Emergency Stop Switch
A22E
Install in 22-dia. or 25-dia.
Panel Cutout
• Direct opening mechanism with minimum
contact separation of 3 mm in accordance with
EN60947-5-1, Æ . (only for NC contacts)
• Safety lock mechanism prevents misuse.
(No tampering – in accordance with EN 418)
• Easy mounting and removal of Switch Blocks
using an incorporated lever.
• Finger protection mechanism on Switch Unit
provided as a standard feature.
• Install using either round, forked crimp terminals,
or ferrules.
For additional installation of emergency-stop switches.
A22Z-3466-1
Emergency-stop switches can be
installed easily far from machines.
A22E-#-#
A22E
A22Z-B101Y
Control Box
A22E
G-303
Model Number Structure
Model Number Legend
Completely Assembled
Shipped as a set which includes the Pushbutton, Lamp (lighted models only), and Switch.
1
2
3
4
A22E#-#-#-#
3 Light Source
1 Lighted/Non-lighted
Code
Description
4 Contacts
Without Voltage Reduction Unit
Code
None Non-lighted
Code
01
SPST-NC
L
None Non-lighted
11
SPST-NO + SPST-NC
6D
02
DPST-NC
Lighted (see note)
Note: Lighted Emergency Stop
Switches are available
only for the 40-dia. pushlock turn-reset models.
Description
MP
40 dia.
LP
60 dia.
S
30 dia.
M
40 dia.
L
60 dia.
SK
30 dia.
MK
40 dia.
LED
6 VDC
6A
6 VAC
12A
12 VAC/VDC
24A
24 VAC/VDC
With Voltage Reduction Unit
2 Head Size
Code
Operating Voltage
Description
None Non-lighted
T1
Push-pull
LED
T2
Push-lock, turn-reset
Push-lock key reset
110 VAC*1
220 VAC*2
Note: The LED lamp (24 VAC/VDC) can be
lit by directly applying 110 VAC/VDC
(220 VAC/VDC) to the lamp terminal.
LED incorporates the 24-VAC/VDC
models.
*1) Operational voltage: 95 to 110 VAC
*2) Operational voltage: 190 to 230 VAC
Subassembled
The Pushbutton, Lamp, or Switch can be ordered separately. Use them in combination for models that are not available as assembled Units. These
can also be used as inventory for maintenance parts.
Unit Combinations
Non-lighted
Lighted
(without Voltage
Reduction Unit)
Pushbutton
Pushbutton
Switch
Lamp
Switch (without Voltage Reduction Unit)
∑ LED
∑ Incandescent
Lighted
(with Voltage
Reduction Unit)
Pushbutton
Lamp
Switch (with Voltage Reduction Unit)
∑ LED
G-304
Safety Sensors / Components
1. Pushbutton
Lighted/Non-lighted
1
2
A22E#-#
1 Lighted/Non-lighted
Code
2 Head Size
Description
Code
None Non-lighted
Lighted (see note)
L
Note: Lighted Emergency Stop
Switches are available
only for the 40-dia. pushlock turn-reset models.
Description
MP
40 dia.
LP
60 dia.
S
30 dia.
M
40 dia.
L
60 dia.
SK
30 dia.
MK
40 dia.
