SENSORS
Exclusive Control Unit for Light Curtain
SF-C10 SERIES
Related Information
■■General terms and conditions.............. F-7
■■General precautions...................... P.1501
■■SF4B-C / SF4C / SF4B / SF2B................P.499~ / P.531~ / P.565~ / P.609~
■■Korea’s S-mark.............................. P.1506
LASER
SENSORS
PHOTOELECTRIC
SENSORS
MICRO
PHOTOELECTRIC
SENSORS
AREA
SENSORS
LIGHT CURTAINS /
SAFETY
COMPONENTS
PRESSURE /
FLOW
SENSORS
INDUCTIVE
PROXIMITY
SENSORS
Conforming to Machine,
Low Voltage (SF-C11/C13
only) & EMC Directive
Listing
Certified
Certified
(SF-C11/C13 only)
PARTICULAR
USE SENSORS
SENSOR
OPTIONS
SIMPLE
WIRE-SAVING
UNITS
WIRE-SAVING
SYSTEMS
MEASUREMENT
SENSORS
panasonic.net/id/pidsx/global
STATIC ELECTRICITY
PREVENTION
DEVICES
LASER
MARKERS
PLC
HUMAN MACHINE
INTERFACES
ENERGY CONSUMPTION
VISUALIZATION
COMPONENTS
FA COMPONENTS
MACHINE VISION
SYSTEMS
Less setup time for safety circuits
Plug-in type control unit
Quick-connection
Connecting to the light curtain is
done using plug-in connections,
which shortens setup and
replacement time.
UV CURING
SYSTEMS
SF-C11 / SF-C14EX(-01)
Easy setup requiring no torque control
A spring method is used for the
terminal blocks for connections
other than to the light curtain. There
is no need to control tightening
torques for
Flat-tipped screwdriver
these
Lead wire
terminal
blocks.
Ferrule (sleeve) terminal
(Please arrange separately.)
Removable terminal blocks
reduce maintenance time
Removable terminal blocks are
used. This reduces the work
required for reconnecting wiring
during maintenance.
Removable!
Uses a
spring method!
Selection
Guide
Light Curtains
Safety
Components
Optical Touch
Switch
Release button
Lead wire insertion hole
Control Units
Definition of
Sensing Heights
SF-C10
SF-CL1T264T
SF-AC
Robust type control unit
SF-C12
Metal enclosure with a IP65 protective structure
The strong metal enclosure has a built-in safety relay. It
has an IP65 protective structure, so that it can be set up
individually without needing to be inserted into a control
panel.
IP65
Slim type control unit
Slim design
22.5 mm 0.886 in thickness, so can be inserted even
into narrow spaces inside panels.
Metal enclosure
Slim
22.5 mm
0.886 in
Connecting to the light curtain is done
using plug-in connector connections
SF-C13
Spring-type terminal block
No torque control needed
Exclusive Control Unit for Light Curtain
SF-C10 SERIES
Building of muting control circuits is easy
SF-C14EX(-01)
The method used to build the safety circuit is selectable
It is possible to build muting control circuits using a stand-alone light curtain from the SF4B series. The SF-C14EX(-01)
application expansion unit allows the light curtain, muting sensors and muting lamps to be connected together directly,
so that muting control circuits can be built very easily.
Building
method
Using SF4B series functions
Building
method
Using the SF-C14EX(-01) internal circuits
Muting control
Muting control
Muting
lamps
Muting
sensors
Exclusive mating
cable for
SF-C14EX(-01)
Safety output
Terminal blocks
SF4B
series
External devices
(Force-guided relay, etc.)
No safety relay unit needed
!
Low cost s space!
Save
Muting
lamps
Muting
sensors
SF4B
series
Safety output
SF-C14EX(-01)
External devices
(Force-guided relay, etc.)
Light curtain connector connection.
Terminal blocks for peripheral circuits available.
g!
Less wirin aintenance!
m
Reduced
Motor, etc.
704
FIBER
SENSORS
LASER
SENSORS
PHOTOELECTRIC
SENSORS
MICRO
PHOTOELECTRIC
SENSORS
AREA
SENSORS
LIGHT CURTAINS /
SAFETY
COMPONENTS
PRESSURE /
FLOW
SENSORS
INDUCTIVE
PROXIMITY
SENSORS
PARTICULAR
USE SENSORS
SENSOR
OPTIONS
SIMPLE
WIRE-SAVING
UNITS
WIRE-SAVING
SYSTEMS
Motor, etc.
MEASUREMENT
SENSORS
STATIC ELECTRICITY
PREVENTION
DEVICES
Both safety and productivity can be obtained by stopping only one part of the device SF-C14EX(-01)
LASER
MARKERS
Three safety circuit systems packaged into a single unit!
PLC
Three safety circuit systems 1 Light curtain output
circuit, 2 Muting control circuit, and 3 Emergency stop
circuit are packaged into a single unit. Functions that
require multiple safety relay units and muting control
units can be concentrated into a single unit, which
results in large space savings, less wiring and less
installation work.
Previous model
High-speed response 14 ms (Including light curtain)
High-speed response has been achieved due to the
adoption of the semiconductor output. Avoids the
response delays that occur when using more than
one safety relay unit, and greatly reduces the light
curtain safety distance and improves ease of working.
Of course, it is not necessary to exchange the safety
relays within the unit anymore, which contributes to the
reduction of running cost.
SF-C14EX(-01)
Including light curtain response time
Light curtain
1
Muting sensor
Emergency stop button
2
SF4B series Muting sensor
3
1
Emergency stop button
2
3
pace!
Saves s g!
in
ir
w
s
s
!
e
L
struction
n
o
c
s
Les
Safety relay Muting unit
unit
Furthermore, due to the
semiconductor output,
Safety relay
unit
SF-C14EX(-01)
1
2
3
2
2
3
External contactor
(Force-guided relay, etc.)
1
1
(Force-guided relay, etc.)
3
Motor
1 Light curtain output circuit
3 Emergency stop circuit
1
2
Motor
2 Muting control circuit
3
ENERGY CONSUMPTION
VISUALIZATION
COMPONENTS
FA COMPONENTS
MACHINE VISION
SYSTEMS
UV CURING
SYSTEMS
Previous model
14 ms
10 ms
20 ms
35 ms
Customer's
logical
connection
circuit
Selection
Guide
Light Curtains
Safety
Components
Optical Touch
Switch
Control Units
SF-C14EX(-01)
Customer's logical connection circuit
External contactor
High response speed of 14 ms!
Greatly reduced safety distance!
HUMAN MACHINE
INTERFACES
ms!
ed!
Total 14
not requir
cement is
la
p
re
y
la
Re
Definition of
Sensing Heights
SF-C10
SF-CL1T264T
SF-AC
705
FIBER
SENSORS
LASER
SENSORS
PHOTOELECTRIC
SENSORS
MICRO
PHOTOELECTRIC
SENSORS
AREA
SENSORS
LIGHT CURTAINS /
SAFETY
COMPONENTS
PRESSURE /
FLOW
SENSORS
INDUCTIVE
PROXIMITY
SENSORS
PARTICULAR
USE SENSORS
SENSOR
OPTIONS
SIMPLE
WIRE-SAVING
UNITS
WIRE-SAVING
SYSTEMS
MEASUREMENT
SENSORS
STATIC ELECTRICITY
PREVENTION
DEVICES
LASER
MARKERS
PLC
Exclusive Control Unit for Light Curtain
SF-C10 SERIES
Three safety circuit systems can be controlled independently so that equipment can be stopped all together or partially SF-C14EX(-01)
Motors that use muting control and those that do not use it can be controlled independently!
Controls the motors that use muting control
(robots) and the motors that do not use muting
control (turntables) with a single unit.
When the workpiece comes in, the turntable
can be stopped and the robot can keep
operating condition, to protect the safety of the
operator and to maintain productivity.
