0
登录后你可以
  • 下载海量资料
  • 学习在线课程
  • 观看技术视频
  • 写文章/发帖/加入社区
创作中心
发布
  • 发文章

  • 发资料

  • 发帖

  • 提问

  • 发视频

创作活动
3G2A5-AD005

3G2A5-AD005

  • 厂商:

    OMRON(欧姆龙)

  • 封装:

    -

  • 描述:

    INPUT MODULE 2 ANALOG

  • 数据手册
  • 价格&库存
3G2A5-AD005 数据手册
C120/C500/C1000H/C2000H Analog I/O Modules Cat. No. W121-E3-1   Notice: OMRON products are manufactured for use according to proper procedures by a qualified operator and only for the purposes described in this manual. The following conventions are used to indicate and classify precautions in this manual. Always heed the information provided with them. Failure to heed precautions can result in injury to people or damage to the product. ! DANGER! Indicates information that, if not heeded, is likely to result in loss of life or serious injury. ! WARNING Indicates information that, if not heeded, could possibly result in loss of life or serious injury. ! Caution Indicates information that, if not heeded, could result in relatively serious or minor injury, damage to the product, or faulty operation. OMRON Product References All OMRON products are capitalized in this manual. The terms Unit and Module are capitalized when refering to an OMRON product. The abbreviation “Ch,” which appears in some displays and on some OMRON products, often means “word” and is abbreviated “Wd” in documentation in this sense. The abbreviation “PLC” means Programmable Controller and is not used as an abbreviation for anything else. Visual Aids The following headings appear in the left column of the manual to help you locate different types of information. Note Indicates information of particular interest for efficient and convenient operation of the product. 1, 2, 3... 1. Indicates lists of one sort or another, such as procedures, checklists, etc. © OMRON, 1996                                                                                                                 !                                              TABLE OF CONTENTS SECTION 1 System Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1--1 1--2 1--3 1--4 1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Basic Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Example Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Allocated Words . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 2 3 3 SECTION 2 Components and Switch Settings . . . . . . . . . . . . . . . . 5 2--1 AD101 Analog Input Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2--2 DA101 Analog Output Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 9 SECTION 3 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 3--1 3--2 3--3 3--4 3--5 AD001 through AD005 Analog Input Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . AD006 and AD007 Analog Input Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . AD101 Analog Input Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DA001 through DA005 Analog Output Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DA101 Analog Output Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 15 18 21 24 SECTION 4 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 4--1 4--2 4--3 4--4 4--5 AD001 through AD005 Analog Input Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . AD006 and AD007 Analog Input Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . AD101 Analog Input Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DA001 through DA005 Analog Output Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DA101 Analog Output Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 30 31 40 43 SECTION 5 Programming Considerations . . . . . . . . . . . . . . . . . . . . 47 5--1 5--2 5--3 5--4 5--5 AD001 through AD005 Analog Input Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . AD006 and AD007 Analog Input Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . AD101 Analog Input Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DA001 through DA005 Analog Output Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DA101 Analog Output Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 50 52 69 71 Appendix A -- Standard Models . . . . . . . . . . . . . . . . . . 73 Appendix B -- Specifications . . . . . . . . . . . . . . . . . . . . . 75 Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81 Revision History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83   About this Manual: This manual describes the installation and operation of Analog Input Modules and Analog Output Modules for the C120, C500, C1000H, and C2000H SYSMAC C-series PLCs. These Modules are classified as Special I/O Modules and include the following: Analog Input Modules The Analog Input Modules convert analog inputs to digital (binary) form. The type and range of input as well as the digital format depend on the model. Some models provide additional features such as peak values, means, or scaling. PLC C120 C500 C1000H C2000H Applicable models 3G2A6-AD001 3G2A6-AD002 3G2A6-AD003 3G2A6-AD004 3G2A6-AD005 3G2A6-AD006 3G2A6-AD007 C500-AD101 3G2A5-AD001 3G2A5-AD002 3G2A5-AD003 3G2A5-AD004 3G2A5-AD005 3G2A5-AD006 3G2A5-AD007 Analog Output Modules Analog Output Modules convert digital (binary) data to analog outputs. The type and range of output as well as the digital format depend on the model. PLC C120 C500 C1000H C2000H Applicable models 3G2A6-DA001 3G2A6-DA002 3G2A6-DA003 3G2A6-DA004 3G2A6-DA005 C500-DA101 3G2A5-DA001 3G2A5-DA002 3G2A5-DA003 3G2A5-DA004 3G2A5-DA005 Be sure to familiarize yourself with the information in this manual and your PLC’s Operation Manual before you try to install or use an Analog I/O Module. Model References If an Analog I/O Module is referred to using only the last half of the model number (i.e., 3G2A5 or 3G2A6 is omitted), the information being provided applies to all Modules whose model number ends with the number given.   SECTION 1 System Design This section describes the basic use of Analog I/O Modules in a Control System and illustrates the type of applications in which they might be found. 1--1 1--2 1--3 1--4 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Basic Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Example Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Allocated Words . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1--4--1 AD001 through AD005 Analog Input Modules . . . . . . . . . . . . . . . . . . . . . . . 1--4--2 AD006 and AD007 Analog Input Modules . . . . . . . . . . . . . . . . . . . . . . . . . . 1--4--3 AD101 Analog Input Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1--4--4 DA001 through DA005 Analog Output Modules . . . . . . . . . . . . . . . . . . . . . 1--4--5 DA101 Analog Output Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 2 3 3 4 4 4 4 4       1--1 Section 1--2 Introduction Analog I/O Modules are used to interface the digital operation of the PLC with analog I/O field devices. Analog Input Modules convert analog signal from input devices to digital PLC data. Analog Output Modules convert digital PLC data to analog signals for output devices. 1--2 Basic Configuration This diagram shows some of the possible field devices for the Analog I/O Modules. Any I/O device may be used as long as its voltage/current requirements fall within the specified ranges (see Appendix B). The I/O device connected to the Analog I/O Module will often serve as an interface for another device, e.g., a preamplifier may interface a pressure gauge to increase the signal level to Analog Input Module requirements; a regulator may interface a heating system to control temperature. Analog Input Module Analog Output Module Temperature Pressure Speed Flow rate Voltage Current Power Power factor Preamp Inverter Servomotor Transducer controller Chart recorder  M M     1--3 Section 1--4 Example Configurations Below are two examples of how the Analog I/O Modules can be employed in control systems. The first diagram shows a temperature regulating system and the second shows a servomotor positioning system. Analog Input Module PLC Transducer Temperature sensing element Valve controller Output Module fuel Sensor M Platform Servo controller Analog Output Module Servo motor Encoder Locating pulse High-speed Counter Module 1--4 Allocated Words Each Analog I/O Module is allocated either two or four words. This section specifies only the actual number of words allocated to the Modules; use of these words is dealt with in Section 4 Operation. The first word allocated to the Module is designated as “n” in this manual. Remaining words, which are always consecutive, are designated as n+1, n+2, etc. Refer to you PLC’s Operation Manual for details on how words are allocated to Modules.      1--4--1 Section 1--4 AD001 through AD005 Analog Input Modules Each of these Analog Input Modules is allocated two words, one for each analog input point. Word n is for point 1, and word n+1 is for point 2. Each of these words contains the decimal-converted value for the analog input point. 1--4--2 AD006 and AD007 Analog Input Modules Each of these Analog Input Modules is allocated four words, one for each analog input point. Word n is for point 1, word n+1 is for point 2, word n+2 is for point 3, and word n+3 is for point 4. Each of these words contains the decimal-converted value for the analog input point. 1--4--3 AD101 Analog Input Modules Each of these Analog Input Modules is allocated either two or four words, depending on the switch settings. The operation of the Module is completely different depending on this switch setting. Refer to later sections of this manual for details. 1--4--4 DA001 through DA005 Analog Output Modules Each of these Analog Output Modules is allocated two words, one for each analog output point. Word n is for point 1; word n+1 is for point 2. Each of these words contains the digital-converted value for the analog output point. 1--4--5 DA101 Analog Output Modules Each of these Analog Output Modules is allocated four words, one for each analog output point. Word n is for point 1, word n+1 is for point 2, word n+2 is for point 3, and word n+3 is for point 4. Each of these words contains the digital-converted value for the analog output point.  SECTION 2 Components and Switch Settings This section describes the switch settings for the AD101 Analog Input Module and the DA101 Analog Output Module. There are no switch settings required on the other Analog I/O Modules. 2--1 AD101 Analog Input Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2--2 DA101 Analog Output Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 9       2--1 Section 2--1 AD101 Analog Input Modules There are two settings necessary for this Module: the operation mode and the input ranges (offset and gain) for each input point Operation Mode Select either two-word or four-word operation. If you select two-word operation, data is transferred between the Analog Input Module and PLC using the I/O READ and I/O WRITE instructions, WRIT(87) and READ(88). If you select four-word operation, data is transferred between the Analog Input Module and PLC via the MOVE instruction, MOV(21). Use of WRIT(87) and READ(88) will simplify programming and shorten the time required to access analog input data. The switch for this setting is on the back of the Module and will not be accessible while the Module is mounted to a Rack. Be sure to set this switch before mounting the Module to the PLC. The setting of the switch is read when the PLC power is turned ON. Caution Only the following C120 and C500 CPUs are equipped with WRIT(87) and READ(88), which are required for two-word operation: 3G2C4-SC023-E and 3G2C3-CPU11-EV1 With all other C120 and C500 CPUs, you must use four-word operation. These instructions are supported by all C1000H and C2000H CPUs. Two-word operation is not possible if the Analog I/O Module is mounted to a Slave Rack in a Remote I/O System, regardless of the CPU. Four-word operation Two-word operation Back of Module Input Ranges Each input point is set with an offset (minimum) of 1 V (4 mA) and a gain (maximum) of 5 V ( 20 mA) at the factory. Use the following procedure to change these settings if necessary. The offset and gain can be set to anywhere between 0 and 10 V (0 and 20 mA) as long as the gain is greater than the offset. (Refer to Section 3 Operation for details on AD conversion.) Caution If an offset is set below 0 V (0 mA), the binary-converted value will be locked at 000hex; if a gain is set above 10 V (20 mA), the binary-converted value will be locked at FFFhex for voltage inputs, but not for current inputs.       