temperature can be measured at the initial startup: K 8001) Note 3)
T (when using °C): K -1000 to K 4000
T (when using °F): K -1480 to K 7520 Note 1)
(When range over using °C: K -1001, K 4001 or K 8000)
(When range over using °F: K -1481, K 7521 or K 8000)
(When the thermocouple broken: K8000) Note 2)
(Until the temperature can be measured at the initial startup: K 8001) Note 3)
R (when using °C): K 0 to K 15000
R (when using °F): K 320 to K 15900 Note 1)
(When range over using °C: K 0, K 15001 or K 16000)
(When range over using °F: K 0, K 15901 or K 16000)
(When the thermocouple broken: K 16000) Note 2)
(Until the temperature can be measured at the initial startup: K 16001) Note 3)
Resolution
0.1 °C
Sampling
Note 5)
cycle
300 ms: when using 2 channels for an input points Note 4)
500 ms: when using 4 channels for an input points Note 4)
700 ms: when using 6 channels for an input points Note 4)
900 ms: when using 8 channels for an input points Note 4)
Overall
accuracy
Range for K and J (-100 to 500 °C):
Range for T
(-100 to 400 °C):
Range for R
(0 to 99.9 °C):
(100 to 299.9 °C):
(300 to 1500 °C):
±0.8 °C or less
±0.8 °C or less
±3 °C or less
±2.5 °C or less
±2 °C or less
Input impedance
more than 1 MΩ
Insulation
method
• Between thermocouple input terminals and control unit internal circuits:
Photo-coupler insulation/DC-DC insulation
• Between thermocouple input terminal channels: PhotoMOS relay insulation
1. Communication specifications
Version
CC-Link Ver.1.10
Communication method Broadcast polling method
Transmission speed 10 Mbits/s, 5 Mbits/s, 2.5 Mbits/s, 625 kbits/s, 156 kbits/s
Ver.1.10 CC-Link cable
Max.
transmission
CC-Link high-performace cable
distance 10 Mbits/s
100 m
Note 1)
160 m
400 m
900 m
1200 m
5 Mbits/s
2.5 Mbits/s
625 kbits/s
156 kbits/s
Transmission distance
(Total distance)
Transmission speed (Baud rate)
Number of control I/O point
per an I/O link unit
Remote I/O map allocation
Interface
Transmission error check
100 m
150 m
200 m
600 m
1200 m
Product number
Part number
Rated voltage
Variable input voltage range
Rated frequency
Frequency range
Input
Number of phases
Surge current
Leakage current
Allow able momentary power off time
Rated voltage
Voltage accuracy
Rated current
Output
Output current range
Ripple voltage
Protective Over-current protection
functions Over-voltage protection
K.J.T
R
0 - 99.9 °C
100 - 299.9 °C
300 - 1500 °C
2 °C
6 °C
5 °C
4 °C
12
1) The measurement range available for degree Celsius is not available for degree Fahrenheit, of which the upper-limit measurement is set lower than degree Celsius, since the
digital value (temperature value displayed) for degree Fahrenheit is bigger than that for degree Celsius.
2) When the thermocouple is broken, the digital value will become K8000 or K16000 within 70 seconds since broken. Practice in the ladder program a process for avoiding a risk,
would be resulting from a broken thermocouple, and exchange the thermocouple.
3) Until the conversion data will be ready after the initial startup was made, the digital value shows K8001 or K16001. Those are not a temperature data. Create a ladder program,
so that they are not acquired as a temperature data.
4) The settings of the input channel selection switch.
5) Conversion values for 6-time measurements (6 from the latest 8 measurements, excluding the max. and min.) are averaged, so that it takes time for the digital value to be
displayed due to the rapid temperature change.
6) The control unit reads the data for 2 channels per 1 scan by the control unit. Read data by utilizing the sample program given in the product specifications and manual.
10 M bit/s (10BASE-T: RJ45)
Supported protocol TCP, UDP, IP, DHCP, FTP, TELNET, HTTP, SMTP, and PPP
Memory size
Approx. 148 kB (for storing htm files)
Setup method
Setup using FP Web Configurator Tool
Applicable crimp teriminals
FP0-PSA4
FP0-PSA1
AFP0634
AFP0631
100 to 240 V AC
85 to 264 V AC
50/60 Hz
47 to 63 Hz
Single-phase
30 A (0 - P) or less, with cold start
0.75 mA or less
10 ms or more
24 V DC
±5%
0.6 A
0.7 A Note)
0 to 0.6 A
0 to 0.7 A
500 mV or less
0.735 A or more
0.63 A or more
Available
Manufacturer
JST
Mfg.Co.,Ltd.
Part number
Applicable wiring
V1.25-M3 (round type)
V1.25-S3A (fork type)
0.35 to 1.65 mm2
AWG #22 to #15
V2-M3 (round type)
V2-S3A (fork type)
1.04 to 2.00 mm2
AWG #17 to #14
7.2 mm .283 inch or less
Control unit current consumption
Type of unit
FP0 control unit
FP0 expansion unit
FP0 intelligent unit
Input/Output points Input: 32 points Note 6)
Notes
Ethernet
communication
■ Current consumption
When CC-Link
Standard
slave unit with a
specifications thermocouple unit
0.8 °C
3 °C
2.5 °C
2 °C
RS232C
communication
RS232C ⇔ Ethernet conversion
(PLC remote programming via Ethernet)
E-mail sending function
Web-server function
Transparent communication (Server/Client)
PPP server function
RS232C terminal block 3-pin: Mainly used for PLC connection
RS232C D-Sub 9-pin: Mainly used for Modem connection
10 BASE-T (RJ45): Used for Ethernet connection and setup
Transmission speed: 1200, 2400, 4800, 9600, 19200,
38400, 57600, 115200 bits/s
Data length: 7 bits/8 bits, Parity: Even/Odd/None
Note: Start up may not be possible if a device with a large inrush current is connected even if below the rated current. In such a case,
we recommend suppressing the inrush current by inserting a 1 to 2Ω resister between the power supply unit and the device.
For details concerning the CC-Link, refer to the CC-Link Partner Association.
When an FP0 thermocouple unit is used with an FP0 CC-Link slave unit, the
measurement accuracy of the thermocouple unit which is installed on the left of
the CC-Link slave unit is as shown in the table below.
Communication
functions
Communication
interface
32X/32Y
Conforming to RS485
CRC (Cyclic Redumdancy Check) method
■ Power supply unit specifications
The cable length has restrictions in communication speed, CC-Link version,
and dedicated cables to be used.
Thermocouple
Max. 700 m 2,296.588 ft.(using twisted pair cable)
Max. 400 m 1,312.336 ft.(using VCTF cable)
0.5 Mbits/s
64 points
(Input: 32 points and Output: 32 points) note)
Note: This point number is the number of points that can be linked for inputting and
outputting via the host PLC and network MEWNET-F. If the output for the I/O link unit
error flag is set to ON, this number becomes 63 points (31 input points and 32 output
points).
S-LINK control unit
Length of the multi-drop connected cables at both ends
■ FP Web-Server unit specifications
Description
Two-wire, half duple
Asynchronous method
2-wire cable (Twisted-pair cable or VCTF 0.75 mm2
× 2C equivalent)
CC-Link cable
Interface
RS485
Station type
Remote device station
Number of occupied stations FPΣ: 1 to 4 stations (switch changeover), FP0: 1 station
Note 1)
Item
Communication method
Synchronous method
4 to 20 mA (K 0 to K 4000) Note 1)
1/4000 (12 bits)
500 µs/channel Note 2)
±1% F.S or less (0 to 55 °C), ±0.6% F.S. or less (25 °C)
FP0-A21
Refresh
FP0-A04I
Voltage output: 4 channels/units Current output: 4 channels/units
1 channel/unit
Number of output points
10 V
Conversion
time
Description
FP0-A04V
Item
FP0-A80
Number of input points
Input range
■ I/O Link unit specifications
2. Analog output specifications
Link/Communication
units
This refers to the current consumed via the power supply
connector of the control unit. If expansion units or intelligent units
are added, the current is increased by the value indicated below.
FP0-C10
FP0-C14
FP0-C16
FP0-C32
FP0-T32
100 mA or less
100 mA or less
40 mA or less
FP0-SL1
150 mA or less
FP0-E8X
FP0-E8R
FP0-E8YR
FP0-E8YT/P
FP0-E16X
FP0-E16R
FP0-E16T/P
FP0-E16YT/P
FP0-E32T/P
FP0-A21
FP0-A80
FP0-A04V
FP0-A04I
FP0-TC4
FP0-TC8
FP0-CCLS
FP0-IOL
FP-WEB
AFP15402 (C-NET adapter)
Expansion unit current consumption
This refers to the current consumed via the power
supply connector of the expansion unit. Units with no
value indication don't have a power supply connector.
60 mA or less
10 mA or less
15 mA or less
10 mA or less
15 mA or less
20 mA or less
20 mA or less
25 mA or less
25 mA or less
40 mA or less
20 mA or less
20 mA or less
20 mA or less
20 mA or less
50 mA or less
100 mA or less
100 mA or less
100 mA or less
60 mA or less
100 mA or less
130 mA or less
25 mA or less
40 mA or less
30 mA or less
40 mA or less
40 mA or less
95 mA or less (at 24 V DC), 240 mA or less (at 12 V DC)
50 mA or less
13
FP0
FP0
■ Analog unit specifications
1. Analog input specifications
Description
Item
FP0-A21
8 channels/unit (Number of input points
can be changed 2, 4, 6 and 8 channels.)
