Digital Input Modules for Compact FieldPoint
NI cFP-DI-300, NI cFP-DI-301, NI cFP-DI-304, NI cFP-DI-330
• 8-,16-, or 32-channel inputs • 24 VDC inputs • 4 to 250 VDC inputs • 15 to 250 VAC inputs (50/60 Hz AC) • 3 to 250 VAC inputs (1 kHz AC) • 2,300 Vrms bank isolation for transient overvoltage protection • Hot-swappable with autoconfiguration • -40 to 70 °C operating range
Module cFP-DI-300 cFP-DI-301 cFP-DI-304 cFP-DI-330
Input Channels 8 16 32 8
Input Ranges
Input Type
Compatibility Examples
Separate Ground Plane per Channel
All Channel Update Rate1
Additional Features
18 to 30 VDC Sinking 24 VDC sourcing devices – 1 kHz – 18 to 30 VDC Sinking 24 VDC sourcing devices – 1 kHz – 10 to 30 VDC Sinking 24 VDC sourcing devices – 1 kHz Hysteresis 5 to 48 VDC Sinking or sourcing TTL, CMOS, 12 VDC, 24 VDC, 1 kHz Input current limiting 5 to 250 VAC 48 VDC, 120/240 VAC/VDC (1.5 mA) 1The all-channel update rate refers to the time the module takes to sample all channels. The overall system update rate is affected by other factors, such as the aggregate module update rate and software loop rate. To calculate the system update rate, visit ni.com/info and enter “systemrate.”
Overview
National Instruments cFP-DI-3xx devices are versatile digital input modules available for Compact FieldPoint systems. You can use these modules to monitor digital signals ranging from low-voltage levels up to 250 V. They are commonly used to monitor proximity and limit switches, pushbutton switches, thermostat outputs, relay closures, power circuits, and TTL devices. All the modules include onboard diagnostics to ensure trouble-free installation and maintenance.
Each channel on the cFP-DI-330 includes circuitry that limits the total current to 1.5 mA to prevent damaging the module. All channels on the cFP-DI-3xx modules feature LEDs that indicate the input state of each channel. The modules include an all-channel update rate of 1 kHz. Overall data throughput depends on software loop speeds and network speeds.
Isolation
The cFP-DI-3xx modules feature bank isolation with 2,300 Vrms of breakdown isolation. In addition, the cFP-DI-330 provides double insulation for up to 250 Vrms of operational isolation. You can safely use Compact FieldPoint with the cFP-CB-1 connector block in applications where hazardous voltages are present. These Compact FieldPoint modules do not have channel-to-channel isolation.
Digital Input Modules
The cFP-DI-3xx modules provide built-in module-to-module isolation to protect your Compact FieldPoint system and controller or communication interface from high voltage levels. The cFP-DI-300, cFP-DI-301, and cFP-DI-304 modules use a common ground plane for all the input channels. Each channel on the cFP-DI-300, cFP-DI-301, and cFP-DI-304 modules includes current-limiting circuitry to prevent module damage when connected directly to a 24 VDC source. The cFP-DI-330 uses eight optically isolated input channels so that each digital input has a separate ground plane, and you can use each channel with a different voltage potential. Thus, you can connect one channel to a 5 VDC TTL signal and another signal on the same cFP-DI-330 module to a 250 VAC line voltage.
Field I/O Connections
Compact FieldPoint modules include a built-in power distribution bus that provides multiple power connections on the module. A field-wired power supply connected to the voltage (V) and common (C) terminals is internally connected to a power distribution bus that delivers additional breakout terminals for voltage supply (VSUP) and common (COM). These terminals offer a convenient way to distribute power to field devices that require external power.