Section 2--1 1, 2, 3... 1. First set up a power source and meter. For voltage inputs, you will need a 0 to 10 VDC supply and a DC voltmeter. For current input, you will need a 0 to 20 mA DC supply and a DC ammeter. Mount the Module to the PLC and connect the power source and meter. Voltage and current specifications can be set independently for each input point. The following examples illustrate how to wire the input points Wiring when input 1 is set at 0 to 10 V: Wiring when input 5 is set at 0 to 20 mA: AD101 AD101 15 0 0 + 16 Short terminals 0 to 10 VDC 1 17 16 and 17. 2 2 18 2. 0 to 20 mA DC Turn the PLC power supply and confirm that power is being supplied to the PLC. SW 1 (DIP switch) Use to designate the input point. SW 2 (toggle switch) Use to read in the desired values. 3. Remove the front panel of the Module with flat-blade screwdriver. Pins 1 through 8 on SW 1 represent input points 1 through 8 respectively. Turn ON the pin for the input point to be set and make sure all the other pins are OFF. First we will set input point 1. OFF 4. ON The offset is the lowest voltage or current that will be input. The Module will convert this value to 000 hexadecimal. Apply the desired offset to the terminals of input point 1. Flip SW 2 down to read in as O V or mA the current or voltage currently being applied to the input terminals. This input value will be stored as the offset, i.e., as zero.       Section 2--1 SW 1 Flip SW 2 down. SW 2 5. The gain is the highest voltage or current that will be input. The Module will convert this value to FFF hexadecimal. Apply the desired gain) to the terminals of input point 1. Flip SW 2 to down to read in as10 V or 20 mA current or voltage currently being applied to the input terminals. The input value will be stored as the gain, i.e., as 10 V or 20 mA. SW 1 Flip SW 2 up. SW 2 6.  Continue on in this way to set the offset and gain for input points 2 through 8. Make sure you turn OFF each pin of SW 1 before you turn ON the next pin. Never allow more than one pin of SW 1 to be ON simultaneously. After you are finished setting all the input points, re-attach the front panel to the Module.       2--2 Section 2--2 DA101 Analog Output Modules The output range must be set for each input point using the DIP switches on the back of the Module. Each input point is set to 1 to 5 V at the factory, but double check the settings before use. Be sure to set these switches before mounting the Module, as they will not be accessible while the Module is mounted. DIP switch Port 1 SW1 2 SW1 3 SW2 SW2 4 Pin Output range 0 to 10 V 1 to 5 V 4 to 20 mA 1 OFF ON ON 2 OFF ON ON 3 OFF OFF ON 4 ON OFF OFF 5 OFF ON ON 6 OFF ON ON 7 OFF OFF ON 8 ON OFF OFF 1 OFF ON ON 2 OFF ON ON 3 OFF OFF ON 4 ON OFF OFF 5 OFF ON ON 6 OFF ON ON 7 OFF OFF ON 8 ON OFF OFF Set the pins to the appropriate positions for the output range you are going to use. The pins are set as shown below. Back of Module ON OFF        Section 2--2 SECTION 3 Installation This section provides the dimensions, wiring diagrams, and other information required to install the Analog I/O Modules. Be sure to set back-panel switches as required before mounting the Modules to the Racks. 3--1 AD001 through AD005 Analog Input Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3--1--1 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3--1--2 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3--2 AD006 and AD007 Analog Input Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3--2--1 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3--2--2 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3--3 AD101 Analog Input Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3--3--1 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3--3--2 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3--4 DA001 through DA005 Analog Output Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3--4--1 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3--4--2 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3--5 DA101 Analog Output Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3--5--1 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3--5--2 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 12 13 15 15 16 18 18 18 21 21 22 24 24 24           3--1 3--1--1 AD001 through AD005 Analog Input Modules Dimensions All dimensions given below are in millimeters. 3G2A5-AD001 through 3G2A5-AD005 3G2A6-AD001 through 3G2A6-AD005 (Mounted to 3G2C4-SIO25/SIO26)  Section 3--1          3--1--2 Section 3--1 Wiring Use shielded twisted-pair cable for external connections. Connect the positive and negative terminals of any unused input points to the shield terminal. Use separate power supplies for input points 1 and 2 whenever possible. When using separate power supplies, always connect the negative input terminal to the shield line; failure to do so will produce several percent of error in the converted data. Incorrect wiring will produce inaccuracy in converted data. Use the proper wiring diagram and wire with care. Voltage Inputs VOLTAGE ONLY AD001 AD002 AD003 AD004 AD005  +5VDC 0  +10VDC 0  +5VDC --10  +10VDC --5  +5VDC +1 + -- NC + -- NC NC NC NC NC NC NC NC 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16           Section 3--1 Current Inputs AD001 +4  +20mA NC NC NC NC NC NC NC NC NC  0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16        3--2 3--2--1 Section 3--1 AD006 and AD007 Analog Input Modules Dimensions All dimensions given below are in millimeters. 3G2A5-AD006/AD007 3G2A6-AD006/AD007 (Mounted to 3G2C4-SIO25/SIO26)         3--2--2 Section 3--1 Wiring Voltage Inputs VOLTAGE ONLY AD006 AD007  +5VDC 0  +10VDC +1 + -- + -- + -- + -- NC  0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16        Section 3--1 Current Inputs CURRENT ONLY AD006 4  +20mA Wiring Notes 1. Use twisted-pair cable for external connections. 2. Connect the positive and negative terminals of any unused input points to the shield terminal. 3. For voltage inputs, connect the negative terminal to the shield terminal. Failure to do so may cause an error of several percent in the data. 4. For current inputs, Omron recommends that you use a separate power supply for each input point. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16       3--3 3--3--1 Section 3--3 AD101 Analog Input Modules Dimensions All dimensions given below are in millimeters. 3--3--2 Wiring Terminal Allocations Point 1 Point 2 Point 3 Point 4  + Voltage/current input 1 0 15 + Voltage/current input 5 -- Current input 1 1 16 -- Current input 5 -- Voltage/current input 1 2 17 -- Voltage/current input 5 Shield 3 18 Shield + Voltage/current input 2 4 19 + Voltage/current input 6 -- Current input 2 5 20 -- Current input 6 -- Voltage/current input 2 6 21 -- Voltage/current input 6 Not connected 7 22 Not connected + Voltage/current input 3 8 23 + Voltage/current input 7 -- Current input 3 9 24 -- Current input 7 -- Voltage/current input 3 10 25 -- Voltage/current input 7 Shield 11 26 Shield + Voltage/current input 4 12 27 + Voltage/current input 8 -- Current input 4 13 28 -- Current input 8 -- Voltage/current input 4 14 29 -- Voltage/current input 8 Point 5 Point 6 Point 7 Point 8      Section 3--3 Voltage Input Connections VOLTAGE ONLY AD101  0 +10VDC Adjustable. (See note.) Note Factory default is 0 + -- + -- + -- + -- + -- + -- + -- + --  +5VDC. 0 2 3 4 6 8 10 11 12 14 15 17 18 19 21 23 25 26 27 29 Port1 Port2 Port3 Port4 Port5 Port6 Port7 Port8       Section 3--3 Current Input Connections CURRENT ONLY AD101  0 +20mA Adjustable. (See note.) Note Factory default is 4  20mA. Wiring Notes 1. Use shielded twisted-pair cable for external connections. 2. Connect the positive and negative terminals of any unused input points to the shield terminal. 0 1 2 3 4 5 6 8 9 10 11 12 13 14 15 16 17 18 19 20 21 23 24 25 26 27 28 29  Port 1 Port 2 Port 3 Port 4 Port 5 Port 6 Port 7 Port 8           3--4 3--4--1 Section 3--4 DA001 through DA005 Analog Output Modules Dimensions All dimensions given below are in millimeters. 3G2A5-DA001 through 3G2A5-DA005 3G2A6-DA001 through 3G2A6-DA005 (Mounted to 3G2C4-SIO25/SIO26)            3--4--2 Section 3--4 Wiring Voltage Outputs VOLTAGE ONLY DA001 DA002 DA003 DA004 DA005  +5VDC 0  +10VDC 0  +5VDC --10  +10VDC --5  +5VDC +1 + -NC NC NC + -NC NC NC NC NC NC NC NC NC NC  0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16           Section 3--4 Current Outputs CURRENT ONLY DA001 +4  +20mA Wiring Notes 1. Use 2-conductor shielded twisted-pair cable for external connections to prevent induction and noise. 2. Ground the shields to the Module. 3. Do not use the same cable for signal lines and AC wiring to external devices. 4. Do not run the Module’s cables near or bind them together with main circuit cables or high voltage cables. Keep the external signal cables separate from AC cables. NC NC NC NC NC NC NC NC NC 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16        3--5 3--5--1 Section 3--5 DA101 Analog Output Modules Dimensions All dimensions given below are in millimeters. 3--5--2 Wiring Terminal Allocations Point Output Polarity Terminal 1 Voltage output + 0 -- 1 Current output + 2 -- 3 Voltage output + 4 -- 5 + 6 -- 7 Voltage output + 8 -- 9 Current output + 10 -- 11 Voltage output + 12 -- 13 + 14 -- 15 2 Current output 3 4 Current output Not used.  16       Section 3--5 Voltage Output Connections VOLTAGE ONLY DA101  +10VDC +1  +5VDC 0 (See note.) Note Factory default is +1 + -- + -- + -- + --  +5VDC. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16        Section 3--5 Current Output Connections CURRENT ONLY DA101 +4  +20mA Wiring Notes 1. Use 2-conductor shielded twisted-pair cable for external connections to prevent induction and noise. 2. Ground the shields to the Module. 3. Do not use the same cable for signal lines and AC wiring to external devices. 4. Do not run the Module’s cables near or bind them together with main circuit cables or high voltage cables. Keep the external signal cables separate from AC cables. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16  SECTION 4 Operation This section describes the basic operation of the Analog I/O Modules, including A/D and D/A conversion methods and IR bit allocations and application. 