SF-C14EX(-01) controls three safety
output systems using only a single unit!
Safety circuit 1 : Linked to light curtain beam received /
interrupted status (partial stop)
3
1
2
When the light curtain is interrupted (when an
workpiece enters or a person intrudes), this
circuit switches off (open) the safety output and
stops the turntable.
Safety circuit 2 : Linked to muting control (partial stop)
If an workpiece enters when the turntable
has stopped normally, (muting conditions
are achieved), this circuit allows the robot to
operate.
If an workpiece enters while the turntable is
turning (muting conditions are not achieved),
this circuit switches off (open) the safety output
and stops the robot.
Robot
Motor using muting
Safety circuit 3 : Linked to emergency stop input (all stop)
When the emergency stop button is pressed,
this circuit switches off (open) the safety output
and stops all equipment (turntable and robot).
Emergency stop button
HUMAN MACHINE
INTERFACES
Limit switch
For muting input
SF4B series
Turntable
Motor not using muting
ENERGY CONSUMPTION
VISUALIZATION
COMPONENTS
FA COMPONENTS
MACHINE VISION
SYSTEMS
UV CURING
SYSTEMS
Equipped with blown lamp output for muting lamp
If a lamp in one of the two muting lamps that are
connected to the unit blows, a warning is output. It is
possible to replace the lamp before both lamps blow and
the equipment stops. In addition, auxiliary output that is
linked to the muting function, override function and light
curtain control output is also available.
Function
Selection
Guide
Light Curtains
Safety
Components
Optical Touch
Switch
Control Units
Definition of
Sensing Heights
SF-C10
SF-CL1T264T
SF-AC
Equipped with a digital indicator so that error
details can be understood at a glance!
If a problem should occur, the same output (OFF signal)
as when the object was detected is maintained in order
to ensure safety, and the details of the error appear on
the digital display.
Operation
Auxiliary
output 1
Muting output
ON when the muting
function is invalid
Auxiliary
output 2
Override output
ON when the override
function is invalid
Auxiliary
output 3
Blown lamp output
ON when the muting
lamp is normal
Auxiliary
output 4
Light curtain
auxiliary output
ON when the light curtain is
in light interrupted condition
Supports both PNP and NPN polarities
All Models
A single model can be used for PNP / NPN input switching, reducing the
number of parts that need to be registered.
NPN
PNP
Polarity selection
switch
Exclusive Control Unit for Light Curtain
SF-C10 SERIES
ORDER GUIDE
706
FIBER
SENSORS
LASER
SENSORS
Designation
Appearance
Connector
connection type
control unit
Robust type
control unit
Slim type
control unit
SF-C11
SF-C12
SF-C13
SF-C14EX
Handy-controller
non-compatible type
Application
expansion
unit for
SF4B
series
Model No.
SF-C14EX-01
Description
Applicable cable (Note)
Light curtain connection cable:
SFB-CB□
(For SF4B series)
SF2B-CB□
(For SF2B series)
Extension cable: SFB-CCJ10□
Use 8-core cable with connector to connect to the light
curtain.
Compatible with up to control category 4.
Interference prevention wires and muting function cannot
be used.
Use 12-core cable with connector to connect to the light
Light curtain connection cable:
curtain. Interference prevention wires can be used.
SFB-CB05-MU
Compatible with up to control category 4.
Extension cable: SFB-CCJ10□-MU
Muting function cannot be used.
Light curtain connection cable:
SFB-CCB□(-MU)
(For SF4B series)
SF2B-CCB□
(For SF2B series)
Extension cable: SFB-CC□(-MU)
Use a discrete wire cable to connect to the light curtain.
Muting function and interference prevention wires can be
used.
Compatible with up to control category 4.
PHOTOELECTRIC
SENSORS
MICRO
PHOTOELECTRIC
SENSORS
AREA
SENSORS
LIGHT
CURTAINS /
SAFETY
COMPONENTS
PRESSURE /
FLOW
SENSORS
INDUCTIVE
PROXIMITY
SENSORS
PARTICULAR
USE
SENSORS
SENSOR
OPTIONS
SIMPLE
WIRE-SAVING
UNITS
WIRE-SAVING
SYSTEMS
The muting control function and emergency stop input are
Light curtain connection cable:
equipped, expanding the applications of the light curtains.
SFB-CB□-EX It can be connected to the light curtains using the exclusive
Extension cable: SFB-CCJ10□
connection cable.
Compatible with up to control category 4.
Note: Refer to the SF4B series (p.576~) and SF2B series (p.614) for details of applicable cable.
SF-C12 spare relay set
A set of spare relays (2 safety relays and 1 removal tool) is available for the safety relay that is built into the SF-C12.
Model No.: SF-C12-RY
MEASUREMENT
SENSORS
STATIC
ELECTRICITY
PREVENTION
DEVICES
LASER
MARKERS
PLC
HUMAN
MACHINE
INTERFACES
ENERGY
CONSUMPTION
VISUALIZATION
COMPONENTS
FA
COMPONENTS
MACHINE
VISION
SYSTEMS
UV
CURING
SYSTEMS
Selection
Guide
Light
Curtains
Safety
Components
Optical Touch
Switch
Control
Units
Definition of
Sensing
Heights
SF-C10
SF-CL1T264T
SF-AC
707
Exclusive Control Unit for Light Curtain
SPECIFICATIONS
FIBER
SENSORS
Model No.
Item
PHOTOELECTRIC
SENSORS
Connectable light curtains
MICRO
PHOTOELECTRIC
SENSORS
Applicable standards
LIGHT
CURTAINS /
SAFETY
COMPONENTS
Control category
Enabling path
Contact resistance
MACHINE
VISION
SYSTEMS
UV
CURING
SYSTEMS
Electrical lifetime
Pick-up delay (Auto reset / Manual reset)
Response time
Auxiliary output
Contact protection fuse rating
AgSnO, self cleaning, positively driven
AgNiO + 0.2 µm 0.008 mil Au plating, self cleaning, positively driven
AgSnO, self cleaning, positively driven
100 mΩ or less (initial value)
50 mΩ or less (initial value)
100 mΩ or less (initial value)
6 A (slow blow)
3 A (slow blow)
4 A (slow blow)
10 million operations or more (switching frequency 180 operations/min.) (Note 3)
100,000 operations or more (switching frequency 20 operations/min., 230 V AC / 3 A resistive load) (Note 3)
80 ms or less / 90 ms or less
30 ms or less / 30 ms or less
80 ms or less / 90 ms or less
10 ms or less
14 ms or less
10 ms or less
Safety relay contact (NC contact) ×1 (41-42) (Related to enabling path) Safety relay contact (NC contact) × 1 (31-32) (Related to enabling path) Safety relay contact (NC contact) × 1 (41-42) (Related to enabling path)
2 A (slow blow)