0 to 5 V(K 0 to K 4000) Note 1)/-10 to +10 V
-100 to +100 mV (K -2000 to K +2000) Note 1)
2 channels/unit
Voltage range 0 to 5 V(K 0 to K 4000) Note 1)/
-10 to +10 V (K -2000 to K +2000) Note 1)
Current range
0 to 20 mA (K 0 to K 4000) Note 1)
1/4000 (12 bits)
1 ms/channel Note 2)
±1% FS or less (0 to 55 °C), ±0.6% F.S or less (25 °C)
1 MΩ or more
250 Ω
±15 V
±30 mA
Resolution
Conversion speed
Overall precision
Input
Voltage range
impedance Current range
Absolute
Voltage range
maximum input Current range
Between analog input terminal and FP0 internal
circuit: optical coupler insulation (non-insulated
between channels)
Between analog input terminal and I/O unit external
power supply: based on insulation-type DC/DC
converter
Between analog input terminal and analog output
terminal: based on insulation-type DC/DC converter
Insulation method
Number of I/O contact points
Averaging function
None
Between analog output terminal and FP0 internal
circuit: optical coupler insulation (non-insulated
between channels)
Between analog output terminal and D/A converter
unit external power supply: based on insulationtype DC/DC converter
32 input contact points
Can be switched on and off.
Notes
1) If the analog input value exceeds the upper or lower limit, the digital value will preserve the upper or
lower limit.
2) The number for the input contact point being used varies depending on the expansion position.
FP0-A21
FP0-A21
Output range
0V
Analog
input
1 ms
K0
WX2
Refresh
standby
-10 to +10 V range (K -2000 to K +2000) Note 1)
Voltage range
Current range 0 to 20 mA (K 0 to K 4000) Note 1)
Resolution
Conversion speed
Overall precision
Output impedance Voltage range
Absolute output load resistance Voltage range
Max. output current Current range
0.5 Ω or less
±10 mA
30 Ω or less
1000 Ω or less
Between analog output terminal and FP0
internal circuit: optical coupler insulation
Between analog output terminal and
analog I/O unit extenal power supply:
based on insulation-type DC/DC
converter
Between analog output terminal and
analog input terminal: based on
insulation-type DC/DC converter
Insulation method note 2)
Number of I/O contact points
0V
Analog
input
WX2
Conversion
time
Waiting for
processing
K0
Conversion
time
10 V
0V
Analog output
Refresh
1 ms × No. of
0 ms to
1 ms to
scan time expansions
Note 4)
1 ms × number of
input channels × ( Number of input channels )
2
Note 3)
K0
Between analog output terminal and FP0 internal circuit:
optical coupler insulation (non-insulated between channels)
Between analog output terminal and D/A converter unit
external power supply: based on insulation-type DC/DC
converter
K2000
WX2
1 ms × number
0 ms to
scan time of expansions
Refresh
standby
500 Ω or less
16 output contact points 16 input contact points, 32 output contact points Note 3)
Refresh
10 V
FP0-A80
Transmission line
Notes
1) If the digital input value exceeds the upper or lower limit, D/A conversion will not take place.
(Analog output will remain as the previous data.)
2) The number for the output contact point being used varies depending on the expansion position.
K2000
1 ms × number
of expansions
0 ms to
scan time
500
µs
K2000
FP0-A04V, FP0-04 I
K2000
K0
WX2
0V
Analog output
Conversion
time
0 ms to
scan time
Waiting for
processing
1 ms × mumber
of expansions
Conversion
time
500 µs/1CH
1 ms/2CH
10 V
3) Settings value switch for the number of input channels.
4) With each one scan of the control unit, the data for two channels will be loaded into it. In other words,
if the input channel number switch is set to 8-channel, the data in the control unit will be updated once
every four scans.
3) The data for two channels will be output to the D/A converter unit with one scan of the control unit.
■ Thermocouple unit specifications
■ CC-Link slave unit specifications
Item
Input points
Input range
Digital output
Description
4-channel, 8-channel
(The number of input points can be changed 2, 4, 6 and 8 channels.)
Thermocouple types K and J
-100.0 to 500.0 °C/-148.0 to 790.0 °F Note 1)
Thermocouple type T
Thermocouple type R
-100.0 to 400.0 °C/-148.0 to 752.0 °F
0.0 to 1500.0 °C/32.0 to 1590.0 °F Note 1)
K and J (when using °C): K -1000 to K 5000
K and J (when using °F): K -1480 to K 7900 Note 1)
(When range over using °C: K-1001, K 5001 or K 8000)
(When range over using °F: K-1481, K 7901 or K 8000)
(When the thermocouple broken: K 8000) Note 2)
(Until the temperature can be measured at the initial startup: K 8001) Note 3)
T (when using °C): K -1000 to K 4000
T (when using °F): K -1480 to K 7520 Note 1)
(When range over using °C: K -1001, K 4001 or K 8000)
(When range over using °F: K -1481, K 7521 or K 8000)
(When the thermocouple broken: K8000) Note 2)
(Until the temperature can be measured at the initial startup: K 8001) Note 3)
R (when using °C): K 0 to K 15000
R (when using °F): K 320 to K 15900 Note 1)
(When range over using °C: K 0, K 15001 or K 16000)
(When range over using °F: K 0, K 15901 or K 16000)
(When the thermocouple broken: K 16000) Note 2)
(Until the temperature can be measured at the initial startup: K 16001) Note 3)
Resolution
0.1 °C
Sampling
Note 5)
cycle
300 ms: when using 2 channels for an input points Note 4)
500 ms: when using 4 channels for an input points Note 4)
700 ms: when using 6 channels for an input points Note 4)
900 ms: when using 8 channels for an input points Note 4)
Overall
accuracy
Range for K and J (-100 to 500 °C):
Range for T
(-100 to 400 °C):
Range for R
(0 to 99.9 °C):
(100 to 299.9 °C):
(300 to 1500 °C):
±0.8 °C or less
±0.8 °C or less
±3 °C or less
±2.5 °C or less
±2 °C or less
Input impedance
more than 1 MΩ
Insulation
method
• Between thermocouple input terminals and control unit internal circuits:
Photo-coupler insulation/DC-DC insulation
• Between thermocouple input terminal channels: PhotoMOS relay insulation
1. Communication specifications
Version
CC-Link Ver.1.10
Communication method Broadcast polling method
Transmission speed 10 Mbits/s, 5 Mbits/s, 2.5 Mbits/s, 625 kbits/s, 156 kbits/s
Ver.1.10 CC-Link cable
Max.
transmission
CC-Link high-performace cable
distance 10 Mbits/s
100 m
Note 1)
160 m
400 m
900 m
1200 m
5 Mbits/s
2.5 Mbits/s
625 kbits/s
156 kbits/s
Transmission distance
(Total distance)
Transmission speed (Baud rate)
Number of control I/O point
per an I/O link unit
Remote I/O map allocation
Interface
Transmission error check
100 m
150 m
200 m
600 m
1200 m
Product number
Part number
Rated voltage
Variable input voltage range
Rated frequency
Frequency range
Input
Number of phases
Surge current
Leakage current
Allow able momentary power off time
Rated voltage
Voltage accuracy
Rated current
Output
Output current range
Ripple voltage
Protective Over-current protection
functions Over-voltage protection
K.J.T
R
0 - 99.9 °C
100 - 299.9 °C
300 - 1500 °C
2 °C
6 °C
5 °C
4 °C
12
1) The measurement range available for degree Celsius is not available for degree Fahrenheit, of which the upper-limit measurement is set lower than degree Celsius, since the
digital value (temperature value displayed) for degree Fahrenheit is bigger than that for degree Celsius.
2) When the thermocouple is broken, the digital value will become K8000 or K16000 within 70 seconds since broken. Practice in the ladder program a process for avoiding a risk,
would be resulting from a broken thermocouple, and exchange the thermocouple.
3) Until the conversion data will be ready after the initial startup was made, the digital value shows K8001 or K16001. Those are not a temperature data. Create a ladder program,
so that they are not acquired as a temperature data.
4) The settings of the input channel selection switch.
5) Conversion values for 6-time measurements (6 from the latest 8 measurements, excluding the max. and min.) are averaged, so that it takes time for the digital value to be
displayed due to the rapid temperature change.
6) The control unit reads the data for 2 channels per 1 scan by the control unit. Read data by utilizing the sample program given in the product specifications and manual.
10 M bit/s (10BASE-T: RJ45)
Supported protocol TCP, UDP, IP, DHCP, FTP, TELNET, HTTP, SMTP, and PPP
Memory size
Approx. 148 kB (for storing htm files)
Setup method
Setup using FP Web Configurator Tool
Applicable crimp teriminals
FP0-PSA4
FP0-PSA1
AFP0634
AFP0631
100 to 240 V AC
85 to 264 V AC
50/60 Hz
47 to 63 Hz
Single-phase
30 A (0 - P) or less, with cold start
0.75 mA or less
10 ms or more
24 V DC
±5%
0.6 A
0.7 A Note)
0 to 0.6 A
0 to 0.7 A
500 mV or less
0.735 A or more
0.63 A or more
Available
Manufacturer
JST
Mfg.Co.,Ltd.
