CJ Series Analog I/O Unit
CJ1W-AD/DA/MAD
CSM_CJ1W-AD_DA_MAD_DS_E_1_1
For Various Analog I/Os
• Analog Input Units for converting analog input signals into
binary data
• Analog Output Units for converting binary data into analog
output signals
CJ1W-AD081-V1
CJ1W-DA08V
Features
•
•
•
•
Holds a maximum of 8 analog input signals in 1 unit.
With functions including line disconnection detection, peak value holding, as well as offset and gain adjustment.
Outputs a maximum of 8 output signals with 1 unit.
With functions including output hold, offset and gain adjustment, as well as scaling (CJ1W-DA08V/08C).
System Configuration
Analog Input Unit
CPU Unit
Analog Output Unit
RUN
ERR/ALM
INH
PROGRAMMABLE
PRPHL
CONTROLLER
COMM
SYSMAC
CJ1G-CPU44
AD081-V1
RUN
ERC
ERH
ADJ
B1
DA041
RUN
ERC
ERH
ADJ
A1
B1
A1
OPEN
MCPWR
BUSY
MACH
MACH
No.
1
x10
No.
1
x10
x10
0
x10
0
PERIHERAL
1 2
1 2
MODE
MODE
PORT
Sensor
Temperature
Pressure
Speed
Flow rate
Regulator
(Temperature control)
Preamp
Servocontroller
M
(Position control)
Voltage
Current
Power
Power factor
Transducer
Variable speed
controller
M
(Speed control)
Chart recorder
Sensor
Note: The above diagram is an installation example for the CJ1W-AD041-V1/081-V1 Analog Input Units and CJ1W-DA021/041 Analog Output
Units.
1
CJ1W-AD/DA/MAD
Ordering Information
Analog Input Units
Unit
Product
classification
name
Analog
Input
Units
CJ1
Special
I/O Units
Signal
range
selection
I/O
points
Signal
range
Set
separately
1 to 5 V,
for each
0 to 5 V,
input
0 to 10 V,
±10 V,
Set
separately 4 to 20
mA
for each
input
8
inputs
4
inputs
Resolution
Accuracy at
Conversion
ambient
Speed
temperature
of 25°C)
1/8,000
(Settable
to
1/4,000)
(See
note 1.)
250 μs/
point
max.
(Settable
to 1 ms/
point)
(See note
1.)
External
connection
Voltage:
±0.2% of F.S. Removable
terminal
Current:
±0.4% of F.S. block
(See note 2.)
Current
No. of
consumption
unit
(A)
numbers
allocated 5 V 24 V
Model
Standards
CJ1W-AD081-V1
1
0.42
UC1, N,
L, CE
−
CS1W-AD041-V1
Note: 1. The resolution and conversion speed cannot be set independently. If the resolution is set to 1/4,000, then the conversion speed will be
1 ms/point.
2. At 23 ±2°C
3. For products manufactured from August 2007 onwards.
Analog Output Units
Unit
Product
classification
name
Signal
range
selection
I/O
points
8
outputs
Analog
Output
Units
8
outputs
CJ1
Special
I/O Units
4
outputs
Set
separately
for each
input
2
outputs
Signal
range
Resolution
1 to 5 V,
0 to 5 V,
0 to 10 V, 1/4,000
−10 to 10 V (Settable
to
1/8,000)
(See
4 to 20
note.)
mA
1 to 5 V,
0 to 5 V,
0 to 10 V,
−10 to 10 V,
4 to 20 mA
1/4,000
Accuracy at
No. of
External
Conversion
External
ambient
unit
power
Speed
temperature connection
numbers
supply
of 25°C)
allocated
Current
consumption
(A)
5V
Model
Standards
24 V
24 VDC
1 ms/
point
(Settable ±0.3% of
to 250 μs/ F.S.
point
max.)
1 ms/
point
max.
0.14
(See CJ1W-DA08V
note.)
+10%
−15%
,
140 mA
max.
0.14
24 VDC
+10%
−15%
0.17
UC1, N,
(See CS1W-DA08C
CE
note.)
+10%
−15%
0.2
(See CJ1W-DA041
note.)
,
170 mA
Removable max.
terminal
1
24 VDC
block
Voltage:
±0.3% of
F.S.
Current:
±0.5% of
F.S.
UC1, N,
L, CE
,
200 mA
max.
UC1, N,
L, CE
0.12
24 VDC
0.14
(See CS1W-DA021
note.)
+10%
−15%
,
140 mA
max.
Note: This is for an external power supply, and not for internal current consumption.