3 A (slow blow)
2 A (slow blow)
–
PNP open‑collector transistor
• Max. source current: 60 mA
• Applied voltage: same as supply voltage
between the semiconductor
auxiliary output and +V
• Residual voltage: 2.3 V or less
(at source current 60 mA)
• Leakage current: 2 mA or less
Related to auxiliary output of light curtain
–
On when the light curtain is interrupted
ll
lll
ll
NPN open-collector transistor
PNP open-collector transistor
• Max. source current: 60 mA • Max. sink current: 60 mA
• Applied voltage: same • Applied voltage: same
as supply voltage
as supply voltage
Semiconductor auxiliary output
between the semiconductor
between the semiconductor
(AUX)
auxiliary output and 0 V
auxiliary output and +V
• Residual voltage: 2.3 V or less • Residual voltage: 1.5 V or less
(at sink current 60 mA)
(at source current 60 mA)
• Leakage current: 2 mA or less • Leakage current: 2 mA or less
Output operation
Excess voltage category
Power supply (Ui)
Green LED (lights up when the power is ON)
Enabling path [OUT (Note 4)]
Interlock (INTER_LOCK)
Fault (FAULT)
External relay monitor function
Green LED (lights up when enabling contacts are closed)
Yellow LED (lights up when enabling contacts are opened)
–
Yellow LED (lights up when enabling contacts are opened)
Yellow LED (blinks when fault occurs)
Orange LED (lights up when two light curtain input
polarity selection switch settings are different)
Yellow LED (blinks when fault occurs)
Incorporated
Incorporated (Note 5)
Incorporated
Trailing edge function
Light
Curtains
Safety
Components
Optical Touch
Switch
Control
Units
Definition of
Sensing
Heights
Polarity selection
function (Note 6)
Protection
Ambient temperature
Ambient humidity
Vibration resistance
Connection terminal
SF-C10
Enclosure material
SF-CL1T264T
Weight
SF-AC
Incorporated
Incorporated (Sliding switch allows selection of plus / minus ground)
Minus ground: Correspond to PNP output light curtain
Plus ground: Correspond to NPN output light curtain
Pollution degree
Environmental
resistance
Selection
Guide
NO contact × 3 (13-14, 23-24, 33-34)
Rated operation voltage / current 24 V DC / 2 A, Min. applicable load: 10 mA (at 24 V DC) 30 V DC / 3 A, Min. applicable load: 15 mA (at 24 V DC) 24 V DC / 2 A, Min. applicable load: 10 mA (at 24 V DC)
Indicators
FA
COMPONENTS
NO contact × 2 (13-14, 23-24)
AC-15, DC-13 (IEC 60947-5-1)
Mechanical lifetime
SIMPLE
WIRE-SAVING
UNITS
ENERGY
CONSUMPTION
VISUALIZATION
COMPONENTS
NO contact × 3 (13-14, 23-24, 33-34)
30 V DC / 6 A, 230 V AC / 6 A, resistive load 24 V DC / 1 A, resistive load
30 V DC / 4 A, 230 V AC / 4 A, resistive load
Rated operation voltage (Ue) /
(For inductive load, during contact protection) (For inductive load, during contact protection) (For inductive load, during contact protection)
Rated operation current (le)
Min. applicable load: 10 mA (at 24 V DC) (Note 2) Min. applicable load: 15 mA (at 24 V DC) Min. applicable load: 10 mA (at 24 V DC) (Note 2)
Contact protection fuse rating
HUMAN
MACHINE
INTERFACES
ISO 13849-1 (EN ISO 13849-1, JIS B 9705-1) compliance up to Category 4, PLe standards
Utilization
SENSOR
OPTIONS
PLC
Light curtain manufactured by PID SUNX
24 V DC ±10 % Ripple P-P 10 % or less / 100 mA or less (without light curtain)
Contact material / contacts
LASER
MARKERS
SF4B series
Built-in electronic fuse, Triggering current: 0.5 A or more, Reset after power down
PARTICULAR
USE
SENSORS
STATIC
ELECTRICITY
PREVENTION
DEVICES
SF4B / SF2B series
IEC 61496-1 (Type 4), EN 55011, EN ISO 13849-1 (Category 4, PLe), IEC 61496-1 (Type 4), ISO 13849-1 (Category 4,
PLe), JIS B 9704-1 (Type 4), JIS B 9705-1(Category 4), ANSI/UL 61496-1 (Type 4), UL 1998 (Class 2, excluding SF-C12)
Fuse rating
INDUCTIVE
PROXIMITY
SENSORS
MEASUREMENT
SENSORS
SF-C13
Supply voltage / Current consumption
PRESSURE /
FLOW
SENSORS
WIRE-SAVING
SYSTEMS
SF-C12
Incorporated (Cable connection allows selection of plus / minus ground)
Minus ground: Correspond to PNP output light curtain
Plus ground: Correspond to NPN output light curtain
2
Enclosure: IP40, Terminal: IP20
IP65
Enclosure: IP40, Terminal: IP20
–10 to +55 °C +14 to +131 °F (No dew condensation or icing allowed), Storage: –25 to +70 °C –13 to +158 °F
30 to 85 % RH, Storage: 30 to 95 % RH
35 to 85 % RH, Storage: 35 to 85 % RH
30 to 85 % RH, Storage: 30 to 95 % RH
Resistance / malfunction 10 to 55 Hz frequency, 0.35 mm 0.014 in Resistance 10 to 55 Hz frequency, 0.75 mm 0.030 in Resistance / malfunction 10 to 55 Hz frequency, 0.35 mm 0.014 in
amplitude in X, Y, and Z directions for twenty times each
amplitude in X, Y, and Z directions for two hours each amplitude in X, Y, and Z directions for twenty times each
Detachable spring-cage terminal
European terminal
ABS
Die-cast aluminum
ABS
Net weight: 320 g approx.
Net weight: 1 kg approx.
Net weight: 200 g approx.
Notes: 1) W
here measurement conditions have not been specified precisely, the
conditions used were an ambient temperature of +20 °C +68 °F.
2) If several SF-C11 or SF-C13 units are being used in line together, leave
a space of 5 mm 0.197 in or more between each unit. If the units are
touching each other, reduce the rated operating current for safety output in
accordance with the ambient operating temperature as shown in the graphs
at right.
3) Relay switching lifetime will vary depending on factors such as the type of
load, the switching frequency, and ambient conditions.
4) The operation indicator is marked as “Enabling” on the unit for SF-C12.
5) Terminals for utilizing the functions of the SF4B series are available.
6) Please switch the sliding switch to the PNP side for minus ground and to the
NPN side for plus ground.
Dilating when SF-C11 units
are mounted close together
6
5
4
3
2
1
0
32
Spring-cage terminal
Dilating when SF-C13 units
are mounted close together
Rated operation current (A)
AREA
SENSORS
SF-C11
Rated operation current (A)
LASER
SENSORS
SF-C10 SERIES
35 40 45 50 55
95 104 113 122 131
Ambient temperature (°C °F)
6
5
4
3
2
1
0
32
35 40 45 50 55
95 104 113 122 131
Ambient temperature (°C °F)
Exclusive Control Unit for Light Curtain
SF-C10 SERIES
SPECIFICATIONS
Model No.
