■ Quick Start
To make the module ready for use:
1.
Set Machine Number.
2.
Mount and wire the Unit.
3.
Turn power on.
4.
Create I/O Table.
CJ1W-DCM11-E
DC-Motor Control Unit
To start the motor:
5. Set ramp up time
6. Set PWM duty cycle
7. Set motor bit ON
8. The MOT led should now turn on
INSTRUCTION SHEET
Thank you for purchasing an OMRON product. Read this
instruction sheet thoroughly and familiarise yourself with the
functions and characteristics of the product before using it. To
ensure safe and correct use of this Unit, also read the following
Operation Manual (Cat. No. W393-E1): SYSMAC CJ1 Series
Programmable Controllers.
To stop the motor with brake(direct stop):
1. Enable IN0 and/or IN2
2. Make IN0 or IN2 high
Alternative way to stop the motor with brake:
1. Make motor bit “0”
To stop the motor with ramp(gradual stop):
1. Enable IN1 and/or IN3 high
2. Make IN1 and/or IN3 high
Keep this instruction sheet for future reference.
OMRON MANUFACTURING OF THE NETHERLANDS B.V. 2006
All Rights Reserved
■ Unit specifications
! DANGER
! Caution
Unit type
Applicable PLC models
Storage temperature
Ambient temperature
Ambient humidity
EMC compliance
Current consumption
Do not attempt to take the Unit apart and do not
touch any internal parts while the power is being
supplied. Doing either of these may result in
electrical shock, and serious or fatal injury.
Leave the protective label on top of the Unit as long
as the Unit is not mounted and wired completely, in
order to prevent wire clippings or other materials
from getting inside the Unit. When the mounting
and wiring has been completed, the label must be
removed to allow air circulation and heat radiation.
0425-6701A
Weight
Number
allocated
of
words
CJ1 Special I/O Unit
CJ1-series PLCs
-20 to +75 °C
0 to +55 °C
10 to 90 % (non-condensing)
EN 50081-2, EN 61131-2
PLC side: 200 mA (5V via
busconnection)
Motor side:30mA (no motor load)
Single unit: 106 g (typical)
7 CIO-words. First word allocated =
CIO 2,000 + (N x 10)
(Where N = Machine Number)
■ Dimensions
■ Nomenclature
Unit status indicators
•
RUN
(Green)
•
MOT
(Green)
•
ERH
(Red)
•
ERC
(Red)
•
IN0, IN1, IN2, IN3
24
31
65
CTS21
DCM11
DCM11
RUN
RUN ERC
ERC IN0ERH IN2
RUN
ERC
IN0
IN2
MOT
ERH
IN1
IN3
CH1
CH2
MOT
ERH
IN1
B1
IN3 A1
PNSPO
CJ1W-CTS21-E
2-CHANNEL SSI UNIT
SSI DATA+CLK:RS-422 Line Driver, 1.5 MHz max.
EXT.PS FOR ENCODERS: 5-24 V DC, 0.8 A max.
(Green)
x 101
MACH
No.
x10 1
x 100
Lot No. 000000N0000
MACH
No.
x10 1
Batch No. 000000000
OMRON MANUFACTURING OF THE NETHERLANDS B.V.
MADE IN THE NETHERLANDS
x10 0
90
Machine number rotary switches
95
x10 0
Digital inputs(from top to bottom)
•
IN0
IN1
•
IN2
•
IN3
•
Common D
•
Shield
•
■ Machine number switch
Counter inputs(from top to bottom)
A
•
B
•
Z
•
Common C
•
Shield
•
Name
MACHINE No.
x10
x10
PWM outputs(from top to bottom)
•
•
•
•
•
Shield
24V in
0V in
PWM A out
PWM B out
1
0
Function
Sets the Machine Number (00 – 99).
• Make sure each Machine Number is
used only once per CJ1-CPU.
• Be sure to turn off the power to the Unit
before setting the Machine Number.