Analog I/O Units
Unit
Product
classification
name
Analog
I/O
Units
CJ1
Special
I/O Units
I/O
points
4
inputs
2
outputs
Signal
range
selection
Signal
range
1 to 5 V,
Set
0 to 5 V,
separately
0 to 10 V,
for each
−10 to 10 V,
input
4 to 20 mA
Accuracy at
Conversion
ambient
Resolution
Speed
temperature
of 25°C)
1/4,000
(Settable
to
1/8,000)
1 ms/
point
(Settable
to 500 μs/
point
max.)
External
connection
Voltage:
±0.2% of F.S.
Current:
±0.2% of F.S. Removable
terminal
Voltage:
block
±0.3% of F.S.
Current:
±0.3% of F.S.
Current
No. of
consumption
unit
(A)
numbers
allocated 5 V
24 V
1
0.58
−
Model
Standards
CJ1W-MAD42
UC1, N,
L, CE
Note: The resolution and conversion speed cannot be set independently. If the resolution is set to 1/4,000, then the conversion speed will be 1
ms/point.
Accessories
There is no accessory for the CJ Series Analog I/O Units.
International Standards
• The standards indicated in the "Standards" column are those current for UL, CSA, cULus, NK, and Lloyd standards and EC Directives as of the
end of February 2008. The standards are abbreviated as follows: U: UL, U1: UL (Class I Division 2 Products for Hazardous Locations), C: CSA,
US: cULus, UC1: cULus (Class I Division 2 Products for Hazardous Locations), CU: cUL, N: NK, L: Lloyd, and CE: EC Directives.
• Ask your OMRON representatives for the conditions under which the standards were met.
2
CJ1W-AD/DA/MAD
Individual Specifications
Analog Input Units CJ1W-AD041-V1/AD081-V1
Specifications
Item
CJ1W-AD041-V1
CJ1W-AD081-V1
Unit type
CJ-series Special I/O Unit
Isolation
Between I/O and PLC signals: Photocoupler *1
(No isolation between each I/O signals.)
External terminals
18-point detachable terminal block (M3 screws)
Affect on CPU Unit cycle time
0.2 ms
Power consumption
420 mA max. at 5 VDC
Dimensions
31 × 90 × 65 mm (W × H × D)
Weight
140 g max.
General specifications
Conforms to general specifications for SYSMAC CJ Series.
Mounting position
CJ-series CPU Rack or CJ-series Expansion Rack
Maximum number of Units
Units per Rack (CPU Rack or Expansion Rack): 4 to10 Units max. *2
Data exchange with CPU Units *3
Special I/O Unit Area in CIO Area (CIO 2000 to CIO 2959): 10 words per Unit
Special I/O Unit Area in DM Area (D20000 to D29599): 100 words per Unit
Number of analog inputs
4
Input signal range *4
1 to 5 V
0 to 5 V
0 to 10 V
−10 to 10 V
4 to 20 mA
Maximum rated input (for
1 point)
Voltage Input: ±15 V
Current Input: ±30 mA *5
Input
specifications Input impedance
*6
Resolution *7
Voltage Input: 1 MΩ min.
Current Input: 250 Ω (rated value)
4,000/8,000
Converted output data
Accuracy
*8
Input
functions
8
4,000/8,000
16-bit binary data
23±2°C
Voltage Input: ±0.2% of F.S.
Current Input: ±0.4% of F.S.
0°C to 55°C
Voltage Input: ±0.4% of F.S.
Current Input: ±0.6% of F.S.
A/D conversion time *9
1 ms/250 μs
Mean value processing
Stores the last "n" data conversions in the buffer, and stores the mean value of the conversion
values.
Buffer number: n = 2, 4, 8, 16, 32, 64
Peak value holding
Stores the maximum conversion value while the Peak Value Hold Bit is ON.
Input disconnection
detection
Detects the disconnection and turns ON the Disconnection Detection Flag. *10
1 ms/250 μs
*1. Do not apply a voltage higher than 600 V to the terminal block when performing withstand voltage test on this Unit. Otherwise, internal elements
may deteriorate.
*2. The maximum number of Analog Input Units that can be mounted to one Rack varies depending on the current consumption of the other Units
mounted to the Rack.
Power Supply Unit
Rack
CJ1W-DA021
CJ1W-DA041
(5 VDC 120 mA)
CJ1W-DA08V
CJ1W-DA08C
(5 VDC 140 mA)
CS1W-AD041-V1
CJ1W-AD081-V1
(5 VDC 420 mA)
CJ1W-MAD42
(5 VDC 580 mA)
CJ1W-PA205R
CJ1W-PA205C
CJ1W-PD025
(5.0 A at 5 VDC)
CPU Rack
10
9
7
Expansion Rack
10
10
8
CJ1W-PA202
(2.8 A at 5 VDC)
CPU Rack
10
4
3
Expansion Rack
10
6
4
CJ1W-PD022
(2.0 A at 5 VDC)
CPU Rack
7
2
1
Expansion Rack
10
4
3
3
CJ1W-AD/DA/MAD
*3. Data Transfer with the CPU Unit
CPU Unit to Analog Input Unit Peak hold values
Special I/O Unit Area in CIO Area
10 words per Unit refreshed
(CIO 2000 to CIO 2959,
cyclically
CIO 200000 to CIO 295915)
Special I/O Unit Area in DM Area
(D20000 to D29599)
100 words per Unit refreshed
cyclically
Analog Input Unit to CPU Unit
Analog input values
Line disconnection detection
Alarm flags
Etc.