Item
Connectable light curtains
Applicable standards
Control category
Supply voltage
Current consumption
Safety outputs
Safety output 1
Safety output 2
Safety output 3
Operation mode
(Output operation)
Protection circuit
(Short-circuit protection)
Response time
Auxiliary outputs
Auxiliary output 1
Auxiliary output 2
Auxiliary output 3
Auxiliary output 4 (Note 5)
Operation mode
(Output operation)
Protection circuit
(Short-circuit protection)
Muting lamp output
Environmental resistance
Protection circuit
(Short-circuit protection)
Protection
Ambient temperature
Ambient humidity
Dielectric strength voltage
FIBER
SENSORS
SF-C14EX(-01) (Note 2)
SF4B series
IEC 61496-1 (Type 4), EN 55011, EN ISO 13849-1 (Category 4, PLe), IEC 61496 (Type 4), ISO 13849-1 (Category 4, PLe),
JIS B 9704-1 (Type 4), JIS B 9705-1 (Category 4), ANSI/UL 61496-1 (Type 4), UL 1998 (Class 2)
ISO 13849-1 (EN 954-1, JIS B 9705-1) compliance up to Category 4, PLe standards
24 V DC ±10 % Ripple P-P 10 % or less
0.2 A or less (Excluding light curtain and other external connecting device)
PNP open-collector transistor 2 outputs × 3 or NPN open-collector transistor 2 outputs × 3 (selectable using a slider switch)
• Maximum source current: 200 mA
• Maximum sink current: 200 mA
• Applied voltage: same as supply voltage
• Applied voltage: same as supply voltage
(between the safety output and +V)
(between the safety output and 0 V)
• Residual voltage: 2 V or less (at 200 mA source current)
• Residual voltage: 2 V or less (at 200 mA sink current)
Safety output 1: ON when the light curtain is in light receiving condition, OFF when the light curtain is in light interrupted condition (Note 3)
Safety output 2: ON when the light curtain is in light receiving condition or the muting function is valid
OFF when the light curtain is in light interrupted condition and the muting function is invalid (Note 3)
Safety output 3: ON when the emergency stop is invalid, OFF when the emergency stop is valid
Incorporated
OFF response: 14 ms or less (Safety output 1 and 2: including the response time of the light curtain)
ON response: 90 ms or less (auto-reset) / 140 ms or less (manual reset) (Note 4)
PNP open-collector transistor × 3 or NPN open-collector transistor × 3 (selectable using a slider switch)
• Maximum source current: 60 mA
• Maximum sink current: 60 mA
• Applied voltage: same as supply voltage
• Applied voltage: same as supply voltage
(between the auxiliary output and +V)
(between the auxiliary output and 0 V)
• Residual voltage: 2 V or less (at 60 mA sink current)
• Residual voltage: 2 V or less (at 60 mA source current)
Auxiliary output 1: ON when the muting function is invalid, OFF when the muting function is valid
Auxiliary output 2: ON when the override function is invalid, OFF when the override function is valid
Auxiliary output 3: ON when the muting lamp is normal, OFF when the muting lamp is error
Auxiliary output 4: ON when the light curtain is in light interrupted condition, OFF when the light curtain is in light receiving condition (Note 5)
Incorporated
Applicable muting lamp: 24 V DC, 3.6 to 30 W (L1, L2 of each unit)
Incorporated
Enclosure: IP40, Terminal: IP20
10 to 55 Hz frequency, 0.35 mm 0.014 in amplitude in X, Y and Z directions for two hours each
Weight
MICRO
PHOTOELECTRIC
SENSORS
AREA
SENSORS
LIGHT
CURTAINS /
SAFETY
COMPONENTS
PRESSURE /
FLOW
SENSORS
INDUCTIVE
PROXIMITY
SENSORS
PARTICULAR
USE
SENSORS
SENSOR
OPTIONS
SIMPLE
WIRE-SAVING
UNITS
WIRE-SAVING
SYSTEMS
MEASUREMENT
SENSORS
STATIC
ELECTRICITY
PREVENTION
DEVICES
LASER
MARKERS
PLC
HUMAN
MACHINE
INTERFACES
ENERGY
CONSUMPTION
VISUALIZATION
COMPONENTS
FA
COMPONENTS
MACHINE
VISION
SYSTEMS
UV
CURING
SYSTEMS
1,000 V AC for one min. between all supply terminals connected together and enclosure
Vibration resistance
Connection terminal
PHOTOELECTRIC
SENSORS
30 to 85 % RH, Storage: 30 to 95 % RH
20 MΩ, or more, with 500 V DC megger between all supply terminals connected together and enclosure
Material
LASER
SENSORS
–10 to +55 °C +14 to +131 °F (No dew condensation or icing allowed), Storage: –25 to +70 °C –13 to +158 °F
Insulation resistance
Shock resistance
708
30 G acceleration in X, Y and Z directions for three times each
Enclosure: ABS
Detachable spring-cage terminal
Net weight: 250 g approx.
Notes: 1) Where measurement conditions have not been specified precisely, the conditions used were an ambient temperature of +20 °C +68 °F.
2) S
F-C14EX-01 is Handy-controller non-compatible type.
3) Both safety output 1 and 2 are OFF when the emergency stop is valid regardless of whether the light curtain is in the light receiving or light interrupted
condition.
4) The auto-reset cannot be used with safety output 3.
5) The auxiliary output incorporated in the SF4B series is output.
Selection
Guide
Light
Curtains
Safety
Components
Optical Touch
Switch
Control
Units
Definition of
Sensing
Heights
SF-C10
SF-CL1T264T
SF-AC
709
LASER
SENSORS
PHOTOELECTRIC
SENSORS
MICRO
PHOTOELECTRIC
SENSORS
AREA
SENSORS
LIGHT
CURTAINS /
SAFETY
COMPONENTS
PRESSURE /
FLOW
SENSORS
INDUCTIVE
PROXIMITY
SENSORS
PARTICULAR
USE
SENSORS
SENSOR
OPTIONS
SIMPLE
WIRE-SAVING
UNITS
WIRE-SAVING
SYSTEMS
MEASUREMENT
SENSORS
STATIC
ELECTRICITY
PREVENTION
DEVICES
LASER
MARKERS
PLC
HUMAN
MACHINE
INTERFACES
ENERGY
CONSUMPTION
VISUALIZATION
COMPONENTS
LIGHT CURTAIN WIRING DIAGRAMS
Wiring diagram of SF-C11 and SF4B series or SF2B series (Control category 4 or 2)
For PNP output (minus ground)
UV
CURING
SYSTEMS
When connecting the SF-C11 to the light curtains, make sure
to use the 8-core connection cable with a connector. Refer to
the SF4B series and SF2B series for details.
SFB-CB□, SF2B-CB□, SFB-CCJ10□
• Set the light curtain input polarity selection switch to the
PNP side and ground the 0 V line.
Light curtain input polarity selection switch
+24 V DC
A1
F
Receiver side
connector
L1
RESET
(Note 1)
(Note 1)
(Note 2) X1 X2 X3
A B
Ui
FUSE1
FUSE2
13 23
Terminal arrangement diagram
33 41
K1
NPN
SF-C11 control circuit PNP
K2
Emitter side
connector
F.G.
OUT
A2
AUX
INTER_LOCK
FAULT
14 24 34 42
T1
KA, KB: Magnet contactor
KB
KA
N
T2
0 V TEST
(Note 3)
L1 L2 L3
KB
KA
M
3
Notes: 1) The above diagram is when using manual reset. If automatic reset is
used, disconnect the lead from X2 and connect it to X3. In this case, a
reset (RESET) button is not needed.
2) Use a momentary-type switch as the reset (RESET) button.
3) E
mission halt occurs when the test (TEST) button is open, and emission occurs
when the test (TEST) button is short-circuited. If not using the test (TEST)
button, short-circuit T1 and T2. However, in case of SF2B series, use a test rod
or similar to interrupt the light in order to carry out self-diagnosis separately.
• In the above
diagram, set the
light curtain input
polarity selection
switch to the NPN
side and ground
the + side.
F.G.
Emitter side
connector
X1 X2
X3
A
Ui
SF-C11 control circuit
AUX
T2
Receiver side connector
Control
Units
SF-C10
SF-CL1T264T
SF-AC
MPCE1
FUSE
FUSE
MPCE2
Definition of
Sensing
Heights
OSSD2
+24 V DC
OSSD1
EDM (External relay monitor)
Synchronization wire +
Synchronization wire –
0V
Shielded wire
4
Note: It is not used with the SF2B series.
FAULT
T1
When connecting the SF-C12 to the light curtains, make sure to
use the 12-core connection cable with a connector. Refer to the
SF4B series for details.
SFB-CB05-MU (Cable length: 0.5 m 1.640 ft)
SFB-CCJ10E-MU (Extension cable for emitter, cable length: 10 m 32.808 ft)
SFB-CCJ10D-MU (Extension cable for receiver, cable length: 10 m 32.808 ft)
Terminal arrangement diagram
Light curtain input
polarity selection switches
PNP
Safety
Components
Interlock (Note)
+24 V DC
Emission halt
Auxiliary output
Synchronization wire +
Synchronization wire –
0V
Shielded wire
8
For PNP output (minus ground)
Optical Touch
Switch
1
7
Wiring diagram of SF-C12 and SF4B series (Control category 4)
X1
X2
T1
T2
E–
E+
R–
R+
FB1
FB2
FB3
FB4
32
31
24
23
14
13
A1
A2
FG
Receiver side
connector
3
NPN
PNP
0 V TEST
Emission halt input switch
(Note)
(Note)
Interference
prevention wire
Emitter side connector
Test output terminal
Test input terminal
Semiconductor auxiliary output
Emitter side
connector
5
INTER_LOCK
Not used
Connector
pin No.
