TÜV Rheinland
To Be Discontinued
Last time buy: September 30, 2018
RoHS compliant
Relay for control panel of
2c 7A and 4c 5A
HJ RELAYS
FEATURES
TYPICAL APPLICATIONS
1. Economical prices achieved
2. Useful for wide range of
applications
Gold-plated contact types are capable of
switching under low level (1mA: reference
value) to powerful high level (7A: 2-pole)
loads.
3. Wide range of types available
The lineup includes 2-pole and 4-pole
products, relays with operating indicator
lights, and push-button types. You will
also find relays that absorb surge when
the coil goes to the off state with diodes
(for DC type) or CR circuits (for AC type).
Moreover, the availability of a broad
range of coil voltages meets a wide range
of needs.
4. Sockets and terminal sockets are
available.
Control panels
Power supply units
Molding machines
Machine tools
Welding equipment
Agricultural equipment
Office equipment
Vending machines
Communications equipment
Amusement machines
ORDERING INFORMATION
HJ
Contact arrangement
2: 2 Form C
4: 4 Form C
Operation indication
Nil: Without LED indication
L: With LED indication
Test button
Nil: Without a test button
T: With a test button
Nominal coil voltage
AC 12, 24, 48, 100, 120, 200, 220/240 V
DC 12, 24, 48, 110 V
Surge suppression
Nil: Without
D: With diode
R: With CR circuit
Contact surface
Nil: Without Au plating
6: With Au plating
Notes: 1. Certified by UL/C-UL and TÜV
2. The LED indication color is green for the DC coil and red for the AC coil.
–1–
ASCTB6E 201709-T
To Be Discontinued
Last time buy: September 30, 2018
HJ
TYPES
1. Au plating type
1) Plug-in type
Nominal coil
voltage
12V DC
24V DC
48V DC
100/110V DC
12V AC
24V AC
48V AC
100/110V AC
110/120V AC
200/220V AC
220/240V AC
2) Plug-in type (with LED indication)
2 Form C
Part No.
HJ2-DC 12V-6
HJ2-DC 24V-6
HJ2-DC 48V-6
HJ2-DC110V-6
HJ2-AC 12V-6
HJ2-AC 24V-6
HJ2-AC 48V-6
HJ2-AC100V-6
HJ2-AC120V-6
HJ2-AC200V-6
HJ2-AC220/240V-6
4 Form C
Part No.
HJ4-DC 12V-6
HJ4-DC 24V-6
HJ4-DC 48V-6
HJ4-DC110V-6
HJ4-AC 12V-6
HJ4-AC 24V-6
HJ4-AC 48V-6
HJ4-AC100V-6
HJ4-AC120V-6
HJ4-AC200V-6
HJ4-AC220/240V-6
Standard packing: Carton: 20 pcs.; Case: 200 pcs.
12V DC
24V DC
48V DC
100/110V DC
2 Form C
Part No.
HJ2-DC 12V-D-6
HJ2-DC 24V-D-6
HJ2-DC 48V-D-6
HJ2-DC110V-D-6
100/110V AC
110/120V AC
200/220V AC
220/240V AC
12V DC
24V DC
48V DC
100/110V DC
12V AC
24V AC
48V AC
100/110V AC
110/120V AC
200/220V AC
220/240V AC
12V DC
24V DC
100/110V AC
200/220V AC
Standard packing: Carton: 20 pcs.; Case: 200 pcs.
Nominal coil
voltage
100/110V AC
110/120V AC
200/220V AC
220/240V AC
2 Form C
Part No.
HJ2-L-AC100V-R-6
HJ2-L-AC120V-R-6
HJ2-L-AC200V-R-6
HJ2-L-AC220/240V-R-6
4 Form C
Part No.
HJ4-L-AC100V-R-6
HJ4-L-AC120V-R-6
HJ4-L-AC200V-R-6
HJ4-L-AC220/240V-R-6
2) Plug-in type (with LED indication)
4 Form C
Part No.