Push-pull
Push-lock, turn-reset
Push-lock key reset
2. Lamp
1 2
A22-##
1 Operating Voltage (Rated Voltage)
2 Illumination Color
Code
Incandescent
Code
LED
R
6D
6 VDC (6 VDC)
6A
6 VAC (6 VAC)
12A
12 VAC/VDC (12 VAC/VDC)
24A
24 VAC/VDC (24 VAC/VDC)
Description
Red
3. Switch
Lighted/Non-lighted
1
2
3
A22#-#M-#
1 Lighted/Non-lighted
Code
Description
None Non-lighted
L
Lighted
2 Contacts
Code
3 Voltage Reduction Unit (Lighted Models Only)
Description
Code
Description
01
SPST-NC
11
SPST-NO + SPST-NC
T1
110 VAC*1
02
DPST-NC
T2
220 VAC*2
None
Without Voltage Reduction Unit
A22E
*1) Operational voltage: 95 to 110 VAC
*2) Operational voltage: 190 to 230 VAC
A22E
G-305
Ordering Information
List of Models
Completely Assembled (Ask your local OMRON representative)
Non-lighted Models
Appearance
Push-lock
turn-reset system
Output
40-dia. head
Push-pull
A22E-MP
60-dia. head
Push-pull
A22E-LP
30-dia. head
Push-lock
Turn-reset
A22E-S
40-dia. head
Push-lock
Turn-reset
A22E-M
60-dia. head
Push-lock
Turn-reset
A22E-L
30-dia. head
Push-lock
Key-reset
A22E-SK
40-dia. head
Push-lock
Key-reset
A22E-MK
SPST-NC
A22E-MP-01
SPST-NO/SPST-NC
A22E-MP-11
DPST-NC
A22E-MP-02
SPST-NC
A22E-LP-01
SPST-NO/SPST-NC
A22E-LP-11
DPST-NC
A22E-LP-02
SPST-NC
A22E-S-01
SPST-NO/SPST-NC
A22E-S-11
DPST-NC
A22E-S-02
SPST-NC
A22E-M-01
SPST-NO/SPST-NC
A22E-M-11
DPST-NC
A22E-M-02
SPST-NC
A22E-L-01
SPST-NO/SPST-NC
A22E-L-11
DPST-NC
A22E-L-02
SPST-NC
A22E-SK-01
SPST-NO/SPST-NC
A22E-SK-11
DPST-NC
A22E-SK-02
SPST-NC
A22E-MK-01
SPST-NO/SPST-NC
A22E-MK-11
DPST-NC
A22E-MK-02
Color of cap
Red
Lighted Models
Appearance
40-dia. head
Push-lock
Turn-reset
Output
Lighting
SPST-NC
SPST-NO/SPST-NC
LED
DPST-NC
40-dia. head
Push-lock
Turn-reset with Voltage
Reduction Unit
SPST-NC
SPST-NO/SPST-NC
DPST-NC
G-306
6 VDC
6 VAC
12 VAC/VDC
24 VAC/VDC
6 VDC
6 VAC
12 VAC/VDC
24 VAC/VDC
6 VDC
6 VAC
12 VAC/VDC
24 VAC/VDC
Push-lock turn-reColor of cap
set system
A22EL-M-6D-01
A22EL-M-6A-01
A22EL-M-12A-01
A22EL-M-24A-01
A22EL-M-6D-11
A22EL-M-6A-11
A22EL-M-12A-11
A22EL-M-24A-11
A22EL-M-6D-02
Red
A22EL-M-6A-02
A22EL-M-12A-02
A22EL-M-24A-02
110 VAC
A22EL-M-T1-01
220 VAC
A22EL-M-T2-01
110 VAC
A22EL-M-T1-11
220 VAC
A22EL-M-T2-11
110 VAC
A22EL-M-T1-02
220 VAC
A22EL-M-T2-02
Rated voltage
Safety Sensors / Components
Subassembled
Pushbuttons
Non-lighted
Sealing capability and size
IP65 oil-resistant models
Medium (40 dia.)
Small (30 dia.)
Push-pull
Large (60 dia.)
A22E-MP
A22E-LP
A22E-S
A22E-M
A22E-L
A22E-SK
A22E-MK
---
---
Push-lock, Turn-reset
Push-lock, key-reset
Lighted
IP65
Medium (40 dia.)
Sealing capability and size
A22EL-M
Push-lock, Turn-reset
Lamp
LED
Rated voltage
6 VDC
LED light
Red
6 VAC
A22-6DR
A22-6AR
12 VAC/VDC
A22-12AR
Super-bright
24 VAC/VDC
24 VAC/VDC
A22-24AR
A22-24ASR
Note: For voltage-reduction lighting, use the A22-24AR.