6
OUT
A2
Function
+24 V DC
0V
Safety output (NO contact × 3)
Auxiliary output (NC contact × 1)
Reset output terminal
Reset input terminal (Manual)
Reset input terminal (Automatic)
2
6
B
F
Receiver side
connector
8
5
RESET
A1
NPN
Light
Curtains
1
7
• Set the two light curtain input polarity selection switches to
the PNP side and connect the F.G. terminal to the 0 V line.
Selection
Guide
2
3
4
+24 V DC
Terminal
A1
A2
13-14, 23-24, 33-34
41-42
X1
X2
X3
A
B
T1
T2
AUX
Pin layout for light curtain connectors
Light curtain input polarity
selection switch
For NPN output (plus ground)
FA
COMPONENTS
MACHINE
VISION
SYSTEMS
SF-C10 SERIES
Enabling path Auxiliary Power input
output
24 V DC ±10 %
Note: The above diagram is when using manual reset. If automatic reset is
used, connect a normal close-type pushbutton switch between T1 and
T2 and leave between X1 and X2 open.
Terminal
Function
FG
A2
A1
13-14, 23-24
31-32
FB4
FB3
FB2
FB1
Frame ground (F.G.) terminal
0V
+24 V DC
Safety output (NO contact × 2)
Auxiliary output (NC contact × 1)
External relay monitor
terminal 2
External relay monitor
terminal 1
• In the above diagram, set the two light curtain input
polarity selection switches to the NPN side and connect
the F.G. terminal to the + side.
Terminal
R+
R–
E+
E–
T2
T1
X2
X1
Function
Interference prevention wire – (Receiver side)
Interference prevention wire + (Receiver side)
Interference prevention wire – (Emitter side)
Interference prevention wire + (Emitter side)
Emission halt input
terminal
Automatic reset / manual reset selection terminal
Manual reset: X1 – X2 short-circuited
Pin layout for light curtain connectors
1
10
2
9
3
12
11
8
For NPN output (plus ground)
X1
X2
T1
T2
EE+
RR+
FB1
FB2
FB3
FB4
32
31
24
23
14
13
A1
A2
FG
FIBER
SENSORS
Exclusive Control Unit for Light Curtain
7
6
5
4
Note: Input and
output for pin
Nos. 11 and
12 are not
used by this
product
Connector
pin No.
Emitter side
connector
Receiver side
connector
1
2
3
4
5
6
7
8
9
10
11
12
Interlock
+24 V DC
Emission halt
Auxiliary output
Synchronization wire +
Synchronization wire –
0V
Shielded wire
Interference prevention wire +
Interference prevention wire –
(Override input)
(Muting lamp output)
OSSD2
+24 V DC
OSSD1
EDM (External relay monitor)
Synchronization wire +
Synchronization wire –
0V
Shielded wire
Interference prevention wire +
Interference prevention wire –
(Muting input 1)
(Muting input 2)
Exclusive Control Unit for Light Curtain
710
SF-C10 SERIES
LIGHT CURTAIN WIRING DIAGRAMS
FIBER
SENSORS
LASER
SENSORS
Wiring diagram of SF-C13 and SF4B series or SF2B series (Control category 4 or 2)
For PNP output (minus ground)
For NPN output (plus ground)
• Connect the light curtain control outputs OSSD1 and
OSSD2 to S1 and S2 respectively.
• Connect the light curtain control outputs OSSD1 and
OSSD2 to S4 and S2 respectively and ground the + side.
PHOTOELECTRIC
SENSORS
MICRO
PHOTOELECTRIC
SENSORS
AREA
SENSORS
Emitter
Receiver
Cable color: Gray with black line
Cable color: Gray
+V (Brown)
+24 V DC
INDUCTIVE
PROXIMITY
SENSORS
(Orange / Black) Synchronization –
Output
Emission halt Auxiliary output Interlock setting input
polarity
input / Reset input (Yellow-green / (Pale purple) (Note 4)
setting wire (Pink) (Note 3)
Black) Open
(Shield) (Note 5) 0 V
+V
Load
(Blue)
(Brown)
Output
polarity
setting wire
0 V (Shield)
Load
(Blue) (Note 5)
External device monitoring input (Yellow-green)
Output
polarity
setting wire
(Shield) (Note 5)
S2 S3
(Note 1) FUSE1
S4 X1 X2
X3
F
13 23
OSSD1 (Black)
(Note 1) FUSE1
FUSE2
33 41
A1
F.G.
S1
S2 S3 S4
X1
X2
X3 13 23
F
OUT
0V
F.G.
INTER_LOCK
KA, KB: Magnet contactor
KA
N
STATIC
ELECTRICITY
PREVENTION
DEVICES
RESET
(Note 1, 2)
LASER
MARKERS
K2
FAULT
14 24
MEASUREMENT
SENSORS
33 41
SF-C13 control circuit
K2
AUX
FUSE2
K1
Ui
SF-C13 control circuit
A2
WIRE-SAVING
SYSTEMS
L1
K1
Ui
SIMPLE
WIRE-SAVING
UNITS
OSSD2 (White)
L1
S1
SENSOR
OPTIONS
0 V (Blue)
OSSD2 (White)
A1
PARTICULAR
USE
SENSORS
External device monitoring input (Yellow-green)
OSSD1 (Black)
RESET
(Note 1, 2)
34 42
L1 L2 L3
KB
OUT
KB
KA
M
3
Notes: 1) The above diagram is when using manual reset. If automatic reset
is used, disconnect the lead from X2 and connect it to X3. In this
case, a reset (RESET) button is not needed.
2) Use a momentary-type switch as the reset (RESET) button.
3) This is a test input (pink) for the SF2B series.
4) This is not equipped on the SF2B series.
5) This is a shield for the SF2B series. Output polarity cannot be set.
A2
0V
LIGHT
CURTAINS /
SAFETY
COMPONENTS
PRESSURE /
FLOW
SENSORS
(Orange)
Synchronization +
+24 V DC
(Orange / Black) Synchronization –
Output
polarity Emission halt Auxiliary output Interlock setting input
setting wire input / Reset input (Yellow-green / (Pale purple) (Note 4)
Black) Open +V (Brown)
(Shield) (Note 5) (Pink) (Note 3)
Receiver
Cable color: Gray with black line
Cable color: Gray
+V (Brown)
(Orange)
Synchronization +
0V
(Blue)
Emitter
INTER_LOCK
FAULT
14 24
AUX
KA, KB: Magnet contactor
KA
N
34 42
L1 L2 L3
KB
KB
KA
M
3
Notes: 1) T
he above diagram is when using manual reset. If automatic reset
is used, disconnect the lead from X2 and connect it to X3. In this
case, a reset (RESET) button is not needed.
2) Use a momentary-type switch as the reset (RESET) button.
3) This is a test input (pink) for the SF2B series.
4) This is not equipped on the SF2B series.
5) This is a shield for the SF2B series. Output polarity cannot be set.
PLC
HUMAN
MACHINE
INTERFACES
ENERGY
CONSUMPTION
VISUALIZATION
COMPONENTS
FA
COMPONENTS
MACHINE
VISION
SYSTEMS
UV
CURING
SYSTEMS
Terminal arrangement diagram
A1
A2
S1
S2
S3
S4
AUX
X1
X2
X3
13
14
23
24
33
34
41
42
Terminal
Function
When connecting the SF-C13 to the light curtains, make sure to
use a discrete wire connection cable. Refer to the SF4B series
and SF2B series for details.