4--1 AD001 through AD005 Analog Input Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4--1--1 Block Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4--1--2 A/D Conversion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4--1--3 IR Bit Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4--2 AD006 and AD007 Analog Input Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4--2--1 Block Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4--2--2 A/D Conversion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4--2--3 IR Bit Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4--3 AD101 Analog Input Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4--3--1 Block Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4--3--2 A/D Conversion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4--3--3 Operational Flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4--3--4 Two-word Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4--3--5 Four-word Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4--4 DA001 through DA005 Analog Output Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4--4--1 Block Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4--4--2 D/A Conversion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4--4--3 IR Bit Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4--5 DA101 Analog Output Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4--5--1 Block Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4--5--2 D/A Conversion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4--5--3 Operational Flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4--5--4 IR Bit Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 28 28 29 30 30 30 31 31 32 32 33 33 39 40 41 41 43 43 44 44 45 46           4--1 Section 4--1 AD001 through AD005 Analog Input Modules With the AD001 and AD005, the binary-converted value of each input point is input to a dedicated IR word, i.e., the contents of the IR word allocated to any one input point will always contain the value of the analog input at the most recent I/O refresh period. This data can be used directly in binary form or converted to BCD for further use. This section describes the internal connections of the Module, the AD conversion method used, and the IR bit allocations. Refer to Section 5 Programming Considerations for programming examples. 4--1--1 Block Diagram The following diagram shows the basic internal connections of the Module. The Disconnection detector functions only for input ranges of 1 to 5 V and 4 to 20 mA. Disconnection detector Insullation +Input Input point 1 +Resis tance Memory --Input Shield Range selector Multi plexer +Input Input point 2 A/D converter Photo coupler Bus inter face PLC I/O bus +Resis tance --Input Shield Memory Analog 0 V Photo coupler Timing circuit Insullation Analog power supply 4--1--2 DC/DC 5V converter 0V A/D Conversion The analog inputs are converted to 12-bit binary code. Five different conversion ranges are available, 0 to 10 V, 0 to 5 V, 1 to 5 V (4 to 20 mA), --5 to 5 V, or --10 to 10 V, depending on the model of the Module. The relationships between the analog input values and converted binary values are shown next.           Positive Ranges Section 4--1 Decimal equivalent of binary code Decimal equivalent of binary code 4095 4095 0 0V Positive/Negative Ranges 5 or 10 V Analog input 0 1 V (4 mA) 5 V (20 mA) Analog input Positive and negative values are differentiated via bit 11 (see below). Decimal equivalent of binary code 4095 Bit 11 is 1 for negative values. Bit 11 is for positive values. 0 0V --5 or --10 V 4--1--3 5 or 10 V Analog input IR Bit Allocations Bits in words IR n and IR n+1 are allocated as shown below. Bit 11 provides 211 data for ranges with only positive values, but operates as the Sign Flag for input ranges that include negative values. The Sign Flag will be 0 for positive values and 1 for negative values. Bit 15 is the Disconnection Flag for input ranges of 1 to 5 V and 4 to 20 mA, and will be 1 when a voltage of 0.5 V or less is detected for 1 to 5 V or when a current of 2 mA or less is detected for 4 to 20 mA. Input words Bit IR n: point 1 IR n+1: point 2 0 A/D converted data 20 A/D converted data 20 1 A/D converted data 21 A/D converted data 21 2 A/D converted data 22 A/D converted data 22 A/D converted data 23 A/D converted data 23 A/D converted data 24 A/D converted data 24 A/D converted data 25 A/D converted data 25 6 A/D converted data 26 A/D converted data 26 7 A/D converted data 27 A/D converted data 27 8 A/D converted data 28 A/D converted data 28 9 A/D converted data 29 A/D converted data 29 10 A/D converted data 210 A/D converted data 210 11 A/D converted data Sign Flag 211 12 to 14 0 0 15 Disconnection Flag Disconnection Flag 3 4 5 or A/D converted data 211 or Sign Flag         4--2 Section 4--2 AD006 and AD007 Analog Input Modules With the AD006 and AD007, the binary-converted value of each input point is input to a dedicated IR word, i.e., the contents of the IR word allocated to any one input point will always contain the value of the analog input at the most recent I/O refresh period. This data can be used directly in binary form or converted to BCD for further use. This section describes the internal connections of the Module, the AD conversion method used, and the IR bit allocations. Refer to Section 4 Programming Considerations for programming examples. 4--2--1 Block Diagram The following diagram shows the basic internal connections of the Module. Range selector +Input Input point 1 +Resis tance Memory --Input Shield +Input Input point 2 +Resis tance Multi plexer A/D converter Photo coupler Bus inter face PLC I/O bus --Input Shield +Input Input point 3 Memory +Resis tance --Input Shield Photo coupler +Input Input point 4 Timing circuit +Resis tance --Input Shield Analog Analog 0 V 4--2--2 power supply DC/DC 5V converter 0V A/D Conversion The analog inputs are converted to 10-bit binary code. Two different conversion ranges are available, 0 to 10 V or 1 to 5 V (4 to 20 mA), depending on       Section 4--3 the model of the Module. The relationships between the analog input values and converted binary value are shown below. Decimal equivalent Decimal equivalent of binary code of binary code 1023 1023 Analog input 0 0V 4--2--3 10 V 0 1 V (4 mA) 5 V (20 mA) Analog input IR Bit Allocations Bit Input words IR n: point 1 IR n+2: point 3 IR n+3: point 4 0 A/D converted data 20 A/D converted data 20 A/D converted data 20 A/D converted data 20 1 A/D converted data 21 A/D converted data 21 A/D converted data 21 A/D converted data 21 2 A/D converted data 22 A/D converted data 22 A/D converted data 22 A/D converted data 22 A/D converted data 23 A/D converted data 23 A/D converted data 23 A/D converted data 23 A/D converted data 24 A/D converted data 24 A/D converted data 24 A/D converted data 24 5 A/D converted data 25 A/D converted data 25 A/D converted data 25 A/D converted data 25 6 A/D converted data 26 A/D converted data 26 A/D converted data 26 A/D converted data 26 7 A/D converted data 27 A/D converted data 27 A/D converted data 27 A/D converted data 27 8 A/D converted data 28 A/D converted data 28 A/D converted data 28 A/D converted data 28 9 A/D converted data 29 A/D converted data 29 A/D converted data 29 A/D converted data 29 10 to 15 0 0 0 0 3 4 4--3 IR n+1: point 2 AD101 Analog Input Modules There are two modes of operation available with the AD101: two-word operation and four-word operation. Although the method for reading in analog values varies depending on the operation mode, the binary-converted value of each input point is input into the PLC in binary form. This data can be used directly in binary form or converted to BCD for further use. This section describes the internal connections of the Module, the AD conversion method used, the IR bit allocations, the methods used to input analog values, and special functions available. Refer to Section 4 Programming Considerations for programming examples.       4--3--1 Section 4--3 Block Diagram The following diagram shows the basic internal connections of the Module. +Voltage Input point 1 +Current Timing Common Memory PLC I/O bus Shield +Voltage +Current Input point 2 Multi plexer Common A/D converter Shield +Voltage Input point 3 Bus interface Photo coupler CPU +Current Common Shield +Voltage Input point 4 +Current Common Shield Analog Analog 0 V power supply 4--3--2 DC/DC 5V converter 0V A/D Conversion Analog input values are converted to binary according to the offset and gain values set for the input (most binary values are given in hexadecimal in this manual). Line (1) in the following figures shows the factory settings, 1 to 5 V (4 to 20 mA). This means that an input of 1 V (4 mA) will be converted to 000hex and an input of 5 V (20 mA) will be converted to FFFhex. The maximum ranges, 0 to 10 V (0 to 20 mA), are shown by line (2) in the figures. The offset and gain for any input point can be set anywhere within these ranges as long as the gain is greater than the offset: the offset value is always converted to 000hex, and the gain is always converted to FFFhex.       Section 4--3 The relationships between the input analog values and the converted binary values are shown below. Binary values are given in their hexadecimal equivalents. Voltage Inputs Current Inputs Gain FFF FFF Gain (2) Digital value Digital value (1) 000 000 0 Offset 4--3--3 5V 10 V Analog input voltage 0 4 mA Offset 20 mA Analog input voltage Operational Flow The basic steps involved in setting up and operating the AD101 are shown below. Some of these steps have already been described in this manual. Start Programming Setup Set operating mode. Select either two-word or four-word operation. See Section 2 Components and Switch Settings. Set input ranges. Mount the Module to the Rack, and then set the input range for each input point, See Section 2 Components and Switch Settings. Wiring connections Connect input signal wiring. See Section 4 Installation. Word allocation Programming Allocate I/O and DM areas. See Section 4 Operation. Write the PLC program. Operate 4--3--4 Two-word Operation In two-word operation, there are two types of data transfer that occurs between the Analog Input Module and the PLC. One of these uses the normal       Section 4--3 I/O refresh period to transfer flag and control bit status (see IR Bit Allocations below) between the Analog Input Module and the IR words allocated to the Module. Here, the output word (IR n) is used to designate when peak value for input points are to be read or reset and the input word (IR n+1) is used to confirm data validity and to check when peak values are being read. The other form of data transfer is used to write parameters (e.g., offsets and gains) directly to the Analog Input Module or to read data (i.e., binary-converted analog values or peak values) directly from the Module. In this case the input and output words are used as the operands for the I/O WRITE and I/O READ instructions, WRIT(87) and READ(88). The data being read or written is stored at consecutive words beginning at a word designated as another operand. The general forms of these instructions are shown below. Refer to your PLC’s Operation Manual for details. I/O READ Instruction I/O WRITE Instruction READ (88) WRIT (87) Number of words transferred Specify IR n+1 Beginning destination word Number of words transferred Beginning source word Specify IR n Communications The following diagram illustrated communications between the AD101 Analog Input Module and the