0
登录后你可以
  • 下载海量资料
  • 学习在线课程
  • 观看技术视频
  • 写文章/发帖/加入社区
会员中心
创作中心
发布
  • 发文章

  • 发资料

  • 发帖

  • 提问

  • 发视频

创作活动
E53-COV03

E53-COV03

  • 厂商:

    OMRON(欧姆龙)

  • 封装:

    -

  • 描述:

    E5EJ TERMINAL COVER

  • 数据手册
  • 价格&库存
E53-COV03 数据手册
E5J Temperature Controller Operation Manual Cat. No. Z103-E3-1 Notice: OMRON products are manufactured for use according to proper procedures by a qualified operator and only for the purposes described in this manual. The following conventions are used to indicate and classify precautions in this manual. Always heed the information provided with them. Failure to heed precautions can result in injury to people or damage to the product. ! DANGER Indicates information that, if not heeded, is likely to result in loss of life or serious injury. ! WARNING Indicates information that, if not heeded, could possibly result in loss of life or serious injury. ! Caution Indicates information that, if not heeded, could result in relatively serious or minor injury, damage to the product, or faulty operation. OMRON Product References All OMRON products are capitalized in this manual. The word “Unit” is also capitalized when it refers to an OMRON product, regardless of whether or not it appears in the proper name of the product. The abbreviation “Ch,” which appears in some displays and on some OMRON products, often means “word” and is abbreviated “Wd” in documentation in this sense. The abbreviation “PC” means Programmable Controller and is not used as an abbreviation for anything else. Visual Aids The following headings appear in the left column of the manual to help you locate different types of information. Note Indicates information of particular interest for efficient and convenient operation of the product. 1, 2, 3... 1. Indicates lists of one sort or another, such as procedures, checklists, etc.  OMRON, 1998 All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of OMRON. No patent liability is assumed with respect to the use of the information contained herein. Moreover, because OMRON is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in this publication. v TABLE OF CONTENTS SECTION 1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1 1-2 1-3 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SECTION 2 Sensor and Mode Settings . . . . . . . . . . . . . . . . . . . . . . . . 2-1 2-2 2-3 Disassembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Output Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Internal Switch Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SECTION 3 Settings Before Operation . . . . . . . . . . . . . . . . . . . . . . . . . 3-1 3-2 3-3 3-4 3-5 Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Setting Flowchart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . List of Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Parameters on Display Level 0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Parameters on Display Level 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SECTION 4 Fuzzy Self-tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1 4-2 4-3 Fuzzy Self-tuning Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Terminology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SECTION 5 Installation and Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1 5-2 5-3 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Terminal Arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SECTION 6 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1 6-2 Error Display and Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SECTION 7 Event Input Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1 Event Input Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SECTION 8 Heater Burnout Detection . . . . . . . . . . . . . . . . . . . . . . . . . 8-1 8-2 8-3 8-4 Heater Burnout Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Heater Burnout Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Wiring the Current Transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Heater Burnout Alarm Value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SECTION 9 Engineering Level Settings . . . . . . . . . . . . . . . . . . . . . . . . 