Transistor Remote I/O Terminals with 3-tier Terminal Blocks
DRT2-@D16TA(-1)
A Smart Slave with a 3-tier Terminal
Block That Means Wiring Locations
Are Easy to Understand with No
Sharing of Terminals.
• Easy wiring with no sharing of terminals. Easy-to-understand wiring
locations.
• No relay terminal block terminals required.
• Detachable cassette-type circuit sections.
Smart Slave Functions
Operation time monitor
Contact operation counter
Unit conduction time monitor
Total ON time monitor
Unit comments
Connected device comments
Network power supply voltage monitor
I/O power supply monitor function
Communications error log function
Power-ON inrush current protection (input or I/O only)
Input filter (input or I/O only)
Removable terminal block
Communications speed auto-detection
No need to wire Unit power supply
Last maintenance date
Ordering Information
Specifications
I/O connections
Rated internal
circuit power
supply voltage
I/O power supply
voltage
NPN (+ common)
Model
DRT2-ID16TA
Inputs
PNP (- common)
DRT2-ID16TA-1
16 points
NPN (- common)
M3
screw terminals
Outputs
PNP (+ common)
NPN (input: + common, output: - common)
I/O
PNP (input: - common, output: + common)
Supplied from
Basic Unit.
DRT2-OD16TA
24 VDC
DRT2-MD16TA-1
General Specifications
Communications power supply voltage
11 to 25 VDC (Supplied from communications connector)
Unit power supply voltage
80 mA
Noise immunity
Conforms to IEC61000-4-4, 2 kV (power line)
Vibration resistance
10 to 60 Hz, 0.7-mm double amplitude, 60 to 150 Hz, 50 m/s2 for
80 min each in the X, Y, and Z directions
Shock resistance
150 m/s2 (3 times each in 6 directions on 3 axes)
Dielectric strength
500 VAC (between isolated circuits)
Insulation resistance
20 MΩ min. (between isolated circuits)
Ambient operating temperature
-10°C to 55°C
Ambient operating humidity
25% to 85% (with no condensation)
Ambient atmosphere
No corrosive gases
Ambient storage temperature
-25°C to 65°C
Mounting method
DIN 35 mm-track mounting, M4 screw mounting
Screw tightening torque
M2 (communications connector screws): 0.26 to 0.3 N m
M3 (screw terminals): 0.5 N m
M3 (screw terminals): 0.5 N m
M4 (unit mounting): 0.6 to 0.98 N m
Weight
300 g max.
32
·
·
DRT2-OD16TA-1
DRT2-MD16TA
Input: 8 points/
Output: 8 points
·
·
Transistor Remote I/O Terminals with 3-tier Terminal Blocks
DRT2-@D16TA(-1)
Input Specifications
● 16-point Inputs Terminals with Transistors
Item
Model
DRT2-ID16TA
● 8-point Inputs/8-point Outputs Terminals with
Transistors
DRT2-ID16TA-1
Internal I/O common
NPN
PNP
I/O points
16 inputs
ON voltage
15 VDC min. (between
input and V terminal)
15 VDC min. (between
input and G terminal)
OFF voltage
5 VDC max. (between
input and V terminal)
5 VDC max. (between
input and G terminal)
OFF current
1.0 mA max.
Input current
24 VDC: 6.0 mA max./point
17 VDC: 3.0 mA max./point
ON delay time
1.5 ms max.
OFF delay time
1.5 ms max.
Number of circuits per
common
Item
8 per common
Model
DRT2-MD16TA
DRT2-MD16TA-1
Internal I/O common
NPN
PNP
I/O points
8 inputs
ON voltage
15 VDC min. (between
input and V terminal)
15 VDC min. (between
input and G terminal)
OFF voltage
5 VDC max. (between
input and V terminal)
5 VDC max. (between
input and G terminal)
OFF current
1.0 mA max.
Input current
24 VDC: 6.0 mA max./point
17 VDC: 3.0 mA max./point
ON delay time
1.5 ms max.
OFF delay time
1.5 ms max.
Number of circuits per
common
8 per common
Output Specifications
● 16-point Outputs Terminals with Transistors
Item
Model
DRT2-OD16TA
● 8-point Inputs/8-point Outputs Terminals with
Transistors
DRT2-OD16TA-1
Internal I/O common
NPN
I/O points
16 outputs
PNP
Rated output current
0.5 A/point
Residual voltage
1.2 VDC max.
(0.5 A DC between output
and G terminal)
Item
1.2 VDC max.
(0.5 A DC between output
and V terminal)
Model
DRT2-MD16TA
NPN
PNP
I/O points
8 outputs
Rated output current
0.5 A/point
Residual voltage
1.2 VDC max.
(0.5 A DC between output
and G terminal)
Leakage current
0.1 mA max.