PLC during two-word operation. The I/O READ and I/O WRITE instructions are used to directly read and write data. Refer to the next page for details on IR n and IR n+1. READ(88) IR n+1 (input word) WRIT(87) AD101 Analog Input Module IR n (output word) PL C I/O refresh IR n+1 I/O refresh IR n IR Bit Allocations The following bits are used to control data transfer between the Analog Input Module and the PLC as explained below the table. The first three bits in each word are system handshaking flags, bit 03 of n+1 is used to confirm data,       Section 4--3 and the other bits are used to control and monitor reading of peak input values. Bit Ouput word: IR n Input word: IR n+1 00 (PC Busy Flag) (A/D Busy Flag) 01 (PC Write Finished Flag) (A/D Read Finish Flag) 02 (PC Read Finished Flag) (A/D Write Finish Flag) 03 Not used. Unconfirmed Data Flag 04 to 06 Not used. Not used. 07 Peak Reset Bit Not used. 08 Peak Read Bit 0 Peak Flag 0 09 Peak Read Bit 1 Peak Flag 1 10 Peak Read Bit 2 Peak Flag 2 11 Peak Read Bit 3 Peak Flag 3 12 Peak Read Bit 4 Peak Flag 4 13 Peak Read Bit 5 Peak Flag 5 14 Peak Read Bit 6 Peak Flag 6 15 Peak Read Bit 7 Peak Flag 7 Handshaking Flags Bits 00 through 02 of both the input and output words are system handshaking flags and cannot be used in programming. The status of these bits determines whether or not the I/O READ and I/O WRITE instructions will be executed as desired (see Reading Data and Writing Data below). Unconfirmed Data Flag This bit turns ON when data has not been confirmed (for example, when the power has just been turned on). Be sure this flag is OFF before reading data. Peak Reset Bit This bit is turned ON with one or more of the Peak Read Bits to reset the peak values of the input points designated by the Peak Read Bit. Peak Read Bits If the Peak Reset Bit is OFF, these bits are turned ON to read the peak values. The peak value for each ON bit will be read in the next time READ(88) is executed for the input word. If the Peak Read Bit is turned ON for an input point, the data read with the next READ(88) will be the peak value; if the Peak Read Bit is turned OFF for a point, the data read with the next READ(88) will be the normal input value. Here, however, “the next READ(88)” is the next one following the next I/O refresh period. The Peak Flags can be used to check to see whether peak values have been reached. The Peak Read Bits are also used with the Peak Reset Bit to reset the peak values. Peak Flags The Peak Flags turn ON to indicate that the input value for the input point has reached a peak value. input points for which peak values have been read instead of normal input values. Writing Data WRIT(87) is used to transfer operating parameter directly to the Analog I/O Module and is executed only when both the A/D Busy Flag (IR n+1, bit 00) and A/D Read Finished Flag (IR n+1, bit 01) are OFF. If either of these flags is ON when WRIT(87) is reached in the program, WRIT(87) will be executed as NOP. After WRIT(87) has been executed, the PC Write Finished Flag (IR n, bit 01) will turn ON for one scan and the Equals flag ( SR 6306 or SR 25506) will turn ON.       Data Writing Area Section 4--3 WRIT(87), is used to transfer a maximum of 26 words of data to the Analog Input Module. The first word, m, is specified by the user and written as the beginning source word of WRIT(87). All consecutive words must be in the same data area (DM m through DM m+25). The first two words are used to specify which points will be used and which points the mean and scaling functions will be used for. If the mean or scaling values are not required for an input point, no data need be provided, i.e., you need to transfer only the data that is actually required for operation as specified in the first two words. If not all of the data is required, fewer words will need to be transferred. DM word Bit 15 14 13 12 11 10 9 DM m Specify points for mean function DM m+1 Specify points for scaling function DM m+2 Mean value 1 DM m+3 Mean value 2 DM m+4 Mean value 3 DM m+5 Mean value 4 DM m+6 Mean value 5 DM m+7 Mean value 6 DM m+8 Mean value 7 DM m+9 Mean value 8 DM m+10 Scaling offset 1 DM m+11 Scaling gain 1 DM m+12 Scaling offset 2 DM m+13 Scaling gain 2 DM m+14 Scaling offset 3 DM m+15 Scaling gain 3 DM m+16 Scaling offset 4 DM m+17 Scaling gain 4 DM m+18 Scaling offset 5 DM m+19 Scaling gain 5 DM m+20 Scaling offset 6 DM m+21 Scaling gain 6 DM m+22 Scaling offset 7 DM m+23 Scaling gain 7 DM m+24 Scaling offset 8 DM m+25 Scaling gain 8 8 7 6 5 4 3 2 1 0 Specify points to be used 0 0 Caution Input the mean value and scaling values only for points for which the mean and/or scaling function has been designated. If one of these is not needed for a point, move all other parameters up one word to replace it. For example, if a mean value is not required for input point 3 but is required for points 1, 2, and 4, the mean value for point 4 would be placed in DM m+ 04 instead of DM m+5. Point Specification  If a point is to be used, turn the corresponding bit ON. If a point is not to be used, turn the corresponding bit OFF.      DM m Section 4--3 07 06 05 04 03 02 01 00 Input point 1 to Input point 8 Mean Value Specification If mean for an input point is to be used, turn the corresponding bit ON. If mean is not to be used, turn the corresponding bit OFF. DM m 15 14 13 12 11 10 09 08 Input point 1 to Input point 8 Specify the sampling count (2 through 9999) for the mean value. Enter data for each point specified for the mean function. Data must be specified in BCD. The actual words where data will need to be stored will depend on the actual data required. If a large count is set, the conversion time may exceed the10-ms-per-point conversion time by 1 or 2 ms. DM m+2 15 to 00 to to DM m+9 Scaling Input point 1 15 to 00 Input point 8 If scaling is to be used for an input point, turn the corresponding bit ON. If scaling is not to be used, turn the corresponding bit OFF. DM m 15 14 13 12 11 10 09 08 Input point 1 to Input point 8 Enter the offset and gain for each point for which the scaling function has been designated. The offset is the value that is to correspond to 000hex. The gain is the value corresponding to FFFhex. The offset and gain must be set in BCD and must be in the range 0 through 9999. The gain must be greater than the offset. DM m+10 15 to 00 DM m 11 15 to 00 Offset Input point 1 Gain to to DM m 24 DM m 25 15 15 to to 00 00 Offset Input point 8 Gain       Section 4--3 Reading Data READ(88) will be executed when the A/D Busy Flag (IR n+1, bit 00) is OFF and the A/D Write Finished Flag (IR n+1, bit 02) is ON. If the A/D Busy Flag is ON or the A/D Write Finished Flag is OFF, READ(88) will not be executed. The data transferred for READ(88) depends on the status of the Peak Read Bits, i.e., if the Peak Read Bit for an input is ON, the peak value will be transferred; if the Peak Read Bit is OFF, the normal binary-converted value will be transferred. The Peak Flags can be used to confirm what data has been transferred. The last word transferred always contains the Disconnection Flags. Data Reading Area READ(88) is used to transfer a maximum of 9 words of data beginning from DM l. The first word, l, is specified by the user and written as the beginning destination word of READ(88). You can select any area of DM as long as the end of the area is not exceeded (DM l through DM l+8). DM word Bit 15 14 13 12 11 10 DM l Input point 1 converted data DM l+1 Input point 2 converted data DM l+2 Input point 3 converted data DM l+3 Input point 4 converted data DM l+4 Input point 5 converted data DM l+5 Input point 6 converted data DM l+6 Input point 7 converted data DM l+7 Input point 8 converted data DM l+8 0 9 8 0 7 6 5 4 3 2 1 0 Disconnection Flags Note Do not allocate the same area for both writing and reading data. Input Point Converted Data DM l+2 A/D converted data is written to the specified words. When scaling is used, data is in 4-bit BCD (bits 00 to 15). When scaling is not used, data is in 3-bit hexadecimal (bits 00 to 11). 15 to 00 to DM l+7 Disconnection Flags Input point 1 to 15 to 00 Input point 8 When an input line disconnection is detected, the flag assigned to the input point will turn ON. The offset value must be at least 1 V (1 mA) for these flags to work. DM l+8 07 06 05 04 03 02 01 00 Input point 1 to Input point 8       4--3--5 Section 4--3 Four-word Operation With four-word operation, IR n and IR n+2 are used as dedicated output and input words, respectively. IR n+1 is used to control data transfer and IR n+3 is used to monitor data transfer. To write data, move the desired data to IR n and then set the proper control bits to designate what data has been set. The data will be read in at the next I/O refresh period. To read data, set the proper control bits and then move the data input to IR n+2 to the desired storage location after checking the flags to confirm that the desired data has been input. Individual control bits and flags are described following the allocations table below. IR Bit Allocations Bit Output IR n Input IR n+1 IR n+2 IR n+3 00 Point 1 Control Bit Point 1 Read Flag 01 Point 2 Control Bit Point 2 Read Flag 02 Point 3 Control Bit Point 3 Read Flag 03 Point 4 Control Bit Point 4 Read Flag 04 Point 5 Control Bit Point 5 Read Flag 05 06 Point 6 Control Bit Writing data Point 7 Control Bit Point 6 Read Flag Reading data Point 7 Read Flag 07 Point 8 Control Bit Point 8 Read Flag 08 Normal/Peak Control Bit Disconnection Flag 09 10 Normal/Peak Flag Not used. 11 Not used. 12 Peak Reset Bit 13 A/D Conversion Bit 14 PC Write Completed Bit A/D Read Completed Flag 15 PC Read Completed Bit A/D Write Completed Flag Not used. Point Control Bits Turn ON one of the Point Control Bits to designate the desired input point when writing the number of sampling counts for the mean value and when reading binary-converted data. When using peak hold, turn the A/D Conversion Bit OFF. When not using peak hold, turn this flag ON. Normal/Peak Control Bit Turn this flag and the A/D Conversion Bit ON to read normal binary-converted values and turn this flag and the A/D Conversion Bit OFF to read peak values. Peak Reset Bit Turn this bit ON to reset an input point for which the peak value is being read. A/D Conversion Bit Turn this flag ON when reading normal data, and turn it OFF when reading peak values or writing the number of sampling counts for the mean value. Point Read Flags One of these flags turns ON to designate the input point for which data is being read. Disconnection Flag When the signal line of the point designated by the Point Read Flags is burned out or disconnected, this flag turns ON. The offset must be set to at least 1 V (4 mA) for this flag to work.            Section 4--4 Normal/Peak Flag This flag turns ON when the data being read is normal data and turns OFF when the data is the peak value. Mean Function If the both the Normal/Peak Control Bit and the A/D Conversion Bit are turned OFF, the value in IR n will be read in as the sampling count for the mean value for the input point specified by the Point Control Bits. Specify the sampling count (2 through 9999) for the mean value. Set the count to 0 to turn OFF the mean function for that point. Data must be specified in BCD. Note The scaling function does not work with 4-word operation. 