9-1 9-2 9-3 Engineering Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Engineering Level Parameter List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Engineering Level Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 2 2 4 9 10 10 11 17 18 19 20 22 23 27 28 31 32 35 36 37 38 41 42 42 45 46 49 50 50 51 51 55 56 56 58 vii TABLE OF CONTENTS SECTION 10 Auto-tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-1 10-2 10-3 10-4 Starting Auto-tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Conditions that Prevent Auto-tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Force-ending Auto-tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Changing Parameters during Auto-tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 64 64 64 64 Appendices A Dimensions/Mounting Holes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Revision History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . viii 65 69 71 About this Manual: This manual describes the installation and operation of the Thermac E5J Temperature Controller and includes the sections described below. Please read this manual carefully and be sure you understand the information provided before attempting to install and operate the Thermac E5J Temperature Controller. Section 1 describes the specifications and basic features of the Thermac E5J Temperature Controller. Section 2 describes the sensor and mode settings of the Thermac E5J Temperature Controller that are necessary before turning on the Thermac E5J Temperature Controller. Section 3 describes the settings of the Thermac E5J Temperature Controller that are necessary before operating the Thermac E5J Temperature Controller. Section 4 provides the procedures required to adjust all PID constants using fuzzy self-tuning according to the characteristics of the device for ideal temperature control. Section 5 describes the installation and wiring of the Thermac E5J Temperature Controller. Section 6 describes the troubleshooting of the Thermac E5J Temperature Controller. Section 7 describes how the event input function of the Thermac E5J Temperature Controller works. Section 8 describes the basic features of heater burnout detection and necessary steps that should be taken at the time of heater burnout, as well as the method of obtaining heater burnout alarm values. Section 9 describes the parameters that can be changed on the engineering level. These parameters should be changed only when the values set before shipping do not suit the application. After these parameters are changed on the engineering level, record the contents of the changes for your future reference. Section 10 describes how to execute auto-tuning. The Appendix provides the dimensions and mounting specifications for the various Thermac E5J Temperature Controller Units. ! WARNING Failure to read and understand the information provided in this manual may result in personal injury or death, damage to the product, or product failure. Please read each section in its entirety and be sure you understand the information provided in the section and related sections before attempting any of the procedures or operations given. ix SECTION 1 Introduction This section describes the specifications and basic features of the Thermac E5J Temperature Controller. 1-1 1-2 1-3 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3-1 Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3-2 Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 2 4 4 6 1 Models 1-1 Section 1-2 Features The basic features of the Thermac E5J Temperature Controller are outlined below. Fuzzy Self-tuning When using a conventional temperature controller for ideal temperature control, it is necessary to adjust the PID constants of the temperature controller according to the controlled device. The Thermac E5J Temperature Controller incorporates a fuzzy self-tuning function, thus allowing ideal temperature control without any adjustment of the PID constants. The user needs only to set the E5J to the desired temperature for ideal temperature control. Auto-tuning Auto-tuning is also available. It is useful when appropriate results are not obtained through fuzzy self-tuning. (Refer to Section 10 Auto-tuning.) Event Input Function It is possible to select a set point out of a maximum of two set values on the E5CJ-B