SFB-CCB□(-MU), SF2B-CCB□, SFB-CC□(-MU)
A1
+24 V DC
A2
0V
S1 to S4
Light curtain control output (OSSD) input terminal
AUX
Semiconductor auxiliary output
X1
Reset output terminal
X2
Reset input terminal (Manual)
X3
Reset input terminal (Automatic)
13-14, 23-24, 33-34
Safety output (NO contact × 3)
SF-C10
41-42
Auxiliary output (NC contact × 1)
SF-CL1T264T
Use a separate terminal block to carry out wiring
for light curtains that cannot be connected to the
SF-C13.
Selection
Guide
Light
Curtains
Safety
Components
Optical Touch
Switch
Control
Units
Definition of
Sensing
Heights
SF-AC
711
FIBER
SENSORS
LASER
SENSORS
PHOTOELECTRIC
SENSORS
MICRO
PHOTOELECTRIC
SENSORS
AREA
SENSORS
LIGHT
CURTAINS /
SAFETY
COMPONENTS
PRESSURE /
FLOW
SENSORS
INDUCTIVE
PROXIMITY
SENSORS
PARTICULAR
USE
SENSORS
Exclusive Control Unit for Light Curtain
LIGHT CURTAIN WIRING DIAGRAMS
Wiring diagram of SF-C14EX(-01) and SF4B series (Control category 4)
WIRE-SAVING
SYSTEMS
MEASUREMENT
SENSORS
STATIC
ELECTRICITY
PREVENTION
DEVICES
LASER
MARKERS
• Set the output polarity selection switch to the PNP side and ground the 0 V line.
Emergency
stop switch
+24 V DC
HUMAN
MACHINE
INTERFACES
ENERGY
CONSUMPTION
VISUALIZATION
COMPONENTS
FA
COMPONENTS
MACHINE
VISION
SYSTEMS
UV
CURING
SYSTEMS
(Note 1)
KA RESET
KB (Note 2)
(Note 1)
KC RESET
KD (Note 2)
PLC etc.
KE RESET
KF (Note 2)
A1 S11 S12 S21 S22 X11 X12 X13 X21 X22 X23 X31 X32 AUX1 AUX2 AUX3 AUX4 IE+ IE– IR+ IR–
Receiver side NPN
Output polarity
connector
selection switch
PNP
SF-C14EX(-01) control circuit
Muting sensor 1
(PNP output type)
Muting sensor 2
(NPN output type)
Override input
TEST
Muting lamp
output 1
3.6 to 30 W
0V
Muting lamp
output 2
3.6 to 30 W
KA to KF: Force-guided relay or
magnet contactors.
Notes: 1) The above diagram is when using manual reset. If automatic reset is used, disconnect the lead from X12 and X22, and connect them to X13 and X23 as
shown by the dotted lines. In this case, a reset (RESET) button is not needed. Terminals X31 to X32 are for manual reset only.
2) Use a momentary-type switch for the reset (RESET) button.
For NPN output (plus ground)
• Set the output polarity selection switch to the NPN side and ground the + side of the power supply input.
Emergency
stop switch
(Note 1)
KA RESET
KB (Note 2)
(Note 1)
KC RESET
KD (Note 2)
KE RESET
KF (Note 2)
PLC etc.
F.G.
A1 S11 S12 S21 S22 X11 X12 X13 X21 X22 X23 X31 X32 AUX1 AUX2 AUX3 AUX4 IE+ IE– IR+ IR–
Receiver side NPN
Output polarity
connector
selection switch
PNP
Emitter side
connector
SF-C14EX(-01) control circuit
Safety
Components
Optical Touch
Switch
Control
Units
Definition of
Sensing
Heights
SF-C10
SF-CL1T264T
SF-AC
Notes: 1) The left diagram is when using manual reset. If automatic
reset is used, disconnect the lead from X12 and X22, and
connect them to X13 and X23 as shown by the dotted
lines. In this case, a reset (RESET) button is not needed.
Terminals X31 to X32 are for manual reset only.
2) Use a momentary-type switch for the reset (RESET) button.
A2 S3+ S3 S3– S4+ S4 S4– T1 T2 O1 O2 L1+ L1– L2+ L2– 14 24 34 44 54 64
KB
KD
KF
+V OUT 0V +V OUT 0V
0V
KA
Muting sensor 1
(PNP output type)
KC
TEST
Muting sensor 2
(NPN output type)
Override input
Terminal
Light
Curtains
• If the emergency stop switch is
not used, short-circuit between the
terminals S11 to S12 and S21 to S22
directly.
A2 S3+ S3 S3– S4+ S4 S4– T1 T2 O1 O2 L1+ L1– L2+ L2– 14 24 34 44 54 64
KB
KD
KF
+V OUT 0V +V OUT 0V
0V
F.G.
KA
KC
KE
Muting lamp
output 1
3.6 to 30 W
Muting lamp
output 2
3.6 to 30 W
KE
24 V
KA to KF: Force-guided relay or
magnet contactors.
Terminal arrangement diagram
Selection
Guide
S3+ S3 S3– S4+ S4 S4–
Emitter side
connector
+24 V DC
PLC
• When connecting the SF-C14EX to
the light curtains, make sure to use
the following connecting cable.
SFB-CB05-EX (Cable length: 0.5 m 1.640 ft)
SFB-CB5-EX (Cable length: 5 m 16.404 ft)
SFB-CB10-EX (Cable length: 10 m 32.808 ft)
• If the NO (Normally Open) contact
switch is used as a muting sensor,
wire it as shown in the figure below.
For PNP output (minus ground)
SENSOR
OPTIONS
SIMPLE
WIRE-SAVING
UNITS
SF-C10 SERIES
Pin layout for light curtain connectors
Function
Terminal
Function
14 Safety output 1, Light received / Light S11 Emergency stop
24 interrupted output of the light curtain S12 contact input
2 NC input
34 Safety output 2, Light curtain output S21 Between S11 and S12
44 including the muting function
S22 Between S21 and S22
S3–
S4+
S4
S4–
T1
T2
O1
O2
(PNP output type)
S3+, S3–: Power supply
S3: Sensor output
Muting sensor input 2
(NPN output type)
S4+, S4–: Power supply
S4: Sensor output
Test input terminal
Open: Test mode
Short-circuit: Normal operation
Override input terminal
Open: Invalid
Short-circuit: Valid
3
Interference
Interference
prevention wire – prevention wire –
4
Auxiliary output
5
Synchronization Synchronization
wire +
wire +
X31 Safety output 3 reset input
X32 X31 - X32: Manual reset
6
Synchronization Synchronization
wire –
wire –
AUX1 Auxiliary output 1, Muting output
7
0V
0V
AUX2 Auxiliary output 2, Override output
8
Shielded wire
Shielded wire
X21 Safety output 2 reset input
X22 X21 - X22: Manual reset
X23 X21 - X23: Auto-reset
AUX3 Auxiliary output 3, Blown lamp output
AUX4 Auxiliary output 4, Light curtain auxiliary output
IR+ Interference prevention terminal, Receiver side +
0V
Receiver side
connector
+24 V DC
L2+ Muting lamp output
L2– 2
A2
Emitter side
connector
2
IE+ Interference prevention terminal, Emitter side +
+24 V DC
Connector
pin No.