Input signal conversion settings
Signal range settings
Averaging function
CPU Unit to Analog Input Unit
Resolution/conversion time
settings
Operation mode settings
*4. Input signal ranges can be set for each input.
*5. Voltage input or current input are chosen by using the voltage/current switch at the back of the terminal block.
*6. The Analog Input Unit must be operated according to the input specifications provided here. Operating the Unit outside these specifications
will cause the Unit to malfunction.
*7. The resolution can be set to 8,000 and the conversion time to 250 μs in the DM Area (m+18). There is only one setting for both of these, i.e.,
they are both enabled or disabled together.
*8. The accuracy is given for full scale. For example, an accuracy of ±0.2% means a maximum error of ±8 (BCD).
The default setting is adjusted for voltage input. To use current input, perform the offset and gain adjustments as required.
*9. A/D conversion time is the time it takes for an analog signal to be stored in memory as converted data after it has been input. It takes at least
one cycle before the converted data is read by the CPU Unit.
*10. Line disconnection detection is supported only when the range is set to 1 to 5 V or 4 to 20 mA. If there is no input signal when the 1 to 5 V or
4 to 20 mA range is set, the Line Disconnection Flag will turn ON.
Input Function Block Diagram
Analog Input Unit
Analog input 1
A/D
Input disconnection
detection
Analog input 2
Same as above.
Analog input 3
Same as above.
Analog input 4
Same as above.
Analog input 5
Same as above.
Analog input 6
Same as above.
Analog input 7
Same as above.
Analog input 8
Same as above.
CPU Unit
Mean value
processing
disabled
Peak value
hold function
disabled
Mean value
processing
enabled
Peak value
hold function
enabled
I/O
refresh
Special I/O
Unit Area
Analog
input 1
conversion
value
Note: There are only four analog inputs for the CJ1W-AD041-V1.
4
CJ1W-AD/DA/MAD
External Interface
CJ1W-AD041-V1
CJ1W-AD081-V1
Front
With Terminal Block
With Terminal Block Removed
Indicators
B1
78
Voltage/current
switch
456
23
ON
ON
1
2
ON
1
2
23
x10 0
901
901
O
N
O
N
MODE
1
2
1 2
1 2
MODE
ON
x10 0
456
78
78
Terminal block
A1
1
No.
456
MACH
x10 1
456
78
901
No.
RUN
ERC
ERH
ADJ
A1
23
MACH
x10 1
B1
901
Unit number
setting switch
AD081-V1
23
RUN
ERC
ERH
ADJ
2
AD081-V1
Terminal block
DIN Track
mounting pin
Terminal block lock lever
Operating mode switch
(pull down to release
terminal block)
Side
Slider
Expansion connector
Slider
5
CJ1W-AD/DA/MAD
Indicators
The indicators show the operating status of the Unit. The following table shows the meanings of the indicators.
LED
Meaning
RUN (green)
Indicator
Operating
ERC (red)
Operating status
Lit
Operating in normal mode.
Not lit
Unit has stopped exchanging data with the CPU Unit.
Alarm has occurred (such as disconnection detection) or initial
settings are incorrect.
Lit
Error detected by Unit
Not lit
ERH (red)
Error in the CPU Unit
ADJ (yellow)
Operating normally.
Lit
Error has occurred during data exchange with the CPU Unit.
Not lit
Operating normally.
Flashing
Adjusting
Operating in offset/gain adjustment mode.
Not lit
Other than the above.
Internal Circuit
The following diagrams show the internal circuit of the analog input section.
Input Circuits
15 kΩ
15 kΩ
Input (+)
Input circuit
and
conversion
circuit
250 Ω
1 MΩ
AG
(analog 0 V)
15 kΩ
15 kΩ
Input (–)
Voltage/
current
input switch
1 MΩ
AG (common to all inputs)
Internal Configuration
Photocoupler insulation
Indicators/Switch
MPU
Bus
interface
RAM ROM
A/D
converter
Multiplexer
and
amplifier
Externally
connected
terminal
INPUT
EEP-ROM
Oscillator
Division
+15V
+5 V
Insulation-type
DC-to-DC
converter
Regulator
+5V
−15V
CJ-series PC
6
CJ1W-AD/DA/MAD
Terminal Arrangement
The signal names corresponding to the connecting terminals are as shown in the following diagram.
