Low-Cost Industrial Digital I/O – 150 V
NI 6521
• 8, ±30 VDC digital inputs with 60 V channel-to-channel isolation • 8 nonlatching mechanical relay outputs • 150 V AC/DC maximum switching voltage with maximum switching current of 2 A and maximum switching power of 60 W • UL listed: UL 61010-1 (IEC 61010-1) • High-reliability industrial feature set includes isolation, programmable power-up states, digital filtering, watchdog timers, and change detection • NI measurement services software for highest productivity and performance
Recommended Software
• LabVIEW • LabWindows/CVI • Measurement Studio
Other Compatible Software
• C, C++ • Microsoft Visual Studio .NET 2003
Measurement Services Software (included)
• NI-DAQmx driver, Version 7.5 or later
Safety
Operating Systems
• Windows 2000/NT/XP • LabVIEW Real-Time
INPUT Product NI 6521 Bus PCI, PXI Inputs 8 Isolation 60 V channel-to-channel Low Threshold ±4 VDC High Threshold ±11 VDC Mechanical Relay Outputs 8
OUTPUT Max Voltage 150 V AC/DC Max Current 2A Max Power 60 W Industrial Feature Set
Overview and Applications
The National Instruments 6521 products are industrial digital I/O devices with eight channel-to-channel isolated digital inputs and eight nonlatching mechanical relay outputs. You can use the eight differential, isolated, ±30 VDC digital inputs to read the status of sensors, actuators, and logic devices. You can use the bipolar digital input channels to read from both sinking and sourcing devices. NI 6521 devices register a logic low if the voltage is between ±4 V, and register a logic high if the voltage is less than -11 V or greater than +11 V. NI 6521 devices offer three single-pole double-throw (SPDT) Form C relays and five single-pole single-throw (SPST) Form A relays. You can use NI 6521 relay outputs to switch devices requiring up to 150 V AC/DC. NI 6521 relay outputs have maximum current rating of 2A and maximum switching power of 60 W. Note: The switching current is limited by the maximum switching power and maximum voltage. (current = power/voltage) NI 6521 devices offer completely programmable configuration and do not require setting up jumpers or DIP switches. These devices are ideal for use with a programmable automation controller (PAC) for automotive test, industrial monitoring, and control applications. With high-current drive, highvoltage outputs, and isolation, you can connect the digital I/O module directly to a wide array of industrial electronic devices, sensors, and actuators. NI 6521 devices take advantage of NI-DAQmx measurement services software (Version 7.5 or later) to speed up application development with
many helpful features such as DAQ Assistant, automatic code generation, and high-performance multithreaded streaming technology.
Safety
• • • • • UL listed: UL 61010-1 (IEC 61010-1) Keyed connector Insulation covers Complete software configuration High-voltage accessories NI 6521 devices are UL listed and require the use of a keyed connector to prevent high-voltage signals from accidentally being connected to a low-voltage device. For added safety, PCI-6521 includes insulation covers on both sides of the board to prevent the user from coming in contact with high-voltage traces. Complete software configuration means that the user at no point is required to come in the vicinity of high-voltage traces. Several low-cost, high-voltage accessory options are available to ensure safe operation.
Isolation
Channel-to-channel . . . . . . . . . . . . . . . . . . . . . . .60 VDC continuous1 Channel-to-bus . . . . . . . . . . . . . . . . . . . . . . . . . .150 VDC continuous2 Channel-to-earth . . . . . . . . . . . . . . . . . . . . . . . . .150 VDC continuous3
1 2 3
Verified by 620 Vrms dielectric withstand test, 5 s Verified by 1400 Vrms dielectric withstand test, 5 s Verified by 850 Vrms dielectric withstand test, 5 s
Low-Cost Industrial Digital I/O – 150 V
connected to industrial actuators such as pumps, valves, motors, and relays. NI 6521 devices hold these known safe I/O states after receiving power, while your computer boots and your software application can begin running. Programmable power-up states are glitch-free, meaning the outputs never go through an incorrect state during power up. You can configure each individual output line as logic high or logic low. NI 6521 devices store the settings in onboard nonvolatile memory and implement the power-up states automatically after power is applied to the device.
Hardware
High-Reliability Industrial Feature Set
NI 6521 devices offer a set of high-reliability features designed for demanding automation applications: • Isolation provides an extended voltage range for direct connection to industrial sensors and actuators • Programmable power-up states provide safe operation when connected to pumps/valves/motors/relays • Watchdog timer detects computer or application crashes and ensures safe recovery to know digital I/O states • Change detection triggers your application and returns I/O data after a digital event to minimize processor usage • Programmable input filters eliminate glitches/spikes and remove noise
Watchdog Timers for Fault Detection and Recovery
Watchdog timers are an innovative technology that provide protection against a wide variety of fault conditions: • Computer crash – total OS crash • Application crash – software application ceases to respond • Driver crash – device driver ceases to respond • PCI bus failure – communications cease to respond With watchdogs, the digital outputs go to a safe state when a fault condition is detected. Watchdogs are important whenever the module is connected to actuators such as pumps, valves, motors, and relays. NI 6521 devices monitor the software application; if the application fails to reset the watchdog timer within the time limit, the device automatically sets the output lines to a user-defined safe state. NI 6521 devices remain in the watchdog state until the watchdog timer is disarmed by the application and new I/O values are written, the NI 6521 is reset, or the computer is restarted.
