Pushbutton Switch (Cylindrical 30-dia.)
ZAP
CSM_ZAP_DS_E_4_1
Long Service Life with Built-in Z-series
Basic Switch
• Using a Basic Switch enables direct switching of large-capacity
loads
• Shock-absorbing construction of Operation Unit protects the Switch
• Drip-proof Pushbutton construction enables use in locations subject to
splashing water and oil and scattering dust.
• Pushbuttons are available in three shapes and six colors.
Refer to Safety Precautions for All Pushbutton Switches/
Indicators and Safety Precautions on page 3.
Ordering Information
Shape of Operation
Unit
Classification
Output
Blue (-A)
Operation Unit color
Green (-G)
Red (-R)
Black (-B)
White (-W)
Yellow (-Y)
1
ZAP-A
ZAP-B
ZAP-G
ZAP-R
ZAP-W
ZAP-Y
2
2ZAP-A
2ZAP-B
2ZAP-G
2ZAP-R
2ZAP-W
2ZAP-Y
1
ZAP-1A
ZAP-1B
ZAP-1G
ZAP-1R
ZAP-1W
ZAP-1Y
2
2ZAP-1A
2ZAP-1B
2ZAP-1G
2ZAP-1R
2ZAP-1W
2ZAP-1Y
1
ZAP-2A
ZAP-2B
ZAP-2G
ZAP-2R
ZAP-2W
ZAP-2Y
2
2ZAP-2A
2ZAP-2B
2ZAP-2G
2ZAP-2R
2ZAP-2W
2ZAP-2Y
36 dia. 25 dia.
Momentary
operation
36 dia. 25 dia.
40 dia.
Note: Models with special specifications are available for use in environments with high humidity or outdoors.
Contact your OMRON representative for information.
Specifications
Ratings
Item
Non-inductive load (A)
Rated voltage (V)
NC
Note: 1.
2.
3.
4.
5.
NO
Inductive load (A)
Lamp load
Inductive load
NC
NO
Motor load
NC
NO
NC
NO
125 VAC
200 VAC
500 VAC
15
15
10
3
2.5
1.5
1.5
1.25
0.75
15
15
6
5
3
1.5
2.5
1.5
0.75
8 VDC
14 VDC
30 VDC
125 VDC
250 VDC
15
15
6
0.5
0.25
3
3
3
0.5
0.25
1.5
1.5
1.5
0.5
0.25
15
10
5
0.05
0.03
5
5
5
0.05
0.03
2.5
2.5
2.5
0.05
0.03
Built-in Switch
Z-15G5-B
Resistive load
The above values are for steady-state currents.
Inductive load: Power factor = 0.4 (AC); time constant = 7 ms (DC).
The lamp load has an inrush current of 10 times the steady-state current.
The motor load has an inrush current of 6 times the steady-state current.
Standard testing condition.
(1) Ambient temperature: 20 ±2°C
(2) Ambient humidity: 65% ±5%RH
(3) Operating frequency: 20 times/min
1
ZAP
Specifications
Characteristics
Operating frequency
Operating Characteristics
Mechanical
60 operations/min
Electrical
20 operations/min
Model
Operating characteristics
Operating force
OF
ZAP-@@
2ZAP-@@
Approx. 5.88 to
14.71 N
Approx. 9.81 to
17.70 N
Insulation resistance
100 MΩ min. (at 500 VDC)
Contact resistance
30 mΩ max. (initial value)
Note: Operating force may vary depending on thickness of mounting panel.
1,000 VAC, 50/60 Hz for 1 min
Contact Form
Dielectric
strength
Vibration resistance
Between terminals of same
polarity
Between current-carrying metal part
2,000 VAC, 50/60 Hz for
and ground, and between each termi1 minute
nal and non-current-carrying metal part
Double-throw contacts
NC
COM
NO
Approved Safety Standards
500 m/s2
2
200 m/s max. (1 ms max.)
Mechanical
1,000,000 operations min.
Electrical
500,000 operations min.
Weight
Inrush
current
Contact form
10 to 55 Hz, 1.5-mm double
amplitude (1 ms max.)