Part number
Applicable wiring
V1.25-M3 (round type)
V1.25-S3A (fork type)
0.35 to 1.65 mm2
AWG #22 to #15
V2-M3 (round type)
V2-S3A (fork type)
1.04 to 2.00 mm2
AWG #17 to #14
7.2 mm .283 inch or less
Control unit current consumption
Type of unit
FP0 control unit
FP0 expansion unit
FP0 intelligent unit
Input/Output points Input: 32 points Note 6)
Notes
Ethernet
communication
■ Current consumption
When CC-Link
Standard
slave unit with a
specifications thermocouple unit
0.8 °C
3 °C
2.5 °C
2 °C
RS232C
communication
RS232C ⇔ Ethernet conversion
(PLC remote programming via Ethernet)
E-mail sending function
Web-server function
Transparent communication (Server/Client)
PPP server function
RS232C terminal block 3-pin: Mainly used for PLC connection
RS232C D-Sub 9-pin: Mainly used for Modem connection
10 BASE-T (RJ45): Used for Ethernet connection and setup
Transmission speed: 1200, 2400, 4800, 9600, 19200,
38400, 57600, 115200 bits/s
Data length: 7 bits/8 bits, Parity: Even/Odd/None
Note: Start up may not be possible if a device with a large inrush current is connected even if below the rated current. In such a case,
we recommend suppressing the inrush current by inserting a 1 to 2Ω resister between the power supply unit and the device.
For details concerning the CC-Link, refer to the CC-Link Partner Association.
When an FP0 thermocouple unit is used with an FP0 CC-Link slave unit, the
measurement accuracy of the thermocouple unit which is installed on the left of
the CC-Link slave unit is as shown in the table below.
Communication
functions
Communication
interface
32X/32Y
Conforming to RS485
CRC (Cyclic Redumdancy Check) method
■ Power supply unit specifications
The cable length has restrictions in communication speed, CC-Link version,
and dedicated cables to be used.
Thermocouple
Max. 700 m 2,296.588 ft.(using twisted pair cable)
Max. 400 m 1,312.336 ft.(using VCTF cable)
0.5 Mbits/s
64 points
(Input: 32 points and Output: 32 points) note)
Note: This point number is the number of points that can be linked for inputting and
outputting via the host PLC and network MEWNET-F. If the output for the I/O link unit
error flag is set to ON, this number becomes 63 points (31 input points and 32 output
points).
S-LINK control unit
Length of the multi-drop connected cables at both ends
■ FP Web-Server unit specifications
Description
Two-wire, half duple
Asynchronous method
2-wire cable (Twisted-pair cable or VCTF 0.75 mm2
× 2C equivalent)
CC-Link cable
Interface
RS485
Station type
Remote device station
Number of occupied stations FPΣ: 1 to 4 stations (switch changeover), FP0: 1 station
Note 1)
Item
Communication method
Synchronous method
4 to 20 mA (K 0 to K 4000) Note 1)
1/4000 (12 bits)
500 µs/channel Note 2)
±1% F.S or less (0 to 55 °C), ±0.6% F.S. or less (25 °C)
FP0-A21
Refresh
FP0-A04I
Voltage output: 4 channels/units Current output: 4 channels/units
1 channel/unit
Number of output points
10 V
Conversion
time
Description
FP0-A04V
Item
FP0-A80
Number of input points
Input range
■ I/O Link unit specifications
2. Analog output specifications
Link/Communication
units
This refers to the current consumed via the power supply
connector of the control unit. If expansion units or intelligent units
are added, the current is increased by the value indicated below.
FP0-C10
FP0-C14
FP0-C16
FP0-C32
FP0-T32
100 mA or less
100 mA or less
40 mA or less
FP0-SL1
150 mA or less
FP0-E8X
FP0-E8R
FP0-E8YR
FP0-E8YT/P
FP0-E16X
FP0-E16R
FP0-E16T/P
FP0-E16YT/P
FP0-E32T/P
FP0-A21
FP0-A80
FP0-A04V
FP0-A04I
FP0-TC4
FP0-TC8
FP0-CCLS
FP0-IOL
FP-WEB
AFP15402 (C-NET adapter)
Expansion unit current consumption
This refers to the current consumed via the power
supply connector of the expansion unit. Units with no
value indication don't have a power supply connector.
60 mA or less
10 mA or less
15 mA or less
10 mA or less
15 mA or less
20 mA or less
20 mA or less
25 mA or less
25 mA or less
40 mA or less
20 mA or less
20 mA or less
20 mA or less
20 mA or less
50 mA or less
100 mA or less
100 mA or less
100 mA or less
60 mA or less
100 mA or less
130 mA or less
25 mA or less
40 mA or less
30 mA or less
40 mA or less
40 mA or less
95 mA or less (at 24 V DC), 240 mA or less (at 12 V DC)
50 mA or less
13
FP0 Product types
FP0
4 Link/communication units
1 Control units
Product name
10
Input: 6
Output: 4
24 V DC
EEPROM
(2.7 k steps)
10
Input: 6
Output: 4
24 V DC
FP0 C14 Control Unit
EEPROM
(2.7 k steps)
14
Input: 8
Output: 6
24 V DC
FP0 C14 Control Unit
with RS232C port
EEPROM
(2.7 k steps)
14
Input: 6
Output: 4
24 V DC
FP0 C16 Control Unit
EEPROM
(2.7 k steps)
16
Input: 8
Output: 8
24 V DC
EEPROM
(2.7 k steps)
16
Input: 8
Output: 8
24 V DC
FP0 C10 Control Unit
EEPROM
(2.7 k steps)
FP0 C10 Control Unit
with RS232C port
FP0 C16 Control Unit
with RS232C port
EEPROM
(5 k steps)
32
Input: 16
Output: 16
EEPROM
(5 k steps)
32
Input: 16
Output: 16
24 V DC
FP0 T32 Control Unit
EEPROM
with RS232C port and
(10 k steps)
Clock/Calendar function
32
Input: 16
Output: 16
24 V DC
FP0 C32 Control Unit
FP0 C32 Control Unit
with RS232C port
FP0 S-LINK Control
Unit with RS232C port
Specications
Built-in memory
(Program
Number of I/O points Power supply
capacity)
voltage
EEPROM
(5 k steps)
128
(S-LINK Input: 64
section) Output: 64
24 V DC
Input
Output
Product
number
Connection type
Part number
FP0-C10RS
FP0-C10RM
FP0-C10CRS
FP0-C10CRM
Terminal block FP0-C14RS
24 V DC
Sink/Sourse (±common) Relay output: 2 A Molex connector FP0-C14RM
24 V DC
Terminal block FP0-C14CRS
Sink/Sourse (±common) Relay output: 2 A Molex connector FP0-C14CRM
Transistor output:
FP0-C16T
24 V DC
NPN 0.1 A
Sink/Sourse (±common) Transistor output: MIL connector
FP0-C16P
PNP 0.1 A
Transistor output:
FP0-C16CT
NPN 0.1 A
24 V DC
Sink/Sourse (±common) Transistor output: MIL connector
FP0-C16CP
PNP 0.1 A
Transistor output:
FP0-C32T
24 V DC
NPN 0.1 A
Sink/Sourse (±common) Transistor output: MIL connector
FP0-C32P
PNP 0.1 A
Transistor output:
FP0-C32CT
24 V DC
NPN 0.1 A
MIL connector
Transistor
output:
Sink/Sourse (±common)
FP0-C32CP
PNP 0.1 A
Transistor
output:
24 V DC
FP0-T32CT
NPN 0.1 A
MIL connector
Sink/Sourse (±common)
Transistor output:
FP0-T32CP
PNP 0.1 A
Terminal block
24 V DC
Relay output: 2 A
Sink/Sourse (±common)
Molex connector
Terminal block
24 V DC
Relay output: 2 A
Sink/Sourse (±common)
Molex connector
Terminal block
24 V DC
AFP02123
AFP02113
AFP02123C
AFP02113C
AFP02223
AFP02213
AFP02223C
AFP02213C
Product
number
Part number
FP0 CC-Link Slave Unit
24 V DC
FP0ñCCLS
AFP07943
FP0 I/O Link Unit
This is a link unit designed to make the FP0 function as a station to MEWNET-F
(remote I/O system).
This is an RS485 adapter designed to allow use of the Computer link function for
connecting to a host computer via C-NET. It comes with a 30cm 11.811 inch
FP0 tool port cable. A power supply is not required.
24 V DC
FP0ñIOL
AFP0732
C-NET Adapter S2 Type
(for FP0 side)
100 to 240 V AC
Specications
This unit is for making the FP0 function as a slave station of the CC-Link.
Only one unit can be connected to the furthest right edge of the FP0 expansion
bus.
Note: Accuracy will change if an FP0 thermocouple unit is used at the same time.
For details, please refer to the catalog or to the CC-Link Unit manual.
AFP02343
C-NET Adapter (RS485)
(for computer side)
This is an RS485 adapter designed to allow use of the Computer link function for
connecting to a network-connected PLC via C-NET from a host computer.