4--4 DA001 through DA005 Analog Output Modules With the DA001 through DA005, the binary-converted value for each output point is placed in a dedicated IR word, i.e., the contents of the IR word allocated to any one output point contains the value of to be converted for output as an analog value. This section describes the internal connections of the Module, the AD conversion method used, and the IR bit allocations. Refer to Section 4 Programming Considerations for programming examples.            4--4--1 Section 4--4 Block Diagram The following diagram shows the basic internal connections of the Module. Point 1 + Voltage output _ Analog 0 V D/A Memory + Current output _ Photocoupler Bus interface Ranger selector Point 2 + Voltage output _ Analog 0 V D/A + Current output _ Memory Photocoupler Photocoupler Analog power supply DC/DC converter PLC I/O bus Timing circuit 5V 0V The current outputs are not connected in Modules whose voltage output range is other than 1 to 5 V. 4--4--2 D/A Conversion These Modules convert 12-bit binary data to voltage or current output. Each Module has a different type of output. Outputs can be either unipolar or bipolar, with the resolution depending on the model. Unipolar Outputs Output ranges: 0 to 10 V, 0 to 5 V, or 1 to 5 V (4 to 20 mA) Data format: 12-bit binary Data conversion for unipolar outputs is illustrated below.            10 V (5 V) Section 4--4 5 V (20 mA) Output Output 1 V (4 mA) 0V 0 Digital value 4095 0 0 to 10 V Output or 0 to 5 V Outputs Bipolar Output 4095 1 to 5 V (4 to 20 mA) Outputs Output range: -10 to 10 V, -5 to 5 V Data format: 11-bit binary +1 Sign Flag (The Sign Flag is bit 11; OFF is positive, ON is negative.) Data conversion for bipolar outputs is illustrated below. Output 10 V (5 V) --2047 0 0V 2047 Digital value --10 V (5 V) Note:  Digital value The numbers 2048 to 4095 represent the values --0 to --2047.       4--4--3 Section 4--5 IR Bit Allocations Bit allocations of the words that contain the values that will be converted to analog values for output from each output point on the Analog Output Module are shown below. Bit Output words IR n: Point 1 IR n+1: Point 2 0 D/A conversion data 20 D/A conversion data 20 1 D/A conversion data 21 D/A conversion data 21 2 D/A conversion data 22 D/A conversion data 22 D/A conversion data 23 D/A conversion data 23 D/A conversion data 24 D/A conversion data 24 D/A conversion data 25 D/A conversion data 25 6 D/A conversion data 26 D/A conversion data 26 7 D/A conversion data 27 D/A conversion data 27 9 D/A conversion data 29 D/A conversion data 29 10 D/A conversion data 210 D/A conversion data 210 11 D/A conversion data 211 or Sign Flag D/A conversion data 211 or Sign Flag 12 to 15 Usable as work bits. Usable as work bits. 3 4 5 Note For bipolar outputs, bit 11 is OFF for positive output values and ON for negative output values. 4--5 DA101 Analog Output Modules With the DA101, the binary-converted value for each output point is placed in a dedicated IR word, i.e., the contents of the IR word allocated to any one output point contains the value of to be converted for output as an analog value. This section describes the internal connections of the Module, the AD conversion method used, and the IR bit allocations. Refer to Section 4 Programming Considerations for programming examples.        4--5--1 Section 4--5 Block Diagram The following diagram shows the basic internal connections of the Module. Memory Bus interface PLC I/O bus Photocoupler Memory Memory D/A + Current output _ Point 2 + Voltage output -D/A + Current output _ Point 3 + Voltage output -D/A + Current output _ Point 4 + Voltage output -- Timing circuit Memory Photocoupler 4--5--2 Point 1 + Voltage output -- D/A Range selector + Current output _ 0V 5V DC/DC converter Analog power supply D/A Conversion This Module converts 3-digit hexadecimal values (000 to FFF) from the specified words (IR n to n+3) for output from the Analog Output Module. The output range depends on the setting of the DIP switches (see Section 2 Components and Switch Settings). The following diagram shows the basic flow of data from some PLC memory area, to the IR words allocated to the Analog Outputs Module, to the Module itself, and finally to the external device. BCD data 0 to 4095 Hexadecimal data 0 to 0FFF  BCD to BIN conversion IR n to IR n+3 Data transfer D/A conversion Analog output External device       Section 4--5 The following diagram illustrates the conversion of values in IR n to IR n+3 to analog output values. The specific analog output ranges to which the binary values are converted depends on the switch settings of the Module. 10 V 5 V (20 mA) Output Output 1 V (4 mA) 0V 0 4--5--3 FFF (4095) Digital value 0 FFF (4095) Digital value Operational Flow The basic operational flow is illustrated below. Some of these steps have already been described. Start Set the output ranges Mount the Unit. Use the DIP switches on the back of the Module. The Module is allocated 4 words. Wire connections. Connect the points to the external device Program. Write a PLC program which transfers binary data in the range 0000 through 0FFF to the IR n through IR n+3. Operate        4--5--4 Section 4--5 IR Bit Allocations Bit allocations of the words that contain the values that will be converted to analog values for output from each output point on the Analog Output Module are shown below. Bit Output words IR n: Point 1 IR n+1: Point 2 IR n+2: Point 3 IR n+3: Point 4 0 D/A conversion data 20 D/A conversion data 20 D/A conversion data 20 D/A conversion data 20 1 D/A conversion data 21 D/A conversion data 21 D/A conversion data 21 D/A conversion data 21 2 D/A conversion data 22 D/A conversion data 22 D/A conversion data 22 D/A conversion data 22 D/A conversion data 23 D/A conversion data 23 D/A conversion data 23 D/A conversion data 23 D/A conversion data 24 D/A conversion data 24 D/A conversion data 24 D/A conversion data 24 D/A conversion data 25 D/A conversion data 25 D/A conversion data 25 D/A conversion data 25 6 D/A conversion data 26 D/A conversion data 26 D/A conversion data 26 D/A conversion data 26 7 D/A conversion data 27 D/A conversion data 27 D/A conversion data 27 D/A conversion data 27 8 D/A conversion data 28 D/A conversion data 28 D/A conversion data 28 D/A conversion data 28 9 D/A conversion data 29 D/A conversion data 29 D/A conversion data 29 D/A conversion data 29 10 D/A conversion data 210 D/A conversion data 210 D/A conversion data 210 D/A conversion data 210 11 D/A conversion data 211 211 211 D/A conversion data 211 12 to 15 Usable as work bits. 3 4 5  D/A conversion data Usable as work bits. D/A conversion data Usable as work bits. Usable as work bits. SECTION 5 Programming Considerations This section provides examples of the most common methods of programming for the Analog I/O Modules. Be sure to read Section 3 Operation first to understand the basic operation of the Module before attempting to study these programs. 5--1 AD001 through AD005 Analog Input Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5--2 AD006 and AD007 Analog Input Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5--3 AD101 Analog Input Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5--3--1 Two-word Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5--3--2 Four-word Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5--4 DA001 through DA005 Analog Output Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5--5 DA101 Analog Output Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 50 52 52 59 69 71           5--1 Section 5--1 AD001 through AD005 Analog Input Modules All that is necessary in programming these Modules is to access the binary-converted analog values at the allocated IR words and use it as required by the control system. The following example program converts two input points to two 4-digit BCD values (4095 maximum) and outputs the result. The words allocated to each Module are shown above the Module. The program is shown on the following page. In programming, ANDW(34) is used to read the data and at the same time filter out the converted value, i.e., only bits 0 through 11. IR 01 IR 02 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 Input point 1 Input point 2 Analog Input Module  IR 03 00 01 02 03 04 05 06 07 IR 04 Input point 1 4-digit BCD output. COM 08 09 10 11 12 13 14 15 COM Output Module X 100 X 101 X 102 X 103 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 00 01 02 03 04 05 06 07 IR 05 Input point 2 4-digit BCD output. COM 08 09 10 11 12 13 14 15 COM Output Module X 100 X 101 X 102 X 103 Disconnection detection 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 00 01 02 03 04 05 06 07 for input point 1 COM 08 09 10 11 12 13 14 15 COM Output Module Disconnection detection for input point 2          Section 5--1 Always ON Flag 6113 ANDW(34) For input point 1 01 #)FFF DM 000 BCD(24) DM 000 03 Reads the converted data from IR 01 and stores it in DM 000. Converts the content of DM 000 to BCD and outputs it to IR 03. 0115 0501 Always ON Flag 6113 For input point 2 ANDW(34) 02 #)FFF DM 001 BCD(24) DM 001 Reads the converted data from IR 02 and stores it in DM 001. Converts the content of DM 001 to BCD and outputs it to IR 04. 04 0215 0509 Address Instruction 00000 00001 LD ANDW(34) Operands 6113 # DM 00002 LD OUT Instruction 00005 00006 LD ANDW(34) 01 0FFF 000 000 03 0115 0501 Operands 6113 # DM 00007 BCD(24) DM 00003 00004 Address BCD(24) DM 00008 00009 02 0FFF 001 LD OUT 001 04 0115 0501         5--2 Section 5--2 AD006 and AD007 Analog Input Modules All that is necessary in programming these Modules is to access the binary-converted analog values at the allocated IR words and use it as required by the control system. The following example program converts four input points to four 4-digit BCD values (1023 maximum) and outputs the result. The words allocated to each Module are shown above the Module. The program is shown on the following page. In programming, ANDW(34) is used to read the data and at the same time filter out the converted value, i.e., only bits 0 through 9. IR 01 IR 02 IR 03 IR 04 Input point 1 Input point 2 Input point 3 Input point 4 Analog Input Module  IR 06 IR 05 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 00 01 02 03 04 05 06 07 COM 08 09 10 11 12 13 14 15 COM Output Module Input point 1 4-digit BCD output. X 100 X 101 X 102 X 103 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 00 01 02 03 04 05 06 07 COM 08 09 10 11 12 13 14 15 COM Output Module IR 07 Input point 2 4-digit BCD output. X 100 X 101 X 102 X 103 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 00 01 02 03 04 05 06 07 COM 08 09 10 11 12 13 14 15 COM Output Module IR 08 Input point 3 4-digit BCD output. X 100 X 101 X 102 X 103 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 00 01 02 03 04 05 06 07 COM 08 09 10 11 12 13 14 15 COM Output Module Input point 4 4-digit BCD output. X 100 X 101 X 102 X 103        Section 5--2 Always ON Flag 6113 ANDW(34) For input point 1 01 #03FF DM 000 BCD(24) DM 000 05 Reads the converted data from IR 01 and stores it in DM 000. Converts the content of DM 000 to BCD and outputs it to IR 05. Always ON Flag 6113 For input point 2 ANDW(34) 02 #03FF DM 001 BCD(24) DM 001 Reads the converted data from IR 02 and stores it in DM 001. Converts the content of DM 001 to BCD and outputs it to IR 06. 06 Always ON Flag 6113 For input point 3 ANDW(34) 03 #03FF DM 002 BCD(24) DM 002 Reads the converted data from IR 03 and stores it in DM 002. Converts the content of DM 002 to BCD and outputs it to IR 07. 