Direct Sensor Connection with Isolation
Isolation, a form of built-in signal conditioning, provides several advantages such as an extended voltage range for direct connection to industrial sensors and actuators. Isolation also improves signal quality and protects computer circuitry. NI 6521 devices provide channel-tochannel isolation where every channel is physically and electrically separated from the others. This isolation breaks ground loops, improves common-mode voltage and noise rejection, and permits the two parts of the circuit to be at different voltage levels. Many industrial applications require isolation to protect the electronics from transient voltage spikes and provide greater common-mode noise rejection in electrically noisy environments containing machinery and inductive loads.
Trigger Your Application with Change Detection
With change detection, you can automatically trigger your software application to perform a digital read operation upon a digital change of state. A digital change of state is defined as the rising edge (0 to 1 transition) or falling edge (1 to 0 transition) on one or more digital lines. To minimize the effects of noisy input lines, use programmable input filters in combination with change detection to eliminate spurious change detection events caused by noise or glitches. NI-DAQmx also includes multithreaded streaming technology so digital change detection events can occur independent of other data acquisition activities such as analog input or output events. Using change detection, you can monitor for digital events with minimal processor usage. No polling is necessary because the digital I/O module generates an interrupt to automatically wake up your application. Using NI-DAQmx software technology, the NI 6521 devices notify the software application when the event is detected, causing the application to automatically perform a read operation.
Figure 1. NI 6521 Hardware Block Diagram
Glitch-Free Startup with Programmable Power-Up States
Using programmable power-up states, you can configure the initial NI 6521 output states in software to ensure glitch-free operation when
BUY ONLINE a t ni.com o r CALL (800) 813 3693 (U.S.)
2
Low-Cost Industrial Digital I/O – 150 V
Eliminate Noise with Programmable Input Filters
Programmable input filters remove noise, glitches, and spikes on input, and provide debouncing for digital switches and relays. This feature is important for applications in noisy industrial environments to prevent false readings caused by noise. You can configure the programmable input filter for each digital line by setting the filter time in seconds. Any digital noise, glitch, or spike that is shorter than half of the specified filter time is blocked by the digital I/O device, preventing invalid readings and false triggers for change detection events.
Software
NI-DAQmx Software Technology
NI 6521 devices require and are shipped with NI-DAQmx driver software, Version 7.5 or later. NI-DAQmx software is also available for download from ni.com/downloads. With NI-DAQmx, you can use your NI digital I/O device in NI LabVIEW, ANSI C, Microsoft Visual C++, and the Microsoft .NET languages C# and Visual Basic .NET. Using NI-DAQmx technology, you can access the full functionality and state-of-the-art hardware technology of your NI 6521 digital I/O devices. NI-DAQmx technology speeds up your development with many features such as automatic code generation to make configuration and programming easy. The NI 6521 devices take full advantage of key NI-DAQmx software technologies such as multithreaded streaming technology for dramatic improvements in I/O performance and ease of use. • Use DAQ Assistant to guide you to fast, accurate measurements with no programming. • Use automatic code generation to create your application in LabVIEW, C, Visual Basic .NET, or C#. • Take advantage of multithreaded streaming technology for 1,000X performance improvements. • Use automatic timing, triggering, and synchronization technology to make advanced applications easy. • Visit ni.com for more than 3,000 FREE software downloads to jump-start your project. • Use the NI-DAQmx functions for software configuration of all digital I/O features without hardware switches/jumpers. • Develop your application with easy and open programming in LabVIEW, ANSI C, Microsoft Visual C++, C#, and Visual Basic .NET.
Relay Forms
Relays are classified by number of poles and number of throws. The pole of a relay is the terminal common to every path. Each position where the pole can connect is called a throw. A relay can be made of n poles and m throws. A single-pole single-throw (SPST) relay has one pole and one throw. A single-pole double-throw (SPDT) relay has one pole and two throws.
Single-Pole Single-Throw (SPST) Relay
Single-Pole Double-Throw (SPDT) Relay
Figure 2. Relay Diagrams
Form Form A Form C Symbol Description SPST relay with a normally open default state SPDT relay that breaks the connection with one throw before making contact with the other (break-before-make)
Table 1. Relay Descriptions
Nonlatching Relays
A nonlatching relay has a power-off initial position of normally closed (NC). This position is maintained by the force of a spring or permanent magnet while no current flows. The normally open (NO) contact is maintained by the force of a magnetic field while current flows through the coil. When the current stops, the relay reverts back to its initial NC position. Nonlatching relays return to the default NC position in case of a fault or power failure. This feature is particularly useful when controlling a motor or valve where the motor or valve needs to be turned off in case of power failure or fault.