AFP02353
FP Web-Server Unit
Unit for connecting FP series/RS232C interface and Ethernet
Web-Server function and E-mail sending function
AFP02343C
AFP02353C
AFP02553
AFP02543C
AFP02553C
Product name
FP0 Power Supply Unit
Product name
FP0 E8
Expansion Unit
FP0 E16
Expansion Unit
Number of I/O points
8
Input:
8
Input: 4
Output: 4
8
Output: 8
Power supply
voltage
8
16
Input: 16
16
Input: 8
Output: 8
16
Input: 8
Output: 8
16
Output:16
Output
24 V DC
Sink/Sourse (±common)
8
Output: 8
Input
24 V DC
24 V DC
Product
number
Connection type
MIL connector
Part number
AFP03003
FP0-E8X
Terminal block FP0-E8RS
24 V DC
Relay output: 2 A
Sink/Sourse (±common)
Molex connector FP0-E8RM
Relay output: 2 A Terminal block FP0-E8YRS
FP0-E8YT
Transistor output:
MIL connector
FP0-E8YP
NPN 0.1 A
24 V DC
MIL connector FP0-E16X
Sink/Sourse (±common)
AFP03023
AFP03013
AFP03020
AFP03040
AFP03050
24 V DC
Terminal block
Sink/Sourse (±common) Relay output: 2 A Molex connector
24 V DC
Transistor output: MIL connector
Sink/Sourse (±common)
NPN 0.1 A
AFP03323
AFP03313
AFP03343
AFP03353
AFP03340
AFP03350
AFP03543
AFP03553
Transistor output:
NPN 0.1 A
MIL connector
FP0-E16RS
FP0-E16RM
FP0-E16T
FP0-E16P
FP0-E16YT
FP0-E16YP
FP0-E32T
FP0-E32P
AFP03303
Input: 16
Transistor output:
24 V DC
FP0 E32
MIL connector
32
Output:16
NPN 0.1 A
Sink/Sourse (±common)
Expansion Unit
Notes 1) The control units and relay output type expansion units come with a power cable (part number AFP0581).
(The transistor output type expansion units need no power cable.)
2) The terminal block type relay output units have 2 terminal blocks (9 pins) made by Phoenix. Use a 2.5 mm .098 inch wide screwdriver.
Preferably use the specific terminal block screwdriver (part number AFP0806, Phoenix type code SZS0, 4 × 2.5 mm .098 inch) or equivalent.
3) The connector-type relay output units have 2 connectors made by Nihon Molex (Molex type code 51067-0900, 9 pins).
Use the specific Molex connector press-fit tool (part number AFP0805, Nihon Molex type code 57189-5000) or equivalent.
4) The transistor output units have a press-fit socket for wire-pressed terminal cable and contacts.
Use the press-fit tool (part number AXY52000) for wire-pressed terminal cable.
3 Intelligent units
Specications
Product name
FP0 Analog I/O Unit
FP0 A/D Converter Unit
FP0 D/A Converter Unit
FP0 Thermocouple Unit
14
Number or channels : 2 channels
Input range
: 0 to 5 V, -10 to +10 V (Resolution: 1/4000)
0 to 20 mA (Resolution: 1/4000)
Output specifications Number or channels : 1 channels
Output range
: -10 to +10 V (Resolution: 1/4000)
0 to 20 mA (Resolution: 1/4000)
Input specifications Number or channels : 8 channels
Input range
: 0 to 5, -10 to +10 V (Resolution: 1/4000)
0 to 20 mA (Resolution: 1/4000)
Output specifications Number or channels : 4 channels
Output range
: -10 to +10 V (Resolution: 1/4000)
4 to 20 mA (Resolution: 1/4000)
Product number
24 V DC
Part number
Specications
Output: 0.7 A, 24 V DC
Input voltage: 100 to 240 V AC
Product name
AFP0480
FP0-A80
AFP0401
FP0-A04V
AFP04121
K, J, T, R thermocouple, Resolution: 0.1 °C
FP0-A04 I
FP0-TC4
AFP04123
AFP0420
K, J, T, R thermocouple, Resolution: 0.1 °C
FP0-TC8
AFP0421
AFP0610
Product
number
Part number
FP0-PSA4
AFP0634
Standard Programming Tool
Software
Control FPWIN GR Ver.2
Part number
Specifications
English-language
menu
Standard
Upgrade (to upgrade from Ver.1.1)
AFPS10520
Chinese-language
menu
Standard
Upgrade (to upgrade from Ver.1.1)
AFPS10820
Korean-language
menu
Standard
AFPS10920
Full type (for all type FP series PLC)
AFPS50540
Small type (for FP0, FPΣ, FP1, FP-e and FP-M)
AFPS51540
Upgrade (for full type)
AFPS50540R
Conforms to IEC61131-3
Programming Tool Software
Control FPWIN Pro Ver.5
English-language
menu
PC Connection Cable
Between D-sub 9 pins and DIN 5 pins, 3 m length
AFPS10520R
AFPS10820R
AFC8503
7 Options and additional parts
Product name
Specifications
Part number
Data clear type
AFP8670
Data hold type
AFP8671
Terminal Screwdriver
Relay output type
Necessary when wiring terminals block (Phoenix).
AFP0806
Molex Connector Pressure Contact Tool
Necessary when wiring relay output type and Molex connectors. (MOLEX: 57189-5000)
AFP0805
Multi-Wire Connector Pressure Contact Tool
Necessary when wiring transistor output type connectors.
AXY52000
Slim 30 Type Mounting Plate
Screw-stop attachment plate for 30 mm 1.181 inch width the unit.
AFP0811 (set for 10)
Slim Type Mounting Plate
Screw-stop attachment plate for FP0 expansion unit. Slim model.
AFP0803 (set for 10)
Flat Type Mounting Plate
Screw-stop attachment plate for FP0 control unit. Flat model.
FP Memory Loader
AFP0804 (set for 10)
Relay Output Molex Type
I/O Cable
Loose-wiring cable (9 leads) AWG20, with Molex socket attached at one end,
0.5 mm2, 1 set: 2 cables (blue & white).
Length: 1 m 3.281 ft. AFP0551 (2 cable set)
Transistor Output Type
I/O Cable
Wire-pressed terminal cable (10 leads) AWG22, 0.3 mm2 with connectors
attached at one end, 1 set: 2 cables (blue & white).
Length: 1 m 3.281 ft. AFP0521 (2 cable set)
Flat Cable Connector for
FPΣ/FP0 Transistor Type Unit
If you are using flat cable connector, request the part specified below for a connector with an
asymmetrical design to prevent mistaken polarity. (10-pin)
Terminal Socket
Attaches to relay output and terminal block type. Additional part
Molex Socket
Attaches to relay output and Molex connector types. Additional part
Wire-Press Socket
Attaches to transistor output type. Additional part
Power Cable
Attaches to FP0 various units. Additional part Length: 1 m 3.281 ft.
Input specifications
FP0-A21
AFP8532
FP-WEB
6 Programming tools
AFP02643C
AFP02653C
AFP8536
24 V DC
5 Power supply unit
2 Expansion units
Specications
AFP15402
AFP02543
AFP02700
FP0-SL1
Power supply
voltage
Product name
Length: 3 m 9.843 ft. AFP0553 (2 cable set)
Length: 3 m 9.843 ft. AFP0523 (2 cable set)
AXM110915
AFP0802
(2 sockets per pack)
AFP0801
(2 sockets per pack)
AFP0807
(2 sockets per pack)
AFP0581
(1 socket per pack)
15
FP0 Product types
FP0
4 Link/communication units
1 Control units
Product name
10
Input: 6
Output: 4
24 V DC
EEPROM
(2.7 k steps)
10
Input: 6
Output: 4
24 V DC
FP0 C14 Control Unit
EEPROM
(2.7 k steps)
14
Input: 8
Output: 6
24 V DC
FP0 C14 Control Unit
with RS232C port
EEPROM
(2.7 k steps)
14
Input: 6
Output: 4
24 V DC
FP0 C16 Control Unit
EEPROM
(2.7 k steps)
16
Input: 8
Output: 8
24 V DC
EEPROM
(2.7 k steps)
16
Input: 8
Output: 8
24 V DC
FP0 C10 Control Unit
EEPROM
(2.7 k steps)
FP0 C10 Control Unit
with RS232C port
FP0 C16 Control Unit
with RS232C port
EEPROM
(5 k steps)
32
Input: 16
Output: 16
EEPROM
(5 k steps)
32
Input: 16
Output: 16
24 V DC
FP0 T32 Control Unit
EEPROM
with RS232C port and
(10 k steps)
Clock/Calendar function
32
Input: 16
Output: 16
24 V DC
FP0 C32 Control Unit
FP0 C32 Control Unit
with RS232C port
FP0 S-LINK Control
Unit with RS232C port
Specications
Built-in memory
(Program
Number of I/O points Power supply
capacity)
voltage
EEPROM
(5 k steps)
128
(S-LINK Input: 64
section) Output: 64
24 V DC
Input
Output
Product
number
Connection type
Part number
FP0-C10RS
FP0-C10RM
FP0-C10CRS
FP0-C10CRM
Terminal block FP0-C14RS
24 V DC
Sink/Sourse (±common) Relay output: 2 A Molex connector FP0-C14RM
24 V DC
Terminal block FP0-C14CRS
Sink/Sourse (±common) Relay output: 2 A Molex connector FP0-C14CRM
Transistor output:
FP0-C16T
24 V DC
NPN 0.1 A
Sink/Sourse (±common) Transistor output: MIL connector
FP0-C16P
PNP 0.1 A
Transistor output:
FP0-C16CT
NPN 0.1 A
24 V DC
Sink/Sourse (±common) Transistor output: MIL connector
FP0-C16CP
PNP 0.1 A
Transistor output:
FP0-C32T
24 V DC
NPN 0.1 A
Sink/Sourse (±common) Transistor output: MIL connector
FP0-C32P
PNP 0.1 A
Transistor output:
FP0-C32CT
24 V DC
NPN 0.1 A
MIL connector
Transistor
output:
Sink/Sourse (±common)
FP0-C32CP
PNP 0.1 A
Transistor
output:
24 V DC
FP0-T32CT
NPN 0.1 A
MIL connector
Sink/Sourse (±common)
Transistor output:
FP0-T32CP
PNP 0.1 A
Terminal block
24 V DC
Relay output: 2 A
Sink/Sourse (±common)
Molex connector
Terminal block
24 V DC
Relay output: 2 A
Sink/Sourse (±common)
Molex connector
Terminal block
24 V DC
AFP02123
AFP02113
AFP02123C
AFP02113C
AFP02223
AFP02213
AFP02223C
AFP02213C
Product
number
Part number
FP0 CC-Link Slave Unit
24 V DC
FP0ñCCLS
AFP07943
FP0 I/O Link Unit
This is a link unit designed to make the FP0 function as a station to MEWNET-F
(remote I/O system).