HJ4-DC 12V
HJ4-DC 24V
HJ4-DC 48V
HJ4-DC110V
HJ4-AC 12V
HJ4-AC 24V
HJ4-AC 48V
HJ4-AC100V
HJ4-AC120V
HJ4-AC200V
HJ4-AC220/240V
Nominal coil
voltage
12V DC
24V DC
48V DC
100/110V DC
12V AC
24V AC
48V AC
100/110V AC
110/120V AC
200/220V AC
220/240V AC
2 Form C
Part No.
HJ2-L-DC 12V
HJ2-L-DC 24V
HJ2-L-DC 48V
HJ2-L-DC110V
HJ2-L-AC 12V
HJ2-L-AC 24V
HJ2-L-AC 48V
HJ2-L-AC100V
HJ2-L-AC120V
HJ2-L-AC200V
HJ2-L-AC220/240V
4 Form C
Part No.
HJ4-L-DC 12V
HJ4-L-DC 24V
HJ4-L-DC 48V
HJ4-L-DC110V
HJ4-L-AC 12V
HJ4-L-AC 24V
HJ4-L-AC 48V
HJ4-L-AC100V
HJ4-L-AC120V
HJ4-L-AC200V
HJ4-L-AC220/240V
Standard packing: Carton: 20 pcs.; Case: 200 pcs.
3) Plug-in type (with a test button)
2 Form C
Part No.
HJ2-T-DC 12V
HJ2-T-DC 24V
HJ2-T-AC100V
HJ2-T-AC200V
4 Form C
Part No.
HJ4-L-DC 12V-D-6
HJ4-L-DC 24V-D-6
HJ4-L-DC 48V-D-6
HJ4-L-DC110V-D-6
Standard packing: Carton: 20 pcs.; Case: 200 pcs.
Standard packing: Carton: 20 pcs.; Case: 200 pcs.
Nominal coil
voltage
2 Form C
Part No.
HJ2-L-DC 12V-D-6
HJ2-L-DC 24V-D-6
HJ2-L-DC 48V-D-6
HJ2-L-DC110V-D-6
6) Plug-in type (with CR and LED indication)
2. Without Au plating type
1) Plug-in type
2 Form C
Part No.
HJ2-DC 12V
HJ2-DC 24V
HJ2-DC 48V
HJ2-DC110V
HJ2-AC 12V
HJ2-AC 24V
HJ2-AC 48V
HJ2-AC100V
HJ2-AC120V
HJ2-AC200V
HJ2-AC220/240V
12V DC
24V DC
48V DC
100/110V DC
4 Form C
Part No.
HJ4-AC100V-R-6
HJ4-AC120V-R-6
HJ4-AC200V-R-6
HJ4-AC220/240V-R-6
Standard packing: Carton: 20 pcs.; Case: 200 pcs.
Nominal coil
voltage
Nominal coil
voltage
Standard packing: Carton: 20 pcs.; Case: 200 pcs.
5) Plug-in type (with CR)
2 Form C
Part No.
HJ2-AC100V-R-6
HJ2-AC120V-R-6
HJ2-AC200V-R-6
HJ2-AC220/240V-R-6
4 Form C
Part No.
HJ4-L-DC 12V-6
HJ4-L-DC 24V-6
HJ4-L-DC 48V-6
HJ4-L-DC110V-6
HJ4-L-AC 12V-6
HJ4-L-AC 24V-6
HJ4-L-AC 48V-6
HJ4-L-AC100V-6
HJ4-L-AC120V-6
HJ4-L-AC200V-6
HJ4-L-AC220/240V-6
4) Plug-in type (with diode and LED indication)
4 Form C
Part No.
HJ4-DC 12V-D-6
HJ4-DC 24V-D-6
HJ4-DC 48V-D-6
HJ4-DC110V-D-6
Standard packing: Carton: 20 pcs.; Case: 200 pcs.
Nominal coil
voltage
12V DC
24V DC
48V DC
100/110V DC
12V AC
24V AC
48V AC
100/110V AC
110/120V AC
200/220V AC
220/240V AC
2 Form C
Part No.
