0
登录后你可以
  • 下载海量资料
  • 学习在线课程
  • 观看技术视频
  • 写文章/发帖/加入社区
会员中心
创作中心
发布
  • 发文章

  • 发资料

  • 发帖

  • 提问

  • 发视频

创作活动
NICFP-2210

NICFP-2210

  • 厂商:

    NI

  • 封装:

  • 描述:

    NICFP-2210 - Compact FieldPoint Real-Time Controllers - National Instruments Corporation

  • 数据手册
  • 价格&库存
NICFP-2210 数据手册
Compact FieldPoint Real-Time Controllers NI cFP-2220, NI cFP-2210, NI cFP-2200 • Execution target for NI LabVIEW Real-Time applications • 400 MHz real-time processor with up to 256 MB of SDRAM • Up to 512 MB of nonvolatile storage, removable CompactFlash and USB ports • Up to 2 Ethernet ports for communication for distributed real-time systems • Dual redundant 11 to 30 VDC power supply inputs, low power • Up to 4 serial ports (3 RS232 and 1 RS485) for communication • Industrial certifications, -40 to 70 °C operating temperature range Operating Systems • LabVIEW Real-Time (VxWorks) Recommended Software • LabVIEW Real-Time Module 8.5.1 or later • NI-FieldPoint driver 6.0.1 or later Controller cFP-2220 cFP-2210 cFP-2200 DRAM Memory (MB) 256 256 128 Internal Nonvolatile Storage (MB) 256 128 128 Removable CompactFlash  – – Removable USB  – – Ethernet Ports 2 1 1 RS232 Ports 3 2 1 RS485 Ports 1 0 0 Table 1. NI cFP-22xx Selection Guide Overview The NI Compact FieldPoint programmable automation controller (PAC) is designed for industrial control applications performing advanced embedded control, data logging, and network connectivity. It combines the packaging, specifications, and reliability of a programmable logic controller (PLC) with the software, flexibility, connectivity, and functionality of a PC. Compact FieldPoint, a reliable platform designed for rugged industrial environments, features 2,300 V transient overvoltage protection, -40 to 70 °C temperature range, and backup power supply connections to protect against primary power failure. The cFP-22xx controllers include an industrial 400 MHz Freescale MPC5200 real-time processor for intelligent distributed applications requiring industrial-grade reliability – such as process and discrete control systems – to open and close valves, run control loops, log data on a centralized or local level, and perform real-time simulation and analysis. The cFP-22xx controllers also offer up to 256 MB of SDRAM and onboard memory, plus CompactFlash and USB slots on the cFP-2220 for external storage. With the 10/100 Mb/s Ethernet and serial ports, you can communicate via TCP/IP, UDP, Modbus, and serial protocols, as well as take advantage of the built-in Web (HTTP) and file (FTP) servers. The Compact FieldPoint real-time controller connects to a 4- or 8-slot solid backplane and controls a wide variety of hot-swappable I/O modules. The modular I/O architecture with built-in signal conditioning and isolation provides direct connectivity to industrial sensors such as analog voltage, 4 to 20 mA current, thermocouples, RTDs, pressure, strain, flow, pulse-width modulation (PWM), and 24 V digital I/O. Software NI LabVIEW is a graphical development environment that delivers unparalleled flexibility and ease of use in demanding industrial measurement, automation, and control applications. With LabVIEW, you can quickly create user interfaces for interactive software system control and easily construct simple or complex applications using an extensive palette of functions and tools – from simple analog PID process control loops to high-channel-count hybrid control systems. For extreme reliability and determinism, cFP-22xx controllers run the LabVIEW Real-Time Module on the Wind River VxWorks real-time operating system (RTOS), providing the functionality, connectivity, and flexibility of LabVIEW software on a small industrial platform. Compact FieldPoint Real-Time Controllers Expansion I/O with NI cFP-1808 For systems that require more than eight Compact FieldPoint modules, the cFP-1808 expansion chassis provides an easy way to add expansion I/O over Ethernet or serial. A single cFP-22xx controller can connect to as many additional cFP-1808 network interface systems as the Ethernet network allows. Figure 1. Expansion I/O for Compact FieldPoint Controllers with NI cFP-1808 Network Interface Ordering Information NI cFP-2220 ......................................................................777317-2220 NI cFP-2210 ......................................................................777317-2210 NI cFP-2200 ......................................................................777317-2200 Recommended Compact FieldPoint System Products NI cFP-BP-4 (4-slot backplane) ..............................................778617-04 NI cFP-BP-8 (8-slot backplane) ..............................................778617-08 NI cFP-CB-1 (general connecter block)..................................778618-01 NI PS-5 power supply............................................................778805-90 BUY NOW! For complete product specifications, pricing, and accessory information, call 800 813 3693 (U.S.) or go to ni.com/compactfieldpoint. BUY ONLINE a t ni.com o r CALL 800 813 3693 (U.S.) 2 Compact FieldPoint Real-Time Controllers Power Requirements Caution: You must use a National Electric Code (NEC) UL-listed Class 2 power supply with cFP-22xx controllers. Power supply range ............................ 