Digital Input Modules for Compact FieldPoint
V VSUP (Ch 0) SinkingOutput Device with External Power +
COM (Ch 0) VSUP (Ch 0) VSUP (Ch 1)
V
C
–
SourcingOutput Device with External Power
INA (Ch 1) INB (Ch 1) COM (Ch 1) VSUP (Ch 2) Input Circuitry
+ –
Sourcing Output Device with External Power
+
VIN (Ch 0)
Input Circuitry
COM (Ch 0)
SinkingOutput Device Powered by cFP-DI-330
INA (Ch 2) INB (Ch 2) COM (Ch 2) Input Circuitry
Sourcing Output Device Powered by cFP-DI-30x
VSUP (Ch 1)
VIN (Ch 1)
Input Circuitry
COM (Ch 1) VSUP (Ch 3) SourcingOutput Device Powered by cFP-DI-330 INA (Ch 3) INB (Ch 3) COM (Ch 3) Switch VSUP (Ch n) INA (Ch n) Switch INB (Ch n) COM (Ch n) Input Circuitry To next channel cFP-DI-300/301/304 COM (Ch n) Input Circuitry VIN (Ch n) Input Circuitry VSUP (Ch n)
To next channel cFP-DI-330
Ordering Information
NI cFP-DI-300 ......................................................................777318-300 NI cFP-DI-301 ......................................................................777318-301 NI cFP-DI-304 ......................................................................777318-304 NI cFP-DI-330 ......................................................................777318-330 Recommended Compact FieldPoint System Products NI cFP-2120 ......................................................................777317-2120 NI cFP-BP-4 ............................................................................778617-04 NI cFP-BP-8 ............................................................................778617-08 NI cFP-CB-1............................................................................779618-01 NI PS-5 power supply............................................................778805-90 NI Developer Suite Professional Control Edition..................777906-03
Wiring Schematics for the cFP-DI-3xx Modules
BUY NOW!
For complete product specifications, pricing, and accessory information, call 800 813 3693 (U.S.) or go to ni.com/compactfieldpoint.
BUY ONLINE a t ni.com o r CALL 800 813 3693 (U.S.)
–
–
INB (Ch 0)
Input Circuitry
+
INA (Ch 0)
– C 15 to 30 VDC External Power Supply
+
5 to 250 V External Power Supply
2
Digital Input Modules for Compact FieldPoint
Specifications
Typical for -40 to 70 °C unless otherwise noted.
Digital Input Channels
cFP-DI-300, cFP-DI-330 .......................................................... 8 cFP-DI-301.............................................................................. 16 cFP-DI-304.............................................................................. 32
Input Characteristics
Input impedance cFP-DI-300, cFP-DI-301...................................................... 5 kΩ cFP-DI-304.......................................................................... 30 kΩ Input current limiting cFP-DI-330........................................... 1.5 mA
Input Voltages
cFP-DI-300, cFP-DI-301, cFP-DI-304....................................... 0 to 30 VDC cFP-DI-330.............................................................................. 0 to 250 VDC or 0 to 250 VAC (50/60 Hz AC) or 0 to 250 VAC (1 kHz AC)
Digital Logic Levels
cFP-DI-300 Input Voltage (V) Input Current (µA) 15 ≥3000 cFP-DI-301 15 ≥3000 cFP-DI-304 ≤5 ≤150 ≥10 ≥330 cFP-DI-330 ON State ≤1 VDC, ≤1 ≥4 VDC, ≥15 VAC (50/60 Hz AC), VAC ≥3 VAC (1 kHz AC) OFF State ON State OFF State ON State OFF State ON State OFF State
Hysteresis (cFP-DI-304)
Input voltage .......................................................................... 2 V min Input current........................................................................... 60 µA min
Isolation Voltage
cFP-DI-30x Channel-to-ground Continuous .................................................................... Withstand...................................................................... Channel-to-backplane Continuous .................................................................... Withstand...................................................................... Channel-to-channel ........................................................... cFP-DI-330 Maximum isolation voltage............................................... Transient overvoltage ............................................................
250 Vrms 2,300 Vrms, 5 s max 250 Vrms 2,300 Vrms, 5 s max None 250 Vrms, Installation Category II 2,300 Vrms
Physical Characteristics
LED indicators Power (green) .................................................................... Ready (green)..................................................................... , , or (green) ....................................... Dimensions ........................................................................... Weight cFP-DI-300/301 .................................................................. cFP-DI-330.......................................................................... cFP-DI-304.......................................................................... Power on and self-test passed Module configured and ready Input state of each channel 127.0 by 65.9 by 23.9 mm (5.00 by 2.60 by 0.94 in.) 100 g (3.6 oz) 103 g (3.7 oz) 193 g (6.81 oz)
BUY ONLINE a t ni.com o r CALL 800 813 3693 (U.S.)
3
Digital Input Modules for Compact FieldPoint
Power Requirements (from Network Module)
cFP-DI-300.............................................................................. cFP-DI-301.............................................................................. cFP-DI-304.............................................................................. cFP-DI-330.............................................................................. 185 mW 325 mW 1W 200 mW
Environment
Operating temperature .......................................................... -40 to 70 °C Storage temperature.............................................................. -55 to 85 °C Relative humidity ................................................................... 10 to 90%, noncondensing
Shock and Vibration
Operating vibration, random (IEC 60068-2-64)...................... 10 to 500 Hz, 5 grms Operating vibration, sinusoidal (IEC 60068-2-6).................... 10 to 500 Hz, 5 g Operating shock (IEC 60068-2-27) ......................................... 50 g, 3 ms half sine, 18 shocks at 6 orientations; 30 g, 11 ms half sine, 18 shocks at 6 orientations
Safety and Compliance
Safety
This product is designed to meet the requirements of the following standards of safety for electrical equipment for measurement, control, and laboratory use: • IEC 61010-1, EN 61010-1 • UL 61010-1, CSA 61010-1 Note: For UL and other safety certifications, refer to the product label or visit ni.com/certification, search by model number or product line, and click the appropriate link in the Certification column.