•
•
Digital input: 24V / 6mA / 4 points
Counter input: 24V / 8mA / 1 channel
•
Output: PWM 24V / 4A
On-time (s)
No-time limit
5
0
1
4
DC-current (A)
10
■ LED Indicators
Indicator
RUN
Colour
Green
ERC
Red
ERH
Red
MOT
Green
IN0
Yellow
IN1
Yellow
IN2
Yellow
IN3
Yellow
Status
Off
On
Off
On
Condition
Unit is deactivated
Unit is activated
No over-current, Bridge-IC OK
System panic, Error log read error,
Error log write error, invalid PWM
duty cycle value, over-current, PWM
direction change error
Blinking Bridge IC error
Off
No power or no PLC, CPU related
error active
On
Initialisation with the PLC failed
Off
Motor drive ‘OFF’
On
Motor drive ‘ON’
Blinking Over temperature or 24V power
failure
Off
Digital input ‘OFF’
On
Digital input ‘ON’
Off
Digital input ‘OFF’
On
Digital input ‘ON’
Off
Digital input ‘OFF’
On
Digital input ‘ON’
Off
Digital input ‘OFF’
On
Digital input ‘ON’
Word
n+3
Bit
00
01
02
03
04
05
06
07
08
■ Operating the Unit via CIO
09
n = CIO 2000 + (N x 10), with N the Machine Number of the Unit.
10
Word
n
Bit
00
01
02-03
04-07
08
09
10
11
12-14
15
n+1
00-15
n+2
00-07
08-15
Function
Motor ON/OFF.
Note: A transition from 0 to 1 will trigger the
motor ON. Vice versa for motor OFF.
Reset counter
Set PWM frequency. 00 = 20kHz(default)
01=10kHz 10=2kHz 11=1kHz
11
12
13
14
Reserved
Function digital input 0
0=normal digital input (default)
1=Forward stop(with brake)
Function digital input 1
0=normal digital input (default)
1=Forward stop(with ramp)
Function digital input 2
0=normal digital input (default)
1=Reverse stop(with brake)
Function digital input 3
0=normal digital input (default)
1=Reverse stop(with ramp)
Reserved
Function digital counter input
0 = count AZ (32 bits, default)
1 = count ABZ (32 bits 2’s complement)
PWM with direction: -100,0%...0%...100,0%
Note: Negative value’s are to be entered in
2’s complement representation. In hex, the
PWM range would be: FC18...0000...03E8
PWM ramp down(default 00)
PWM signal with ramp down time from 0 to
25,6 seconds. Only active from a higher to a
lower, or a more negative to a less negative
value.
PWM ramp up(default 00)
PWM signal with ramp up time from 0 to
25,6 seconds. Only active from a lower to a
higher, or a less negative to a more negative
value.
15
n+4
00-07
08-14
15
n+5
00-15
n+6
00-15
Function
Digital input 0
0 = input is low 1=input is high
Digital input 1
0 = input is low 1=input is high
Digital input 2
0 = input is low 1=input is high
Digital input 3
0 = input is low 1=input is high
Motor controlled
0= not controlled
1= controlled
Motor running
0 = motor stopped
1 = motor running
PWM on the A or B output
0 = A outputs the PWM signal
1 = B outputs the PWM signal
Note: when there is no PWM output, the
value of bit 06 corresponds with the last
valid PWM output. Default, it is 0.
Reserved
DC motor voltage
0 = no DC-motor voltage
1 = DC motor voltage OK
Motor brake
0 = motor brake off
1 = motor brake on
Direction change error
0 = error not active
1 = error active
Illegal PWM value error
0 = error not active
1 = error active
Reserved
Reserved
Working temperature error
0 = error not active
1 = error active (temperature too high)
Unit driver error
0 = error not active
1 = error active (temperature too high)
Input current dc-motor unit
Current value from 0 to 10A (100mA/bit)
Reserved
Current overload
0 : I < 10A
1: I >10A
32 bits counter input, lower 16 bits counter
part
32 bits counter input, upper 16 bits counter
part
PNSPO
OMRON EUROPE B.V.
Wegalaan 67-69
NL-2132 JD Hoofddorp
The Netherlands
Phone (+31) 23 - 56 81 300
Fax
(+31) 23 - 56 81 388
Internet: www.eu.omron.com
Note: Specification subject to change without notice.
Printed in The Netherlands
2