This is an RS485 adapter designed to allow use of the Computer link function for
connecting to a host computer via C-NET. It comes with a 30cm 11.811 inch
FP0 tool port cable. A power supply is not required.
24 V DC
FP0ñIOL
AFP0732
C-NET Adapter S2 Type
(for FP0 side)
100 to 240 V AC
Specications
This unit is for making the FP0 function as a slave station of the CC-Link.
Only one unit can be connected to the furthest right edge of the FP0 expansion
bus.
Note: Accuracy will change if an FP0 thermocouple unit is used at the same time.
For details, please refer to the catalog or to the CC-Link Unit manual.
AFP02343
C-NET Adapter (RS485)
(for computer side)
This is an RS485 adapter designed to allow use of the Computer link function for
connecting to a network-connected PLC via C-NET from a host computer.
AFP02353
FP Web-Server Unit
Unit for connecting FP series/RS232C interface and Ethernet
Web-Server function and E-mail sending function
AFP02343C
AFP02353C
AFP02553
AFP02543C
AFP02553C
Product name
FP0 Power Supply Unit
Product name
FP0 E8
Expansion Unit
FP0 E16
Expansion Unit
Number of I/O points
8
Input:
8
Input: 4
Output: 4
8
Output: 8
Power supply
voltage
8
16
Input: 16
16
Input: 8
Output: 8
16
Input: 8
Output: 8
16
Output:16
Output
24 V DC
Sink/Sourse (±common)
8
Output: 8
Input
24 V DC
24 V DC
Product
number
Connection type
MIL connector
Part number
AFP03003
FP0-E8X
Terminal block FP0-E8RS
24 V DC
Relay output: 2 A
Sink/Sourse (±common)
Molex connector FP0-E8RM
Relay output: 2 A Terminal block FP0-E8YRS
FP0-E8YT
Transistor output:
MIL connector
FP0-E8YP
NPN 0.1 A
24 V DC
MIL connector FP0-E16X
Sink/Sourse (±common)
AFP03023
AFP03013
AFP03020
AFP03040
AFP03050
24 V DC
Terminal block
Sink/Sourse (±common) Relay output: 2 A Molex connector
24 V DC
Transistor output: MIL connector
Sink/Sourse (±common)
NPN 0.1 A
AFP03323
AFP03313
AFP03343
AFP03353
AFP03340
AFP03350
AFP03543
AFP03553
Transistor output:
NPN 0.1 A
MIL connector
FP0-E16RS
FP0-E16RM
FP0-E16T
FP0-E16P
FP0-E16YT
FP0-E16YP
FP0-E32T
FP0-E32P
AFP03303
Input: 16
Transistor output:
24 V DC
FP0 E32
MIL connector
32
Output:16
NPN 0.1 A
Sink/Sourse (±common)
Expansion Unit
Notes 1) The control units and relay output type expansion units come with a power cable (part number AFP0581).
(The transistor output type expansion units need no power cable.)
2) The terminal block type relay output units have 2 terminal blocks (9 pins) made by Phoenix. Use a 2.5 mm .098 inch wide screwdriver.
Preferably use the specific terminal block screwdriver (part number AFP0806, Phoenix type code SZS0, 4 × 2.5 mm .098 inch) or equivalent.
3) The connector-type relay output units have 2 connectors made by Nihon Molex (Molex type code 51067-0900, 9 pins).
Use the specific Molex connector press-fit tool (part number AFP0805, Nihon Molex type code 57189-5000) or equivalent.
4) The transistor output units have a press-fit socket for wire-pressed terminal cable and contacts.
Use the press-fit tool (part number AXY52000) for wire-pressed terminal cable.
3 Intelligent units
Specications
Product name
FP0 Analog I/O Unit
FP0 A/D Converter Unit
FP0 D/A Converter Unit
FP0 Thermocouple Unit
14
Number or channels : 2 channels
Input range
: 0 to 5 V, -10 to +10 V (Resolution: 1/4000)
0 to 20 mA (Resolution: 1/4000)
Output specifications Number or channels : 1 channels
Output range
: -10 to +10 V (Resolution: 1/4000)
0 to 20 mA (Resolution: 1/4000)
Input specifications Number or channels : 8 channels
Input range
: 0 to 5, -10 to +10 V (Resolution: 1/4000)
0 to 20 mA (Resolution: 1/4000)
Output specifications Number or channels : 4 channels
Output range
: -10 to +10 V (Resolution: 1/4000)
4 to 20 mA (Resolution: 1/4000)
Product number
24 V DC
Part number
Specications
Output: 0.7 A, 24 V DC
Input voltage: 100 to 240 V AC
Product name
AFP0480
FP0-A80
AFP0401
FP0-A04V
AFP04121
K, J, T, R thermocouple, Resolution: 0.1 °C
FP0-A04 I
FP0-TC4
AFP04123
AFP0420
K, J, T, R thermocouple, Resolution: 0.1 °C
FP0-TC8
AFP0421
AFP0610
Product
number
Part number
FP0-PSA4
AFP0634
Standard Programming Tool
Software
Control FPWIN GR Ver.2
Part number
Specifications
English-language
menu
Standard
Upgrade (to upgrade from Ver.1.1)
AFPS10520
Chinese-language
menu
Standard
Upgrade (to upgrade from Ver.1.1)
AFPS10820
Korean-language
menu
Standard
AFPS10920
Full type (for all type FP series PLC)
AFPS50540
Small type (for FP0, FPΣ, FP1, FP-e and FP-M)
AFPS51540
Upgrade (for full type)
AFPS50540R
Conforms to IEC61131-3
Programming Tool Software
Control FPWIN Pro Ver.5
English-language
menu
PC Connection Cable
Between D-sub 9 pins and DIN 5 pins, 3 m length
AFPS10520R
AFPS10820R
AFC8503
7 Options and additional parts
Product name
Specifications
Part number
Data clear type
AFP8670
Data hold type
AFP8671
Terminal Screwdriver
Relay output type
Necessary when wiring terminals block (Phoenix).
AFP0806
Molex Connector Pressure Contact Tool
Necessary when wiring relay output type and Molex connectors. (MOLEX: 57189-5000)
AFP0805
Multi-Wire Connector Pressure Contact Tool
Necessary when wiring transistor output type connectors.
AXY52000
Slim 30 Type Mounting Plate
Screw-stop attachment plate for 30 mm 1.181 inch width the unit.
AFP0811 (set for 10)
Slim Type Mounting Plate
Screw-stop attachment plate for FP0 expansion unit. Slim model.
AFP0803 (set for 10)
Flat Type Mounting Plate
Screw-stop attachment plate for FP0 control unit. Flat model.
FP Memory Loader
AFP0804 (set for 10)
Relay Output Molex Type
I/O Cable
Loose-wiring cable (9 leads) AWG20, with Molex socket attached at one end,
0.5 mm2, 1 set: 2 cables (blue & white).
Length: 1 m 3.281 ft. AFP0551 (2 cable set)
Transistor Output Type
I/O Cable
Wire-pressed terminal cable (10 leads) AWG22, 0.3 mm2 with connectors
attached at one end, 1 set: 2 cables (blue & white).
Length: 1 m 3.281 ft. AFP0521 (2 cable set)
Flat Cable Connector for
FPΣ/FP0 Transistor Type Unit
If you are using flat cable connector, request the part specified below for a connector with an
asymmetrical design to prevent mistaken polarity. (10-pin)
Terminal Socket
Attaches to relay output and terminal block type. Additional part
Molex Socket
Attaches to relay output and Molex connector types. Additional part
Wire-Press Socket
Attaches to transistor output type. Additional part
Power Cable
Attaches to FP0 various units. Additional part Length: 1 m 3.281 ft.
Input specifications
FP0-A21
AFP8532
FP-WEB
6 Programming tools
AFP02643C
AFP02653C
AFP8536
24 V DC
5 Power supply unit
2 Expansion units
Specications
AFP15402
AFP02543
AFP02700
FP0-SL1
Power supply
voltage
Product name
Length: 3 m 9.843 ft. AFP0553 (2 cable set)
Length: 3 m 9.843 ft. AFP0523 (2 cable set)
AXM110915
AFP0802
(2 sockets per pack)
AFP0801
(2 sockets per pack)
AFP0807
(2 sockets per pack)
AFP0581
(1 socket per pack)
15
FP0 Mounting plates
FP0 Options
■ Installation and dimensions
■ Wiring tools
● Direct mounting on a panel 1: Use of the slim type mounting plate
The control unit and expansion units can be directly mounted on a panel by using the optional slim type mounting plate.
Control unit only
Control unit + Expansion units
Terminal screwdriver
Molex connector pressure contact tool
Multi-wire connector pressure contact tool
Necessary when wiring relay output type and
terminals block (Phoenix).
Necessary when wiring connector type and relay
output
Necessary when wiring transistor output type
connectors.