Malfunction
Shock re- Destruction
sistance Malfunction
Durability
Name
• The built-in Z-15G5-B Switch is approved for UL and CSA.
Approx. 130 to 210 g
NC
30 A max.
NO
15 A max.
Ambient operating temperature
−25 to 80°C (with no icing or
condensation)
Ambient operating humidity
35% to 85%RH
Ambient storage temperature
−25 to 80°C (with no icing or
condensation)
Degree of protection
IP65 (Operation Unit only)
Electric shock protection class
Class II
PTI (proof tracking index)
175
Pollution degree
3 (IEC947-5-1)
Dimensions Insert one of the following letters into the box (@) at the end of the model number. Refer to Ordering Information for color symbols. (Unit: mm)
ZAP-@
2ZAP-@
ZAP-@
2ZAP-@
Washer
26
Mounting panel thickness:
1.6 to 6 mm
Z-15G5-B Basic Switch
Rubber packing
24.6
25 dia.
25 dia.
36 dia.
37
*
49.2
52
24.6
26
9.75
19
43.5
10.8 t
40 dia.
Three, M4 ✕ 5.5
Terminal screws
(with toothed washer)
51.8 max.
* Chromed plating
ZAP-1@
2ZAP-1@
ZAP-2@
2ZAP-2@
40 dia. 36 dia.
36 dia. 25 dia.
*
Mounting panel thickness:
1.6 to 6 mm
t
t
15.8
* Chromed plating
Mounting panel thickness:
1.6 to 6 mm
*
27.6
* Chromed plating
2
ZAP
Dimensions
(Unit: mm)
Panel Cutouts
Accessories
Rubber Cap
• Use the special rubber cap to use the Switch in locations subject to
significant splashing water and oil or scattering dust.
Cannot be used, however, with the (2) ZAP-2.
5.2 dia.
15
30.5±0.3
dia. hole
Color
Blue (-A)
Black (-B)
Green (-G)
Red (-R)
White (-W)
Yellow (-Y)
Model
ZB-A
ZB-B
ZB-G
ZB-R
ZB-W
ZB-Y
Safety Precautions
Refer to Safety Precautions for All Pushbutton Switches/Indicators.
Precautions for Correct Use
Insulation
• After wiring the Switch, ensure an appropriate insulating distance.
Wiring
• Tighten the terminal screws to a torque of 0.78 to 1.18 N·m.
Mounting
• Tighten the face nut to a torque of 0.98 to 1.76 N·m.
• For panel mounting, always use a washer (or a nameplate) and
rubber packing.
Washer
(or nameplate)
Rubber packing
Mounting panel
t = 1.6 to 6 mm
3
Terms and Conditions Agreement
Read and understand this catalog.
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you
have any questions or comments.
Warranties.
(a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship
for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron
disclaims all other warranties, express or implied.
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT
NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS. BUYER
ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE
PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.
Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the
Products or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at
Omron’s election, to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or
replacement thereof) the non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount
equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsible for warranty,
repair, indemnity or any other claims or expenses regarding the Products unless Omron’s analysis confirms that the Products
were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate
modification. Return of any Products by Buyer must be approved in writing by Omron before shipment. Omron Companies shall
not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or
electronic components, circuits, system assemblies or any other materials or substances or environments. Any advice,
recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above
warranty.
See http://www.omron.com/global/ or contact your Omron representative for published information.
Limitation on Liability; Etc.
OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,
WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.
Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted.
Suitability of Use.
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the
combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable
third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself
is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine,
system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product
with respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE
QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS,
AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
OVERALL EQUIPMENT OR SYSTEM.
Programmable Products.
Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence
thereof.
Performance Data.
Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining
suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate
it to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability.
Change in Specifications.
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our
practice to change part numbers when published ratings or features are changed, or when significant construction changes are
made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers
may be assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at
any time to confirm actual specifications of purchased Product.
Errors and Omissions.
Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is
assumed for clerical, typographical or proofreading errors or omissions.
2013.7
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2013 All Right Reserved.