HJ2-L-DC 12V-6
HJ2-L-DC 24V-6
HJ2-L-DC 48V-6
HJ2-L-DC110V-6
HJ2-L-AC 12V-6
HJ2-L-AC 24V-6
HJ2-L-AC 48V-6
HJ2-L-AC100V-6
HJ2-L-AC120V-6
HJ2-L-AC200V-6
HJ2-L-AC220/240V-6
Standard packing: Carton: 20 pcs.; Case: 200 pcs.
3) Plug-in type (with diode)
Nominal coil
voltage
Nominal coil
voltage
4) Plug-in type (with LED indication and a test button)
4 Form C
Part No.
HJ4-T-DC 12V
HJ4-T-DC 24V
HJ4-T-AC100V
HJ4-T-AC200V
Nominal coil
voltage
12V DC
24V DC
100/110V AC
200/220V AC
2 Form C
Part No.
HJ2-L-T-DC 12V
HJ2-L-T-DC 24V
HJ2-L-T-AC100V
HJ2-L-T-AC200V
4 Form C
Part No.
HJ4-L-T-DC 12V
HJ4-L-T-DC 24V
HJ4-L-T-AC100V
HJ4-L-T-AC200V
Standard packing: Carton: 20 pcs.; Case: 200 pcs.
–2–
ASCTB6E 201709-T
To Be Discontinued
Last time buy: September 30, 2018
HJ
5) Plug-in type (with diode)
6) Plug-in type (with diode and LED indication)
2 Form C
Part No.
HJ2-DC 12V-D
HJ2-DC 24V-D
HJ2-DC 48V-D
HJ2-DC110V-D
Nominal coil
voltage
12V DC
24V DC
48V DC
100/110V DC
4 Form C
Part No.
HJ4-DC 12V-D
HJ4-DC 24V-D
HJ4-DC 48V-D
HJ4-DC110V-D
12V DC
24V DC
48V DC
100/110V DC
Standard packing: Carton: 20 pcs.; Case: 200 pcs.
100/110V AC
110/120V AC
200/220V AC
220/240V AC
4 Form C
Part No.
HJ4-L-DC 12V-D
HJ4-L-DC 24V-D
HJ4-L-DC 48V-D
HJ4-L-DC110V-D
Standard packing: Carton: 20 pcs.; Case: 200 pcs.
7) Plug-in type (with CR)
Nominal coil
voltage
2 Form C
Part No.
HJ2-L-DC 12V-D
HJ2-L-DC 24V-D
HJ2-L-DC 48V-D
HJ2-L-DC110V-D
Nominal coil
voltage
8) Plug-in type (with CR and LED indication)
2 Form C
Part No.
HJ2-AC100V-R
HJ2-AC120V-R
HJ2-AC200V-R
HJ2-AC220/240V-R
4 Form C
Part No.
HJ4-AC100V-R
HJ4-AC120V-R
HJ4-AC200V-R
HJ4-AC220/240V-R
2 Form C
Part No.
HJ2-L-AC100V-R
HJ2-L-AC120V-R
HJ2-L-AC200V-R
HJ2-L-AC220/240V-R
Nominal coil
voltage
100/110V AC
110/120V AC
200/220V AC
220/240V AC
Standard packing: Carton: 20 pcs.; Case: 200 pcs.
4 Form C
Part No.
HJ4-L-AC100V-R
HJ4-L-AC120V-R
HJ4-L-AC200V-R
HJ4-L-AC220/240V-R
Standard packing: Carton: 20 pcs.; Case: 200 pcs.
