CS1 BASIC I/O MODULES
Basic I/O Selection
This section describes the standard, high-density and mixed I/O modules,
terminal blocks and cables used in a CS1 system.
Input Configuration
What input voltage do you need?
DC
Type
5 VDC
12 VDC
12-24 VDC
24 VDC
Model number
C200H-ID501
C200H-ID111
C200H-ID211
CS1W-ID211
CS1W-ID231
CS1W-ID261
CS1W-ID291
CS1W-IDP01
See page
C-42
C-42
C-42
C-42
AC
Type
100-120 VAC
200-240 VAC
Model number
C200H-IA121
C200H-IA221
C200H-IA122V
CS1W-IA211
C200H-IA222V
C-42
See page
C-42
AC/DC
Type
12-24 VAC/DC
24 VAC/DC
100-120 VAC/DC
Model number
C200H-IM211
C200H-IM212
CS1W-IA111
See page
C-42
C-42
C-42
How many input points are required?
Choose from the available point densities below.
Input Points
8
16
32
64
96
DC inputs
C200H-ID211
CS1W-ID211
CS1W-ID231
CS1W-ID261
CS1W-ID291
CS1W-IDP01
C200H-ID501
C200H-ID111
AC inputs
C200H-IA121
CS1W-IA211
–
–
–
C200H-IA221
C200H-IA122V
–
–
–
C-42
C-42
C-42
C200H-IA222V
AC/DC inputs
C200H-IM211
See page
C-42
CS1W-IA111
C200H-IM212
C-38
C-42
CS1 BASIC I/O MODULES
What are the input current requirements?
Input Current
DC inputs
4.1 mA or Below
C200H-ID111
7 mA or Below
CS1W-ID211
10 mA or Below
C200H-ID211
CS1W-ID231
CS1W-ID261
CS1W-ID291
CS1W-IDP01
AC inputs
–
–
CS1W-IA211
C200H-IA121
C200H-IA122V
C200H-IA221
C200H-IA222V
AC/DC inputs
CS1W-IA111 (DC In)
C200H-IM212
CS1W-IA111 (AC In)
C200H-IM211
See page
C-42
C-42
C-42
Are terminal blocks and connection cables necessary?
Input modules with 8 or 16 points have removable terminal blocks that accept direct
wiring from input devices. High-density 32-, 64- and 96-point modules use cables and
terminal blocks to connect inputs and consolidate wiring back to the control panel. For
more information see page C-67.
Module
Connector Type
Terminal Block
Cable
CS1W-ID211
Removable terminal block
Not required
Not required
Fujitsu-compatible
connector on module
XW2B-40G4 or G5
XW2Z-B
Two XW2B-40G4 or G5
Two XW2Z-B
CS1W-IDP01
CS1W-IA111
CS1W-IA211
C200H-ID211
C200H-IA121
C200H-IA221
C200H-IA122V
C200H-IA222V
C200H-IM211
C200H-IM212
CS1W-ID231
CS1W-ID261
CS1W-ID291
Two XW2B-60G4 or G5
Two XW2Z-H-1
C200H-ID501
Two XW2B-20G4 or G5
Two XW2Z-A
C200H-ID111
Two XW2B-40G4 or G5
Two XW2Z-B
Note: For more information on wiring connections, please refer to the wiring section starting on page D-1.
C-39
CS1 BASIC I/O MODULES
Output Configuration
How many output points are required?
Choose from the available point densities below.
Output Points
5
8
12
16
32
64
96
Transistor
–
C200H-OD411
C200H-OD211
CS1W-OD211
CS1W-OD231
CS1W-OD261
CS1W-OD291
C200H-OD215
C200H-OD219
C200H-OD213
Sinking (NPN)
C200H-OD218
C200H-OD501
Transistor
C200H-OD214
–
C200H-OD217
C200H-OD216
Sourcing (PNP)
CS1W-OC201
Relay
C200H-OC223
Triac
–
CS1W-OA201
See page
C-51
C-51, C-52
CS1W-OD212
CS1W-OD232
CS1W-OD262
CS1W-OD292
C200H-OD21A
C200H-OC222
CS1W-OC211
–
–
–
C200H-OA222V
CS1W-OA211
–
–
–
C-51, C-52
C-51, C-52
C-51
C-51
C200H-OC221
C200H-OA224
C-51, C-52
Are terminal blocks and connection cables necessary?
Output modules with 5, 8 or 16 points have removable terminal blocks that accept direct wiring from output devices. High-density 32-, 64- and 96point modules use cables and terminal blocks to connect inputs and consolidate wiring back to the control panel. For more information see page C-67.