CJ1W-AD041-V1
Input 2 (+)
B1
Input 2 (−)
B2
Input 4 (+)
B3
Input 4 (−)
B4
AG
B5
N.C.
B6
N.C.
B7
N.C.
B8
N.C.
B9
A1
Input 1 (+)
A2
Input 1 (−)
A3
Input 3 (+)
A4
Input 3 (−)
A5
AG
A6
N.C.
A7
N.C.
A8
N.C.
A9
N.C.
A1
Input 1 (+)
A2
Input 1 (−)
A3
Input 3 (+)
A4
Input 3 (−)
A5
AG
A6
Input 5 (+)
A7
Input 5 (−)
A8
Input 7 (+)
A9
Input 7 (−)
CJ1W-AD081-V1
Input 2 (+)
B1
Input 2 (−)
B2
Input 4 (+)
B3
Input 4 (−)
B4
AG
B5
Input 6 (+)
B6
Input 6 (−)
B7
Input 8 (+)
B8
Input 8 (−)
B9
Note: 1.
2.
3.
4.
The analog input numbers that can be used are set in the Data Memory (DM).
The input signal ranges for each input are set in the Data Memory (DM). They can be set in units of input numbers.
The AG terminals are connected to the 0 V analog circuit in the Unit. Connecting shielded input lines can improve noise resistance.
Do not connect anything to NC terminals.
7
CJ1W-AD/DA/MAD
Analog Output Units CJ1W-DA021/DA041/DA08V/DA08C
Specifications
Item
CJ1W-DA021
CJ1W-DA041
Unit type
CJ-series Special I/O Unit
Isolation *1
Between I/O and PLC signals: Photocoupler
(No isolation between each I/O signals.)
External terminals
18-point detachable terminal block (M3 screws)
Affect on CPU Unit cycle time
0.2 ms
Power consumption
5 VDC, 120 mA max.
CJ1W-DA08V
CJ1W-DA08C
5 VDC, 140 mA max.
24 VDC +10%
−15% (inrush current: 20 A max., pulse width: 1 ms max.)
External power supply
140 mA max.
200 mA max.
140 mA max.
Dimensions
31 × 90 × 65 mm (W × H × D)
Weight
150 g max.
General specifications
Conforms to general specifications for SYSMAC CJ-series Series.
Mounting position
CJ-series CPU Rack or CJ-series Expansion Rack
Maximum number of Units
Units per Rack (CPU Rack or Expansion Rack): 10 Units max. *2
Data exchange with CPU Unit *3
Special I/O Unit Area
CIO 200000 to CIO 295915
(Words CIO 2000 to CIO 2959)
170 mA max.
Internal Special I/O Unit DM Area
(D20000 to D29599)
Output Specifications and Functions
Item
CJ1W-DA021
CJ1W-DA041
Number of analog outputs
2
4
Output signal range *4
1 to 5 V/4 to 20 mA
0 to 5 V
0 to 10 V
−10 to +10 V
Output impedance
0.5 Ω max. (for voltage output)
Max. output current (for 1 point)
CJ1W-DA08V
CJ1W-DA08C
8
8
1 to 5 V
0 to 5 V
0 to 10 V
−10 to +10 V
4 to 20 mA
12 mA (for voltage output)
2.4 mA
(for voltage output)
−
Maximum permissible load
resistance
600 Ω (current output)
−
350 Ω
Resolution
4,000 (full scale)
4,000/8,000 *8
Set data
16-bit binary data
25°C
Voltage output: ±0.3% of F.S.
Current output: ±0.5% of F.S.
±0.3% of F.S.
±0.3% of F.S.
0°C to 55°C
Voltage output: ±0.5% of F.S.
Current output: ±0.8% of F.S.
±0.5% of F.S.
±0.6% of F.S.
D/A conversion time *6
1.0 ms max. per point
1.0 ms or 250 μs max. per point
Output hold function
Outputs the specified output status (CLR, HOLD, or MAX) under any of the following circumstances.
When the Conversion Enable Bit is OFF. *7
In adjustment mode, when a value other than the output number is output during adjustment.
When output setting value error occurs or PLC operation stops.
When the CPU Unit is on standby.
When the Load is OFF.
Scaling function
Setting values in any specified unit within a range of ±32,000 as the upper and lower limits allows D/A
conversion to be executed and analog signals to be output with these values as full scale.
(With the CJ1W-DA08V/DA08C, this function is enabled only for a conversion time of 1.0 ms and a
resolution of 4,000.)
Accuracy *5
*1. Do not apply a voltage higher than 600 V to the terminal block when performing withstand voltage test on this Unit.