ON delay time
0.5 ms max.
Leakage current
0.1 mA max.
OFF delay time
1.5 ms max.
ON delay time
0.5 ms max.
OFF delay time
1.5 ms max.
Number of circuits per
common
8 per common
Number of circuits per
common
8 per common
DRT2-MD16TA-1
Internal I/O common
1.2 VDC max.
(0.5 A DC between output
and V terminal)
Dimensions
(Unit: mm)
DRT2-ID16TA(-1)
DRT2-OD16TA(-1)
DRT2-MD16TA(-1)
180
DRT2-ID16TA
0
REMOTE TERMINAL DC24V
MS
(54)
50
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
IN
NS
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
58
(83)
Mounting Hole Dimension
40±0.2
( ) Dimensions in parentheses
are reference values.
Two, 4.2-dia. or M4
170±0.2
Transistor Remote I/O Terminals with 3-tier Terminal Blocks
DRT2-@D16TA(-1)
33
Wiring Diagrams
DRT2-ID16TA-1 (PNP)
V1
G1
G1
G1
G1
V2
V2
V2
V2
G2
G2
G2
G2
Brown
(White)
Blue
(black)
7
V1
V1
V1
V1
G1
G1
G1
G1
8
9
15
V2
V2
V2
V2
G2
G2
G2
G2
Sensor with
PNP output
(e.g., photoelectric
sensor or proximity sensor)
Two-wire sensor
(Limit switch, etc.)
Two-wire sensor
(Limit switch, etc.)
Two-wire sensor
(Limit switch, etc.)
DRT2-OD16TA (NPN)
Sensor with
PNP output
(e.g., photoelectric
sensor or proximity sensor)
DRT2-OD16TA-1 (PNP)
0
1
7
V1
V1
V1
V1
G1
G1
G1
G1
Solenoid
valve, etc.
8
9
15
V2
V2
V2
V2
G2
G2
G2
G2
Solenoid
valve, etc.
Solenoid
valve, etc.
0
1
7
V1
V1
V1
V1
G1
G1
G1
G1
Solenoid
valve, etc.
Solenoid
valve, etc.
8
9
15
V2
V2
V2
V2
G2
G2
G2
G2
Solenoid
valve, etc.
Solenoid
valve, etc.
Solenoid
valve, etc.
DRT2-MD16TA-1 (PNP)
7
V1
V1
V1
V1
G1
G1
G1
G1
Two-wire sensor
(Limit switch, etc.)
0
1
7
V2
V2
V2
V2
G2
G2
G2
G2
Sensor with
NPN output
(e.g., photoelectric
sensor or proximity sensor)
0
1
7
V1
V1
V1
V1
G1
G1
G1
G1
Brown
(White)
Blue
(black)
Blue
(Black)
Brown
(Red)
Black
(White)
1
Brown
(White)
Blue
(black)
0
Solenoid
valve, etc.
Solenoid
valve, etc.
Transistor Remote I/O Terminals with 3-tier Terminal Blocks
0
1
7
V2
V2
V2
V2
G2
G2
G2
G2
Blue
(Black)
Brown
(Red)
Black
(White)
DRT2-MD16TA (NPN)
34
1
Sensor with
NPN output
(e.g., photoelectric
sensor or proximity sensor)
Sensor with
NPN output
(e.g., photoelectric
sensor or proximity sensor)
Two-wire sensor
(Limit switch, etc.)
0
Blue
(Black)
Brown
(Red)
Black
(White)
V1
15
Brown
(White)
Blue
(black)
V1
9
Brown
(White)
Blue
(black)
V1
8
Blue
(Black)
Brown
(Red)
Black
(White)
7
Brown
(White)
Blue
(black)
1
Blue
(Black)
Brown
(Red)
Black
(White)
0
Blue
(Black)
Brown
(Red)
Black
(White)
DRT2-ID16TA (NPN)
Two-wire sensor
(Limit switch, etc.)
Sensor with
PNP output
(e.g., photoelectric
sensor or proximity sensor)
DRT2-@D16TA(-1)
Solenoid
valve, etc.
Solenoid
valve, etc.
Read and Understand This Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or
comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified)
from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER
WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS
IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT
LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's
application or use of the products.
At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,
machine, system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:
• Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.
• Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,
safety equipment, and installations subject to separate industry or government regulations.
• Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or
establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual
specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the
result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON
Warranty and Limitations of Liability.
ERRORS AND OMISSIONS
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,
typographical, or proofreading errors, or omissions.
2009.8
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2009 All Right Reserved.