11 to 30 VDC Recommended power supply cFP-BP-4 system ............................. 15 W cFP-BP-8 system ............................. 20 W Power consumption ............................ 6.1 W + 1.1 (I/O module power requirements) Specifications Specifications subject to change without notice. The following specifications are typical for the range -40 to 70 °C unless otherwise noted. Memory cFP-2200.............................................. 128 MB nonvolatile; 128 MB DRAM cFP-2210.............................................. 128 MB nonvolatile; 256 MB DRAM cFP-2220.............................................. 256 MB nonvolatile; 256 MB DRAM Memory lifetime (nonvolatile) ............ 100,000 writes per block Physical Characteristics If you need to clean the controller, wipe it with a dry towel. Screw-terminal wiring ........................ Use copper conductor wire with 10 mm (0.39 in.) of insulation stripped from the end External digital I/O terminals ......... 16 to 28 AWG Power supply terminals .................. 14 to 30 AWG Torque for screw terminals................. 0.5 to 0.6 N•m (4.4 to 5.3 lb•in.) Weight................................................. 278 g (9.8 oz) Network Network interface............................... 10BASE-T and 100BASE-TX Ethernet Compatibility ....................................... IEEE 802.3 Communication rates.......................... 10 Mb/s, 100 Mb/s, autonegotiated Maximum cabling distance................. 100 m/segment Environmental The cFP-22xx controllers are intended for indoor use only, but they may be used outdoors if mounted in a suitably sealed enclosure. Operating temperature (IEC 60068-2-1, IEC 60068-2-2)........... Storage temperature (IEC 60068-2-1, IEC 60068-2-2)........... Operating humidity (IEC 60068-2-56).................................. Storage humidity (IEC 60068-2-56)..... Maximum altitude............................... Pollution degree (IEC 60664) .............. -40 to 70 °C -55 to 85 °C 10 to 90% RH, noncondensing 5 to 95% RH, noncondensing 2,000 m 2 Serial Ports cFP-2200.............................................. 1 RS232 port cFP-2210.............................................. 2 RS232 ports cFP-2220.............................................. 3 RS232 ports; 1 RS485 port RS232 (DTE) Ports Baud rate............................................. Data bits.............................................. Stop bits.............................................. Parity ................................................... Flow control ........................................ Up to 115,200 b/s 5, 6, 7, 8 1, 1.5, 2 Odd, Even, Mark, Space RTS/CTS, XON/XOFF, DTR/DSR RS485 (DTE) Port Baud rate............................................. Data bits.............................................. Stop bits.............................................. Parity ................................................... Flow control ........................................ Wire mode .......................................... 9,600 to 115,200 b/s 5, 6, 7, 8 1, 1.5, 2 Odd, Even, Mark, Space XON/XOFF 4-wire isolation voltage, port to earth ground Continuous...................................... 100 Vrms Dielectric withstand ....................... 740 Vrms, verified by 5 s test Shock and Vibration To meet these specifications, you must panel mount the Compact FieldPoint system and affix ferrules to the ends of the power terminal wires. Operating shock (IEC 60068-2-27) ...... 30 g, 11 ms half sine; 50 g, 3 ms half sine; 18 shocks at 6 orientations Operating vibration, random (IEC 60068-2-64).................................. 5 grms, 10 to 500 Hz Operating vibration, sinusoidal (IEC 60068-2-6).................................... 5 g, 10 to 500 Hz USB Port (cFP-2220 only) Maximum data rate ........................... 12 Mb/s Maximum current ............................... 500 mA Safety Voltages Connect only voltages that are within these limits V terminal to C terminal ..................... 