RATING
1. Coil data
1) AC coils (50/60Hz)
Nominal coil current [±20%]
Nominal operating power
60Hz
85.4mA
50Hz
60Hz
Max. applied voltage
(at 70°C 158°F)
12V AC
50Hz
102.9mA
24V AC
48V AC
100/110V AC
110/120V AC
200/220V AC
220/240V AC
54.5mA
30.7mA
11.8mA/13.9mA
10.9mA/12.5mA
6.8mA/8.1mA
6.8mA/7.8mA
45.6mA
25.9mA
10.0mA/11.6mA
9.1mA/10.3mA
5.7mA/6.7mA
5.6mA/6.4mA
Approx. 1.2 to
1.5 V A
Approx. 1.0 to
1.3 V A
110%V of
nominal voltage
Nominal coil
voltage
Pick-up voltage
(at 20°C 68°F)
Drop-out voltage
(at 20°C 68°F)
80%V or less of
nominal voltage
(Initial)
30%V or more of
nominal voltage
(Initial)
Pick-up voltage
(at 20°C 68°F)
Drop-out voltage
(at 20°C 68°F)
80%V or less of
nominal voltage
(Initial)
10%V or more of
nominal voltage
(Initial)
2) DC coils
Nominal coil
voltage
12V DC
24V DC
48V DC
100/110V DC
Nominal operating
power
Max. applied voltage
(at 70°C 158°F)
75mA [±10%]
Coil resistance
(at 20°C 68°F)
160Ω
37mA [±10%]
18mA [±15%]
9.1mA/10mA [±15%]
650Ω
2,600Ω
11,000Ω
0.9W
110%V of
nominal voltage
Nominal coil current
–3–
1.1W
ASCTB6E 201709-T
To Be Discontinued
Last time buy: September 30, 2018
HJ
2. Specifications
Characteristics
Contact
Rating
Item
Arrangement
Contact resistance (Initial)
Contact material
Nominal switching capacity (resistive load)
Max. switching power (resistive load)
Max. switching voltage
Max. switching current*4
Nominal operating power
Min. switching capacity Au plating type
(Reference value)*1
Without Au plating type
Insulation resistance (Initial)
Specifications
2 Form C
4 Form C
Max. 50 mΩ (By voltage drop 6 V DC 1A)
Au plating type: Au plating Ag Without Au plating type: Ag
7 A 250V AC, 7 A 30V DC
5 A 250V AC, 5 A 30V DC
1,750 VA
1,250 VA
250V AC, 125V DC
7A
5A
0.9W 1.2 VA
1mA 1V DC
1mA 5V DC
Min. 100MΩ (at 500V DC) Measurement at same location as “Breakdown voltage” section.
Between open contacts
Between contact sets
Between contact and coil
Temperature rise (coil) (at 70°C 158°F)
Operate time*2
1,000 Vrms for 1min. (Detection current: 10mA.)
2,000 Vrms for 1min. (Detection current: 10mA.)
2,000 Vrms for 1min. (Detection current: 10mA.)
Max. 60°C 140°F (By resistive method, nominal coil voltage)
Max. 20ms (Nominal coil voltage applied to the coil, excluding contact bounce time.)
Max. 20ms (Nominal coil voltage applied to the coil, excluding contact bounce time.)
(without diode)
Min. 100 m/s2 (Half-wave pulse of sine wave: 11 ms; detection time: 10μs.)
Min. 1,000 m/s2 (Half-wave pulse of sine wave: 6 ms.)
10 to 55 Hz at double amplitude of 1.0 mm (Detection time: 10μs.)
10 to 55 Hz at double amplitude of 1.0 mm
Min. 2×107 (at 180 times/min.)
Min. 105 (5A 250V AC)
Min. 105 (7A 250V AC)
Min. 5×105 (5A 250V AC)
Min. 2×105 (3A 250V AC)
Min. 105 (7A 30V DC)
Min. 105 (5A 30V DC)
Ambient temperature: –40°C to +70°C –40°F to +158°F
Humidity: 5 to 85% R.H. (Not freezing and condensing at low temperature)
20 times/min. (at nominal switching capacity)
Approx. 34g 1.20 oz
Breakdown voltage
(Initial)
Electrical
characteristics
Release time*2
Shock resistance
Mechanical
characteristics
Vibration resistance
Functional
Destructive
Functional
Destructive
Mechanical
Expected life
Electrical (resistive load) (at 20 times/min.)
Conditions for operation, transport and storage*3
(Not freezing and condensing at low temperature)
Max. Operating speed
Conditions
Unit weight
Notes: In accordance with the Electrical Appliance and Material Safety Law, you cannot exceed a voltage of 150V AC when using the 4 Form C type.
For more information, please inquire.