Incandescent
Rated voltage
6 VAC
A22-12
28 VAC
A22-24
130 VAC
A22-H1
A22E
A22-5
14 VAC
A22E
G-307
Switch (Standard Load)
Without Voltage Reduction Unit
Classification
Non-lighted
Lighted
Appearance
Switch Action
Momentary
Contacts
For standard loads
SPST-NO
SPST-NC
SPST-NO + SPSTNC
DPST-NO
DPST-NC
Momentary
A22-10M
A22-01M
A22L-10M
A22L-01M
A22-11M
A22L-11M
A22-20M
A22-02M
A22L-20M
A22L-02M
Lighted (110 VAC)
Lighted (220 VAC)
With Voltage Reduction Unit
Classification
Appearance
Switch Action
Momentary
Contacts
For standard loads
SPST-NO
SPST-NC
SPST-NO + SPSTNC
DPST-NO
DPST-NC
Momentary
A22L-10M-T1
A22L-01M-T1
A22L-10M-T2
A22L-01M-T2
A22L-11M-T1
A22L-11M-T2
A22L-20M-T1
A22L-02M-T1
A22L-20M-T2
A22L-02M-T2
Note: 1. The above illustrations are for the DPST-NO contact.
2. When using with a Voltage Reduction Unit, use the A22-24AR.
G-308
Safety Sensors / Components
Accessories (Order Separately)
Item
Switch Blocks
Lamp Sockets
Mounting Latches
Appearance
Classification
SPST-NO
Model
A22-10
SPST-NC
A22-01
Direct lighting
110 VAC
Voltagereduction
220 VAC
lighting
For momentary-action
models
A22-TN
A22-T1
A22-T2
A22-3200
For alternate-action models A22-3210
Lock Ring
Rounded shape
A22Z-3360
Hole Plug
Round
A22Z-3530
A22Z-B101
Control Boxes
(Enclosures)
One hole
One hole, yellow box
(for emergency stop)
Two holes
Three holes
Connectors
Applicable ca- 7 to 9 dia.
ble diameter
9 to 11 dia.
(mm)
A22Z-B101Y
Remarks
Provided as standard. Order Switch
Blocks only when adding or replacing
them.
Used when changing the lighting
method.
Provided as standard. Order Mounting
Latches only when mounting Switch
Blocks or Lamp Sockets that are purchased individually.
The body is equipped with a Lock Fitting. This Lock Fitting is used when a
more secure lock feature is required.
Can be plugged into pre-cut panel
holes for future expansion. The color is
black.
Material: Polycarbonate resin
A22Z-B102
A22Z-B103
A22Z-3500-1
A22Z-3500-2
A22Z-R25
Plastic connector used to extend
a cable from the Switch Box.
Can be fit into a 25-dia. hole in the
panel.
Since this is not attached to the main
body, order separately.
25-dia. Ring
–––
Legend Plates for Emergency Stop
60-dia. black letters on yellow back-ground
90-dia. black letters on yellow back-ground
Lamp Extractor
–––
A22Z-3901
Rubber tool used to replace Lamps
easily
Tightening Tool
–––
A22Z-3905
Tool used to tighten nuts from the back
of the panel
---
A22Z-3380
Use to fix the lever on the Switch.
A22Z-3466-1
A22Z-3476-1
“EMERGENCY STOP” is indicated on
the plate.
A22E
Lock Plate
A22E
G-309
Specifications
Approved Standards
Recognized
organization
UL (See note.)
AZCO
Standards
UL508
EN60947-5-1
File No.
E41515
C9805502
Note: UL-approved for CSA C22.2 No. 14 and bears the cR mark.
Approved Standard Ratings
• UL, cUL (File No. E41515)
6 A at 220 V, 10 A at 110 VAC
• EN60947-5-1 (Low Voltage Directive)
Rated current: 10 A; Rated voltage: 220 VAC
LED Indicators without Voltage Reduction Unit
Ratings
Contacts (Standard Load)
Rated
carry
current
10
Rated
voltage
24 VAC
110 VAC
220 VAC
380 VAC
440 VAC
24 VDC
110 VDC
220 VDC
380 VDC
AC15
(inductive load)
10
5
3
2
1
---
Rated current (A)
AC12
DC13
(resistive (inducload)
tive load)
10
10
6
--3
2
1.5
0.5
--0.2
0.1
DC12
(resistive load)
Rated voltage
6 VDC
6 VAC
12 VAC/VDC
24 VAC/VDC
Rated current
60 mA
60 mA
30 mA
15 mA
Operating voltage
6 VDC±5%
6 VAC/VDC±5%
12 VAC/VDC±5%
24 VAC/VDC±5%
Super-bright LED Indicator
Rated voltage
24 VAC/VDC
Rated current
15 mA
Operating voltage
24 VAC/VDC ±5%
Rated current
200 mA
80 mA
40 mA
20 mA
Operating voltage
5 VAC/VDC
12 VAC/VDC
24 VAC/VDC
100 VAC/VDC
---
Incandescent Lamp
10
2
0.6
0.2
Note: 1. Rated current values are determined according to the testing conditions. The above ratings were obtained by conducting tests under the following conditions.