Part number: AFP0806
■ Parts for mounting
25.0
.984
10.0
.394
100
3.937
6.0
.236
UP
UP
UP
UP
90.0
3.543
φ 5.0
φ .197
AFP0803
30
1.181
60.0
2.362
φ 10.0
φ .394
3.5
.138
φ 5.0
φ .197
2.5
.098
AFP0803
AFP0803
AFP0803
AFP0803
6
.236
60.0
2.362
6.2
.244
6.0
.236
UP
90.0
3.543
φ 5.0
φ .197
AFP0803
Slim 30 type mounting plate
Slim type mounting plate
Screw-stop attachment plate.
30 mm 1.181 inch width type
Screw-stop attachment plate.
Slim model.
Part number: AFP0811 (set of 10)
When mounting the 32-I/O-point type or FP0SL1 control unit, position the right-side surface
of the unit flush with that of the plate.
60.0
2.362
3- φ5.0
3- φ.197
10.0
.394
3.5
.138
AFP0804
2.5
.098
2.2
.087
60.0 70.0
2.362 2.756
75.0
2.953
25.0 25.0 25.0
.984 .984 .984
60.0 ±0.5
2.362 ±.020
25.0
.984
90.0
3.543
60.0
2.362
φ 10.0
φ .394
AFP0811
UP
90.0
3.543
60.0
2.362
φ 10.0
φ .394
4.0
.158
Part number: AXY52000
UP
45 1.772
30 1.181
4.0
.158
Four plates connected
φ 10.0 φ .394
φ 5.0 10
φ .197 .394
4 .157
17.5 12.5
.689 .492
UP
30 1.181
45 1.772
62.5
2.460
One plate
Dimensions after mounting with the slim type
mounting plates
90 3.543
● Mounting dimensions (Unit: mm inch)
Slim type mounting plate
Part number: AFP0805
17.5 .689
Part number: AFP0803 (set of 10)
60.0 ±0.5
2.362 ±.020
3- φ 5.0
3- φ .197
φ 5.0
φ .197
φ 10.0 φ .394
4.0
.158
Flat type mounting plate
60.0 ±0.5
2.362 ±.020
Screw-stop attachment plate.
Flat model.
Part number: AFP0804 (set of 10)
12.5
.492
60.0
2.362
3- φ 5.0
3- φ .197
■ Flat cable connector
■ I/O cables
If you are using flat cable connector, request the part
specified below for a connector with an asymmetrical
design to prevent mistaken polarity.
φ 5.0
φ .197
Part number: AXM110915
● Direct mounting on a panel 2: Use of the flat type mounting plate (Note: Expansion is impossible.)
The control unit can be directly mounted on a panel by using the optional flat type mounting plate.
Mounting on a DIN rail is also possible.
Mounting on a panel
Relay output Molex type I/O cable
Transistor output type I/O cable
Loose-wiring cable (9 leads) AWG20, with Molex socket attached
at one end, 0.5 mm2,1 set: 2 cables (blue & white).
2 cable set
2 cable set
Wire-pressed terminal cable (10 leads) AWG22, 0.3 mm2 with
connectors attached at one end, 1 set: 2 cables (blue & white).
2 cable set
2 cable set
Part number: AFP0551
Part number: AFP0553
Part number: AFP0521
Part number: AFP0523
Notes:
• One I/O cable set (2 cables) is necessary with the following models: FP0-C10RS/C10RM, C14RS/C14RM, E8RS/E8RM, E16RS/E16RM
• One I/O cable set (2 cables) is necessary with the following models: FP0-C16T/C16P/E16X/E16T/E16P/E16YT/E16YP
• Two I/O cable sets (total 4 cables) are necessary with the following models: FP0-C32T/C32P/E32T/E32P
● Mounting dimensions (Unit: mm inch)
Flat type mounting plate
Dimensions after mounting with the flat type
mounting plate
31.2* 1.228
25.0*.984
60.0
2.362
6.2
.244
■ Additional parts
YO–7
0
RUN
1
2
3
PROG.
4
5
6
ERROR
7
ALARM
RUN
UP
90.0
3.543
AFP0804
2.2
.086
16
4.0
.157
φ 5.0
φ .197
φ 10.0
φ .394
60.0 ±0.5
2.362 ±.020
60.0
2.362
PROG.
90.0
3.543
YO–7
0
1
2
3
4
5
6
7
3- φ 5.0
3- φ.197
* When mounting the 32-I/O-point
type or FP0-SL1 control unit, these
dimensions increase by 5 mm .197
inch each.
Terminal socket
Molex socket
Wire-press socket
Power cable
Attaches to relay output and terminal block
type. Additional part
Attaches to relay output and Molex connector
types. Additional part
Attaches to transistor output type.
Additional part
Attaches to control unit and relay output type
expansion unit. Additional part
Length: 1 m
3.281ft. Part number: AFP0581
(1 cable per pack)
Part number: AFP0802
(2 sockets per pack)
Part number: AFP0801
(2 sockets per pack)
Part number: AFP0807
(2 sockets per pack)
17
FP0 Mounting plates
FP0 Options
■ Installation and dimensions
■ Wiring tools
● Direct mounting on a panel 1: Use of the slim type mounting plate
The control unit and expansion units can be directly mounted on a panel by using the optional slim type mounting plate.
Control unit only
Control unit + Expansion units
Terminal screwdriver
Molex connector pressure contact tool
Multi-wire connector pressure contact tool
Necessary when wiring relay output type and
terminals block (Phoenix).
Necessary when wiring connector type and relay
output
Necessary when wiring transistor output type
connectors.
Part number: AFP0806
■ Parts for mounting
25.0
.984
10.0
.394
100
3.937
6.0
.236
UP
UP
UP
UP
90.0
3.543
φ 5.0
φ .197
AFP0803
30
1.181
60.0
2.362
φ 10.0
φ .394
3.5
.138
φ 5.0
φ .197
2.5
.098
AFP0803
AFP0803
AFP0803
AFP0803
6
.236
60.0
2.362
6.2
.244
6.0
.236
UP
90.0
3.543
φ 5.0
φ .197
AFP0803
Slim 30 type mounting plate
Slim type mounting plate
Screw-stop attachment plate.
30 mm 1.181 inch width type
Screw-stop attachment plate.
Slim model.
Part number: AFP0811 (set of 10)
When mounting the 32-I/O-point type or FP0SL1 control unit, position the right-side surface
of the unit flush with that of the plate.
60.0
2.362
3- φ5.0
3- φ.197
10.0
.394
3.5
.138
AFP0804
2.5
.098
2.2
.087
60.0 70.0
2.362 2.756
75.0
2.953
25.0 25.0 25.0
.984 .984 .984
60.0 ±0.5
2.362 ±.020
25.0
.984
90.0
3.543
60.0
2.362
φ 10.0
φ .394
AFP0811
UP
90.0
3.543
60.0
2.362
φ 10.0
φ .394
4.0
.158
Part number: AXY52000
UP
45 1.772
30 1.181
4.0
.158
Four plates connected
φ 10.0 φ .394
φ 5.0 10
φ .197 .394
4 .157
17.5 12.5
.689 .492
UP
30 1.181
45 1.772
62.5
2.460
One plate
Dimensions after mounting with the slim type
mounting plates
90 3.543
● Mounting dimensions (Unit: mm inch)
Slim type mounting plate
Part number: AFP0805
17.5 .689
Part number: AFP0803 (set of 10)
60.0 ±0.5
2.362 ±.020
3- φ 5.0
3- φ .197
φ 5.0
φ .197
φ 10.0 φ .394
4.0
.158
Flat type mounting plate
60.0 ±0.5
2.362 ±.020
Screw-stop attachment plate.
Flat model.
Part number: AFP0804 (set of 10)
12.5
.492
60.0
2.362
3- φ 5.0
3- φ .197
■ Flat cable connector
■ I/O cables
If you are using flat cable connector, request the part
specified below for a connector with an asymmetrical
design to prevent mistaken polarity.
φ 5.0
φ .197
Part number: AXM110915
● Direct mounting on a panel 2: Use of the flat type mounting plate (Note: Expansion is impossible.)
The control unit can be directly mounted on a panel by using the optional flat type mounting plate.
Mounting on a DIN rail is also possible.
Mounting on a panel
Relay output Molex type I/O cable
Transistor output type I/O cable
Loose-wiring cable (9 leads) AWG20, with Molex socket attached
at one end, 0.5 mm2,1 set: 2 cables (blue & white).
2 cable set
2 cable set
Wire-pressed terminal cable (10 leads) AWG22, 0.3 mm2 with
connectors attached at one end, 1 set: 2 cables (blue & white).
2 cable set
2 cable set
Part number: AFP0551
Part number: AFP0553
Part number: AFP0521
Part number: AFP0523
Notes:
• One I/O cable set (2 cables) is necessary with the following models: FP0-C10RS/C10RM, C14RS/C14RM, E8RS/E8RM, E16RS/E16RM
• One I/O cable set (2 cables) is necessary with the following models: FP0-C16T/C16P/E16X/E16T/E16P/E16YT/E16YP
• Two I/O cable sets (total 4 cables) are necessary with the following models: FP0-C32T/C32P/E32T/E32P
● Mounting dimensions (Unit: mm inch)
Flat type mounting plate
Dimensions after mounting with the flat type
mounting plate
31.2* 1.228
25.0*.984
60.0
2.362
6.2
.244
■ Additional parts
YO–7
0
RUN
1
2
3
PROG.
4
5
6
ERROR
7
ALARM
RUN
UP
90.0
3.543
AFP0804
2.2
.086
16
4.0
.157
φ 5.0
φ .197
φ 10.0
φ .394
60.0 ±0.5
2.362 ±.020
60.0
2.362
PROG.