Electromagnetic Compatibility
This product is designed to meet the requirements of the following standards of EMC for electrical equipment for measurement, control, and laboratory use: • EN 61326 EMC requirements; Minimum Immunity • EN 55011 Emissions; Group 1, Class A • CE, C-Tick, ICES, and FCC Part 15 Emissions; Class A Note: For EMC compliance, operate this device according to product documentation.
CE Compliance
This product meets the essential requirements of applicable European Directives, as amended for CE marking, as follows: • 2006/95/EC; Low-Voltage Directive (safety) • 2004/108/EC; Electromagnetic Compatibility Directive (EMC) Note: Refer to the Declaration of Conformity (DoC) for this product for any additional regulatory compliance information. To obtain the DoC for this product, visit ni.com/certification, search by model number or product line, and click the appropriate link in the Certification column.
Waste Electrical and Electronic Equipment (WEEE)
EU Customers: At the end of their life cycle, all products must be sent to a WEEE recycling center. For more information about WEEE recycling centers and National Instruments WEEE initiatives, visit ni.com/environment/weee.htm.
BUY ONLINE a t ni.com o r CALL 800 813 3693 (U.S.)
4
NI Services and Support
IN TA
PL
SERVICE NEEDS
LO Y
V DE
NI has the services and support to meet your needs around the globe and through the application life cycle – from planning and development through deployment and ongoing maintenance. We offer services and service levels to meet customer requirements in research, design, validation, and manufacturing. Visit ni.com/services.
Local Sales and Technical Support
In offices worldwide, our staff is local to the country, giving you access to engineers who speak your language. NI delivers industry-leading technical support through online knowledge bases, our applications engineers, and access to 14,000 measurement and automation professionals within NI Developer Exchange forums. Find immediate answers to your questions at ni.com/support. We also offer service programs that provide automatic upgrades to your application development environment and higher levels of technical support. Visit ni.com/ssp.
MA IN
Training and Certification
NI training is the fastest, most certain route to productivity with our products. NI training can shorten your learning curve, save development time, and reduce maintenance costs over the application life cycle. We schedule instructor-led courses in cities worldwide, or we can hold a course at your facility. We also offer a professional certification program that identifies individuals who have high levels of skill and knowledge on using NI products. Visit ni.com/training.
EL OP
AN
Professional Services
Our NI Professional Services team is composed of NI applications and systems engineers and a worldwide National Instruments Alliance Partner program of more than 600 independent consultants and integrators. Services range from start-up assistance to turnkey system integration. Visit ni.com/alliance.
OEM Support
We offer design-in consulting and product integration assistance if you want to use our products for OEM applications. For information about special pricing and services for OEM customers, visit ni.com/oem.
P DE
Hardware Services
NI Factory Installation Services
NI Factory Installation Services (FIS) is the fastest and easiest way to use your PXI or PXI/SCXI combination systems right out of the box. Trained NI technicians install the software and hardware and configure the system to your specifications. NI extends the standard warranty by one year on hardware components (controllers, chassis, modules) purchased with FIS. To use FIS, simply configure your system online with ni.com/pxiadvisor.
Calibration Services
NI recognizes the need to maintain properly calibrated devices for high-accuracy measurements. We provide manual calibration procedures, services to recalibrate your products, and automated calibration software specifically designed for use by metrology laboratories. Visit ni.com/calibration.
Repair and Extended Warranty
NI provides complete repair services for our products. Express repair and advance replacement services are also available. We offer extended warranties to help you meet project life-cycle requirements. Visit ni.com/services.
ni.com • 800 813 3693
National Instruments • info@ni.com
*351572A-01*
351572A-01 2007-9294-161-101-D
©2008 National Instruments Corporation. All rights reserved. FieldPoint, National Instruments, National Instruments Alliance Partner, NI, ni.com, NI Developer Suite, and SCXI are trademarks of National Instruments. Other product and company names listed are trademarks or trade names of their respective companies. A National Instruments Alliance Partner is a business entity independent from NI and has no agency, partnership, or joint-venture relationship with NI.