Module
Connector Type
Terminal Block
Cable
CS1W-OC201
Removable terminal block
Not required
Not required
Fujitsu-compatible connector
on module
XW2B-40G4 or G5
XW2Z-B
XW2B-40G4 or G5
XW2Z-B
CS1W-OC211
CS1W-OD211
CS1W-OD212
CS1W-OA201
CS1W-OA211
C200H-OC223
C200H-OC221
C200H-OC222
C200H-OD411
C200H-OD213
C200H-OD214
C200H-OD216
C200H-OD211
C200H-OD217
C200H-OD21A
C200H-OA222V
C200H-OA224
CS1W-OD231
CS1W-OD232
CS1W-OD261
Two XW2B-40G4 or G5
Two XW2Z-B
CS1W-OD262
Two XW2B-40G4 or G5
Two XW2Z-B
CS1W-OD291
Two XW2B-60G4 or G5
Two XW2Z-H-1
CS1W-OD292
Two XW2B-60G4 or G5
Two XW2Z-H-1
C200H-OD215
Two XW2B-20G4 or G5
Two XW2Z-A
C200H-OD218
XW2B-40G4 or G5
XW2Z-B
C200H-OD219
Two XW2B-40G4 or G5
Two XW2Z-B
C200H-OD501
Two XW2B-20G4 or G5
Two XW2Z-A
Note: For more information on wiring connections, please refer to the wiring section starting on page D-1.
C-40
CS1 BASIC I/O MODULES
Mixed I/O Configuration
What input voltage and transistor output type (NPN or PNP) do you need?
Input Voltage
5 VDC
12 VDC
24 VDC
See page
Sinking outputs (NPN)
CS1W-MD561
C200H-MD115
CS1W-MD261
C-63
CS1W-MD291
C-63
C200H-MD215
C-63
CS1W-MD262
C-63
CS1W-MD292
C-63
C200H-MD501
Sourcing outputs (PNP)
–
–
How many input/output points are required?
Choose from the available point densities below.
I/O Points
16 In/16 Out
32 In/32 Out
48 In/ 48 Out
See page
C200H-MD501
CS1W-MD261
CS1W-MD291
C-63
C200H-MD115
CS1W-MD262
CS1W-MD292
C-63
C200H-MD215
CS1W-MD561
C-63
Are terminal blocks and connection cables necessary?
High-density I/O modules use cables and terminal blocks to connect inputs/outputs and
consolidate wiring back to the control panel. For more information see page C-67.
Module
Connector Type
Terminal Block
Cable
CS1W-MD261
Fujitsu-compatible connector
on module
Two XW2B-40G4 or G5
Two XW2Z-B
Two XW2B-40G4 or G5
Two XW2Z-B
CS1W-MD561
Two XW2B-40G4 or G5
Two XW2Z-B
CS1W-MD291
Two XW2B-60G4 or G5
Two XW2Z-H-1
CS1W-MD292
Two XW2B-60G4 or G5
Two XW2Z-H-1
CS1W-MD262
Note: For more information on wiring connections, please refer to the wiring section starting on page D-1.
Configuration Guidelines
Remember to add all the current consumptions of basic I/O, special I/O modules, and CPU bus units to determine which power
supply is appropriate.
Please refer to the System Configuration section for current consumption of individual modules.
For more I/O options, see the Industrial Networks and Communication section for DeviceNet I/O on page C-123 and
CompoBus/S I/O on page C-138.
C-41
Basic and High-density I/O Modules
Input Module Specifications
Input Module
CS1W-ID211
16 points
Input Module
CS1W-ID231
32 points
Input Module
CS1W-ID261
64 points
Input Module
CS1W-ID291
96 points
AC Input Modules
CS1W-IA111/IA211
16 points
J DC Input Modules
Classification
CS1 Basic I/O
/
Input voltage
24 VDC
Inputs
16 pts
32 pts
64 pts
96 pts
Connections
Removable terminal block
Connector
Input Current
7 mA
6 mA
6 mA
5 mA
Model
CS1W-ID211
CS1W-ID231
CS1W-ID261
CS1W-ID291
C200H Basic I/O
12 to 24 VDC
8 pts
Connector
10 mA
C200H-ID211
C200H Group-2 I/O
12 VDC
64 pts
4.1 mA
C200H-ID111
Note: The previous Modules work with the CS1: C200H-ID212/215/216/217/218/219.