and four set values on the E5AJ-B via their event input terminals from the PCs connected to these Temperature Controllers. The control operation of the E5AJ-B via can be stopped with an event input signal. Watertight Construction The E5J can be used in places where water is sprayed onto the E5J, because the front panel of the E5J assures IP54 when the E5J is panelmounted (except for front panel of the E5CJ, which assures IP50). If greater watertightness is required, use the Y92A-N, a dedicated watertight cover (sold separately). Advanced PID The E5J incorporates an advanced PID function, which is also incorporated by the Thermac X Temperature Controller. The advanced PID function prevents temperature overshooting the moment the Temperature Controller starts operating, assures a short startup time, and performs ideal temperature control by quickly responding to external disturbances. Output Units The E53-R Relay Unit, E53-Q, E53-Q3, and E53-Q4 Voltage Output Units for driving SSRs, and E53-C3, E53-C3D, E53-V34, and E53-V35 Linear Output Unit can be connected to any E5J Temperature Controller (except the E5CJ) with ease according to the desired output configuration and application. 1-2 Models The thermocouples and platinum resistance thermometers listed in the following table can be connected to any Thermac E5J Temperature Controller. Input Selectable internally. Platinum resistance thermometer JPt100 Temperature range (°C) INPUT Factory-set to 2 (K) 1300 1000 800 600 400 200 100 0 –100 –200 Setting no. 2 Pt100 Thermocouple K J T L U 1300 N 1300 850 650.0 850 650.0 400.0 400.0 –100 –199.9 –199.9 –200 0.8 1.9 2 –100 –199.9 3 4 5 –199.9 –200 6 7 Models Section 1-2 E5AJ (Standard Model with Communications Function) 96 X 96mm Alarm 2 relay output points with heater burnout alarm (see note 1) Event input 2 points (set point selection, RUN/STOP) (see note 2) Control output Replaceable Output Unit (sold separately) Model Communications function --- E5AJ-A2HB RS-232C E5AJ-A2H01 RS-422 E5AJ-A2H02 RS-485 E5AJ-A2H03 Communications Board add-on model Note E5AJ-A2HM 1. No heater burnout alarm is output if the E53-C3 Current Output Unit is used with the E5AJ. 2. The event input function is not incorporated by models that have a communications function. E5EJ (Standard Model with Communications Function) 48 X 96mm Alarm 2 relay output points with heater burnout alarm (see note 1) Event input 2 points (set point selection, RUN/STOP) (see note 2) Control output Model Replaceable Output Unit (sold separately) Communications function --- E5EJ-A2HB RS-232C E5EJ-A2H01 RS-422 E5EJ-A2H02 RS-485 E5EJ-A2H03 Communications Board add-on model Note E5EJ-A2HM 1. No heater burnout alarm is output if the Linear Output Unit is used with the E5EJ. 2. The event input function is not incorporated by models that have a communications function. 3 Specifications Section 1-3 E5CJ (Simple and Standard Models) 48 X 48mm Type Simple model type Alarm --- Heater burnout alarm --- Event input --- Model Control output Standard model type 2 replay output points with the same common. (see note 1) Yes (see note) Relay output E5CJ-R E5CJ-R2 1 point (set point selection) E5CJ-R2HB Voltage output E5CJ-Q E5CJ-Q2 E5CJ-Q2HB Current output E5CJ-C E5CJ-C2 E5CJ-C2B Note No heater burnout alarm is output if a current control output is used. Communications Boards Communications Model RS-232C E53-J01 RS-422 E53-J02 RS-485 E53-J03 Note For details, refer to the E5AJ/E5EJ Communications Manual (Z102). 1-3 Specifications 1-3-1 Ratings E5J Item Specification Supply voltage 100 to 240 VAC, 50 or 60 Hz Operating voltage range Power consumption 85 to 110% of supply voltage E5AJ E5EJ E5CJ Input CT input Control output E5AJ/E5EJ E5CJ Relay output SPST-NO, 3 A at 250 VAC (resistive load) Voltage output 20 mA at 12 VDC (with short-circuit protection) Current output 4 to 20 mA DC with a load of 600 Ω max. and a resolution of approx. 