(1) Ambient temperature: 20×±2°C
(2) Ambient humidity: 65±5%
(3) Operating frequency: 20 operations/minute
2. Minimum applicable load: 10 mA at 5 VDC
Rated voltage
6 VAC/VDC
14 VAC/VDC
28 VAC/VDC
130 VAC/VDC
Voltage-reduction Lighting
Rated voltage
110 VAC
220 VAC
Operational voltage
95 to 115 VAC
190 to 230 VAC
Applicable lamp
(BA9S/13# gold)
LED Lamp
(A22-24A#)
Contacts (Microload)
Rated applicable load
50 mA at 5 VDC
(Resistive load)
G-310
Minimum applicable load
1 mA at 5 VDC
Safety Sensors / Components
Characteristics
Item
Allowable operating
frequency
Mechanical
Electrical
Insulation resistance
Dielectric strength
Vibration resistance
Shock resistance
Durability
Mechanical
Malfunction (See note 2.)
Mechanical
Electrical
Ambient temperature
(See note 1.)
Ambient humidity
Degree of protection
Electric shock protection class
PTI (tracking characteristic)
Degree of contamination
Emergency Stop Switches
Non-lighted model: A22E
Lighted model: A22EL
30 operations/minute max.
30 operations/minute max.
100 MΩ min. (at 500 VDC)
2,500 VAC, 50/60 Hz for 1 min between terminals of same polarity
2,500 VAC, 50/60 Hz for 1 min between terminals of different polarity and also
between each terminal and ground
Malfunction (See note 2.): 10 to 55 Hz, 1.5-mm double amplitude
1,000 m/s2
250 m/s2 max.
Momentary operation: 300,000 operations min.
300,000 operations min.
Operating:
Operating:
-20°C to 55°C
-20°C to 70°C
Storage:
Storage: -40°C to 70°C
-40°C to 70°C
Operating: 35% to 85%
IP65
IP65
(oil-resistant)
Class II
175
3 (IEC947-5-1)
Note: 1. With no icing or condensation.
2. Malfunction within 1 ms.
Operating Characteristics (for SPST-NO/SPST-NC)
Item
Total travel force
(TTF) max.
Total travel
(TT)
Releasing force (RF) min.
Emergency Stop Switches
Push-lock turn-reset system
A22E, A22EL
44.1 N
10±1 mm
0.25 N·m max.
(See note.)
A22E
Note: Rotation torque for Emergency Stop Pushbutton.
A22E
G-311
Nomenclature
Pushbutton
Push-lock Turn-reset System
Available Color: Red
Non-lighted
Lighted
Lamp
∑ Light source
LED Lamp
Incandescent Lamp
Switch
∑ Contact Ratings
10 A at 110 VAC (resistive load)
10 A at 24 VDC (resistive load)
∑ Lighting Method
Non-lighted
Lighted (without Voltage Reduction Unit)
Lighted (with Voltage Reduction Unit)
(The above figures are examples of the lighted model.)
Safety Lock Mechanism to Prevent Misuse
Lock position
This Switch can be intentionally used to stop equipment in an emergency. Even if an object or person touches the Pushbutton by mistake, the
contact will not be released unless the Pushbutton reaches the lock position.
This Switch uses a finger protection mechanism to prevent electrical shocks. Moreover, it is
provided with a mechanism to prevent terminal screws from coming off and also allows
connection to either round or forked crimp terminals.
Finger protection
Mechanism for preventing
terminal screws from coming
off (loosening the screws do
not cause them to come off)
G-312
Safety Sensors / Components
Dimensions
Note: All units are in millimeters unless otherwise indicated.