*2. The maximum number of Analog Output Units that can be mounted to one Rack varies depending on the current consumption of the other
Units mounted to the Rack.
Select a 24-VDC power supply based on the surge current. The following OMRON external power supplies are recommended.
Manufacturer
OMRON
Model number
Specifications
S8VS-06024
100 to 240 VAC, 60 W
S8VS-12024
100 to 240 VAC, 120 W
S8VM-05024
100 to 240 VAC, 50 W
S8VM-10024
100 to 240 VAC, 100 W
8
CJ1W-AD/DA/MAD
*3. Data exchange methods with the CPU Unit are as follows:
Special I/O Unit Area in CIO Area
10 words per Unit
CIO 2000 to CIO 2959
Refreshed cyclically
(CIO 200000 to CIO 295915)
100 words per Unit
Special I/O Unit Area in DM Area
Refreshed at power ON or
D20000 to D29599
restart
CPU Unit to Analog Analog output values
I/O Unit
Conversion enable bits
Analog I/O Unit to
CPU Unit
Alarm flags
Output signal conversion settings and signal range
CPU Unit to Analog
settings
I/O Unit
Output status when holding outputs
*4. Output signal ranges can be set for each output.
*5. The accuracy is given for full scale. For example, an accuracy of ±0.3% means a maximum error of ±12 (BCD) at a resolution of 4,000. For
the CJ1W-DA021/041, the accuracy is at the factory setting for a current output. When using a voltage output, adjust the offset gain as required.
*6. D/A conversion time is the time required for converting and outputting the PLC data. It takes at least one cycle for the data stored in the PLC
to be read by the Analog Output Unit.
*7. When the operation mode for the CPU Unit is changed from RUN mode or MONITOR mode to PROGRAM mode, or when the power is turned
ON, the Output Conversion Enable Bit will turn OFF. The output status specified according to the output hold function will be output.
*8. The CJ1W-DA08V/08C can be set to a conversion cycle of 250 μs and a resolution of 8,000 using the setting in D(m+18).
Output Function Block Diagram
Analog Output Unit
Output value,
hold
Output hold
enabled
Analog output 1
D/A
Output hold
disabled
Analog output 2
Same as above.
Analog output 3
Same as above.
Analog output 4
Same as above.
Output value,
no hold
CPU Unit
Special I/O
Unit Area
Analog
output 1
set value
Only analog outputs 1 and 2 are
used by the CJ1W-DA021.
9
CJ1W-AD/DA/MAD
External Interface
CJ1W-DA021/041/08V/08C
Side
Front
Slider
With Terminal Block
Indicators
DA041
RUN
ERC
ERH
ADJ
78
23
No.
456
MACH
x10 1
A1
901
Unit number
switches
B1
901
456
78
23
x10 0
O
N
Expansion
connector
1 2
MODE
Terminal block
Terminal block lock lever
(pull down to release terminal block)
Slider
Operating mode switch
(Not applicable to DA08V.)
DIN Track mounting pin
The terminal block is attached by a connector. It can be removed by pressing down on the lever at the bottom of the terminal block. Be sure that
this lever is raised during normal operation.
Indicators
The indicators show the operating status of the Unit. The following table shows the meanings of the indicators.
LED
RUN (green)
ERC (red)
Meaning
Operating
Error detected by Unit
Indicator
Lit
Not lit
Lit
Not lit
ERH (red)
Error in the CPU Unit
ADJ (yellow)
Adjusting
Lit
Not lit
Flashing
Not lit
Operating status
Operating in normal mode.
Unit has stopped exchanging data with the CPU Unit.
Alarm has occurred (such as disconnection detection) or initial
settings are incorrect.
Operating normally.
Error has occurred during data exchange with the CPU Unit.
Operating normally.
Operating in offset/gain adjustment mode.
Other than the above.
10
CJ1W-AD/DA/MAD
Internal Circuit
The following diagrams show the internal circuit of the analog output section.
Voltage Output Circuits
Voltage output section
Output
switch and
conversion
circuit
AMP
Voltage
output (+)
Voltage
output (–)
AG (common to all outputs)
Current Output Circuit
Current output section
Current
output (+)
AMP
Output
switch and
conversion
circuit
AMP
Current
output (−)
Internal Configuration
MPU
Bus
interface
RAM ROM
Photocoupler insulation
Indicators/Switch
OUTPUT
D/A
converter
Multiplexer
and
amplifier
Externally
connected
terminal
EEPROM
Oscillator
Division
+15 V
+24 V Insulation-type
DC-to-DC
converter
CJ-series PLC
Regulator
+5 V
−15 V
External power
supply (24 VDC)
11
CJ1W-AD/DA/MAD
Terminal Arrangement
The signal names corresponding to the connecting terminals are as shown in the following diagram.