2600 ON/OFF or advanced PID with fuzzy self-tuning and auto-tuning 2 SPST-NO relay output points, 3 A at 250 VAC (resistive load) 2 SPST-NO relay output points (with the same common), 1 A at 250 VAC (resistive load) Digital setting with Up Key and Down Key E5AJ/E5EJ E5CJ Setting method 4 10 VA (at 24 VAC) 10 VA (at 100 VAC) to 6 W (at 24 VDC) C) 14 VA (at 240 VAC) 10 VA (at 100 VAC) to 14 VA (at 240 VAC) 10 VA (at 100 VAC) to 12 VA (at 240 VAC) Thermocouples (K, J, T, L, U, and N) and platinum resistance thermometers (JPt100 and Pt100) Dedicated CT (E54-CT1 or E54-CT3) Replaceable Output Unit (sold separately) Control mode Alarm output 24 V AC/DC, 50 or 60 Hz Specifications Section 1-3 Item Indication method Specification E5AJ All digital indication (PV: Red, 15 mm; SV: Green, 10.5 mm) E5EJ All digital indication (PV: Red, 14 mm; SV: Green, 9.5 mm) E5CJ All digital indication (PV: Red, 12 mm, SV: Green 8.0 mm) Event input Contact input: ON: 1 kΩ max. OFF: 100 kΩ min. No-contact input: ON: residual voltage of 3 V max; OFF: current leakage of 1 mA max. • Key protect Other function • Cooling operation/Heating operation • Heater burnout alarm Model with event input (E5J-B) • Set point selection (set point x 2) • RUN/STOP (E5AJ-B and E5EJ-B only) Ambient operating temperature –10°C to 55°C (with no condensation) Ambient operating humidity 35 to 85% Storage temperature –25°C to 65°C (with no condensation) Output Units Model Specification E53-R Relay Output Unit SPDT (SPST-NO when used with the E5J), 5 A at 250 VAC (resistive load) E53-Q Voltage Output Unit NPN, 40 mA at 12 VDC (with short-circuit protection) E53-Q3 Voltage Output Unit NPN, 20 mA at 24 VDC (with short-circuit protection) E53-Q4 Voltage Output Unit PNP, 20 mA at 24 VDC (with short-circuit protection) E53-C3 Linear Output Unit 4 to 20 mA DC with a load of 600 Ω max. (with a resolution of approximately 2600 when used with the E5J) (see note) E53-C3D Linear Output Unit 0 to 20 mA DC with a load of 600 Ω max. (with a resolution of approximately 2600 when used with the E5J) E53-V34 Linear Output Unit 0 to 10 VDC with a load of 1 kΩ min. (with a resolution of approximately 2600 when used with the E5J) E53-V35 Linear Output Unit 0 to 5 VDC with a load of 1 kΩ min. (with a resolution of approximately 2600 when used with the E5J) Note The E53-C cannot be used. Current Transformer (CT) Item Specification Maximum continuous heater current 50 A Dielectric strength 1,000 VAC Vibration resistance 50 Hz, approx. 98 m/s2 (10G) Weight E54-CT1: Approx. 11.5 g E54-CT3: Approx. 50 g 5 Specifications Section 1-3 1-3-2 Characteristics E5J Item Specification Indication accuracy ±0.5% or ±1°C whichever is larger ± 1 digit max. Hysteresis (for ON/OFF control) Thermocouple K, T, or N at a temperature of –100°C; thermocouple U at ± 2°C ± 1 digit max. 0.1 to 999.9°C/° F (in units of 0.1°C/°F) Proportional band 0.1 to 999.9°C/°F (in units of 0.1°C/°F) Integral time 0 to 3999 s (in units of 1 s) Derivative time 0 to 3999 s (in units of 1 s) Control period Relay or voltage output:1 to 99 s (in units of 1 s) Manual reset value (I = 0) 0.0 to 100.0% (in units of 0.1%) Alarm setting range With K, J, L, or N input: –1999 to 9999° C/°F (in units of 1°C/°F) With JPt100, Pt100, T, or U input: –199.9 to 999.9° C/°F (in units of 0.1°C/°F) Sampling period 500 ms Output refresh period 500 ms Display refresh period 500 ms Insulation resistance 20 MΩ min. at 500 VDC (measured with an Output Unit) Dielectric strength Malfunction Destruction Malfunction 2000 VAC, 50/60 Hz for 1 min. between charged terminals different from each other in polarity 10 to 55 Hz, 9.8 m/s2 (1G) 10 min. in X, Y, and Z directions 10 to 55 Hz, 19.6 m/s2 (2G) 2 hr. in X, Y, and Z directions 196 m/s2 (20G) 3 times each in 3-axis 6 directions (98 m/s2 (10G) for the relay) Destruction 294 m/s2 (30G) 3 times each in 3-axis 6 directions E5AJ Approx. 360 g; mounting bracket: approx. 65 g E5EJ Approx. 280 g; mounting bracket: approx. 65 g E5CJ Approx. 170 g; adapter: approx. 