J High Speed DC Input Module
Classification
Input voltage
Inputs
Connections
Min. pulse width
Model
CS1 Basic I/O
24 VDC
16 pts
Removable block
0.1 ms
CS1W-IDP01
J TTL Input Module
Classification
Input voltage
Inputs
Connections
Remarks
Model
C200H Special I/O
5 VDC
32 pts
Connector
8 pts. can be set as
high-speed inputs
CS1W-ID501
J AC Input Modules
Classification
Input voltage
Inputs
Connections
Remarks
Model
CS1 Basic I/O
/
100 to 120 VAC/VDC
16 pts
Removable terminal block
—
CS1W-IA111
200 to 240 VAC
16 pts
—
CS1W-IA211
100 to 120 VAC
8 pts
p
—
C200H-IA121
—
C200H-IA221
EC compliant
C200H-IA122
—
C200H-IA222
C200H Basic I/O
/
Removable terminal block
200 to 240 VAC
100 to 120 VAC
16 p
pts
200 to 240 VAC
Note: Previous C200H modules work with the CS1: C200H-IA122/222.
J AC/DC Input Modules
Classification
Input voltage
Inputs
Connections
Remarks
Model
C200H Basic I/O
/
12 to 24 VAC/VDC
8 pts
Removable terminal block
—
C200H-IM211
24 VAC/VDC
16 pts
—
C200H-IM212
C--42
Programmable Controller
CS1
Basic and High-Density I/O Modules
Input Modules — Circuit Configuration and Terminal Arrangement
J Input Modules
Model
Circuit configuration
Terminal arrangement
CS1W-ID211
(16 pts)
CS1W-ID231
DC Input Module
(32 pts)
Programmable Controller
CS1
C--43
Basic and High-density I/O Modules
Input Modules — Circuit Configuration and Terminal Arrangement
J DC Input Modules
Model
Circuit configuration
Terminal arrangement
CS1W-ID261
DC Input Module
(64 pts)
(This table continues on the next page.)
C--44
Programmable Controller
CS1
Basic and High-Density I/O Modules
Input Modules — Circuit Configuration and Terminal Arrangement
DC Input Modules (continued)
Model
Circuit configuration
CS1W-ID291
Input Module
(96 pts)
Terminal arrangement
(This table continues on the next page.)
Programmable Controller
CS1
C--45
Basic and High-density I/O Modules
Input Modules — Circuit Configuration and Terminal Arrangement
DC Input Modules (continued)
Model
Circuit configuration
Terminal arrangement
C200H-ID211
DC Input Module
(8 pts)
C200H-ID111
DC Input Module
(64 pts)
Illustrator says it can’t open because
wrong kind of file.
Ω
Ω
40.eps
Ω
Ω
CS1W-IDP01
High Speed
DC Input Module
(16 pts)
(This table continues on the next page.)
C--46
Programmable Controller
CS1
next graphic after 40.eps
Basic and High-Density I/O Modules
Input Modules — Circuit Configuration and Terminal Arrangement
DC Input Modules (continued)
Model
Circuit configuration
C200H-ID501
Special I/O
(32 pts)
Programmable Controller
CS1
C--47
Basic and High-density I/O Modules
Input Modules — Circuit Configuration and Terminal Arrangement
J AC Input Modules
Model
Circuit configuration
Terminal arrangement
CS1W-IA111
AC/DC Input Module
(16 pts)
Ω
Ω
CS1W-IA211
AC Input Module
(16 pts)
C200H-IA121
AC Input Module
(8 pts)
(This table continues on the next page.)
C--48
Programmable Controller
CS1
Basic and High-Density I/O Modules
Input Modules — Circuit Configuration and Terminal Arrangement
AC Input Modules (continued)
Model
Circuit configuration
Terminal arrangement
C200H-IA221
AC input module
(8 points)
C200H-IA122
AC input module
(16 points)
C200H-IA222
AC input module
(16 points)
Programmable Controller
CS1
C--49
Basic and High-density I/O Modules
Input Modules — Circuit Configuration and Terminal Arrangement
J AC/DC Input Modules
Model
Circuit configuration
Terminal arrangement
C200H-IM211
AC/DC Input
Modules
(8 points)
C200H-IM212
AC/DC Input
Modules
(16 points)
C--50
Programmable Controller
CS1
Basic and High-Density I/O Modules
Output Modules
Output Module
CS1W-OC21
16 points
Output Module
CS1W-OD23
32 points
Output Module
CS1W-OD26
64 points
Output Module
CS1W-OD29
96 points
AC Output Modules
CS1W-OD21
16 points
J Relay Contact Output Modules
Classification
CS1 Basic I/O
/
C200H Basic I/O
/
Outputs
8 pts (independent)
16 pts
5 pts
8 pts
Maximum switching capacity
2 A,, 250 VAC
Connector type
Removeable
t
terminal
i l block
bl k
12 pts
Model
CS1W-OC201
CS1W-OC211
C200H-OC223
C200H-OC221
C200H-OC222
Note: The previous Modules work with the CS1: C200H-OC224/224N/225/226N.