Low-Cost 37-Pin Accessories
Several low-cost, high-voltage accessory options are available for connecting to the 37-pin D-Sub connector of NI 6521 devices. NI 6521 devices ship with an accessory safety kit for keying connectors.
BUY ONLINE a t ni.com o r CALL (800) 813 3693 (U.S.)
3
Low-Cost Industrial Digital I/O – 150 V
Ordering Information
P1.1NO P1.1COM P1.1NC P1.3NO P1.3COM P1.5NO P1.5COM P1.7NO P1.7COM NO CONNECT P0.1+ P0.1P0.3+ P0.3P0.5+ P0.5P0.7+ P0.720 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 P1.0NO P1.0COM P1.0NC P1.2NO P1.2COM P1.2NC P1.4NO P1.4COM P1.6NO P1.6COM NO CONNECT P0.0+ P0.0P0.2+ P0.2P0.4+ P0.4P0.6+ P0.6-
NI PCI-6521............................................................................779312-01 NI PXI-6521............................................................................779313-01 Additional Accessory Safety Kit............................................779445-01
Family NI 6521 Accessory CB-37F-HVD (779491-01) (PXI Only) TB-2621 (779444-01) TB-37F-37CP (779185-01) Cable SH37F-37M (778621-01, 778621-02) – –
Includes NI-DAQmx 7.5 or later For information on extended warranty and value added services, visit ni.com/services.
BUY NOW!
For complete product specifications, pricing, and accessory information, call (800) 813 3693 (U.S.) or go to ni.com/daq.
Figure 3. NI 6521, 37-Pin D-Sub I/O Connector
CB-37F-HVD
TB-2621
SH37F-37M
TB-37F-37CP
BUY ONLINE a t ni.com o r CALL (800) 813 3693 (U.S.)
4
NI Services and Support
NI has the services and support to meet your needs around the globe and through the application life cycle – from planning and development through deployment and ongoing maintenance. We offer services and service levels to meet customer requirements in research, design, validation, and manufacturing. Visit ni.com/services.
Local Sales and Technical Support
In offices worldwide, our staff is local to the country, giving you access to engineers who speak your language. NI delivers industry-leading technical support through online knowledge bases, our applications engineers, and access to 14,000 measurement and automation professionals within NI Developer Exchange forums. Find immediate answers to your questions at ni.com/support. We also offer service programs that provide automatic upgrades to your application development environment and higher levels of technical support. Visit ni.com/ssp.
SERVICE NEEDS
Training and Certification
NI training is the fastest, most certain route to productivity with our products. NI training can shorten your learning curve, save development time, and reduce maintenance costs over the application life cycle. We schedule instructor-led courses in cities worldwide, or we can hold a course at your facility. We also offer a professional certification program that identifies individuals who have high levels of skill and knowledge on using NI products. Visit ni.com/training.
Hardware Services
NI Factory Installation Services
NI Factory Installation Services (FIS) is the fastest and easiest way to use your PXI or PXI/SCXI combination systems right out of the box. Trained NI technicians install the software and hardware and configure the system to your specifications. NI extends the standard warranty by one year on hardware components (controllers, chassis, modules) purchased with FIS. To use FIS, simply configure your system online with ni.com/pxiadvisor.
Professional Services
Our Professional Services Team is comprised of NI applications engineers, NI Consulting Services, and a worldwide National Instruments Alliance Partner program of more than 600 independent consultants and integrators. Services range from start-up assistance to turnkey system integration. Visit ni.com/alliance.
Calibration Services
NI recognizes the need to maintain properly calibrated devices for high-accuracy measurements. We provide manual calibration procedures, services to recalibrate your products, and automated calibration software specifically designed for use by metrology laboratories. Visit ni.com/calibration.
OEM Support
We offer design-in consulting and product integration assistance if you want to use our products for OEM applications. For information about special pricing and services for OEM customers, visit ni.com/oem.
Repair and Extended Warranty
NI provides complete repair services for our products. Express repair and advance replacement services are also available. We offer extended warranties to help you meet project life-cycle requirements. Visit ni.com/services.
ni.com • (800) 813 3693
National Instruments • info@ni.com
© 2005 National Instruments Corporation. All rights reserved. CVI, LabVIEW, Measurement Studio, National Instruments Alliance Partner, NI, ni.com, NI-DAQ, RTSI, and SCXI are trademarks of National Instruments. Other product and company names listed are trademarks or trade names of their respective companies. A National Instruments Alliance Partner is a business entity independent from NI and has no agency, partnership, or joint-venture relationship with NI.
2005-6218-301-101