CJ1W-DA021
Voltage output 2 (+)
B1
Output 2 (−)
B2
Current output 2 (+)
B3
N.C.
B4
N.C.
B5
N.C.
B6
N.C.
B7
N.C.
B8
0V
A1
Voltage output 1 (+)
A2
Output 1 (−)
A3
Current output 1 (+)
A4
N.C.
A5
N.C.
A6
N.C.
A7
N.C.
A8
N.C.
A9
24 V
A1
Voltage output 1 (+)
A2
Output 1 (−)
A3
Current output 1 (+)
A4
Voltage output 3 (+)
A5
Output 3 (−)
A6
Current output 3 (+)
A7
N.C.
A8
N.C.
A9
24 V
B9
CJ1W-DA041
Voltage output 2 (+)
B1
Output 2 (−)
B2
Current output 2 (+)
B3
Voltage output 4 (+)
B4
Output 4 (−)
B5
Current output 4 (+)
B6
N.C.
B7
N.C.
B8
0V
B9
CJ1W-DA08V (Voltage Output)
and CJ1W-DA08C (Current Output)
Output 2 (+)
B1
Output 2 (−)
B2
Output 4 (+)
B3
Output 4 (−)
B4
Output 6 (+)
B5
Output 6 (−)
B6
Output 8 (+)
B7
Output 8 (−)
B8
0V
B9
Note: 1.
2.
3.
4.
A1
Output 1 (+)
A2
Output 1 (−)
A3
Output 3 (+)
A4
Output 3 (−)
A5
Output 5 (+)
A6
Output 5 (−)
A7
Output 7 (+)
A8
Output 7 (−)
A9
24 V
The analog output numbers that can be used are set in the Data Memory (DM).
The output signal ranges for each output are set in the Data Memory (DM). They can be set in units of output numbers.
The N.C. terminals are not connected to internal circuit.
The following OMRON external power supplies are recommanded.
Manufacturer
OMRON
Model number
Specifications
S8VS-06024
100 to 240 VAC, 60 W
S8VS-12024
100 to 240 VAC, 120 W
S8VM-05024
100 to 240 VAC, 50 W
S8VM-10024
100 to 240 VAC, 100 W
5. Use a separate power supply from the one used for Basic I/O Units. Faulty Unit operation may be caused by noise if power is supplied
from the same source.
12
CJ1W-AD/DA/MAD
Analog I/O Unit CJ1W-MAD42
Specifications
Item
CJ1W-MAD42
Unit type
CJ-series Special I/O Unit
Isolation
Between I/O and PLC signals: Photocoupler
(No isolation between each I/O signals.)
External terminals
18-point detachable terminal block (M3 screws)
Current consumption
580 mA max. at 5 V DC
Dimensions
31 × 90 × 65 mm (W × H × D)
Weight
150 g max.
General specifications
Conforms to general specifications for SYSMAC CJ-series Series.
Mounting position
CJ-series CPU Rack or CJ-series Expansion Rack
(Cannot be mounted to a C200H Expansion I/O Rack or a SYSMAC BUS Slave Rack.)
Maximum number of Units *
CPU Rack: 7 Units max.
Expansion Rack: 8 Units max.
Overall system:
(7 Units max. on CPU Rack) + (8 Units per Expansion Rack × 3 Racks) = 31 Units max.
Special I/O Unit Area CIO 200000 to CIO 295915 (Words CIO 2000 to CIO 2959):
Data exchange with CPU Units Exchanges 10 words of data per Unit.
Internal Special I/O Unit DM Area (D20000 to D29599)
* The maximum number of Analog I/O Units that can be mounted to one Rack will varies depending on the Power Supply Unit model and the
current consumption of the other Units mounted to the Rack.
Power Supply Units
Maximum number of Units
CJ1W-PA205R/PD025
CPU Rack: 7 Units max.
Expansion Racks: 8 Units/Rack max.
CJ1W-PA202
CPU Rack: 3 Units max.
Expansion Racks: 4 Units/Rack max.
Input Specifications and Functions
Item
Voltage input
Current input
Number of analog inputs
4
Input signal range *1
1 to 5 V
0 to 5 V
0 to 10 V
−10 to 10 V
4 to 20 mA *2
Maximum rated input (for 1
point) *3
±15 V
±30 mA
External input impedance
1 MΩ min.
250 Ω (rated value)
Resolution
4,000/8,000 (full scale) *6
Converted output data
Accuracy *4
16-bit binary data
25°C
±0.2% of F.S.
0°C to 55°C
±0.4% of F.S.
A/D conversion time *5
1.0 ms/500 μs max. per point
Mean value processing
Stores the last "n" data conversions in the buffer, and stores the mean value of the conversion values.