07 Always ON Flag 6113 For input point 4 ANDW(34) 04 #03FF DM 003 BCD(24) DM 003 Reads the converted data from IR 04 and stores it in DM 003. Converts the content of DM 003 to BCD and outputs it to IR 08. 08       Address Instruction 00000 00001 LD ANDW(34) Section 5--3 Operands LD ANDW(34) 5--3 DM 00009 00010 LD ANDW(34) # DM 00011 DM 6113 03 03FF 002 BCD(24) 02 03FF 001 BCD(24) Operands # DM 00008 000 05 6113 # DM 00005 LD ANDW(34) BCD(24) DM 00003 00004 Instruction 00006 00007 01 03FF 000 # DM 00002 Address 6113 002 07 6113 04 03FF 003 BCD(24) 001 06 DM 003 08 AD101 Analog Input Modules The operation of the AD101 Analog Input Module depends on the setting of the operation mode switch (see Section 2 Components and Switch Settings.) Although two-word operation simplifies programming and always direct reading of analog input values without delays caused by waiting for the I/O refresh period, it is possible only on CPUs that support the I/O WRITE and I/O READ Instructions, WRIT(87) and READ(88). 5--3--1 Two-word Operation READ(88) are used to program transfer of normal and peak binary-converted analog values from the Analog Input Module to the PLC and WRIT(87) is used to program transfer of parameters from the PLC to the Analog Input Module. When programming, take into account the difference between the time data is written memory and time data is input or output via READ(88) and WRIT(87), i.e., there must be one I/O refresh period between any MOV(21)’s used to set control bits and READ(88) and WRIT(87). 1 scan I/O MOV(21) WRIT(87) refresh When executing WRIT(87) Time Data is written to shared memory Data is output Time lag In the following example, we will use the C500 as an example. All 8 points will be used. Means will be calculated for points 5 through 8, and scaling will be performed for points 7 and 8. The Module will be mounted in IR 00, so that IR 00 will be the output word and IR 01 will be the input word. DM 000 through DM 009 will be used for writing data, and DM 100 through DM 108 will be used for reading data. DM 200 through DM 207 will be used to hold the peak values of points 1 through 8.       Section 5--3 Allocation for Reading Data The following tables show the memory locations to which the program will move the various values resulting from the analog inputs. Input point Normal converted data Peak value BCD converted data 1 DM 100 DM 200 DM 300 2 DM 101 DM 201 DM 301 3 DM 102 DM 202 DM 302 4 DM 103 DM 203 DM 303 5 DM 104 DM 204 DM 304 6 DM 105 DM 205 DM 305 7 DM 106 DM 206 DM 306 8 DM 107 DM 207 DM 307 Disconnection Flag DM 108 The following table shows the memory locations from which the program will write parameters to the Analog Input Module. Allocation for Writing Data Address Set value DM 000 F0FF Mean value specification/point to be used DM 001 C000 Scaling specification DM 002 0005 Point 5 DM 003 0010 Point 6 Mean value data DM 004 0020 Point 7 (Sampling counts) DM 005 0050 Point 8 DM 006 0000 Point 7 Offset data DM 007 3000 Point 7 Gain data DM 008 1000 Point 8 Offset data DM 009 5000 Point 8 Gain data Contents of DM 000 DM 000 Scaling data Contents of DM 001 F 0 F F Upper 8 bits Contents DM 001 Lower 8 bits C 0 0 0 Upper 8 bits Set to 00 (not used) Mean specification 1 1 1 1 0 0 0 0 Points to be used 1 1 1 1 Scaling specification 1 1 1 1 1 1 1 1 Specify points 5 through 8 Specify points 1 through 8 0 0 0 0 Specify points 7 and 8 Note: The data writing area extends to 27 words maximum. If some points are not used for mean value or scaling, as shown above, the area will be smaller. Set only the data which needs to be set according to the settings of the first two words (here DM 000 and DM 001).       Section 5--3 First Scan Flag 6115 MOV(21) #FOFF Specifies the points to be used and mean value settings. DM000 MOV(21) #C000 DM001 MOV(21) #0005 Specifies scaling settings. Input point 5 (5 samples) DM002 MOV21 #0010 Input point 6 (10 samples) DM003 MOV(21) #0020 DM004 MOV(21) #0050 Sets the mean data (sampling counts). Input point 7 (20 samples) Input point 8 (50 samples) DM005 These settings can be made via the Programming Console using data modification functions instead of in programming, if desired. Input point 7 offset data MOV(21) #0000 DM006 MOV(21) #3000 Input point gain data DM007 MOV(21) #1000 Sets the scaling data. Input point 8 offset data DM008 MOV(21) #5000 Input point 8 gain data DM009 61115 WRIT(87) #0010 DM000 00 Transfers the 10 words of parameters from DM 000 through DM 009 to the Analog Input Module. EQ 3200 6306 3200 (Continued on next page.)  When the transfer is complete, SR 6306 (the Equal Flags) turns ON. Here, IR 3200 is used as a work bit to hold the status of EQ at this point.      Section 5--3 (From previous page.) 3200 0103 READ(88) 0009 01 DM100 (EQ) 3201 A/D converted data and the Disconnection Flags from points 1 through 8 are read in and stored in DM 100 through DM 108. IR 0103 (the Unconfirmed Data Flag) stops unconfirmed data from being accepted. 6306 3201 TR 1 3201 MOV(21) DM108 When reading is complete, SR 6306 (the Equal Flags) turns ON, activating IR 3201. Disconnection Flags (the lower 8 bits of DM 108) are output to IR 34. 34 3400 BCD(24) DM100 Input point 1 DM300 3401 BCD(24) DM101 Input point 2 DM301 3402 BCD(24) DM102 DM302 Input point 3 3403 BCD(24) DM103 Input point 4 DM303 3404 BCD(24) Binary data from points 1 through 6 is converted to BCD and written to DM 300 through DM 305. IR 3400 through 3407 are used as work bits activated by the Disconnection Flags to prevent data from being moved when an input is disconnected. Input point 5 DM104 DM304 3405 BCD(24) DM105 Input point 6 DM305 3406 MOV(21) DM106 Input point 7 DM306 3407 MOV(21) DM107 Input point 8 Scaling (BCD output) is performed on points 7 and 8 and the data is written to DM 306 and DM 307 without conversion. DM307 3300 0008 3301 0009 3302 0010 (Continued on next page.)       Section 5--3 (From previous page.) 3303 0011 3304 0012 3305 0013 3306 IR 33 is used for peak values. IR 0008 through IR 0015 are used to activate moving the peak values into the desired storage locations. Turn ON the Peak Read Bits and check the Peak Flags to read the peak values (see the next page). IR 0007 is used as the Peak Reset Flag. Turn both the Peak Reset Flag and the Peak Read Bit ON to reset a peak value. 0014 3307 0015 3308 0007 0008 0108 MOV(21) DM100 DM200 0009 0109 MOV(21) DM101 DM201 0010 0110 MOV(21) DM102 DM202 0011 0111 MOV(21) DM103 DM203 0012 0112 MOV(21) DM104 DM204 0013 0113 MOV(21) DM105 DM205 0014 0114 MOV(21) DM106 DM206 0015 0115 MOV(21) DM107 DM207  IR 0108 through IR 0115 are used as Peak Flags. When the input point data reaches a peak value, the flag corresponding to the input point will turn ON. When both the Peak Read Bit and Peak Flags are ON, the peak value, which will have been read at the last READ(87), will be written to DM 200 through DM 207.      Address 00000 00001 00002 00003 00004 00005 00006 00007 00008 00009 00010 00011 00012 Instruction Section 5--3 Operands LD MOV(21) 6115 # DM #F0FF 000 # DM #C000 001 # DM #0005 002 # DM #0010 003 # DM #0020 004 # DM #0050 005 # DM #0000 006 # DM #3000 007 # DM #1000 008 # DM #5000 009 6115 MOV(21) MOV(21) MOV(21) MOV(21) 00031 00032 00033 00034 00035 00036 00037 00038 00039 MOV(21) MOV(21) LD WRIT(87) LD AND NOT OUT LD NOT AND NOT OR READ(88) LD NOT AND LD OUT LD NOT OUT MOV(21) TR AND NOT 0010 000 00 3200 6306 3200 3200 0103 3201 0009 01 100 6306 3201 3201 1 108 34 3400 00040 00041 00042 00043 00044 00045 00046 00047 00048 00059 00060 00062 00063 00064 00065 00066 00067 00068 00069 00070 00071 00072 00073 00074 00075 00076 00077 Operands BCD(24) LD AND NOT BCD(24) LD AND NOT BCD(24) LD AND NOT BCD(24) LD AND NOT BCD(24) MOV(21) DM 00026 00028 00029 00030 Instruction MOV(21 ) DM 00020 00021 00022 00023 00024 00025 00027 MOV(21) # DM 00013 00014 00015 00016 00017 00018 00019 Address LD AND NOT BCD(24) LD AND NOT MOV(21) LD AND NOT MOV(21) LD OUT LD OUT LD OUT LD OUT LD OUT LD OUT LD OUT LD OUT LD OUT DM DM TR 100 300 1 3401 DM DM TR 101 301 1 3402 DM DM TR 102 302 1 3403 DM DM TR 103 303 1 3404 DM DM TR 104 304 1 3405 DM DM TR 105 305 1 3406 DM DM TR 106 306 1 3407 DM DM 107 307 3300 0008 3301 0009 3302 0010 3303 0011 3304 0012 3305 0013 3306 0014 3307 0015 3308 0007 (Continued on next page.)       Address 00077 00078 00079 Instruction Section 5--3 Operands LD AND MOV(21) DM DM 00080 00081 00082 LD AND MOV(21) DM DM 00083 00084 00085 LD AND MOV(21) DM DM 00086 00087 00088 LD AND MOV(21) DM DM  Address 0008 0108 100 200 0009 0109 100 200 0010 0110 100 200 0011 0111 100 200 00089 00090 00091 00092 00093 00094 00095 00096 00097 00098 00099 00100 Instruction Operands LD AND MOV(21) 0012 0112 DM DM 100 200 0013 0113 DM DM 100 200 0014 0114 DM DM 100 200 0015 0115 DM DM 100 200 LD AND MOV(21) LD AND MOV(21) LD AND MOV(21)      5--3--2 Section 5--3 Four-word Operation The following example is for four-word operation. We will be using the C500 in this example. The following table shows the allocations of the IR words allocated to the Analog Input Module. IR Allocations During four-word operation, data is transferred between the Module and PLC according to the settings of these control bits and flags. Bit Output IR 00 Input IR 01 IR 02 IR 03 00 Point 1 Control Bit Point 1 Read Flag 01 Point 2 Control Bit Point 2 Read Flag 02 Point 3 Control Bit Point 3 Read Flag 03 Point 4 Control Bit Point 4 Read Flag 04 Point 5 Control Bit Point 5 Read Flag 05 Point 6 Control Bit Point 6 Read Flag 06 Writing data Point 7 Control Bit Reading data Point 7 Read Flag 07 Point 8 Control Bit Point 8 Read Flag 08 Normal/Peak Control Bit Disconnection Flag 09 10 Normal/Peak Flag Not used. 11 Not used. 12 Peak Reset Bit 13 A/D Conversion Bit 14 PC Write Completed Bit A/D Read Completed Flag 15 PC Read Completed Bit A/D Write Completed Flag DM Area Allocation Not used. The following table shows the bits used to store the various data resulting from the binary-converted analog input values. Input point Mean value (sampling count) Converted data (normal) Converted data (peak value) 1 DM 000 0000 DM 100 DM 200 2 DM 001 0000 DM 101 DM 201 3 DM 002 0000 DM 102 DM 202 4 DM 003 0000 DM 103 DM 203 5 DM 004 0005 DM 104 DM 204 6 DM 005 0010 DM 105 DM 205 7 DM 006 0020 DM 106 DM 206 8 DM 007 0050 DM 107 DM 207       Section 5--3 Program Using Only Point 1 The following program is used when only one of the input points is used. 3201 0314 MOV(21) A/D Read Completed Flag #0000 00 If you are not using mean, set the number of samples to 0 or delete this part of the program. First Scan Flag 6115 3201 3201 3200 0113 Starts A/D conversion. 0108 Turned ON for normal value and OFF for peak value. 0100 Specifies the point. 0114 Indicates PC write is complete. 