8
Interference
Interference
prevention wire + prevention wire +
L1+ Muting lamp output
L1– 1
A1
1
1
54 Safety output 3
X11 Safety output 1 reset input
64 Emergency stop output X12 X11 - X12: Manual reset
S3+ Muting sensor input 1 X13 X11 - X13: Auto-reset
S3
2
3
IE– Interference prevention terminal, Emitter side –
IR– Interference prevention terminal, Receiver side –
7
4
6
5
+24 V DC
Not used
Exclusive Control Unit for Light Curtain
PRECAUTIONS FOR PROPER USE
Part description and function [SF-C14EX(-01)]
1
Emitter side connector
2
Receiver side connector
15 Interlock
1 indicator
(INTER LOCK1)(Yellow)
8
Safety output 1 indicator
(OUT1)(Green)
3
Digital indicator (Red)
4
Power indicator (Ui)
(Green)
11 Output
5
Muting sensor 1
indicator (MU1)(Orange)
13 Auxiliary
6
Test input indicator
(TEST)(Yellow)
16 Interlock
7
9
Muting sensor 2
indicator (MU2)(Orange)
Safety output 2 indicator (OUT2)(Green)
10
Safety output 3 indicator (OUT3)(Green)
No.
Description
12 Auxiliary
output 1
indicator (AUX1)(Orange)
polarity
selection switch
Output waveform (Safety output ON) [SF-C14EX(-01)]
• When safety output is ON, self-diagnosis of the output
circuit is carried out, so that the output transistor will
periodically turn OFF. (OFF pulse width: 100 µs or less)
When the OFF signal is fed back, the receiver judges the
output circuit as normal. When the OFF signal is not fed
back, the receiver judges either the output circuit or wiring
as error, and the safety output maintains OFF status.
Since the OFF signal of SF-C14EX(-01) might cause
malfunction, perform the connecting paying attention
to the input response time of the machine to be
connected to SF-C14EX(-01).
2 indicator
(INTER LOCK2)(Yellow)
14 Auxiliary
output 3
indicator (AUX3)(Orange)
3 indicator
(INTER LOCK3)(Yellow)
Function
1
Emitter side connector
The emitter of SF4B series is connected.
2
Receiver side connector
The receiver of SF4B series is connected.
3
Digital indicator (Red)
Lights up or blinks when there is a problem.
Lights up when blanking function is enabled.
4
Power indicator (Ui) (Green)
Lights up when the power is ON.
5
Lights up when test input is enabled. Blinks while
Test input indicator (TEST) (Yellow) communication with SFB-HC handy-controller is
in progress. (Excluding SF-C14EX-01)
6
Muting sensor 1 indicator (MU1) (Orange) Lights up when muting sensor 1 is ON.
7
Muting sensor 2 indicator (MU2) (Orange) Lights up when muting sensor 2 is ON.
8
Safety output 1 indicator (OUT1) (Green)
Lights up when safety output 1 is ON.
9
Safety output 2 indicator (OUT2) (Green)
Lights up when safety output 2 is ON.
10
Safety output 3 indicator (OUT3) (Green)
Lights up when safety output 3 is ON.
11
Output polarity selection switch
PNP (minus ground) or NPN
(plus ground) can be selected. The
factory setting is PNP (minus ground).
12
Auxiliary output 1 indicator (AUX1) (Orange)
Lights up when auxiliary output 1 is ON.
13
Auxiliary output 2 indicator (AUX2) (Orange)
Lights up when auxiliary output 2 is ON.
14
Auxiliary output 3 indicator (AUX3) (Orange)
Lights up when auxiliary output 3 is ON.
15
Interlock 1 indicator (INTER LOCK1) (Yellow) Lights up when interlock 1 is ON.
16
Interlock 2 indicator (INTER LOCK2) (Yellow) Lights up when interlock 2 is ON.
17
Interlock 3 indicator (INTER LOCK3) (Yellow) Lights up when interlock 3 is ON.
Wiring
• The following solid wire and twisted wires (lead wire) are
recommended.
SF-C11
Power supply and output line connector: 0.2 to 2.5mm2
(AWG24 to 12)
Signal line connector: 0.2 to 1.5mm2 (AWG24 to 16)
SF-C13
Single wire: ø0.4 to ø1.2 mm ø0.016 to ø0.047 in
(AWG26 to 16)
Twisted wire (lead wire): 0.3 to 1.25mm2 (AWG22 to 16)
SF-C14EX(-01)
Power supply line connector (A1, A2): 0.2 to 2.5mm2
(AWG24 to 12)
Other connectors: 0.2 to 1.5mm2 (AWG24 to 16)
712
Refer to p.1501 for general precautions.
output 2
indicator (AUX2)(Orange)
17 Interlock
SF-C10 SERIES
FIBER
SENSORS
LASER
SENSORS
PHOTOELECTRIC
SENSORS
MICRO
PHOTOELECTRIC
SENSORS
AREA
SENSORS
LIGHT
CURTAINS /
SAFETY
COMPONENTS
PRESSURE /
FLOW
SENSORS
INDUCTIVE
PROXIMITY
SENSORS
PARTICULAR
USE
SENSORS
Time chart [SF-C14EX(-01)]
Normal operation
SENSOR
OPTIONS
• The diagram shows operation with safety outputs 1 and 2
in manual-reset mode.
SIMPLE
WIRE-SAVING
UNITS
Light received
Light interrupted
Invalid
Emergency stop
Valid
Muting sensor 1 ON
OFF
Muting sensor 2 ON
OFF
ON
Reset input 1
OFF
ON
Reset input 2
OFF
ON
Reset input 3
OFF
Safety output 1 ON
OFF
(14, 24)
Safety output 2 ON
OFF
(34, 44)
Safety output 3 ON
OFF
(54, 64)
Auxiliary output 1 ON
(Muting output) OFF
Auxiliary output 4 ON
(Auxiliary output of light curtain) OFF
ON
Muting lamp
OFF
output 1 / 2
Light
curtain
WIRE-SAVING
SYSTEMS
MEASUREMENT
SENSORS
0 to 3 sec.
0 to 3 sec.
• The diagram above is the timing chart of SF-C14EX(-01)
in normal operation.
• In normal operation, auxiliary output 2 (override output) is
maintained in the ON state.
• In normal operation, auxiliary output 3 (muting lamp
output) is maintained in the ON state.
STATIC
ELECTRICITY
PREVENTION
DEVICES
LASER
MARKERS
PLC
HUMAN
MACHINE
INTERFACES
ENERGY
CONSUMPTION
VISUALIZATION
COMPONENTS
FA
COMPONENTS
MACHINE
VISION
SYSTEMS
UV
CURING
SYSTEMS
Selection
Guide
Light
Curtains
Safety
Components
Optical Touch
Switch
Control
Units
Definition of
Sensing
Heights
SF-C10
SF-CL1T264T
SF-AC
713
FIBER
SENSORS
LASER
SENSORS
PHOTOELECTRIC
SENSORS
MICRO
PHOTOELECTRIC
SENSORS
AREA
SENSORS
LIGHT
CURTAINS /
SAFETY
COMPONENTS
PRESSURE /
FLOW
SENSORS
INDUCTIVE
PROXIMITY
SENSORS
PARTICULAR
USE
SENSORS
SENSOR
OPTIONS
SIMPLE
WIRE-SAVING
UNITS
WIRE-SAVING
SYSTEMS
MEASUREMENT
SENSORS
STATIC
ELECTRICITY
PREVENTION
DEVICES
LASER
MARKERS
PLC
HUMAN
MACHINE
INTERFACES
ENERGY
CONSUMPTION
VISUALIZATION
COMPONENTS
FA
COMPONENTS
MACHINE
VISION
SYSTEMS
UV
CURING
SYSTEMS
Selection
Guide
Light
Curtains
Safety
Components
Optical Touch
Switch
Control
Units
Definition of
Sensing
Heights
SF-C10
SF-CL1T264T
SF-AC
Exclusive Control Unit for Light Curtain
SF-C10 SERIES
PRECAUTIONS FOR PROPER USE
Time chart [SF-C14EX(-01)]
Test input, Override input
• The diagram shows operation with safety outputs 1 and 2
in auto-reset mode.