J Transistor Output Modules
Classification
Outputs
Maximum switching capacity
Connections
Model
CS1 Basic I/O
/ Module
16 p
pts
12 to 24 VDC, 0.5 A/pt, 8 A/unit sinking
Removable terminal
bl k
block
CS1W-OD211
Connector
CS1W-OD231
24 VDC, 0.5 A/pt, 5 A/unit, sourcing,
load short protection, alarm
32 p
pts
64 pts
96 p
pts
12 to 24 VDC, 0.5 A/pt, 5 A/unit sinking
24 VDC, 0.5 A/pt, 5 A/unit, sourcing,
load short protection, alarm
CS1W-OD232
12 to 24 VDC, 0.3 A/pt, 6.4 A/unit
sinking
CS1W-OD261
24 VDC, 0.3 A/pt, 6.4 A/unit, sourcing,
load short protection, alarm
CS1W-OD262
12 to 24 VDC, 0.1 A sinking, 7.2 A/unit
CS1W-OD291
12 to 24 VDC, 0.1 A sourcing, 7.2 A/unit
C200H Basic I/O
/
M d l
Module
C200H Group-2 I/O
Module
C200H Special I/O
module
CS1W-OD212
CS1W-OD292
Removable terminal
bl k
block
8 pts
12 to 48 VDC, 1 A sinking
8 pts
24 VDC, 2.1 A, sinking
8 pts
24 VDC, 0.8 A, sourcing, load short
protection
C200H-OD214
8 pts
5 to 24 VDC, 0.3 A sourcing
C200H-OD216
12 pts
24 VDC, 0.3 A, sinking
C200H-OD211
12 pts
5 to 24 VDC, 0.3 A sourcing
C200H-OD217
16 pts
24 VDC, 1.0 A, sourcing, load short
protection
C200H-OD21A
32 pts
16 mA at 4.5 V to 100 mA at 26.4 V,
sinking
64 pts
16 mA at 4.5 V to 100 mA at 26.4 V,
sinking
C200H-OD219
32 pts
16 mA at 4.5 V to 100 mA at 26.4 V,
sinking
C200H-OD215
(128-pt dynamic
outputs possible)
Connector
Programmable Controller
C200H-OD411
C200H-OD213
C200H-OD218
CS1
C--51
Basic and High-density I/O Modules
Output Modules
J TTL Output Module
Classification
Specifications
TTL output
p modules
5 VDC,, 35 mA
Model
Static output mode: 32 outputs
C200H-OD501
Dynamic output mode: 128 outputs
J Triac Output Modules
Classification
Outputs
Maximum switching capacity
Connections
Model
CS1 Basic I/O
/
8 pts
250 VAC, 1.2 A, 50/60 Hz
CS1W-OA201
16 pts
250 VAC, 0.5 A, 50/60 Hz
Removable terminal
bl k
block
16 pts
250 VAC, 0.5 A, 50/60 Hz
CS1W-OA221
12 pts
250 VAC, 0.3 A, 50/60 Hz
C200H-OA224
12 pts
250 VAC, 0.3 A, 50/60 Hz
C200H-OA222V
C200H Basic I/O
/
Note: Previous C200H-OA223 module can also be used with CS1 PLCs.
C--52
Programmable Controller
CS1
CS1W-OA211
Basic and High-Density I/O Modules
Output Modules — Circuit Configuration and Terminal Arrangement
J Output Modules
Model
Circuit configuration
Terminal arrangement
CS1W-OC201
(8 pts)
CS1W-OC211
(16 pts)
C200H-OC223
(5 pts)
C200H-OC221
(8 pts)
(This table continues on the next page.)
Programmable Controller
CS1
C--53
Basic and High-density I/O Modules
Output Modules — Circuit Configuration and Terminal Arrangement
Output Modules (Continued)
Model
Circuit configuration
Terminal arrangement
C200H-OC222
(12 pts)
J Transistor Output Modules
Model
Circuit configuration
Terminal arrangement
CS1W-OD211
(16 pts, sinking)
CS1W-OD212
(16 pts, sourcing)
(This table continues on the next page.)
C--54
Programmable Controller
CS1
Basic and High-Density I/O Modules
Output Modules — Circuit Configuration and Terminal Arrangement
Transistor Output Modules (Continued)
Model
Circuit configuration
CS1W-OD231
(32 pts, sinking)
CS1W-OD232
(32 pts, sourcing)
CS1W-OD261
(64 pts, sinking)
(This table continues on the next page.)