10 g Vibration resistance i Shock resistance Weight Enclosure rating Front panel: E5AJ/E5EJ: IEC standard IP54 E5CJ: IEC standard IP50 (see note 1) Rear case: IEC standard IP20 Terminals: IEC standard IP00 Non-volatile memory Memory Protection EMC Emission Enclosure: Emission AC Mains: Immunity ESD: EN55011 Group 1 class A EN55011 Group 1 class A EN61000-4-2: 4 kV contact discharge (level 2) 8 kV air discharge (level 3) Immunity RF-interference: ENV50140: 10 V/m (amplitude modulated, 80 MHz to 1 GHz) (level 3) 10 V/m (pulse modulated, 900 MHz) Immunity Conducted Disturbance: ENV50141: 10 V (0.15 to 80 MHz) (level 3) Immunity Burst: EN61000-4-4: 2 kV power-line (level 3) 2 kV I/O signal-line (level 4) Approved standards UL1092, CSA C22.2 No. 142 Conforms to EN50081-2, EN50082-2, EN61010-1 (IEC1010-1) (see note 2) Conforms to VDE0106/part 100 (Finger Protection), when the separately-ordered terminal cover is mounted. Note 1. The model numbers of the exclusive watertight covers conforming to IP66, NEMA4 are as follows: For E5AJ: Y92A-96N; For E5CJ: Y92A-48N; For E5EJ: Y92A-49N 2. Basic insulation is between the input and output. 6 Specifications Section 1-3 Output Unit Model Life expectancy E53-R Relay Output Unit Heater Burnout Alarm Mechanical 10,000,000 times min. Electrical 100,000 times min. Item Single-phase 50 A VAC (see note 1) Heater current value display accuracy ±5% FS ± 1 digit max. Heater burnout alarm setting range 0.1 to 49.9 A (in units of 0.1 A) (see note 2) 190 ms (see note 3) Min. detection ON time Note Model with Communications Function Specification Max. heater current 1. Use the K2CU-FA-GS (with gate input terminals) for the detection of three-phase heater burnout. 2. The heater burnout alarm is always OFF if the alarm is set to 0.0 A and always ON if the alarm is set to 50.0 A. 3. No heater burnout detection or heater current value measurement is possible if the control output is ON for less than 190 ms. Refer to the E5AJ/E5EJ Communications Manual (Z102) for details. Item Specification Interface RS-232C, RS-422, RS-485 Communications method Half duplex Synchronization method Start-stop synchronization (non-synchronization) 1200, 2400, 4800, 9600, and 19200 bps Communications speed Communications item Writing to Thermac J Set point, alarm value, heater burnout alarm value, proportional band, derivative time, integral time, and input shift value Reading from Thermac J Process value, set point, alarm value, heater burnout alarm value, heater current value, proportional band, derivative time, integral time, output value, input shift and error code 7 SECTION 2 Sensor and Mode Settings This section describes the sensor and mode settings of the Thermac E5J Temperature Controller that are necessary before turning on the Thermac E5J Temperature Controller. 2-1 2-2 2-3 Disassembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Output Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Internal Switch Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3-1 Internal Switch Positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3-2 Input Type Selector Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3-3 Alarm Mode Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3-4 Standby Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3-5 Function Selector Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3-6 Key Protection Switch Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 10 11 11 12 13 14 14 15 9 Output Units 2-1 Section 2-2 Disassembly Before turning on the E5J, set its sensor type and control mode with the internal selectors. Refer to the following illustrations for disassembling the E5J to access the internal switch settings. Hook Press the hook and pull the front panel. After setting the internal switches, insert the internal mechanism into the case until the front panel snaps with the hook. 2-2 Output Units Select the Output Unit according to the application and mount the Output Unit into the socket on the E5J PCB of the as shown in the following illustration. The E5CJ does not require an Output Unit. Refer to 1-3 Specifications for the output ratings of the E5J. Bracket Output Unit Socket Output Units The following Output Units are available. Model Rating E53-R Relay Output Unit SPDT, 5 A at 250 VAC (resistive load) E53-Q Voltage Output Unit E53-C3 Linear Output Unit NPN model, 40 mA at 12 VDC (with short-circuit protecting circuit) NPN model, 20 mA at 24 VDC (with short-circuit protecting circuit) PNP model, 20 mA at 24 VDC (with short-circuit protecting circuit) 4 to 20 mA DC with a load of 600 Ω max. E53-C3D Linear Output Unit 0 to 20 mA DC with a load of 600 Ω max. E53-V34 Linear Output Unit 0 to 10 VDC with a load of 1 kΩ min. E53-V35 Linear Output Unit 0 to 5 VDC with a load of 1 kΩ min. E53-Q3 Voltage Output Unit E53-Q4 Voltage Output Unit After mounting the Output Unit, be sure to secure it with the mounting bracket provided with the Output Unit. If the E53-C3, E53-C3D, E53-V34, and E53-V35 Linear Output Unit is used for control output, no heater burnout alarm is available. Each Voltage Output Unit is used for driving an SSR as shown in the following illustrations. 