A22E-MP
A22E-LP
Non-lighted models
40-dia. Push-pull
Non-lighted models
60-dia. Push-pull
60 dia.
40 dia.
A22E-S
A22E-M
Non-lighted models
30-dia. Push-lock, Turn-reset
Non-lighted models
40-dia. Push-lock, Turn-reset
30 dia.
40 dia.
1.8
41.2
32
A22E-L
Non-lighted models
60-dia. Push-lock, Turn-reset
60 dia.
1.8
A22E-SK
A22E-MK
Non-lighted models
30-dia. Push-lock, Key-reset
Non-lighted models
40-dia. Push-lock, Key-reset
30 dia.
34
22 dia.
1.8
40 dia.
22 dia.
1.8
A22EL-M
A22E
Lighted models
40-dia. Push-lock, Turn-reset
40 dia.
32
A22E
41.2
G-313
Dimensions for Accessories
Legend Plates For Emergency-stop
A22Z-3476-1
A22Z-3466-1
90 dia.
60 dia.
Black letters
Black letters
Yellow
Yellow
22.2 dia.
22.2 dia.
Tightening Wrench
A22Z-3905
30 dia.
11 dia. 8.5 dia.
8 dia.
25-dia. Ring
A22Z-R25
22.2 dia.
22 dia.
24.8 dia.
27 dia.
Lock Ring
A22Z-3360
19.2 dia.
21.2 dia.
25 dia.
Lamp Extractor
A22Z-3901
30 dia.
Lock Plate
A22Z-3380
7.3 dia.
G-314
Safety Sensors / Components
Control Box (Enclosure)
A22Z-B10#
A22Z-B101 (One Hole)
A22Z-B101Y
Four, 4x38 tapping screws
+0.2
dia.
22.1-0.1
Cable Port Hole (Top View)
21 dia.
(Lead cable hole)
16±1 dia.
(Lead cable hole)
Two mounting holes
(10x36) 0.6-mm concave surface
A22Z-B102 (Two Holes)
Four, 4x38 tapping screws
Two, 22.1+0.2
-0.1 dia.
Cable Port Hole (Top View)
21 dia.
(Lead
cable hole)
(10x36) 0.6-mm concave surface
16±1 dia.
(Lead cable hole)
Two
mounting
holes
A22Z-B103 (Three Holes)
Cable Port Hole (Top View)
Four, 4x38 tapping screws
Three, 22.1+0.2
-0.1 dia.
21 dia.
(Lead cable hole)
16±1 dia.
(Lead cable hole)
(10x36) 0.6-mm concave surface
Two
mounting
holes
A22E
Panel Mounting Hole
A22E
G-315
Terminal Arrangement
Terminal Arrangement (Bottom View)
Non-lighted
(SPST-NO + SPST-NC)
Lighted
(SPST-NO + SPST-NC)
Switch
Blocks
M3.5 screws
Lamp Socket
Switch Blocks
Terminal Connection
Type
Terminal connection
Bottom view
Non-lighted
Bottom view
Lighted without Voltage Reduction Unit
Bottom view
Lighted with Voltage
Reduction Unit
Note: The above terminal connection diagrams are examples for SPST-NO +
SPST-NC.
Panel Cutouts
3.2+0.2
0 dia.
R0.8 max.
24.1+0.4
0 dia.
22.3+0.4
0 dia.
With Lock Fitting
22.3+0.4
0 dia.
25+0.5
0 dia.
Without Lock Fitting
Note: 1. When applying coating such as paint to the panel, the dimensions should be those after the application of coating.
2. Recommended panel thickness: 1 to 5 mm.
3. Use an A22Z-R25 Ring when mounting to a panel with 25mm holes.
G-316
Safety Sensors / Components
Installation
Mounting to the Panel
Mounting the Switch on the Pushbutton Unit
Mounting the Operation Unit on the Panel
Insert the Pushbutton Unit into the Switch Unit, aligning the arrow
mark inscribed on the Case with the lever on the Switch Blocks, then
move the lever in the direction indicated by the arrow in the following
figure.
Insert the Operation Unit (Pushbutton, etc.) from the front surface of
the panel, insert the Lock Ring and the mounting nut from the terminal side, then tighten the nut. Before tightening, check that the rubber washer is present between the Pushbutton Unit and the panel.