3200 3201 A/D Read 0314 Completed Flag 3201 TR 1 0300 0315 0309 0308 MOV(21) Designates point 1. A/D Write Completed Flag Disconnection detect flag Normal value 02 Transfers normal value. DM 100 0309 MOV(21) 02 Peak value Transfers peak value. DM 200 0115 3300 0112 3301 3200 Address 00000 00001 00002 00003 Instruction Operands LD NOT AND OR MOV(21) 0314 3201 6115 # 00004 00005 00006 00007 00008 00009 00010 00011 00012 00013 00014 00015  OUT LD NOT AND NOT OUT LD NOT OR OUT LD NOT OR OUT OUT LD 0000 00 3201 3200 3201 0113 3200 3201 0108 0314 3201 0100 0114 0300 Indicates PC read is complete. Turned ON to reset peak value. This bit turns ON to turn OFF IR 0113, the A/D Conversion Bit when the peak value has been read. Address Instruction 00016 00017 00018 00019 00020 AND AND NOT OUT AND MOV(21) 00021 00022 00023 LD AND NOT MOV(21) Operands TR DM TR DM 00024 00025 00026 00027 00028 OUT LD OUT LD OUT 0315 0308 1 0309 02 100 1 0309 02 200 0115 3300 0112 3301 3200      Program Using All 8 Points Section 5--3 The following program can be used when all eight input points are being used. First Scan Flag 6115 MOV(21) #0000 Input point 1 DM 000 MOV21 #0000 Input point 2 DM 001 MOV(21) #0000 If you are not using mean values, set to #0000. See Note 1. Input point 3 DM 002 MOV(21) #0000 Input point 4 Initial parameter setting DM 003 MOV(21) #0005 Input point 5 DM 004 MOV(21) #0010 Input point 6 DM 005 Set the mean data (number of samples.) See Note 2. MOV(21) #0020 Input point 7 DM 006 MOV(21) #0050 Input point 8 DM 007 First Scan Flag 6115 MOV(21) #0001 32 Always OFF Flag 6114 IN Bits 3201 through 3208 are shifted to move consecutive parameters to the output word. SFT(10) 0314 3208 CP Sets the initial value of the shift register. This will be used for writing data consecutively through the output word. 32 ON 6114 R (Continued on next page.) 0314 32 OFF The bits are shifted when bit 0314 goes from OFF to ON. Note 1. When mean is not used, no setting is necessary. The above example includes settings for all points to allow for easy modification. 2. Mean processing starts after the points are specified, It takes 10 ms x (number of samples) for the data to be output.       Section 5--3 (Continued from previous page) 3200 MOV(21) DM 000 00 3201 MOV(21) DM 001 00 3202 MOV(21) DM 002 00 3203 MOV(21) DM 003 00 Bit 3209 turns OFF after 8 parameters are written sequentially output to the Module.. 3204 MOV(21) DM 004 00 3205 MOV(21) DM 005 00 3206 MOV(21) DM 006 00 3207 MOV(21) DM 007 00 3300 3301 0108 3208 3301 0113 DIFU(13) ON for 1 scan Turns ON for normal values and OFF for peak values. A/D conversion starts. Bit 3208 turns ON after data writing is complete. 3209 3209 MOV(21) #0001 3408 Sets the initial value of the shift register. This will be used for reading data. 34 Always OFF Flag 6114 IN The specified bits are shifted sequentially. Bit 0315 is the A/D Write Completed Flag. SFT(10) 0315 3208 CP 34 6114 ON R 34 0315 OFF (Continued on next page.)  The bits are shifted when bit 0315 goes from OFF to ON.      3400 0101 0102 0103 Section 5--3 0104 0105 0106 0107 0100 3200 3401 0100 0102 0103 0104 0105 0106 0107 0101 3201 3402 0100 0101 0103 0104 0105 0106 0107 0102 3202 3403 0100 0101 0102 0104 0105 0106 0107 0103 Specify the points to be read. These are set up so that only one of the operand of these OUT’s is ON at the same time. 3203 3404 0100 0101 0102 0103 0105 0106 0107 0104 3204 3405 0100 0101 0102 0103 0104 0106 0107 0105 3205 3406 0100 0101 0102 0103 0104 0105 0107 0106 3206 3407 0100 0101 0102 0103 0104 0105 0106 0107 3207 (Continued on next page)       Section 5--3 (From previous page.) 0100 0314 0114 PC write is complete.This bit is turned ON when the point to be used is specified. 0101 0102 0103 0104 0105 0106 0107 0300 0315 0308 0309 0108 MOV(21) 02 DM 100 0309 Input point 1 Normal 0108 MOV(21) 02 Peak value DM 200 0301 0315 0308 0309 0108 MOV(21) 02 Input point 2 Normal Data moved to storage locations. DM 101 0309 0108 MOV(21) 02 Peak value DM 201 0302 0315 0308 0309 0108 MOV(21) 02 Input point 3 Normal DM 102 0309 0108 MOV(21) 02 Peak value DM 202 0303 0315 0308 0309 0108 MOV(21) 02 Input point 4 Normal DM 103 0309 0108 MOV(21) (Continued on next page.) 02 DM 203  Peak value IR 0300 through IR 0307 specify input data setting for points 1 through 8. IR 0315 is the A/D Write Completed Flag. IR 0308 is the Disconnection Flag. IR 0309 is the Normal/Peak Flag (usually used with IR 0108).      Section 5--3 (From previous page.) 0304 0315 0308 0309 0108 MOV(21) 02 DM 104 0309 Input point 5 Normal 0108 MOV(21) 02 Peak value DM 204 0305 0315 0308 0309 0108 MOV(21) 02 Input point 6 Normal DM 105 0309 0108 MOV(21) 02 Peak value DM 205 0306 0315 0308 0309 Data moved 0108 MOV(21) 02 Input point 7 Normal DM 106 0309 (continued from previous page). 0108 MOV(21) 02 Peak value DM 206 0307 0315 0308 0309 0108 MOV(21) 02 Input point 8 Normal DM 107 0309 0108 MOV(21) 02 Peak value DM 207 0315 3501 3500 0115 IR 0115, the PC Read Completed Flag, turns ON when IR 0315, the A/D Read Completed Flag, turns ON. 0112 Turns ON when a peak value is reset. IR 0144 is the PC Write Completed Flag See Note 1. 3301 Turns ON when a peak value is being read (any bit can be used). See Note 2. 0114 0114 Note 1. The peak value is reset when the Peak Reset Flag turns OFF. 2. The peak value is held while the Peak Flag is ON. IR 0114 initiates the reading of new peak values while IR 3501 is ON.       Address 00000 00001 00002 00003 00004 00005 00006 00007 00008 00009 00010 00011 00012 00013 00014 00015 00016 00017 00018 00019 00020 00021 00022 00023 00024 00025 Section 5--3 Instruction Operands LD MOV(21) Address 6115 # DM 0000 000 # DM 0000 001 # DM 0000 002 # DM 0000 0003 # DM 0005 004 # DM 0010 005 # DM 0020 006 # DM 0050 007 6115 # 0001 32 6114 0314 3208 6114 MOV(21) 00026 00027 00028 00029 Instruction Operands LD MOV(21) 3205 DM 005 00 3206 DM 006 00 3207 DM 007 00 3300 3301 0108 3208 3301 0113 3209 3209 3408 # 0001 34 6114 0315 3208 6114 LD MOV(21) MOV(21) 00030 00031 LD MOV(21) MOV(21) MOV(21) MOV(21) MOV(21) 00032 00033 00034 00035 00036 00037 00038 00039 00040 00041 LD NOT AND NOT OUT LD AND NOT OUT DIFU(13) LD OR MOV(21) MOV(21) LD MOV(21) LD LD AND NOT LD SFT(10) 32 32 3200 LD MOV(21) DM 000 00 3201 DM 001 00 3202 DM 002 00 3203 DM 003 00 3204 DM 004 00 LD MOV(21) LD MOV(21) LD MOV(21) LD MOV(21) 00042 00043 00044 00045 00046 00047 00048 00049 00050 00051 00052 00053 00054 00055 00056 00057 00058 00059 00060 00061 00062 00063 00064 00065 00066 00067 00068 00069 00070 00071 LD LD NOT AND LD SFT(10) LD OR AND NOT AND NOT AND NOT AND NOT AND NOT AND NOT AND NOT OUT LD OR AND NOT AND NOT AND NOT AND NOT AND NOT AND NOT AND NOT OUT LD OR AND NOT AND NOT AND NOT 34 34 3400 3200 0101 0102 0103 0104 0105 0106 0107 0100 3401 3201 0100 0102 0103 0104 0105 0106 0107 0101 3402 3202 0100 0101 0103 (Continued on next page.)       Address Instruction 00072 00073 00074 00075 00076 00077 00078 00079 00080 00081 00082 00083 00084 00085 00086 00087 00088 00089 00090 00091 00092 00093 00094 00095 00096 00097 00098 00099 00100 00101 00102 00103 00104 00105 00106 00107 00108 00109 00110 00111 00112 00113 00114 00115 00116 00117 00118 00119 00120 00121 00122 00123 00124 00125 00126 00127 AND NOT AND NOT AND NOT AND NOT OUT LD OR AND NOT AND NOT AND NOT AND NOT AND NOT AND NOT AND NOT OUT LD OR AND NOT AND NOT AND NOT AND NOT AND NOT AND NOT AND NOT OUT LD OR AND NOT AND NOT AND NOT AND NOT AND NOT AND NOT AND NOT OUT LD OR AND NOT AND NOT AND NOT AND NOT AND NOT AND NOT AND NOT OUT LD OR AND NOT AND NOT AND NOT AND NOT AND NOT AND NOT AND NOT LD OR Section 5--3 Operands 0104 0105 0106 0107 0102 3403 3203 0100 0101 0102 0104 0105 0106 0107 0103 3404 3204 0100 0101 0102 0103 0105 0106 0107 0104 3405 3205 0100 0101 0102 0103 0104 0106 0107 0105 3406 3206 0100 0101 0102 0103 0104 0105 0107 0106 3407 3207 0100 0101 0102 0103 0104 0105 0106 0100 0101 Address Instruction 00128 00129 00130 00131 00132 00133 00134 00135 00136 00137 00138 00139 00140 00141 00142 OR OR OR OR OR OR AND NOT OUT LD AND AND NOT OUT AND AND MOV(21) 00143 00144 00145 00146 LD AND NOT AND NOT MOV(21) Operands TR DM TR DM 00148 00149 00150 00151 00152 00153 00154 00155 00156 00157 00158 LD AND AND NOT OUT AND AND MOV(21) LD AND NOT AND NOT MOV(21) TR DM TR DM 00159 00160 00161 00162 00163 00164 00165 00166 00167 00168 00169 LD AND AND NOT OUT AND AND MOV(21) LD AND NOT AND NOT MOV(21) TR DM TR DM 00170 00171 LD AND 0102 0103 0104 0105 0106 0107 0314 0114 0300 0315 0308 1 0309 0108 02 100 1 0309 0108 02 200 0301 0315 0308 1 0309 0108 02 101 1 0309 0108 02 201 0302 0315 0308 1 0309 0108 02 102 1 0309 0108 02 202 0303 0315 (Continued on next page.)       Address Instruction 00172 00173 00174 00175 00176 AND NOT OUT AND AND MOV(21) 00177 00178 00179 00180 LD AND NOT AND NOT MOV(21) Section 5--3 Operands TR DM TR DM 00181 00182 00183 00184 00185 00186 00187 00188 00189 00190 00191 LD AND AND NOT OUT AND AND MOV(21) LD AND NOT AND NOT MOV(21) TR DM TR DM 00192 00193 00194 00195 00196 00197 00198 00199 00200 00201 00202  LD AND AND NOT OUT AND AND MOV(21) LD AND NOT AND NOT MOV(21) TR DM TR 0308 1 0309 0108 02 103 1 0309 0108 02 203 0304 0315 0308 1 0309 0108 02 104 1 0309 0108 02 204 0305 0315 0308 1 0309 0108 02 105 1 0309 0108 Address Instruction Operands 02 DM 00203 00204 00205 00206 00207 00208 00209 00210 00211 00212 00213 LD AND AND NOT OUT AND AND MOV(21) LD AND NOT AND NOT MOV(21) TR DM TR DM 00214 00215 00216 00217 00218 00219 00220 00221 00222 00223 00224 LD AND AND NOT OUT AND AND MOV(21) LD AND NOT AND NOT MOV(21) TR DM TR DM 00225 00226 00227 00228 00229 00230 00231 00232 LD OUT LD AND OUT LD AND OUT 205 0306 0315 0308 1 0309 0108 02 106 1 0309 0108 02 206 0307 0315 0308 1 0309 0108 02 107 1 0309 0108 02 207 0315 0115 3501 0114 0112 3500 0114 3301           5--4 Section 5--4 DA001 through DA005 Analog Output Modules All that is necessary in programming these Modules is to move a binary value (up to 4095) to the word allocated to the desired output point. The following example coverts BCD input from outside the PLC to binary and places the results in the proper output words for unipolar outputs. The words allocated to each Module are shown above the Module. The program, written for a C500, is shown on the following page. IR 01 X100 X101 X102 X103 20 21 22 23 20 21 22 23 20 21 22 23 20 21 22 23 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 00 01 02 03 04 05 06 07 IR 02 X100 X101 20 21 22 23 20 21 22 23 COM 08 09 10 11 12 13 14 15 X102 X103 COM Input Module 20 21 22 23 20 21 22 23 IR 03 Input data 1 read timing 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 00 01 02 03 04 05 06 07 COM 08 09 10 11 12 13 14 15 COM 0 1 Input data 1 2 read timing 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 Input Module 00 01 02 03 04 05 06 07 COM 08 09 10 11 12 13 14 15 COM Input Module IR 05 IR 06 IR 04 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 00 01 02 03 04 05 06 07 Input data 1 not convertible Input data 1 not convertible Input data 1 analog output COM 08 09 10 11 12 13 14 15 Input data 1 analog output COM Output Module Analog Output Module            Address TR 1 0300 CMP(20) Input data 1 read condition Section 5--4 01 Compares input 1 data with 4096. 00000 00001 00002 Instruction LD OUT CMP(20) Operands TR 4096 01 4096 6307 6307 (LE) BID(23) 01 05 Converts input 1 data to 12-bit binary and transfers it to the Analog Output Module. 6306 (EQ) 0400 Indicates input 1 data is not convertible. 6305 (GR) 0400 6303 (ER) 00003 00004 00005 00006 00007 00008 00009 00010 00011 00012 00013 AND BIN(23) LD AND OR OR OR OUT LD OUT CMP(20) TR TR (See note.) 00014 00015 AND BIN(23) 0301 CMP(20) 02 Compares input 2 data with 4096. 4096 6307 (LE) BIN(23) 02 06 Converts input 2 data to 12-bit binary and transfers it to the Analog Output Module. 6306 (EQ) 0401 Indicates input 2 data is not convertible. 