Open
Short-circuited
Override input Valid
Invalid
Light received
Light
curtain
Light interrupted
Muting sensor ON
1/2
OFF
Safety output 1 ON
(14, 24)
OFF
Safety output 2 ON
(34, 44)
OFF
Auxiliary output 1 ON
(Muting output) OFF
Auxiliary output 2 ON
(Override output) OFF
ON
Muting lamp
OFF
output 1 / 2
Test input
0 to 1 sec.
3 sec.
Override input time: Max. 60 sec.
• Safety outputs 1 and 2 are OFF during test input.
• The override function becomes valid when all the
conditions listed below are satisfied:
• An incandescent lamp with 3.6 to 30 W is at least connected to
either muting lamp output 1 or 2.
• The signal is input to either muting sensor 1 or 2.
• The override input terminal O1 and O2 is short-circuited and
the test input terminal T1 / T2 is opened within 1 sec. (3 sec.
continuously)
If one of the three conditions above becomes invalid
or the timing exceeds 60 sec., the override function
becomes invalid.
Blown lamp output
• The diagram shows operation with safety outputs 1
and 2 in auto-reset mode.
Light received
Light interrupted
ON
Muting
OFF
sensor 1
ON
Muting
sensor 2
OFF
Safety output 2 ON
OFF
(34, 44)
Auxiliary output 1 ON
(Muting output) OFF
Auxiliary output 3 ON
(Blown lamp output) OFF
ON
Muting lamp
OFF
output 1
ON
Muting lamp
OFF
output 2
Light
curtain
Blown lamp
Blown lamp
Blown lamp
• The lamps are monitored during muting state, and if
either of them breaks, auxiliary output 3 is turned OFF.
If only one lamp breaks, the muting state is maintained,
however, if both lamps break, the muting state is
canceled immediately.
Others
• When connecting this product to a product other than the
connectable input device, the system does not conform
to the control category 4 based on ISO 13849-1:1999(EN
954-1, JIS B 9705-1).
• The power supply unit of SF-C10 series uses the
electronic fuse which does not require any replacement.
• When the electronic fuse trips, turn off the power supply
and eliminate the cause for the overcurrent. After that,
turn the power back on.
• The electronic fuse is not meant to be used for equipment
that is operated continuously. Note that the specification
may not be satisfied by continuous operation.
Refer to p.1501 for general precautions.
• Make sure to carry out the wiring in the power supply off
condition.
• Wrong wiring will damage the product.
• Verify that the supply voltage variation is within the
rating. Note that if a voltage exceeding the rated range is
applied, or if an AC power supply is directly connected,
the unit may get burnt or damaged.
• The DC power supply unit must satisfy the conditions
given below:
1) P
ower supply unit authorized in the region where this
device is to be used.
2) P
ower supply unit conforming to EMC Directive and Lowvoltage Directive (In case CE conformity is required.)
3) P
ower supply unit conforming to the Low-voltage
Directive and with an output of 100 VA or less.
4) T
he frame ground (F.G.) terminal must be connected
to ground when using a commercially available
switching regulator.
5) P
ower supply unit with an output holding time of 20 ms
or more.
6) U
se an isolation transformer for the DC power supply unit.
7) If surges are likely to occur, take countermeasures such
as connecting a surge absorber to the origin of the surge.
8) P
ower supply unit corresponding to CLASS 2 (In case
UL / c UL conformity is required.)
As provided in IEC 60536 (CLASS: Protection against
Electric Shook), this power supply should require no
ground earth and satisfy the insulation distance by double
insulation or reinforced insulation.
If the power supply conforms to Low-voltage Directive
and has an output of 100 VA or less, it can be used as
a suitable product.
• Do not run the wires together with high-voltage lines or
power lines or put them in the same raceway. This can
cause malfunction due to induction.
• This product is not dust-proof / splash proof. Be sure to put
this product into a control box having IP54 construction.
(Excluding SF-C12)
• Avoid dust, dirt and steam.
• Take care that the product does not come in direct contact
with oil, grease, or organic solvents, such as, thinner, etc.
• Note that this equipment is applicable only in the control
circuit grounded in accordance with IEC 60204-1 and
JIS B 9960-1, or in the control circuit in which the insulation
monitor unit (ground fault detection unit) is included.
• This unit is suitable for indoor use only.
• The seal as shown in the drawing on the below is stuck
to the engagement point of unit. If the seal is peeled off
or broken, SF-C10 series will not be certified as “Safety
equipment” and will not be covered by our guarantee.
Do not open!
If this seal is removed or damaged,
the units are not recognized as safety product.
Exclusive Control Unit for Light Curtain
DIMENSIONS (Unit: mm in)
Control unit
4
0.157
46
1.811
23
0.906
13
0.512
40
1.575
25
0.984
35
1.378
67.3
2.650
48.8
1.921
SF-C12
Control unit
2-ø6 ø0.236
2-ø10 ø0.394
6
7 0.276 0.236
6.5
0.256
80
3.150
100
3.937
(
130
5.118
28
1.102
114
4.488 8
0.315
6
0.236
10
0.394
21
0.827
8 0.315
11.5
0.453
Receiver
side
connector
67.5
2.657
6.5
0.256
( )
Suitable for 35 mm 1.378 in width DIN rail
MICRO
PHOTOELECTRIC
SENSORS
AREA
SENSORS
PRESSURE /
FLOW
SENSORS
INDUCTIVE
PROXIMITY
SENSORS
PARTICULAR
USE
SENSORS
SENSOR
OPTIONS
SIMPLE
WIRE-SAVING
UNITS
36.5
1.437
36.5 34.2
1.437 1.346
LASER
SENSORS
LIGHT
CURTAINS /
SAFETY
COMPONENTS
81.4
135 3.205
5.315
6
19.5 0.236
0.768
22 24.5 30.5
0.866 0.965 1.201
)
FIBER
SENSORS
PHOTOELECTRIC
SENSORS
127
5.000
80
3.150
30
1.181
Emitter side
connector
3 × 6 = 18
3 × 0.236 = 0.709
130
5.118
714
The CAD data in the dimensions can be downloaded from our website.
SF-C11
54.1
2.130
SF-C10 SERIES
WIRE-SAVING
SYSTEMS
MEASUREMENT
SENSORS
STATIC
ELECTRICITY
PREVENTION
DEVICES
SF-C13
Control unit
SF-C14EX(-01)
Application expansion unit
LASER
MARKERS
PLC
6.75
0.266
4
0.157
5
0.197
6
0.236
34.5
1.358
35
1.378
67.3
2.650
4 0.157
3 × 5 = 15
3 × 0.197 = 0.591
130
5.118
54.1
2.130
40
1.575
Emitter side
connector
25
34.1
0.984 1.343
35
1.378
91.6
3.606
13
0.512
67.3
2.650
6.5
0.256
80
3.150
80.8
3.181
13
0.512
Suitable for 35 mm 1.378 in width DIN rail
22.5
0.886
5
0.197
10
0.394
HUMAN
MACHINE
INTERFACES
Receiver
side
connector
31.1
1.224
11
0.433
130
5.118
10
0.394
13.5
0.531
46
1.811
38.4 1.512
18 18.4
0.709 0.724
23 0.906
80
3.150
99
3.898
Suitable for 35 mm 1.378 in width DIN rail
6.5
0.256
(
)
ENERGY
CONSUMPTION
VISUALIZATION
COMPONENTS
FA
COMPONENTS
MACHINE
VISION
SYSTEMS
UV
CURING
SYSTEMS
Selection
Guide
Light
Curtains
Safety
Components
Optical Touch
Switch
Control
Units
Definition of
Sensing
Heights
SF-C10
SF-CL1T264T
SF-AC