9
Mixed I/O Link Module
B7AM-6BS
Compact B7A Module Provides
16 Input and 16 Output Points
1 Saves space in control panels,
measures just 114.5 mm (4.51 in) wide
1 Compatible with B7A 8-point mixed I/O
terminal wiring blocks
1 Switch selected transmission speed for
Normal I/O delay (19.2 ms typical) and
short I/O delay (3 ms typical)
1 Switch selected Hold or Load Off
options for handling transmission errors
1 DIN rail or surface mounting
Ordering Information
3 MODEL NUMBER LEGEND
B7AM -- 6 B S
1 2 3 4
1. Classification
M:Mixed I/O model
2. Number of I/O
6: Sixteen input points and sixteen output points
3. Input/Output Configuration
B: NPN input and 100 mA NPN open collector output per point
4. Appearance
S: Screw terminals
3 MIXED I/O LINK MODULES
Appearance
I/O configuration
NPN compatible inputs/
NPN open collector
outputs,100 mA/point
I/O delay (typical)
Normal speed 19.2 ms
High speed 3 ms
(switch selectable)
Error processing
HOLD/LOAD OFF
(switch setting)
Part number
B7AM-6BS
3 POWER SUPPLIES
Input voltage
Output rating
120 to 240 VAC
0.13 A, 24 VDC
Use one to power each input or output block
Application
S82K-00324
Part number
0.3 A, 24 VDC
Use one to power two blocks from a single power supply
S82K-00724
0.6 A, 24 VDC
Use this to power blocks connected to sensors, relays indicator lights
S82K-01524
1.3 A, 24 VDC
Use one where excess power is needed
S82K-03024
B7AM-6BS
B7AM-6BS
Specifications
3 CHARACTERISTICS
General
Item
Normal speed
High speed
Communication method
Unidirectional, time-division multiplex
Transmission distance
500 m max.
100 m max. (See Note 1)
I/O delay
Typical: 19.2 ms; 31 ms max.
Typical: 3 ms; 5 ms max.
Minimum input time (See Note 2)
16 ms
2.4 ms
Operating voltage range
12 to 24 VDC (10.8 to 26.4 VDC)
Insulation resistance
100 MΩ min. at 500 V between each terminal and external parts
Dielectric strength
1,000 VAC, 50/60 Hz for 1 min between each terminal and external parts
Noise immunity (See Note 3)
Noise level: 1.5 kV; pulse width: 100 ns to 1 μs
Vibration resistance
10 to 55 Hz, 1.5 mm double amplitude
Shock resistance
300 m/s2 (approx. 30G)
Ambient temperature
Operating: --10°C to 55°C (14°F to 131°F) with no icing
Storage: --25°C to 65°C (--13°F to 149°F) with no icing
Ambient humidity
Operating: 35% to 85% with no condensation
Note: 1. A shielded transmission cable or a twisted pair or VCTF cable with a thickness of 0.75 mm2 minimum must be used for signal
transmission. If the twisted pair or VCTF cable is used, however, the transmission distance will be 10 m maximum regardless of
whether or not independent power supplies for the Input and the Output Link Terminals are used.
2. The minimum input time is required for the B7AM to read an input signal.
3. As for the high-speed transmission setting, these values are possible without grounding the shielded line.
Mixed I/O Terminal Block
Item
B7A-6BS
I/O delay
Standard (typical 19.2 ms); high-speed (typical 3 ms), switch selectable (See Note 4)
Current consumption (See Note 1)
240 mA max. with all input/output terminals ON
Operating voltage range
12 to 24 VDC
Compatible inputs (See Note 2)
Switches, two-wire sensors with DC output, three-wire NPN sensors
Input logic
Active low
Input voltage range
0 VDC to supply voltage
Input current range
--6 to --3 mA/point (current flowing from input terminals)
Minimum input time
Standard: 16 ms; high-speed: 2.4 ms
ON/OFF threshold
No--contact input:ON voltage: 4 V max.
OFF voltage: 6 V min.
Contact input:
ON discrimination resistance: 660 Ω max.
OFF discrimination resistance: 2 kΩ min.
Output configuration
NPN open collector
Rated load voltage
5 to 24 VDC
Output residual voltage
0.8 V max.
Output current
Sink current, 100 mA max./ point
Error processing
HOLD/LOAD OFF is set using a selection switch (See Note 3)
Mounting strength
No damage when 5 kgf (49 N) pull is applied for 1 min each in all directions
Terminal strength
No damage when 5 kgf (49 N) pull is applied for 1 min each in all directions
Tightening torque
8 to 12 kgf : cm (0.78 to 1.18 N : m)
Weight
Approx. 230 g
Note: 1. Consumption when all 16 input/output points are ON. Excludes external sensor current for Input Terminals and external load
current and error load current for Output Terminals.
2. Power must be supplied to the three-wire sensor via the positive power supply terminal or from an independent power supply.