10 Internal Switch Settings Section 2-3 NPN Model: E53-Q (40 mA at 12 VDC) and E53-Q3 (20 mA at 24 VDC) + LOAD SSR + INPUT – – + + PNP Model: E53-Q4 (20 mA at 24 VDC) LOAD SSR INPUT – 2-3 – Internal Switch Settings 2-3-1 Internal Switch Positions E5AJ Top view ALM2 Alarm mode selector 2 ALM1 Alarm mode selector 1 PROTECT Key protection switch INPUT Input type selector Bottom view ALL OFF SP FUNCTION Function selector E5EJ Top view ALM2 Alarm mode selector 2 PROTECT ALL Key protection switch OFF ALM1 Alarm mode SP selector 1 INPUT Input type selector FUNCTION Function selector 11 Internal Switch Settings Section 2-3 E5CJ ALM2 Alarm mode selector 2 Top view Bottom view PROTECT Key protection switch ALM1 Alarm mode selector 1 INPUT Input type selector SP OFF FUNCTION Function selector ALL Note The E5CJ with no alarm does not incorporate ALM1 or ALM2. 2-3-2 Input Type Selector Setting The input type selector is factory-set to 2 (K). Refer to the following table for the selection of the desired sensor. INPUT Selector no. Input Set temperature range °C °F Specified temperature range °C °F 0, 8 JPt100 –199.9 to 650.0 –199.9 to 999.9 –199.9 to 735.0 –199.9 to 999.9 1, 9 Pt100 –199.9 to 650.0 –199.9 to 999.9 –199.9 to 735.0 –199.9 to 999.9 2 K –200 to 1300 –300 to 2300 –350 to 1450 –560 to 2560 3 J –100 to 850 –100 to 1500 –195 to 945 –260 to 1660 4 T –199.9 to 400.0 –199.9 to 700.0 –199.9 to 460.0 –199.9 to 790.0 5 L –100 to 850 –100 to 1500 –195 to 945 –260 to 1660 6 U –199.9 to 400.0 –199.9 to 700.0 –199.9 to 460.0 –199.9 to 790.0 7 N –200 to 1300 –300 to 2300 –350 to 1450 –560 to 2560 Note The resistance of the JPt100 at a temperature of 100°C is 139.16 Ω and that of the Pt100 at a temperature of 100°C is 138.50 Ω. 1, 2, 3... 1. To use Fahrenheit, set function selector 4 to ON, which is usually set to OFF. 2. Insert the internal mechanism into the case. 3. Turn on the E5J so that d-u will be displayed on the process value display. Then press the Up Key so that f will be displayed on the set value display. 4. Turn off the power in two seconds. 5. Draw the internal mechanism from the case and set function selector 4 to OFF and turn on the E5J. 12 Internal Switch Settings Section 2-3 2-3-3 Alarm Mode Setting ALM1 and ALM2 are both factory-set to 2 (upper limit alarm). Refer to the following table for the selection of the desired alarm mode. ALM2 Selector no. 0 1 Alarm mode ALM1 Alarm output Positive alarm set value OFF No alarm function X X Upper and lower limit alarm (deviation) Setting range Negative alarm set value --Always ON –1999 to 9999 or –199.9 to 999.9 (the decimal position varies with the input type) SP 2 X Upper limit alarm (deviation) X SP 3 Lower limit alarm (deviation) SP X X SP SP X X Always OFF 4 Upper and lower limit range alarm (deviation) 5 Upper and lower limit alarm with standby sequence (deviation) X X Upper limit alarm with standby sequence (deviation) X SP 6 7 SP Absolute value upper limit alarm 9 Absolute value lower limit alarm X SP Lower limit alarm with standby sequence (deviation) 8 Always OFF SP X X SP SP X X 0 0 X X 0 0 If the alarm mode switch is set to 1 to 7, the alarm value is set with the deviation width from the set point as shown in the following diagram. Alarm value 10°C/°F Set point (SP) 100°C/°F If the alarm mode switch is set to 8 or 9, the alarm value is set with the absolute value from 0°C/°F as shown in the following diagram. Alarm value 110°C/°F 0°C/°F 13 Internal Switch Settings Section 2-3 2-3-4 Standby Sequence The alarm output is ON the moment the E5J is turned on because the process value is within the alarm range. To prevent this, select a mode with a standby sequence. If a mode with a await sequence is selected, the alarm output will not be ON even if the process value is within the alarm range unless the process value once goes out of the alarm range. The following diagram shows the operation of the E5J in lower limit alarm mode with a standby sequence. Standby sequence releasing point OFF point due to alarm hysteresis Alarm point Alarm output It is possible to change the alarm hysteresis (set to 0.2°C before shipping) on the engineering level. 