35 V max, Measurement Category I Caution: Do not connect the system to signals or use for measurements within Measurement Category II, III, or IV. BUY ONLINE a t ni.com o r CALL 800 813 3693 (U.S.) 3 Compact FieldPoint Real-Time Controllers Safety Standards This product is designed to meet the requirements of the following standards of safety for electrical equipment for measurement, control, and laboratory use: • IEC 61010-1, EN 61010-1 • UL 61010-1, CSA 61010-1 Note: For UL and other safety certifications, refer to the product label or visit ni.com/certification, search by model number or product line, and click the appropriate link in the Certification column. Electromagnetic Compatibility This product is designed to meet the requirements of the following standards of EMC for electrical equipment for measurement, control, and laboratory use: • EN 61326 EMC requirements; Industrial Immunity • EN 55011 Emissions; Group 1, Class A • CE, C-Tick, ICES, and FCC Part 15 Emissions; Class A Note: For EMC compliance, operate this device according to product documentation. CE Compliance This product meets the essential requirements of applicable European Directives, as amended for CE marking, as follows: • 2006/95/EC; Low-Voltage Directive (safety) • 2004/108/EC; Electromagnetic Compatibility Directive (EMC) Note: Refer to the Declaration of Conformity (DoC) for this product for any additional regulatory compliance information. To obtain the DoC for this product, visit ni.com/certification, search by model number or product line, and click the appropriate link in the Certification column. Waste Electrical and Electronic Equipment (WEEE) EU Customers: At the end of their life cycle, all products must be sent to a WEEE recycling center. For more information about WEEE recycling centers and National Instruments WEEE initiatives, visit ni.com/environment/weee.htm. BUY ONLINE a t ni.com o r CALL 800 813 3693 (U.S.) 4 NI Services and Support IN TA PL SERVICE NEEDS LO Y V DE NI has the services and support to meet your needs around the globe and through the application life cycle – from planning and development through deployment and ongoing maintenance. We offer services and service levels to meet customer requirements in research, design, validation, and manufacturing. Visit ni.com/services. Local Sales and Technical Support In offices worldwide, our staff is local to the country, giving you access to engineers who speak your language. NI delivers industry-leading technical support through online knowledge bases, our applications engineers, and access to 14,000 measurement and automation professionals within NI Developer Exchange forums. Find immediate answers to your questions at ni.com/support. We also offer service programs that provide automatic upgrades to your application development environment and higher levels of technical support. Visit ni.com/ssp. MA IN Training and Certification NI training is the fastest, most certain route to productivity with our products. NI training can shorten your learning curve, save development time, and reduce maintenance costs over the application life cycle. We schedule instructor-led courses in cities worldwide, or we can hold a course at your facility. We also offer a professional certification program that identifies individuals who have high levels of skill and knowledge on using NI products. Visit ni.com/training. EL OP AN Professional Services Our NI Professional Services team is composed of NI applications and systems engineers and a worldwide National Instruments Alliance Partner program of more than 600 independent consultants and integrators. Services range from start-up assistance to turnkey system integration. Visit ni.com/alliance. OEM Support We offer design-in consulting and product integration assistance if you want to use our products for OEM applications. For information about special pricing and services for OEM customers, visit ni.com/oem. P DE Hardware Services NI Factory Installation Services NI Factory Installation Services (FIS) is the fastest and easiest way to use your Compact FieldPoint systems right out of the box. Trained NI technicians install the software and hardware and configure the system to your specifications. NI extends the standard warranty by one year on hardware components (controllers, chassis, modules) purchased with FIS. To use FIS, simply configure your system online with http://ohm.ni.com/advisors/cfp. Calibration Services NI recognizes the need to maintain properly calibrated devices for high-accuracy measurements. We provide manual calibration procedures, services to recalibrate your products, and automated calibration software specifically designed for use by metrology laboratories. Visit ni.com/calibration. Repair and Extended Warranty NI provides complete repair services for our products. Express repair and advance replacement services are also available. We offer extended warranties to help you meet project life-cycle requirements. Visit ni.com/services. ni.com • 800 813 3693 National Instruments • info@ni.com *351585A-01* 351585A-01 2008-9213-161-101-D ©2008 National Instruments Corporation. All rights reserved. FieldPoint, LabVIEW, National Instruments, National Instruments Alliance Partner, NI, ni.com, and SCXI are trademarks of National Instruments. Other product and company names listed are trademarks or trade names of their respective companies. A National Instruments Alliance Partner is a business entity independent from NI and has no agency, partnership, or joint-venture relationship with NI.
NICFP-2210 价格&库存

很抱歉,暂时无法提供与“NICFP-2210”相匹配的价格&库存,您可以联系我们找货

免费人工找货