When using low level loads, contact instability may result depending on conditions of use (switching frequency and ambient conditions, etc.); therefore, please use
the Au plating type.
*1. This value can change due to the switching frequency, environmental conditions and desired reliability level, therefore it is recommended to check this with the
actual load.
*2. For the AC coil types, the operate/release time will differ depending on the phase.
*3. The upper limit of the ambient temperature is the maximum temperature that can satisfy the coil temperature rise value. Refer to Usage, transport and storage
conditions in NOTES.
*4. When using the socket and terminal socket, be sure to verify the max. continuous current.
REFERENCE DATA
AC resistive load
With test button type only
AC resistive
load
1
DC inductive load
L/R=7ms
5
1
0.5
50
AC resistive
load
DC resistive load
50
100 125 250
Contact voltage, V
AC 250V (cos φ =0.4)
AC inductive load
cos φ =0.4
0.1
10
50
100 125 250
Contact voltage, V
–4–
AC 250V (cos φ =1)
100
DC inductive load
L/R=7ms
AC inductive load
cos φ =0.4
10
500
3
DC resistive load
0.1
2-(1). Life curve (2 Form C)
Life, ×104
10
7
5
0.5
1-(2). Max. switching capacity (4 Form C type)
Contact current, A
Contact current, A
1-(1). Max. switching capacity (2 Form C type)
10
0
1
2
3
4
5
6
7
Load current, A
ASCTB6E 201709-T
To Be Discontinued
Last time buy: September 30, 2018
HJ
2-(2). Life curve (4 Form C)
3-(1). Coil temperature rise (2 Form C/AC type)
3-(2). Coil temperature rise (2 Form C/DC type)
Measured portion: Inside the coil
Ambient temperature: 70°C 158°F
Measured portion: Inside the coil
Ambient temperature: 70°C 158°F
70
AC 250V (cos φ =1)
100
50
AC 250V (cos φ =0.4)
10
0
1
2
60
7A
50
0A
40
30
90
100
110
120
70
70
60
60
Temperature rise, °C
Temperature rise, °C
Measured portion: Inside the coil
Ambient temperature: 70°C 158°F
7A
40
0A
100
10
120
0
282V
80V
0A
To digital
memory
200V AC
80
90
100
110
120
Coil applied voltage, %V
Coil applied voltage, %V
4-(2). AC coil surge voltage waveform
(Without CR circuit)
120
4-(1). AC coil surge voltage waveform
(With CR circuit)
5A
30
10
110
110
40
20
100
90
Tested sample: HJ4-AC200V-R
50
20
90
80
Coil applied voltage, %V
3-(4). Coil temperature rise (4 Form C/DC type)
80
0
Coil applied voltage, %V
Measured portion: Inside the coil
Ambient temperature: 70°C 158°F
0
0A
30
10
3-(3). Coil temperature rise (4 Form C/AC type)
30
40
10
80
5A
50
20
Load current, A
50
60
20
0
3
70
Temperature rise, °C
Temperature rise, °C
Life, ×104
500
5-(1). DC coil surge voltage waveform
(Without diode)
Tested sample: HJ4-AC200V
5-(2). DC coil surge voltage waveform
(With diode)
Diode characteristics:
Reverse breakdown voltage: 1,000 V
Forward current: 1 A
ON
OFF
ON
OFF
282V
Approx.
260V
Approx.