2-3-5 Function Selector Settings All the function selector pins are factory-set to OFF. ON OFF To set these pins to ON, use a small flatblade screwdriver. FUNCTION Refer to the following table for function switch setting. Pin no. 1 Output Cooling operation (Normal) ON operation Heating operation (Reverse) OFF Control ON/OFF control mode Level 2 3 4 --- --- --- --- ON See note Advanced PID --- OFF ON Advanced PID with fuzzy self-tuning --- OFF OFF Engineering level --- --- --- ON Normal operation --- --- --- OFF Note The E5J will be in ON/OFF control mode regardless of the setting of pin 3 if pin 2 is set to ON. Output Operation (Pin 1) Heating Operation If pin 1 of the E5J is set to OFF, when the process temperature is lower than the set point, the E5J will operate so that the heater output will increase. Cooling Operation If pin 1 of the E5J is set to ON, when the process temperature is higher than the set point, the E5J will operate so that the output of cooling water will increase. Control Mode (Pins 2 and 3) ON/OFF Control The ON/OFF control is also called two-position operation. Advanced PID Set the E5J in this mode for P, PI, or PD control or if the most suitable PID constants for the controlled device are already known. Advanced PID with Fuzzy Self-tuning Set the E5J in this mode so that Fuzzy self-tuning adjusts the PID constants to the most suitable values according to the controlled device for ideal temperature control. Refer to Section 4 Fuzzy Self-tuning for details. Level (Pin 4) Set pin 4 to ON if it is necessary to change any parameter on the engineering level. Set this pin to OFF for normal operation. 14 Internal Switch Settings Section 2-3 2-3-6 Key Protection Switch Settings The key protection switch is used to prohibit parameter changes as shown in the following table. The key protection switch is factory-set to OFF. SP OFF ALL PROTECT Mode Protection SP Prohibits all set value changes except the set point. The Level Key is not available. The Down Key and Up Key are available only for set point setting. OFF All keys are available. ALL Prohibits all set value changes. The Level Key, Down Key, and Up Key are not available. 15 SECTION 3 Settings Before Operation This section describes the settings of the Thermac E5J Temperature Controller that are necessary before operating the Thermac E5J Temperature Controller. 3-1 3-2 3-3 3-4 3-5 Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Setting Flowchart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . List of Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Parameters on Display Level 0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Parameters on Display Level 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 19 20 22 23 17 Section 3-1 Nomenclature 3-1 Nomenclature The following is the front panel of the E5AJ-A2HB. The front panels of the E5EJ and E5CJ are similar to the front panel of the E5AJ-A2HB. Stop indicator Lit when the E5J is not operating. The E5CJ does not incorporate this indicator. Output indicator Lit when the control output is ON. This indicator is, however, not lit when the E5J has a current output. Level Key Press for 1 s minimum to change levels to set different groups of parameters. Display Key Use this key when shifting the display to the next parameter. Process Value (PV) display Displays not only the process value but also indicates the parameter being displayed on the SV display and error messages. Set Value (SV) display Displays the set temperature and other parameters. Alarm 1 indicator Lit when alarm output 1 is ON. Alarm 2 indicator Lit when alarm output 2 is ON. Heater burnout alarm Lit when there is heater burnout. Once heater burnout is detected, the alarm output will be on hold. Down Key and Up Key The Down Key, when pressed, decreases the set temperature or other parameters. The value successively decreases when the Down Key is held down for 1 s minimum. The Up Key, when pressed, increases the set temperature or other parameters. The value successively increases when the Up Key is held down for 1 s minimum. The value set will be effective on pressing the Display Key or Level Key or 2s after it is set if Display Key or Level Key is not pressed. Note Refer to the E5AJ/E5EJ Communications Manual for the operation of E5J models incorporating a communications function. 