Programmable Controller
CS1
C--55
Basic and High-density I/O Modules
Output Modules — Circuit Configuration and Terminal Arrangement
Transistor Output Modules (Continued)
Model
Circuit configuration
CS1W-OD262
(64 pts, sourcing)
CS1W-OD291
(96 pts, sinking)
CS1W-OD292
(96 pts, sourcing)
(This table continues on the next page.)
C--56
Programmable Controller
CS1
Basic and High-Density I/O Modules
Output Modules — Circuit Configuration and Terminal Arrangement
Transistor Output Modules (Continued)
Model
Circuit configuration
C200H-OD213
(8 pts)
C200H-OD411
(8 pts)
x
C200H-OD211
(12 pts)
x
Programmable Controller
CS1
C--57
Basic and High-density I/O Modules
Output Modules — Circuit Configuration and Terminal Arrangement
Transistor Output Modules (Continued)
Model
Circuit configuration
C200H-OD218
(32 pts)
C200H-OD219
(64 pts)
(This table continues on the next page.)
C--58
Programmable Controller
CS1
Basic and High-Density I/O Modules
Output Modules — Circuit Configuration and Terminal Arrangement
Transistor Output Modules (Continued)
Model
Circuit configuration
C200H-OD216
(8 pts Sourcing)
C200H-OD214
(8 pts Sourcing)
C200H-OD217
(12 pts Sourcing)
C200H-OD217
(12 pts Sourcing)
(This table continues on the next page.)
Programmable Controller
CS1
C--59
Basic and High-density I/O Modules
Output Modules — Circuit Configuration and Terminal Arrangement
Transistor Output Modules (Continued)
C200H-OD215
(used for 32 static
outputs)
C200H-OD215
(used for 128
dynamic outputs)
J TTL Output Modules
Model
Circuit configuration
C200H-OD501
(Used for 32 static
outputs)
C200H-OD501
(Used for 128
Dynamic Inputs)
C--60
Programmable Controller
CS1
Basic and High-Density I/O Modules
Output Modules — Circuit Configuration and Terminal Arrangement
J Triac Output Modules
Model
Circuit configuration
CS1W-OA201
(8 pts)
CS1W-OA211
(16 pts)
C200H-OA221
(8 pts)
(This table continues on the next page.)
Programmable Controller
CS1
C--61
Basic and High-density I/O Modules
Output Modules — Circuit Configuration and Terminal Arrangement
Triac Output Modules (continued)
Model
Circuit configuration
C200H-OA222V
(12 pts)
C200H-OA224
(12 pts)
C--62
Programmable Controller
CS1
Basic and High-Density I/O Modules
Output Modules — Circuit Configuration and Terminal Arrangement
I/O Units
CS1W-MD26j
32/32 points
I/O Units
CS1W-MD29j
48/48 points
TTL I/O Unit
CS1W-MD561
32/32 points
J Mixed I/O Modules
Name
Classification
Inputs/
Outputs
Input
voltage
Max. switching capacity
Connections
Model
DC Input/
Transistor
O t t
Output
Modules
CS1
Basic I/O
U it
Units
32 inputs/
32 outputs
24 VDC
12 to 24 VDC, 0.3 A, sinking
Connector
CS1W-MD261
32 inputs/
32 outputs
48 inputs/
48 outputs
24 VDC
48 inputs/
48 outputs
C200H
Special
p
I/O Units
U it
24 VDC, 0.3 A, sourcing, load short
protection, alarm
CS1W-MD262
12 to 24 VDC, 0.1 A, sinking
CS1W-MD291
12 to 24 VDC, 0.1 A, sourcing
CS1W-MD292
16 inputs/
16 outputs
24 VDC
16 mA at 4.5 V to 100 mA at 26.4 VDC,
sinking
C200H-MD215
(See note 2)
16 inputs/
16 outputs
12 VDC
24 VDC, 50 mA, sinking
C200H-MD115
(See note 2)
Note: 1. In addition to the normal I/O functions, C200H High-density I/O Units (Special I/O Units) provide the following functions.
• Dynamic I/O (except for OD501/OD215): In stead of normal static inputs and normal static outputs, dynamic outputs and dynamic
inputs are used to increase I/O capacity to 128 inputs and 128 outputs through the use of strobe signal outputs. These functions can
be used to reduce wiring to devices with more digits, such as displays and keyboards.
• High-speed Inputs (except OD501/OD215): Eight of the inputs can be set as high-speed inputs to accurately input short pulses from
devices like photomicrosensors.