Operation Unit
When using a Legend Plate Frame, put one rubber washer each
between the Legend Plate Frame and the panel and between the
Operation Unit and the Legend Plate Frame. (One rubber washer will
be provided when one Legend Plate Frame is ordered.)
Align the Lock Ring with the groove in the casing, then insert the
Lock Ring so that its edge is located on the panel side.
Arrow mark
Lever
Tighten the mounting nut at a torque of 0.98 to 1.96 N·m.
When using a Lock Ring, replace with the supplied Lock Ring, insert
the projecting part into the lock slot, and then tighten the mounting
nut.
Rubber washer
Hold here
Mounting nut
Panel
Projecting
part
Removing the Switch
Lock Ring
Lock Ring
Panel
When the panel cutout dimension is 25 dia., remove the supplied
rubber washer and mount the 25-dia. Ring as shown below. (Since
the A22Z-R25 is not attached to the main body, order separately.)
Move the lever in the direction indicated by the arrow in the following
figure, then pull the Pushbutton Unit or the Switch Blocks.
Since the lever has a hole with an inside diameter of 6.5 mm, the
lever can be moved in the specified direction by inserting a screwdriver into the hole and then moving the screwdriver.
Operation Unit
Screwdriver
22 dia.
25-dia. Ring (A22Z-R25)
22.3 dia.
25 dia.
Panel
Lock Ring
25 dia.
22.3 dia.
A22E
Mounting nut
A22E
G-317
Assembling the Cap
Control Box (Enclosure)
Emergency Stop Switch
Mounting the Switch
Insert the protrusion of the Tightening Wrench (A22Z-3905) into the
Cap slot and then turn to remove the Cap.
The Standard-size Legend Plate Frame can be mounted. Mount the
Frame as shown in the following diagram. Mount the Switch in the
same way as for an ordinary panel.
Snap-in Legend Plate
Installing/Replacing the Lamp
Installing/Replacing from the Panel Surface
Insert the Lamp Extractor (A22Z-3901) into the lamp, then rotate the
Extractor while pressing it.
Creating a Cable Port Hole
Place the tip of a screwdriver on the surface where the cable port
hole is to be created with the cover attached and strike the screwdriver to punch a hole. Attempts to punch a hole on the other side of
the case will damage the Box.
Installing/Replacing on the Switch
Grip the indicator with your fingers, then rotate the indicator while
pressing it against the Switch.
Securing the Connector Cable
1. Insert the connector into the cable port hole in the Box and secure
with the fixing nut inside the box.
2. Open a hole in the thin rubber section of the rubber ring.
3. Pass the tightening cap through the cable, insert the cable into
the connector, and tighten the hexagonal nut to secure the cable.
Lock nut
Rubber washer
Connector
Tightening cap
Cable
Inside
Outside
Box
Cable diameter
7 to 9 dia.
9 to 11 dia.
G-318
Connector
A22Z-3500-1
A22Z-3500-2
Safety Sensors / Components
Installing/Removing the Switch Blocks
Wiring
Installing the Switch Blocks
Wiring Round Crimp Terminals
Hook the small protrusion on the Mounting Latch into the groove on
the other side of the lever, then push up the Switch Block in the direction indicated by the arrow in the figure below.
Loosen the terminal screw from the Switch Unit until it completely
comes off the groove, insert a screwdriver as shown in the following
figure, then push up the washer in the direction indicated by the
arrow to temporarily secure it. Now, a round crimp terminal can be
connected. After inserting the terminal, tighten the screws to complete wiring.
Lever
Washer
Mounting
Latch
Screw
Screwdriver
Protrusion
Switch Block
Removing the Switch Blocks
Insert a screwdriver between the Mounting Latch and the Switch
Block, then push down the screwdriver in the direction indicated by
the arrow in the following figure.
Use either of the following screwdrivers.
Flat-head
3 to 6 mm
screwdriver
Phillips
3 to 6 mm
screwdriver
A22E
Screwdriver
A22E
G-319
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Cat. No. A119-E2-03A-X
G-320
In the interest of product improvement, specifications are subject to change without notice.
Safety Sensors / Components