Buffer number: n = 2, 4, 8, 16, 32, 64
Peak value holding
Stores the maximum conversion value while the Peak Value Hold Bit is ON.
Scaling
Enabled only for conversion time of 1 ms and resolution of 4,000. Setting any values within a range of ±32,000
as the upper and lower limits allows the A/D conversion result to be output with these values as full scale.
Input disconnection detection Detects the disconnection and turns ON the Disconnection Detection Flag.
*1. Input and output signal ranges can be set for each input and output.
*2. Voltage input or current input are chosen by using the voltage/current switch at the back of the terminal block.
*3. The Analog I/O Unit must be operated according to the input specifications provided here. Operating the Unit outside these specifications will
cause the Unit to malfunction.
*4. The accuracy is given for full scale. For example, an accuracy of ±0.2% means a maximum error of ±8 (BCD) at a resolution of 4,000.
*5. A/D conversion time is the time it takes for an analog signal to be stored in memory as converted data after it has been input. It takes at least
one cycle before the converted data is read by the CPU Unit.
*6. By means of the D(m+18) setting, the resolution can be changed to 8,000, and the conversion time can be changed to 500 μs.
13
CJ1W-AD/DA/MAD
Output Specifications
Item
Voltage output
Current output
Number of analog outputs
2
Output signal range *1
1 to 5 V
0 to 5 V
0 to 10 V
−10 to 10 V
4 to 20 mA
External output impedance
0.5 Ω max.
−
Maximum external output
current (for 1 point)
2.4 mA
−
Maximum allowed load
resistance
−
600 Ω
Resolution
4,000/8,000 (full scale) *5
Set data
Accuracy *2
16-bit binary data
25°C
±0.3% of F.S.
±0.3% of F.S.
0°C to 55°C
±0.5% of F.S.
±0.6% of F.S.
D/A conversion time *3
1.0 ms/500 μs max. per point
Output hold function
Outputs the specified output status (CLR, HOLD, or MAX) under any of the following circumstances.
When the Conversion Enable Bit is OFF. *4
In adjustment mode, when a value other than the output number is output during adjustment.
When output setting value error occurs or PLC operation stops.
When the CPU Unit is on standby.
When the Load is OFF.
Scaling
Enabled only for conversion time or 1 ms and resolution of 4,000. Setting any values within a range of ±32,000
as the upper and lower limits allows D/A conversion to be executed and analog signals to be output with these
values as full scale.
Ratio conversion function *5
Stores the results of positive and negative gradient analog inputs calculated for ratio and bias as analog output
values.
Positive gradient: Analog output = A × Analog input + B
(A: 0 to 99.99, B: 8,000 to 7FFF hex)
Negative gradient:Analog output = F − A × Analog input + B
(A: 0 to 99.99, B: 8,000 to 7FFF hex, F: Output range maximum value)
*1. Input and output signal ranges can be set for each input and output.
*2. The accuracy is given for full scale. For example, an accuracy of ±0.2% means a maximum error of ±8 (BCD) at a resolution of 4,000.
*3. D/A conversion time is the time required for converting and outputting the PLC data. It takes at least one cycle for the data stored in the PLC
to be read by the Analog I/O Unit.
*4. When the operation mode for the CPU Unit is changed from RUN mode or MONITOR mode to PROGRAM mode, or when the power is turned
ON, the Output Conversion Enable Bit will turn OFF. The output status specified according to the output hold function will be output.
*5. By means of the D(m+18) setting, the resolution can be changed to 8,000, and the conversion time can be changed to 500 μs.
14
CJ1W-AD/DA/MAD
I/O Function Block Diagram
Analog I/O Unit
Input
disconnection
detection
Analog input 1
Mean value
processing disabled
CPU Unit
Peak value hold
function disabled
Scaling
enabled
I/O
refresh
A/D
Scaling
disabled
Analog input 2
Same as above.
Analog input 3
Same as above.
Analog input 4
Same as above.
Mean value
processing enabled
Peak value hold
function enabled
Ratio conversion
disabled
Ratio
conversion Ratio
conversion
enabled
Output hold
enabled
Analog
output 1
conversion
value
Scaling
enabled
Analog
output 1
D/A
Scaling
disabled
Analog
output 2
Same as above.
Output hold
disabled
Special I/O
Unit Area
Analog
input 1
conversion
value
Ratio conversion
disabled
15
CJ1W-AD/DA/MAD
External Information
Front
With Terminal Block Removed
With Terminal Block
Indicators
MAD42
MAD42
456
456
901
x10 0
901
78
78
Voltage/current
switch
ON
1
2
ON
1
2
23
x10 0
78
456
No.