90.0
3.543
YO–7
0
1
2
3
4
5
6
7
3- φ 5.0
3- φ.197
* When mounting the 32-I/O-point
type or FP0-SL1 control unit, these
dimensions increase by 5 mm .197
inch each.
Terminal socket
Molex socket
Wire-press socket
Power cable
Attaches to relay output and terminal block
type. Additional part
Attaches to relay output and Molex connector
types. Additional part
Attaches to transistor output type.
Additional part
Attaches to control unit and relay output type
expansion unit. Additional part
Length: 1 m
3.281ft. Part number: AFP0581
(1 cable per pack)
Part number: AFP0802
(2 sockets per pack)
Part number: AFP0801
(2 sockets per pack)
Part number: AFP0807
(2 sockets per pack)
17
FP0
FP0 Dimensions
● External dimensions (unit: mm inch)
■ FP0 S-LINK Control Unit
● External dimensions
(unit: mm inch)
30.0
1.181
RUN
● Terminal array
PROG
ERROR
ADDRESS
ERROR
3.5
.138
60.0
2.362
C10RS/C10RM/ C14RS/C14RM/
C10CRS/C10CRM C14CRS/C14CRM
(10)
(.394)
25.0
.984
60.0
2.362
Input
EXPANSION
CONNECTOR
ERROR
ALARM
RUN
PROG.
Note 1)
90.0
3.543
90.0
3.543
Output terminal block
RS232C port (C10CR, C14CR only)
(9)
(.354)
(7.5)
(.295)
DIN standard rail
(DIN EN50022 35 mm
1.378 inch width) attachment gap
(17)
(.669)
Notes:
1) DIN rail is attached on the center of the unit.
2) The FP0-E8YRS is not equipped with an input
terminal block.
Output
Approx.
130.0
5.118
X0
X0
X0
X0
X1
X1
X1
X1
X2
X2
X2
X2
X3
X3
X3
X3
X4
X4
(NC)
X4
X5
X5
(NC)
X5
(NC)
X6
(NC)
X6
(NC)
X7
(NC)
X7
COM
COM
COM
COM
Y0
Y0
Y0
Y0
Y1
Y1
Y1
Y1
(NC)
Y2
Y2
Y2
(NC)
Y3
Y3
Y3
COM
COM
(NC)
Y4
SD
60.0
2.362
(10)
(.394)
25.0
.984
EXPANSION
CONNECTOR
ERR
1
2
3
4
ALARM
RUN
EXPANSION
CONNECTOR
MODE
PROG.
RUN
PROG
E16RS/E16RM/
E8YRS
E8RS/E8RM
(unit: mm inch)
60.0
2.362
(10)
(.394)
● External dimensions
● RS232C port
Terminal array
1
2
3
4
5
SET
90.0
3.543
24V
0V
D
G
24V
IN
0V
OFF ON
V0
90.0
3.543
I 0
IN COM
V1
FP0 - SL1
Input terminal block Note 2)
■ FP0 Analog I/O Unit, D/A Converter Unit
I 1
V
OUT
I
COM
(7.5)
(.295)
(9)
(.354)
SG
RD
DIN standard rail
(DIN EN50022 35 mm 1.378 inch width)
attachment gap
(17)
(.669)
SD
■ FP0 A/D Converter Unit, Thermocouple Unit
Y2
Y4
(NC)
Y5
● External dimensions
COM
COM
(NC)
Y6
(unit: mm inch)
Y3
Y5
(NC)
Y7
COM
COM
COM
COM
25.0
.984
FP0 - A21
■ Control units and expansion units * For the relay output type, the terminal block type is listed as the representative type.
FP0-C10RS/C10RM/C10CRS/C10CRM/C14RS/C14RM/C14CRS/C14CRM
FP0-E8RS/E8RM/E8YRS/E16RS/E16RM
■ FP0 CC-Link Unit, I/O Link Unit
● External dimensions
(unit: mm inch)
(10)
(.394)
25.0
.984
60.0
2.362
60.0
2.362
(13)
(.512)
FP0-C16T/C16P/C16CT/C16CP/E16T/E16P/E8X/E8YT/E8YP
3.5
.138
60.0
2.362
Note 3)
Input connector
25.0
.984
Input (8 points/common)
60.0
2.362
18
.709
XO-7
0
RUN
1
2
EXPANSION
CONNECTOR
3
PROG.
4
5
6
7
ERROR
ALARM
RUN
PROG.
YO-7
90.0
3.543
Note 1)
0
90.0
3.543
1
2
3
4
5
6
7
Approx.
130.0
5.118
Note 2)
Output connector
RS232C port (C16CT/C16CP only)
(9)
(.354)
(7.5)
(.295)
DIN standard rail
(DIN EN50022 35 mm
1.378 inch width) attachment gap
(17)
(.669)
Notes:
1) DIN rail is attached on the center of the unit.
2) The FP0-E8X has no output connector.
3) The FP0-E8YT and E8YP has no input connector.
● Terminal array
X0 X1
X2 X3
X4 X5
X6 X7
COM COM
● RS232C port
Terminal array
90.0
3.543
SD
4.5
.177
3.5
.138
SG
RD
■ FP0 Power Supply Unit
● External dimensions
Y1
Y3
Y5
Y7
(-)
(unit: mm inch)
● External dimensions
8.50 .335
60.0
2.362
Note: Two COM terminals on the input circuit are connected
inside the unit.
Note 4)
60.0
2.362
Note 2)
Input connector
30.0
1.181
XO-7
X8-F
0
1
RUN
EXPANSION
2
3
PROG.
4
CONNECTOR
5
6
7
ERROR
8
9
ALARM
A
B
RUN
C
D
E
F
90.0
3.543
PROG.
YO-7
Note 1)
Y8-F
0
90.0
3.543
1
2
3
4
5
90.0
● Terminal array
6
X0 X1
X2 X3
X4 X5
X6 X7
COM COM
X8 X9
XA XB
XC XD
XE XF
COM COM
4.5
.177
● RS232C port
Terminal array
3.5
.138
3.5
.138
■ External Dimensions During Expansions
SG
RD
● Top view
(with DIN rail
attached)
60.0
2.362
SD
(67.5)
(2.657)
Output (16 points/common)
7
8
9
A
B
Approx.
130.0
5.118
C
D
E
F
Note 3)
Output connector
RS232C port (C32CT/C32CP only)
(17)
Notes:
(.669)
1) DIN rail is attached on the center of the unit.
2) The FP0-E32T, E32P, E16X, E16YT and E16YP are
25 mm .984 inch each.
3) The FP0-E16X has no output connector.
4) The FP0-E16YT and E16YP have no input connector.
18
(9)
(.354)
(7.5)
(.295)
DIN standard rail
(DIN EN50022 35 mm
1.378 inch width) attachment gap
60.0
2.362
Output
terminal
Input (16 points/common)
60.0
2.362
18
.709
19.2
.756
3.543
Input
terminal
Connection
terminal
90.0
3.543
● External dimensions (unit: mm inch)
35.0
1.378
FP0-C32T/C32P/C32CT/C32CP/E32T/E32P/E16X/E16YT/E16YP
3.5
.138
(unit: mm inch)
25.0
.984
4.5
.177
3.5
.138
■ FP0 Web-Server Unit
Output (8 points/common)
Y0
Y2
Y4
Y6
(+)
90.0
3.543
FP0-CCLS
● External dimensions (unit: mm inch)
Y0
Y2
Y4
Y6
(+)
Y1
Y3
Y5
Y7
(-)
Y8
YA
YC
YE
(+)
Y9
YB
YD
YF
(-)
B
A
● Front view
XO-7
X8-F
XO-7
C
X8-F
0
RUN
XO-7
Y8-F
Y8-F
Notes:
1) Four COM terminals on the input circuit are connected
inside the unit.
2) Two (+) terminals and two (-) terminals on the output circuit
are connected respectively inside the unit.
4
8
8
8
9
8
9
A
B
B
C
D
E
F
7
9
A
C
D
E
90.0
3.543
5
6
7
B
C
F
3
4
5
6
A
B
D
E
1
2
4
7
9
A
C
0
3
5
6
Y8-F
1
2
4
7
F
YO-7
0
3
5
6
E
Y8-F
1
2
3
D
F
YO-7
0
1
2
(45)
(1.772)
B
C
E
F
YO-7
0
9
B
D
E
F
YO-7
7
A
C
D
E
P ROG.
5
8
9
C
D
6
7
A
B
C
3
4
5
8
9
A
B
RUN
2
3
6
7
8
9
1
4
5
6
7
8
0
2
3
4
5
6
A
X8-F
1
2
3
4
ALARM
XO-7
0
1
2
PROG
ERROR
D
X8-F
0
1
D
E
F
F
(45)
(1.772)
A+B+C+D dimensions
Control unit
type
FP0-C10CRS
FP0-C10CRS
FP0-C10RM
FP0-C10CRM
FP0-C14RS
FP0-C14CRS
FP0-C14RM
FP0-C14CRM
FP0-C16T
FP0-C16P
FP0-C16CT
FP0-C16CP
FP0-C32T
FP0-C32P
FP0-C32CT
FP0-C32CP
FP0-SL1
FP0-T32CT
FP0-T32CP
A+B
A+B+C
A+B+C+D
A
3 expansion
Control unit only 1 expansion unit 2 expansion
connected
units connected units connected
25 mm
.984 inch
50 mm
1.969 inch
75 mm
2.953 inch
100 mm
3.937 inch
30 mm
1.181 inch
55 mm
2.165 inch
80 mm
3.150 inch
105 mm
4.134 inch
19
FP0
FP0 Dimensions
● External dimensions (unit: mm inch)
■ FP0 S-LINK Control Unit
● External dimensions
(unit: mm inch)
30.0
1.181
RUN
● Terminal array
PROG
ERROR
ADDRESS
ERROR
3.5
.138
60.0
2.362
C10RS/C10RM/ C14RS/C14RM/
C10CRS/C10CRM C14CRS/C14CRM
(10)
(.394)
25.0
.984
60.0
2.362
Input
EXPANSION
CONNECTOR
ERROR
ALARM
RUN
PROG.