630V
200V AC
To digital
memory
12V DC
12V DC
–5–
To digital
memory
To digital
memory
Reverse breakdown voltage: 1,000 V
Forward current: 1 A
ASCTB6E 201709-T
To Be Discontinued
Last time buy: September 30, 2018
HJ
DIMENSIONS (mm inch)
The CAD data of the products with a
1. Plug-in type (2 Form C)
(including diode/CR)
CAD Data
mark can be downloaded from: http://industrial.panasonic.com/ac/e/
External dimensions
CAD Data
Max. 28
1.102
Schematic (Bottom view)
Standard type
Max. 21.5
.846
Max. 35
1.378
1
5
4
8
9
13
0.5
.020
0.5
.020
4
8
12
9
12
9
12
14
13
14
(–)13
14(+)
13
(–)
6.8
.268
13
9
1
5
Dimension:
Less than 1mm .039inch:
Min. 1mm .039inch less than 3mm .118 inch:
Min. 3mm .118 inch:
5
8
5
8
9
12
14
(+)
9
12
14
Max. 28
1.102
1
5
8
5
8
9
12
14
(+)
9
12
1
5
2
6
LED AC type
4
8
1
5
2
6
3
7
1
5
13
14
2.5
.098
13
(–)
6.8
.268
2
3
Dimension:
Less than 1mm .039inch:
Min. 1mm .039inch less than 3mm .118 inch:
Min. 3mm .118 inch:
3
7
4
8
(–)13
14(+)
CR AC type
1
2
3
4
5
6
7
8
5
6
7
8
9
10
11
12
14
(+)
9
10
11
12
14
1
13
(–)
2
6
9 10 11 12
14
4
Diode/LED DC type
4.4 13.2
.173 .520
LED DC type
4
8
13
14
9 10 11 12
3
7
Diode DC type
13
4
8
3
7
2
6
14
9 10 11 12
1
1
5
13
9 10 11 12
0.5
.020
5.8+0.4
−0.2
.228+.016
−.008
4
Schematic (Bottom view)
Standard type
Max. 21.5
.846
0.5
.020
CR/LED AC type
Tolerance
±0.1 ±.004
±0.2 ±.008
±0.3 ±.012
Max. 35
1.378
16.8
.661
12.7
.500
6.4
.252
13
4
4
External dimensions
CAD Data
CR AC type
1
1
13
(–)
4
8
4
Diode/LED DC type
14
12
4
8
2.5
.098
13.2
.520
2. Plug-in type (4 Form C)
(including diode/CR)
1
5
Diode DC type
5.8+0.4
−0.2
.228+.016
−.008
LED DC type
1
5
1
16.8
.661
12.7
.500
6.4
.252
LED AC type
2
3
13
CR/LED AC type
4
1
2
3
4
5
6
7
8
5
6
7
8
9
10
11
12
14
(+)
9
10
11
12
13
14
Tolerance
±0.1 ±.004
±0.2 ±.008
±0.3 ±.012
–6–
ASCTB6E 201709-T
To Be Discontinued
Last time buy: September 30, 2018
HJ
3. Plug-in type with a test button (2 Form C)
External dimensions
CAD Data
Max. 28
1.102
Schematic (Bottom view)
Standard type
Max. 21.5
.846
Max. 38
1.496
Max. 36
1.417
12
14
LED DC type
1
5
4
8
9
12
9
12
13
14
(–)13
14(+)
Dimension:
Less than 1mm .039inch:
Min. 1mm .039inch less than 3mm .118 inch:
Min. 3mm .118 inch:
13
9
9
13
1
5
4
8
6.8
.268
14
12
4
8
2.5
.098
0.5
.020 5.8+0.4
−0.2
.228+.016
−.008
13.2
.520
1
5
4
8
LED AC type
0.5
.020
16.8
.661
12.7
.500
6.4
.252
1
5
Tolerance
±0.1 ±.004
±0.2 ±.008
±0.3 ±.012
4. Plug-in type with a test button (4 Form C)
External dimensions
CAD Data
Max. 28
1.102
Schematic (Bottom view)
Standard type
Max. 21.5
.846
1
5
2
6
3
7
4
8
9 10 11 12
Max. 38
1.496
13
Max. 36
1.417
14
LED AC type
0.5
.020
1
5
2
6
3
7
LED DC type
4
8
1
5
9 10 11 12
14
9 10 11 12
13
3
7
4
8
9 10 11 12
14
(–)13
14(+)
6.8
.268
4.4 13.2
.173 .520
13
1 2 3 4
5 6 7 8
16.8
.661
12.7
.500
6.4
.252
2.5
.098
0.5
.020 5.8+0.4
−0.2
.228+.016
−.008
2
6
Dimension:
Less than 1mm .039inch:
Min. 1mm .039inch less than 3mm .118 inch:
Min. 3mm .118 inch:
Tolerance
±0.1 ±.004
±0.2 ±.008
±0.3 ±.012
SAFETY STANDARDS
File No.