2. High-speed inputs, 128-pt dynamic outputs possible
J Mixed I/O TTL Modules
Name
Classification
Inputs/
Outputs
Input
voltage
Max. switching capacity
Connections
Model
TTL I/O
Modules
CS1
Basic I/O
32 inputs/
32 outputs
5 VDC
5 VDC, 35 mA
Connector
CS1W-MD561
(See note)
C200H
Special
I/O Units
16 inputs/
16 outputs
C200H-MD501
(See note)
Note: High-speed inputs, 128-pt dynamic outputs possible
Programmable Controller
CS1
C--63
Basic and High-density I/O Modules
Mixed I/O Modules
J Mixed I/O Modules
Model
Circuit configuration
CS1W-MD261
(32/32 pts, sinking)
CS1W-MD291
(48/48 pts, sinking)
CS1W-MD262
(32/32 pts, sourcing)
(This table continues on the next page.)
C--64
Programmable Controller
CS1
Basic and High-Density I/O Modules
Mixed I/O Modules
Mixed I/O Modules (continued)
Model
Circuit configuration
CS1W-MD292
(48 inputs/48
outputs, sourcing)
C200H-MD115
(16 inputs/
16 outputs, sourcing,
12 VDC)
C200H-MD115
(128 dynamic inputs)
C200H-MD215
(16 inputs/
16 outputs, sourcing,
24 VDC)
(This table continues on the next page.)
Programmable Controller
CS1
C--65
Basic and High-density I/O Modules
Mixed I/O Modules
Mixed I/O Modules (continued)
C200H-MD215
(128 dynamic
inputs/outputs,
24 VDC)
J Mixed I/O TTL Modules
Model
Circuit configuration
CS1W-MD561
(32 inputs/
32 outputs)
C200H-MD501
(16 inputs/
16 outputs, static)
C200H-MD501
(128 dynamic inputs)
C--66
Programmable Controller
CS1
Basic and High-Density I/O Modules
Wiring Devices for High-density I/O Units
Connect High-density I/O Units to Terminal Blocks
J CS1 High-density (96 or 48/48 I/O Points) I/O Units (Basic I/O Units)
CS1 High-density I/O Unit
CS1 High-density I/O Unit
CS1 High-density I/O Unit
CS1W-ID291 (96 inputs)
CS1W-OD291 (96 outputs)
CS1W-OD292 (96 outputs)
CS1W-MD291 (48 inputs, 48 outputs)
CS1W-MD292 (48 inputs, 48 outputs)
CS1W-ID291 (96 inputs)
CS1W-OD291 (96 outputs)
CS1W-OD292 (96 outputs)
CS1W-MD291 (48 inputs, 48 outputs)
CS1W-MD292 (48 inputs, 48 outputs)
CS1W-ID291 (96 inputs)
CS1W-OD291 (96 outputs)
CS1W-OD292 (96 outputs)
CS1W-MD291 (48 inputs, 48 outputs)
CS1W-MD292 (48 inputs, 48 outputs)
XW2Z-jjjH-1
Connecting Cable
(2 sets)
XW2Z-jjjH-2
Connecting Cable
(2 sets)
XW2D-20G6,
XW2B-20G5, or
XW2B-20G4
ConnectorTerminal Block
Conversion Unit
XW2B-60G5 or
XW2B-60G4
ConnectorTerminal Block
Conversion Unit
XW2Z-jjjH-3
Connecting Cable
(2 sets)
XW2D-40G6,
XW2B-40G5, or
XW2B-40G4
ConnectorTerminal Block
Conversion Unit
XW2D-20G6,
XW2B-20G5, or
XW2B-20G4
Connector-Terminal
Block Conversion
Units
XW2D-20G6,
XW2B-20G5, or
XW2B-20G4
Connector-Terminal
Block Conversion Units
XW2D-20G6,
XW2B-20G5, or
XW2B-20G4
Connector-Term
Block Conversio
Units
J CS1 High-density (32, 64, or 32/32 I/O Points) and C200H Group-2 High-den-
sity I/O Units (Basic I/O Units)
CS1 I/O Units with 32,
64, or 32/32 points
C200H Group-2 Highdensity I/O Unit
CS1W-ID231*
CS1W-ID261
CS1W-OD231*
CS1W-OD232*
CS1W-OD261
CS1W-OD262
CS1W-MD261
CS1W-MD262
* Only one connector.
C200H-ID216*
(one I/O Unit connector)
C200H-OD218*
(one I/O Unit connector)
C200H-ID111
C200H-ID217
C200H-OD219
C200H-ID218
C200H-ID219
C200H-OD21B
CS1 I/O Units with 32, C200H Group-2 High64, or 32/32 points
density I/O Unit
CS1W-ID231*
CS1W-ID261
CS1W-MD261 (inputs only)
CS1W-MD262 (inputs only)
* Only one connector.