Terminal block
A1
23
456
MACH
x10 1
B1
901
78
901
No.
x10 1
RUN
ERC
ERH
ADJ
A1
23
MACH
User
number
setting
switch
B1
23
RUN
ERC
ERH
ADJ
Terminal block
DIN Track
mounting pin
Terminal block lock lever
(pull down to release
terminal block)
Side
Slider
Expansion connector
Slider
16
CJ1W-AD/DA/MAD
Indicators
The indicators show the operating status of the Unit. The following table shows the meanings of the indicators.
LED
Meaning
RUN (green)
Indicator
Lit
Operating
ERC (red)
Not lit
Lit
Error detected by Unit
Not lit
ADJ (yellow)
Flashing
Adjusting
ERH (red)
Not lit
Lit
Error in the CPU Unit
Not lit
Operating status
Operating in normal mode.
Unit has stopped exchanging data with the CPU Unit.
Alarm has occurred (such as disconnection detection) or initial
settings are incorrect.
Operating normally.
Operating in offset/gain adjustment mode.
Other than the above.
Error has occurred during data exchange with the CPU Unit.
Operating normally.
Internal Circuit
The following diagrams show the internal circuit of the analog I/O section.
Input Circuits
15 kΩ
Input (+)
15 kΩ
Input circuit
and
conversion
circuit
250 Ω
1 MΩ
15 kΩ
15 kΩ
Input (–)
AG
(analog 0 V)
Voltage/
current
input switch
1 MΩ
AG (common to all inputs)
Output Circuits
Output
switch and
conversion
circuit
AMP
Voltage
output (+)
Voltage
output (–)
AG (common to all outputs)
Current Output Circuits
AMP
Output
switch and
conversion circuit
AMP
Current
output (+)
Current
output (–)
17
CJ1W-AD/DA/MAD
Internal Configuration
Photocoupler insulation
Indicators/Switch
MPU
Bus
interface
RAM ROM
OUTPUT
D/A
converter
Multiplexer
and
amplifier
A/D
converter
Multiplexer
and
amplifier
Externally
connected
terminal
INPUT
EEPROM
Oscillator
Division
+15 V
5V
Insulation-type
DC-to-DC
converter
Regulator
+5 V
−15 V
CJ-series PLC
Terminal Arrangement
The signal names corresponding to the connecting terminals are as shown in the following diagram.
CJ1W-MAD42
Voltage output 2 (+)
B1
Output 2 (–)
B2
Current output 2 (+)
B3
N.C.
B4
Input 2 (+)
B5
Input 2 (–)
B6
AG
B7
Input 4 (+)
B8
Input 4 (–)
B9
Note: 1.
2.
3.
4.
A1
Voltage output 1 (+)
A2
Output 1 (–)
A3
Current output 1 (+)
A4
N.C.
A5
Input 1 (+)
A6
Input 1 (–)
A7
AG
A8
Input 3 (+)
A9
Input 3 (–)
The analog I/O numbers that can be used are set in the Data Memory (DM).
The I/O signal ranges for each input and output are set in the Data Memory (DM). They can be set in units of I/O numbers.
The AG terminal (A7, B7) is connected to the 0 V analog circuit in the Unit. Connecting shielded input lines can improve noise resistance.
The N.C. terminals (A4, B4) are not connected to internal circuit.
18
CJ1W-AD/DA/MAD
Dimensions
(Unit: mm)
CJ-series
CJ1W-AD041-V1/081-V1
CJ1W-DA021/041/08V/08C
CJ1W-MAD42
89
31
65
2.7
Terminal Block
Dimensions
17.5
8.2
AD081-V1
RUN
ERC
ERH
ADJ
B1
A1
6.4
456
901
No.
x10 1
78
7.62
23
MACH
901
23
x10 0
456
78
90
74.77
O
N
1 2
MODE
2.7
Note: The appearance varies with the model.
About Manuals
Cat. No
W345
Model
SYSMAC CS/CJ Series
CS1W-AD041-V1/081-V1/161
CS1W-DA041/08V/08C
CS1W-MAD44
CJ1W-AD041-V1/081-V1
CJ1W-DA021/041/08V/08C
CJ1W-MAD42
Manual name
CS/CJ-series
Analog I/O Units
Operation Manual
Application
Contents
Provides information on using the
Information on using the Analog I/O
CS/CJ-series Analog Input, Analog
Units.
Output, and Analog I/O Units.
19
Read and Understand This Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or
comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified)
from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER
WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS
IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT
LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's
application or use of the products.
At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,
machine, system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:
• Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.
• Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,
safety equipment, and installations subject to separate industry or government regulations.
• Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or
establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual
specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the
result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON
Warranty and Limitations of Liability.
ERRORS AND OMISSIONS
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,
typographical, or proofreading errors, or omissions.
2008.11
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2008 All Right Reserved.