Certification authority: UL/C-UL
File No.
2 Form C
E43149*
7A 250V AC, 7A 30V DC
R50049126
4 Form C
E43149*
5A 250V AC, 5A 30V DC
R50049126
Certification authority: TÜV
7A 250V AC (cosφ =1.0), 7A 30V DC (0ms)
Test button type:
10A 250V AC (cosφ =1.0), 10A 30V DC (0ms)
5A 250V AC (cosφ =1.0), 5A 30V DC (0ms)
* CSA standard: Certified by C-UL
–7–
ASCTB6E 201709-T
To Be Discontinued
Last time buy: September 30, 2018
HJ
NOTES
1. For cautions for use, please read
“General Application Guidelines”.
2. Coil applied voltage
Please refer to “RATING” about coil input
power supply.
3. LED display
Operation is displayed by the light
emitted from the LED. The LED may
remain briefly lit if voltage remains after
the relay opens.
4. Switching lifetime
The switching lifetime is defined under
the standard test condition specified in
the JIS* C 5442 standard (temperature
15 to 35°C 59 to 95°F, humidity 25 to
75%). Check this with the real device as it
is affected by coil driving circuit, load
type, activation frequency, activation
phase,ambient conditions and other
factors.
Also, be especially careful of loads such
as those listed below.
1) When used for AC load-operating and
the operating phase is synchronous.
Rocking and fusing can easily occur due
to contact shifting.
2) High-frequency load-operating
When high-frequency opening and
closing of the relay is performed with a
load that causes arcs at the contacts,
nitrogen and oxygen in the air is fused by
the arc energy and HNO3 is formed. This
can corrode metal materials.
Three countermeasures for these are
listed here.
(1) Incorporate an arc-extinguishing
circuit.
(2) Lower the operating frequency
(3) Lower the ambient humidity
5. Usage, transport and storage
conditions
1) Temperature, humidity and pressure
during usage, storage and transport
(1) Temperature:
–40 to +70°C –40 to +158°F
(2) Humidity: 5 to 85% RH
(Avoid freezing and condensation.)
The humidity range varies with the
temperature. Use within the range
indicated in the graph below.
Temperature and humidity range for
usage, transport, and storage
Humidity, %R.H.
85
5
–40
–40
(Avoid
condensation
when used at
temperatures
higher than
0°C 32°F)
0
+32
Temperature, °C °F
Push
For Lock
For Release
70
+158
(3) Atmospheric pressure: 86 to 106 kPa
2) Condensation
Condensation forms when there is a
sudden change in temperature under
high temperature and high humidity
conditions. Condensation will cause
deterioration of the relay insulation.
3) Freezing
Condensation or other moisture may
freeze on the relay when the
temperatures is lower than 0°C 32°F. This
causes problems such as sticking of
movable parts or operational time lags.
4) Low temperature, low humidity
environments
The plastic becomes brittle if the relay is
exposed to a low temperature, low
humidity environment for long periods of
time.
–8–
1
Release
2) To lock to one side turn 90° counterclockwise while pushing lock and turn 90°
clockwise to release.
Tolerance range
(Avoid freezing
when used at
temperatures
lower than
0°C 32°F)
6. Operation method for test button
1) Push and release 1 gently to confirm
relay switching.
3) Do not use the test button for anything
other than testing, such as when
checking the circuit.
7. Diode characteristics
1) Reverse breakdown voltage: 1,000 V
2) Forward current:
1A
8. Diode and CR built-in type
Since the diode and CR inside the relay
coil are designed to absorb the counter
emf, the element may be damaged if a
large surge, etc., is applied to the diode
and CR. If there is the possibility of a
large surge voltage from the outside,
please implement measures to absorb it.
9. Please connect DC coil types with
LED and built-in diode correctly by
verifying the coil polarity (“+” and “–
”). Connecting with reverse polarity
will cause the LED not to light and
damage the built-in diode due to its
specification.
ASCTB6E 201709-T