C200H-ID216*
C200H-ID111
C200H-ID217
C200H-ID218
C200H-ID219
XW2Z-jjjD
Connecting
Cable
XW2Z-jjjB
Connecting Cable
XW2D-20G6,
XW2B-20G5, or
XW2B-20G4
XW2D-40G6,
XW2B-40G5, or
XW2B-40G4
XW2C-20G5-IN16
J C200H High-density I/O Units (Special I/O Units)
C200H High-density I/O Unit
C200H High-density I/O Unit
C200H-ID215
C200H-OD215
C200H-MD115
C200H-MD215
C200H-MD501
C200H-ID501
C200H-OD501
C200H-ID215
C200H-MD115
C200H-MD215
C200H-MD501
C200H-ID501
XW2Z-jjjA
Connecting Cable
XW2Z-jjjA
Connecting Cable
XW2D-20G6,
XW2B-20G5, or
XW2B-20G4
XW2C-20G5-IN16
Note: See Wiring Solutions section for additional information on cables and terminal blocks.
Programmable Controller
CS1
C--67
Basic and High-density I/O Modules
Interrupt Module
J System Configuration
CS1W-INT01
CPU
I/O interrupt
task
When the input on the Interrupt Input Unit turns ON, the
CPU Unit is notified immediately, cyclic task execution (normal programming) is interrupted and an I/O interrupt task is
executed.
J Features
• High-speed Response (0.42 ms OFF to ON)
• Execute an interrupt task within 1.0 ms after input turns
ON
J Specifications
Classifications
CS1W Basic I/O Unit
Input
voltage
24 VDC
Inputs
16 pts
Input pulse width
ON: 0.1 ms min.
OFF: 0.5 ms min.
Note:
C--68
Connections
Removable
terminal block
Allocations
(CIO 0319 to
CIO 2000)
16 bits
Model
CS1W-INT01
The interrupt function can be used with the CPU Backplane only. (Up to 2 Interrupt Input Units can be mounted to a CPU Rack.)
Programmable Controller
CS1
Basic and High-Density I/O Modules
Analog Timer Module
J System Configuration
Analog Timer Unit
C200H-TM001
Time up
outputs
Timer set input
Timer pause input
T0
Set value
4 pts
Resistance
T3
Set value
Provides four timers easily adjusted on-site via front-panel
adjustments or external variable resistors: No Programming
Device required. Using timer pause inputs enables applications as a accumulative timer.
Resistance
J Specifications
Classification
C200H
Basic I/O
Unit
Timers
4 pts
Setting range
0.1 to 1.0 s, 1 to 10 s,
2 to 60 s, 1 to 10 min
Time setting method
Internal or external
variable resistor
CPU bits
Timer set
input, timer
pause input,
and time up
ouput
Allocations
(CIO 0319 to
CIO 2000)
16 bits
Programmable Controller
Model
C200H-TM001
CS1
C--69
Basic and High-density I/O Modules
B7A Interface Units
Wire-reduction Units that Transfer 16 Points
of I/O Information on Two Signal Wires
C200H-B7AI1 (16 inputs)
C200H-B7A02
C200H-B7AO1 (16 outputs) (32 outputs)
C200H-B7A12
(32 inputs)
C200H-B7A21
(16 inputs/16 outputs)
C200H-B7A22
(32 inputs/32 outputs)
J Connection Example
B7A: 32 inputs and 32 outputs
B7A: 16 inputs and 16 outputs
B7A: 32 outputs
B7A: 32 inputs
CS1 PLC
B7A Link Terminals
16 inputs
16 inputs
16 outputs
16 outputs
16 inputs
16 outputs
16 inputs
C--70
Programmable Controller
CS1
16 inputs
16 outputs
16 outputs
Basic and High-Density I/O Modules
B7A Interface Units
J Specifications
B7A Interface Units
Item
C200H-B7AI1
I/O
capacity
p
y
Inputs
Outputs
Transmission distance
C200H-B7AO1
16 inputs or 15
+ 1 error input
---
---
16 outputs
B7A Group-2 Interface Units
C200H-B7A12
C200H-B7A02
C200H-B7A21
C200H-B7A22
32 inputs
(See note 1.)
---
16 inputs
(See note 2.)
32 inputs
(See note 1.)
---
32 outputs
16 outputs
32 outputs
500 m max. if separate power supplies are used for Unit and Link
Terminals.
Normal operation:
500 m max. if separate power supplies are used for Unit Link Terminals.
100 m max. if same power supply is used for Unit Link Terminals.
100 m max. if same power supply
is used for Unit and Link Terminals.
High-speed operation:
100 m max. with shield connected and 10 m max. without shield connected if separate power supplies are used for Unit Link Terminals. 50 m
max. with shield connected and 10 m max. without shield connected if
same power supply is used for Unit and Link Terminals.