Two-wire sensors must satisfy the following requirements:
Residual voltage: 4 V max.
Current leakage:
1.5 mA max.
The lower limit of control output: 3 mA (Use a bleeder resister to eliminate this restriction.)
3. Default settings are 19.2 ms and LOAD OFF.
2
B7AM-6BS
B7AM-6BS
Nomenclature
Power terminals
Input terminals
Transmission
terminal
Power supply/
error indicator
Input indicators
Selector switch
Output indicators
Transmission
terminal
Power terminals
Indicator Operation
Recommended Solderless Terminals
Indicator
POWER/ERR
I/O
Output terminals
Function
G
Lit when power is supplied and the
Terminal is operating without error.
R
Lit during transmission errors
(SIG2).
N
Not lit when power is not supplied.
O
Lit when the input signals are ON.
N
Not lit when the signals are OFF.
Wire
JIS specifications
0.75 mm2 (AWG#18) RAV 1.25 to 3.5 (vinyl-insulated round
wire) or RAP 1.25
1 25 to 3
3.5
5
1.25 mm2 (AWG#16) (nylon-insulated round wire)
Note: G: Green indicator lit; R: Red indicator lit;
O: Orange indicator lit; N: Not lit
Selector Switch Settings
Transmission speed selector switch
Error processing selector switch
3 ms
19.2 ms
HOLD
LOAD OFF
HIgh-speed: (typical 3 ms)
Standard: (typical 19.2 ms)
When an error occurs, the
output holds the state that
existed right before the error
occurred.
When an error occurs, the
output shuts off everything.
Note: Default settings are 19.2 ms and LOAD OFF.
3
B7AM-6BS
B7AM-6BS
Operation
3 POWER SUPPLY
The six positive and six negative terminals on the terminal block are internally connected. Use positive and negative terminals for the power
supply terminals and another negative terminal for the negative signal line. Connect the SIG1 terminals to SIG2 terminals for the signal lines.
I/O Delay: Normal Speed
(12 to 24 V)
(12 to 24 V)
DC power
supply
DC Power
supply
Set the selector switch to 19.2 ms
Set the selector switch to 19.2 ms
Transmission
distance
500 m max.
Power supply
Power supply
Note: A twisted pair or VCTF cable with a thickness of 0.75 mm2 min. must be used for signal transmission.
I/O Delay: High Speed
(12 to 24 V)
(12 to 24 V)
DC power
supply
DC power
supply
Set the selector switch to 3 ms
Set the selector switch to 3 ms
Transmission distance
100 m max.
Power supply
Power supply
Note: A shielded cable with a thickness of 0.75 mm2 min. must be used for signal transmission. It is recommended that the shield be
grounded.
The maximum transmission distance is 10 m if a twisted pair or VCTF wire with a thickness of 0.75 mm2 is used instead of a
shielded cable for the transmission path.
4
B7AM-6BS
B7AM-6BS
3 CONFIGURATION
Device Connection
Limit switch, proximity sensor, or photoelectric sensor
Limit switch, proximity sensor, or photoelectric sensor
Sixteen-point input
Sixteen-point input
ERR
Sixteen-point output
ERR
Indicator or valve
Sixteen-point output
Indicator or valve
Note: The B7AM transmits input signals from SIG1 (input terminal) to SIG2 (output terminal). If an error results
while the B7AM is transmitting input signals, an error signal is output from the output side only.
B7AM Mixed I/O System Configuration
Mixed I/O Link Module
(16 input and 16 output points)
B7AM
Mixed I/O Link Module
(16 input and 16 output points)
Input
Output
Output
Input
Mixed I/O Link Module
(8 input and 8 output points)
B7AM
B7AM
Mixed I/O Link Module
(8 input and 8 output points)
Input
Output
Output
Input
B7AM
Note: The Mixed I/O Link Modules are either 3 ms (typical, for high-speed models) or 19.2 ms (typical, for normal-speed models).
Use a Mixed I/O Link Module with the same transmission speed (I/O delay time).
5
B7AM-6BS
B7AM-6BS
Dimensions
Unit: mm (inch)
113.5
105
35
85
(3.35)
35.3
77
4
114.5 (4.51)
67.2 (2.65)
Installation
3 INTERNAL CIRCUITS AND TERMINAL ARRANGEMENT
Internal circuit
Power Power
supply supply
Power Power
supply supply
NOTE: DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters to inches divide by 25.4.
9
OMRON ELECTRONICS, INC.
OMRON CANADA, INC.
One East Commerce Drive
Schaumburg, IL 60173
885 Milner Avenue
Scarborough, Ontario M1B 5V8
1-800-55-OMRON
416-286-6465
Cat. No. GC RIO-1
04/00
Specifications subject to change without notice.
Printed in U.S.A.
很抱歉,暂时无法提供与“B7AM-6BS”相匹配的价格&库存,您可以联系我们找货
免费人工找货