Note 1)
90.0
3.543
90.0
3.543
Output terminal block
RS232C port (C10CR, C14CR only)
(9)
(.354)
(7.5)
(.295)
DIN standard rail
(DIN EN50022 35 mm
1.378 inch width) attachment gap
(17)
(.669)
Notes:
1) DIN rail is attached on the center of the unit.
2) The FP0-E8YRS is not equipped with an input
terminal block.
Output
Approx.
130.0
5.118
X0
X0
X0
X0
X1
X1
X1
X1
X2
X2
X2
X2
X3
X3
X3
X3
X4
X4
(NC)
X4
X5
X5
(NC)
X5
(NC)
X6
(NC)
X6
(NC)
X7
(NC)
X7
COM
COM
COM
COM
Y0
Y0
Y0
Y0
Y1
Y1
Y1
Y1
(NC)
Y2
Y2
Y2
(NC)
Y3
Y3
Y3
COM
COM
(NC)
Y4
SD
60.0
2.362
(10)
(.394)
25.0
.984
EXPANSION
CONNECTOR
ERR
1
2
3
4
ALARM
RUN
EXPANSION
CONNECTOR
MODE
PROG.
RUN
PROG
E16RS/E16RM/
E8YRS
E8RS/E8RM
(unit: mm inch)
60.0
2.362
(10)
(.394)
● External dimensions
● RS232C port
Terminal array
1
2
3
4
5
SET
90.0
3.543
24V
0V
D
G
24V
IN
0V
OFF ON
V0
90.0
3.543
I 0
IN COM
V1
FP0 - SL1
Input terminal block Note 2)
■ FP0 Analog I/O Unit, D/A Converter Unit
I 1
V
OUT
I
COM
(7.5)
(.295)
(9)
(.354)
SG
RD
DIN standard rail
(DIN EN50022 35 mm 1.378 inch width)
attachment gap
(17)
(.669)
SD
■ FP0 A/D Converter Unit, Thermocouple Unit
Y2
Y4
(NC)
Y5
● External dimensions
COM
COM
(NC)
Y6
(unit: mm inch)
Y3
Y5
(NC)
Y7
COM
COM
COM
COM
25.0
.984
FP0 - A21
■ Control units and expansion units * For the relay output type, the terminal block type is listed as the representative type.
FP0-C10RS/C10RM/C10CRS/C10CRM/C14RS/C14RM/C14CRS/C14CRM
FP0-E8RS/E8RM/E8YRS/E16RS/E16RM
■ FP0 CC-Link Unit, I/O Link Unit
● External dimensions
(unit: mm inch)
(10)
(.394)
25.0
.984
60.0
2.362
60.0
2.362
(13)
(.512)
FP0-C16T/C16P/C16CT/C16CP/E16T/E16P/E8X/E8YT/E8YP
3.5
.138
60.0
2.362
Note 3)
Input connector
25.0
.984
Input (8 points/common)
60.0
2.362
18
.709
XO-7
0
RUN
1
2
EXPANSION
CONNECTOR
3
PROG.
4
5
6
7
ERROR
ALARM
RUN
PROG.
YO-7
90.0
3.543
Note 1)
0
90.0
3.543
1
2
3
4
5
6
7
Approx.
130.0
5.118
Note 2)
Output connector
RS232C port (C16CT/C16CP only)
(9)
(.354)
(7.5)
(.295)
DIN standard rail
(DIN EN50022 35 mm
1.378 inch width) attachment gap
(17)
(.669)
Notes:
1) DIN rail is attached on the center of the unit.
2) The FP0-E8X has no output connector.
3) The FP0-E8YT and E8YP has no input connector.
● Terminal array
X0 X1
X2 X3
X4 X5
X6 X7
COM COM
● RS232C port
Terminal array
90.0
3.543
SD
4.5
.177
3.5
.138
SG
RD
■ FP0 Power Supply Unit
● External dimensions
Y1
Y3
Y5
Y7
(-)
(unit: mm inch)
● External dimensions
8.50 .335
60.0
2.362
Note: Two COM terminals on the input circuit are connected
inside the unit.
Note 4)
60.0
2.362
Note 2)
Input connector
30.0
1.181
XO-7
X8-F
0
1
RUN
EXPANSION
2
3
PROG.
4
CONNECTOR
5
6
7
ERROR
8
9
ALARM
A
B
RUN
C
D
E
F
90.0
3.543
PROG.
YO-7
Note 1)
Y8-F
0
90.0
3.543
1
2
3
4
5
90.0
● Terminal array
6
X0 X1
X2 X3
X4 X5
X6 X7
COM COM
X8 X9
XA XB
XC XD
XE XF
COM COM
4.5
.177
● RS232C port
Terminal array
3.5
.138
3.5
.138
■ External Dimensions During Expansions
SG
RD
● Top view
(with DIN rail
attached)
60.0
2.362
SD
(67.5)
(2.657)
Output (16 points/common)
7
8
9
A
B
Approx.
130.0
5.118
C
D
E
F
Note 3)
Output connector
RS232C port (C32CT/C32CP only)
(17)
Notes:
(.669)
1) DIN rail is attached on the center of the unit.
2) The FP0-E32T, E32P, E16X, E16YT and E16YP are
25 mm .984 inch each.
3) The FP0-E16X has no output connector.
4) The FP0-E16YT and E16YP have no input connector.
18
(9)
(.354)
(7.5)
(.295)
DIN standard rail
(DIN EN50022 35 mm
1.378 inch width) attachment gap
60.0
2.362
Output
terminal
Input (16 points/common)
60.0
2.362
18
.709
19.2
.756
3.543
Input
terminal
Connection
terminal
90.0
3.543
● External dimensions (unit: mm inch)
35.0
1.378
FP0-C32T/C32P/C32CT/C32CP/E32T/E32P/E16X/E16YT/E16YP
3.5
.138
(unit: mm inch)
25.0
.984
4.5
.177
3.5
.138
■ FP0 Web-Server Unit
Output (8 points/common)
Y0
Y2
Y4
Y6
(+)
90.0
3.543
FP0-CCLS
● External dimensions (unit: mm inch)
Y0
Y2
Y4
Y6
(+)
Y1
Y3
Y5
Y7
(-)
Y8
YA
YC
YE
(+)
Y9
YB
YD
YF
(-)
B
A
● Front view
XO-7
X8-F
XO-7
C
X8-F
0
RUN
XO-7
Y8-F
Y8-F
Notes:
1) Four COM terminals on the input circuit are connected
inside the unit.
2) Two (+) terminals and two (-) terminals on the output circuit
are connected respectively inside the unit.
4
8
8
8
9
8
9
A
B
B
C
D
E
F
7
9
A
C
D
E
90.0
3.543
5
6
7
B
C
F
3
4
5
6
A
B
D
E
1
2
4
7
9
A
C
0
3
5
6
Y8-F
1
2
4
7
F
YO-7
0
3
5
6
E
Y8-F
1
2
3
D
F
YO-7
0
1
2
(45)
(1.772)
B
C
E
F
YO-7
0
9
B
D
E
F
YO-7
7
A
C
D
E
P ROG.
5
8
9
C
D
6
7
A
B
C
3
4
5
8
9
A
B
RUN
2
3
6
7
8
9
1
4
5
6
7
8
0
2
3
4
5
6
A
X8-F
1
2
3
4
ALARM
XO-7
0
1
2
PROG
ERROR
D
X8-F
0
1
D
E
F
F
(45)
(1.772)
A+B+C+D dimensions
Control unit
type
FP0-C10CRS
FP0-C10CRS
FP0-C10RM
FP0-C10CRM
FP0-C14RS
FP0-C14CRS
FP0-C14RM
FP0-C14CRM
FP0-C16T
FP0-C16P
FP0-C16CT
FP0-C16CP
FP0-C32T
FP0-C32P
FP0-C32CT
FP0-C32CP
FP0-SL1
FP0-T32CT
FP0-T32CP
A+B
A+B+C
A+B+C+D
A
3 expansion
Control unit only 1 expansion unit 2 expansion
connected
units connected units connected
25 mm
.984 inch
50 mm
1.969 inch
75 mm
2.953 inch
100 mm
3.937 inch
30 mm
1.181 inch
55 mm
2.165 inch
80 mm
3.150 inch
105 mm
4.134 inch
19
FP0
Programmable Controllers
ARCT1B164E
0
ZERO
Suitable for Installation
Virtually Anywhere
Actual size:
W30 × H90 × D60 (mm)
W1.181 × H3.543 × D2.362 (inch)
!"## $
%
&##'!
(
&##'!"
I/O 10 points/14 points
Relay output,
terminal block type
(
) (
I/O 16 points
Transistor
output type
) (
I/O 32 points
Transistor
output type
)
. /
- /
0
1 23/45%
6
7
ARCT1B164E-1 200605
)
*+,
-
*
$
http://www.nais-e.com/plc/
Matsushita Electric Works, Ltd.