6305 (GR) 0401 6303 (ER)  Note The error flag turns on if the input data is not in BCD form. 00016 00017 00018 00019 00020 00021 LD AND OR OR OR OUT 01 05 1 6306 6305 0400 6303 0400 0301 1 02 4096 6307 TR 1 Input data 2 read condition 0300 1 TR 02 06 1 6306 6305 0401 6303 0401       5--5 Section 5--5 DA101 Analog Output Modules All that is necessary in programming this Modules is to move a binary value (up to 4095) to the word allocated to the desired output point. The following program, written for the C500, transfer data between the PLC and Analog Output Module. The conversion data is stored in DM 100. The Module will uses IR 10 through IR 13. Only the programming for point 1 (IR 10) is shown. The programming for the rest of the points follows the same logic. Program for BCD Data TR 1 0000 CMP(20) Output condition DM 100 Compares the content of DM 100 with 4096. #4096 6307 () 3000 If the data is not greater than 0FFF, the data is transferred to the Module. If the data is not convertible, IR 3000 is turned ON. 6303 (ER) 3000 Address 00000 00001 00002 Instruction LD OUT CMP(20) Operands TR DM # 00003  AND NOT Address Instruction 0001 1 00004 MOV(21) 100 0FFF 6305 00005 00006 00007 00008 00009 Operands DM LD AND OR OR OUT TR 100 10 1 6305 6303 3000 3000 Appendix A Standard Models Analog Input Modules PLC C120 Specifications Model 1 to 5 V, 4 to 20 mA 3G2A6-AD006 0 to 10 V 3G2A6-AD007 C500 0 to 10 V, 0 to 20 mA (adjustable) C500-AD101 C1000H 1 to 5 V, 4 to 20 mA 3G2A5-AD001 C2000H 0 to 10 V 3G2A5-AD002 0 to 5 V 3G2A5-AD003 --10 to 10 V 3G2A5-AD004 --5 to 5 V 3G2A5-AD005 1 to 5 V, 4 to 20 mA 3G2A5-AD006 0 to 10 V 3G2A5-AD007 Analog Output Modules PLC C120 Specifications Model 1 to 5 V, 4 to 20 mA 3G2A6-DA001 0 to 10 V 3G2A6-DA002 0 to 5 V 3G2A6-DA003 --10 to 10 V 3G2A6-DA004 --5 to 5 V 3G2A6-DA005 C500 0 to 10 V, 1 to 5 V, 4 to 20 mA C500-DA101 C1000H 1 to 5 V, 4 to 20 mA 3G2A5-DA001 C2000H 0 to 10 V 3G2A5-DA002 0 to 5 V 3G2A5-DA003 --10 to 10 V 3G2A5-DA004 --5 to 5 V 3G2A5-DA005 Expansion I/O Racks (For connecting Analog I/O Modules to the C120) Power supply Model 100 VAC 3G2C4-SI025 200 VAC 3G2C4-SI026     Appendix A Appendix B Specifications AD001 through AD005 Analog Input Modules All general specifications of the AD001 through AD005 conform to those of the C Series except the following: • Insulation resistance between the external terminals and the frame: 5 MΩ min. (at 250 VDC) • Dielectric strength between the external terminals and the frame: 500 VAC, 50/60 Hz for 1 minute Number of analog inputs 2 Input signal range (See Note 1.) Voltage inputs 1 to 5 V (AD001) 0 to 10 V (AD002) 0 to 5 V (AD003) --10 to 10 V (AD004) --5 to 5 V (AD005) Current inputs  min. Current input: 250  4 to 20 mA (AD001) Input impedance Voltage input:: 1 M Resolution 1/4095 (full scale) PLC signal 12-bit binary (for bipolar outputs, 11-bit binary + 1 sign bit.) Linearity error Accuracy temperature coefficient ±0.1% max. ±0.2% max. (full scale at 25°C) ±100 PPM/°C (full scale) Conversion time 2.5 ms max./port Conversion cycle 5 ms max. Max. PLC write delay (See Note 2.) 1s Conversion method Sequential comparison Max. input signal Voltage input: ±15 V Accuracy Current input: ±60 mA External connections Terminal block (not removable) Power consumption 500 mA max. at 5 VDC Weight 600 g max. Note The PC write delay is the time required for a change in the input signal to be converted and transferred to the PLC bus. Analog input 0 Time Conversion cycle A filter inside the Module causes the digital signal to increase in a stepwise fashion. Digital output (to PLC) 0000 PC write delay Time     Appendix B AD006 and AD007 Analog Input Modules All general specifications of the AD006 and AD007 Analog Input Modules conform to those of the C Series except the following: • Insulation resistance between the external terminals and the frame: 5 MΩ min. (at 250 VDC) • Dielectric strength between the external terminals and the frame: 500 VAC, 50/60 Hz for 1 minute Number of analog inputs 4 Input signal range (See Note 1.) Voltage inputs 0 to 10 V (AD007) 1 to 5 V (AD006) Current inputs 4 to 20 mA (AD006)  min. Current input: 250  Input impedance Voltage input:: 1 M Resolution 1/1023 (full scale) PLC signal 10-bit binary Linearity error Accuracy temperature coefficient ±0.2% max. ±0.2% max. (full scale at 25°C) ±150 PPM/°C (full scale) Conversion time 2.5 ms max./port Conversion cycle 10 ms max. Max. PC write delay (See Note 2.) 1s Conversion method Sequential comparison Max. input signal Voltage input: ±15 V Accuracy Current input: ±60 mA External connections Terminal block (not removable) Power consumption 750 mA max. at 5 VDC Weight 650 g max. Note The PC write delay is the time required for a change in the input signal to be converted and transferred to the PLC bus. Analog input 0 Conversion cycle A filter inside the Module causes the digital signal to increase in a stepwise fashion. Digital output (to PLC) 0000 PC write delay Time     Appendix B AD101 Analog Input Module All general specifications of the AD101 Analog Input Module conform to those of the C Series. Number of analog inputs 8 Input signal range Voltage inputs: 0 to 10 VDC (adjustable) Current inputs: 0 to 20 mA (adjustable) Resolution (See Note 1.) 1/4096 max. Accuracy 25°C 0 to 55°C ±0.5% (full scale, including linearity error) ±1.0% (full scale, including linearity error) Conversion time (See Note 2.) 10 ms max./port Input impedance Voltage input 1M Current input 250 Voltage ±15 V ±30 mA Max. input signal Current  min.  PLC signal 12-bit binary Number of words 32 or 64 (selectable) External connections 30-pin terminal block (not removable) Isolation Between input terminals and PLC: photocoupler Between input terminals and Module: none Power consumption 880 mA max. at 5 VDC Dimensions 34.5 (W) x 250 (H) x 120 (D) mm Weight 700 g max. Note 1. This is the resolution when the difference between offset and gain is at least 4 V (16 mA). The resolution is less for smaller ranges (e.g., if the difference is 2 V, the resolution is 1/2048). 2. This is the conversion time when the signal changes from one end of the range to the other. The smaller the signal change, the shorter the conversion time.     Appendix B DA001 through DA005 Analog Output Modules All general specifications of the DA001 through AD005 Analog Output Modules conform to those of the C Series except the following: • Insulation resistance between the external terminals and the frame: 5 MΩ min. (at 250 VDC) • Dielectric strength between the external terminals and the frame: 500 VAC, 50/60 Hz for 1 minute Number of analog outputs 2 1 to 5 V (DA001) 0 to 10 V (DA002) Output signal range Voltage outputs 0 to 5 V (DA003) --10 to 10 V (DA004) --5 to 5 V (DA005) Current outputs  4 to 20 mA (DA001) Max. output impedance Voltage output:: 0.5 Max. output current Voltage output: 15 mA Max. load resistance Current output: 550 Resolution 1/4095 (full scale) PLC signal 12-bit binary (for bipolar outputs, 11-bit binary + 1 sign bit.) Linearity error Accuracy temperature coefficient ±1/2 LSB max. (at 25°C) ±0.2% max. (full scale, at 25°C) ±50 PPM/°C Conversion time 5 ms max. Conversion cycle PLC program scan time External connections Terminal block (not removable) Power consumption 550 mA max. at 5 VDC Weight 600 g max. Accuracy      Appendix B DA101 Analog Output Module All general specifications of the DA101 Analog Output Module conform to those of the C Series. Number of analog outputs 4 Output signal range Voltage outputs 1 to 5 V 0 to 10 V Current outputs Resolution 1/4096 Accuracy 25°C 4 to 20 mA ±0.5% max. (full scale, including linearity error) ±1.0% max. (full scale, including linearity error) 0 to 55°C Conversion time (See Note.) 10 ms max. Max. output impedance Voltage output: 0.5 Max. output current Voltage output: 10 mA Max. load resistance Current output: 400 PLC signal 12-bit binary Number of words 64 External connections 17-pin terminal block (not removable) Isolation Between output terminals and PLC: photocoupler   Between output terminals and Module: none Power consumption 1.3 A max. 5 VDC Dimensions 34.5 (W) x 250 (H) x 113 (D) mm Weight 650 g max. Note This is the conversion time when the signal changes from one end of the range to the other. The smaller the signal change, the shorter the conversion time.      Appendix B Index A AD001 -- AD005 Analog Input Modules A/D conversion, 28 block diagram, 28 dimensions, 12 IR bit allocations, 29 programming, 48 specifications, 75 wiring, 13 word allocations, 4 AD006 -- AD007 Analog Input Modules A/D conversion, 30 block diagram, 30 dimensions, 15 IR bit allocations, 31 programming, 50 specifications, 76 wiring, 16 word allocations, 4 AD101 Analog Input Modules, 6 block diagram, 32 data reading area, 38 Intelligent I/O Write, 35 PLC communications, 34 specifications, 77 word allocations, 4 word setting, 6 A/D conversion, 32 data writing area, 36 dimensions, 18 four-word operation, 39, 59 input and conversion, 33 input ranges, 6 Intelligent I/O Read, 38 operation mode, 6 operational flow, 33 peak read bit, 35 peak reset bit, 35 programming, 52 two-word operation, 33, 52 unconfirmed data, 35 wiring, 18 B basic configuration, 2 C configuration examples, 3 D DA001 -- DA005 Analog Output Modules bipolar output, 42 block diagram, 41 D/A conversion, 41 dimensions, 21 IR bit allocations, 43 programming, 69 specifications, 78 unipolar output, 41 wiring, 22 word allocations, 4 DA101 Analog Output Modules, 9 block diagram, 44 conversion and output, 44 dimensions, 24 DIP switches, 9 IR bit allocations, 46 operational overflow, 45 program for BCD data, 71 program for binary data, 72 programming, 71 specifications, 79 unipolar output, 41 wiring, 24 word allocations, 4 S Standard Models Analog Input Modules, 73 Analog Output Modules, 73 Expansion I/O Racks, 73 system configuration basic, 2 samples, 3 W wiring AD101 Analog Input Modules, 18 DA001 -- DA005 Analog Output Modules, 22 AD001 -- AD005 Analog Input Modules, 13 AD006 -- AD007 Analog Input Modules, 16 DA101 Analog Output Modules, 24 word allocations, 3 81    Revision History C120/C500/C1000H/C2000H Analog I/O Modules A manual revision code appears as a suffix to the catalog number on the front cover of the manual. Cat. No. W121-E3-1 Revision code The following table outlines the changes made to the manual during each revision. Page numbers refer to the previous version. Revision code Date Revised content E1-3 June 1991 AD001 through AD005 added. TR bits and mnemonic code added to programs. Page 6: CPU model numbers corrected in caution. Page 30 : Bottom model number corrected and dimension changed from 100 to 103 in bottom graphic. Pages 32, 34: “kW” corrected to “k .” Page 35: Model numbers corrected in headings. Page 41: Operand corrected in third ANDW(34). Page 44: “61115” corrected to “6115” and operand in first MOV(21) corrected. Page 45: Instruction names and function codes corrected. Page 56: Function code corrected for BID and operand corrected in bottom OUT. Page 59: PC--Analog I/O Unit applicability corrected.  E3-1 June 1996 Major Revision for Section 3. Wiring drawings were updated for accuracy.  OMRON ELECTRONICS LLC 1 Commerce Drive Schaumburg, IL 60173 847.843.7900 For US technical support or other inquiries: 800.556.6766 OMRON CANADA, INC. 885 Milner Avenue Toronto, Ontario M1B 5V8 416.286.6465 OMRON ON-LINE Global - http://www.omron.com USA - http://www.omron.com/oei Canada - http://www.omron.ca W121-E3-1 OMRON ELECTRONICS LLC Printed in the U.S.A. Specifications subject to change without notice.
3G2A5-AD005 价格&库存

很抱歉,暂时无法提供与“3G2A5-AD005”相匹配的价格&库存,您可以联系我们找货

免费人工找货