Transmission delay
19.2 ms typical, 31 ms max.
Normal operation:
19.2 ms typical, 31 ms max.
HIgh-speed operation: 3 ms typical, 5 ms max. (See note 3.)
Internal current
consumption
100 mA max. at 5 VDC
External power supply
(See note 4.)
10 mA max. at
12 to 24 VDC
±10%
Weight
200 g max.
I/O word allocations
The unit number set with the I/O number setting switch on the front panel is invalid. I/O words are allocated
consecutively according to the mounting position, in the same way as with basic I/O Units.
Note:
30 mA max. at
12 to 24 VDC
±10%
50 mA max. at
12 to 24 VDC
±10%
60 mA max. at
12 to 24 VDC
±10%
50 mA max. at
12 to 24 VDC
±10%
80 mA max. at
12 to 24 VDC
±10%
300 g max.
1. Can also be used for 32 inputs or 30 inputs + 2 error inputs by changing input mode.
2. Can also be used for 16 inputs or 15 inputs + 1 error input by changing input mode.
3. Normal and high-speed operation set via switch.
4. Not including power supply to B7A Link Terminals
J Applicable B7A Link Terminals
Input Terminals
Type
Screw terminals
Model
B7A-T6j1
Transmission delay
Normal ((19.2 ms))
Output Terminals
Type
Screw terminals
B7AS-T6j1
B7A-T6j6
B7AS-T6j6
Modules
Interface
connectors
t
Model
B7A-R6jj1
Transmission delay
Normal ((19.2 ms))
B7AS-R6jj1
High-speed
g p
(3 ms))
B7A-T6D2
Normal (19.2 ms)
B7A-T6D7
High-speed
(3 ms)
B7A-TjE3
Normal (19.2 ms)
B7A-TjE8
High-speed
(3 ms)
B7A-R6jj6
B7AS-R6jj6
Modules
Interface
connectors
t
High-speed
g p
(3 ms))
B7A-R6A52
Normal (19.2 ms)
B7A-RA57
High-speed
(3 ms)
B7A-RjAj3
Normal (19.2 ms)
B7A-RjAj8
High-speed
(3 ms)
Programmable Controller
CS1
C--71
Basic and High-density I/O Modules
Safety Relay Unit
This Safety Relay Unit mounts as an I/O Unit and provides
both safety relays and inputs for monitoring.
J Features
• Safety relays and monitor inputs in 1 Unit to reduce wiring
and space.
CS1W-SF200
• Safety relays operate with separate power supply from
PLC.
• Monitor safety circuit output, K1/K2 relay, or power status
from PLC.
• Four general-purpose inputs provided.
J Internal Connections
• Safety standards: EN954-1 and EN60204-1
J Specifications
Item
Indicator
Indicator
Safety
circuits
Indicator
Internal
circuits
Specifications
Contact
resistance
100 mΩ (5 VDC, 1 A, voltage drop method)
Operating
time
300 ms max. (not including bounce)
Response
time
10 ms max. (time from input OFF to main contact
OFF, not including bounce)
Insulation
resistance
(See note.)
20 MΩ min. (at 500 VDC) for following: Safety
circuits-safety outputs, General inputs-safety
outputs, Different poles of safety outputs, and
safety circuits-general inputs
Withstand
voltage (See
note.)
2,500 VAC, 50/60 Hz for 1 min for following:
Safety circuits-safety outputs, General
inputs-safety outputs, Different poles of safety
outputs 500 VAC, 50/60 Hz for 1 min for Safety
circuits-general inputs
Durability
Mechanical: 5,000,000 min. (7,200 time/hr)
Electrical: 100,000 min. (1,800 time/hr)
Weight
300 g
Note: Measured while mounted to PLC.
J Ratings of Safety Circuits
Item
Power
3.3 kΩ
General
inputs
0.01 µF
Specification
Supply voltage
24 VDC
Fluctuation
--15%/
+10%
Consumption
24 VDC: 1.7 W max.
Inputs
Current
75 mA max.
Switching
g
Rated load
250 VAC, 5 A
Rated ON current
5A
470 Ω
Input indicator
of supply voltage
J Ratings of General Inputs
Item
C--72
Programmable Controller
CS1
Specifications
Power voltage
24 VDC
Fluctuation
--15%/
+10%
Input impedance
3.3 kΩ
Input current
7 mA typ. (24 VDC)
ON voltage/current
14.4 VDC min./3 mA min.
OFF voltage/current
5 VDC max./1 mA max.
ON/OFF response
8 ms max. (Set to 1 to 32 in PC Setup)
Circuits
4 points, 1 common
ON points
100% simultaneously ON
of supply voltage