18 Setting Flowchart 3-2 Section 3-2 Setting Flowchart The Thermac E5J Temperature Controller starts control at the set point and continues controlling even while set values are being input for each display level. Therefore, when operating the E5J after inputting all the set values, turn the power supply to the Temperature Controller off and then on again. All parameters for the E5J Temperature Controller are divided into three levels according to how frequently they are used. Display Level 0 Parameters that are changed frequently are ranked as display level 0 parameters. Display level 1 Parameters that are not changed frequently are ranked as display level 1 parameters. Engineering Level Parameters that are changed with only a few applications are ranked as engineering level parameters. OFF ON Pin 4 of the function selector Level Key Press for 1 s min. Display level 0 Display level 1 Level Key Press for 1 s min. Set point setting Alarm 1 setting Alarm 2 setting Output display Control period setting Hysteresis setting Set point 0 setting Set point 1 setting (Set point 2 setting) (Set point 3 setting) (Input shift value setting) Heater current value display Heater burnout alarm setting Proportional band setting Integral time setting Derivative time setting Manual reset value setting Each parameter is set with the Up Key or Down Key. Each value set will be effective on pressing the Display Key or Level Key or 2 s after it is selected if Display Key or Level Key is not pressed. No value can be, however, changed when the key protection switch is ON. The parameters in parentheses are changed if their initial values are changed on the engineering level. Engineering level °C/°F selection Stable range Alpha Automatic return of display mode Standby sequence reset method Input shift display selection Alarm 1 hysteresis Alarm 2 hysteresis Set point lower limit Set point upper limit Event input 2 function selection Refer to Section 9 Engineering Level Settings for details on each parameters on the engineering level and how to change them. 19 List of Parameters 3-3 Section 3-3 List of Parameters Display Level 0 Display Name Setting range Setting before shipping Remarks --- Process value display and set point setting Set point lower limit to set point upper limit (°C/°F) 0 The present set point is displayed and can be changed if the E5J incorporates an event input function AL-1 Alarm set value 1 –1999 to 9999 °C/°F 0 Not displayed if alarm mode switch 1 is set to 0. 0 Not displayed if alarm mode switch 2 is set to 0. The decimal position varies with the kind of input. AL-2 Alarm set value 2 –1999 to 9999 °C/°F The decimal position varies with the kind of input. To go to the next level, press the Level Key for 1 s min. Note The values shown in Fahrenheit are applicable only for E5J--F Models. Display Level 1 Display Name Setting before shipping Remarks 0 Output value display 0.0 to 100.0 % CP Control period 1 to 99 s 20 Displayed and can be set if the E5J in PID control operation has relay control output or voltage control output. HYS Hysteresis 0.1 to 999.9 °C/°F 1.0 (1.8) Displayed and can be set when the E5J is in ON/OFF control operation. SP-0 Set point 0 Set point lower limit to set point upper limit (°C/°F) 0 For models incorporating an event input function. SP-1 Set point 1 Set point lower limit to set point upper limit (°C/°F) 0 For models incorporating an event input function. SP-2 Set point 2 Set point lower limit to set point upper limit (°C/°F) 0 For models incorporating an event input 2 function. Set point lower limit to set point upper limit (°C/°F) 0 SP-3 in-S 20 Setting/Display Range Set point 3 Input shift value –199.9 to 999.9 °C/°F 0.0 Displayed and can be set if the default value is changed on the engineering level. For models incorporating an event input 2 function. Displayed and can be set if the default value is changed on the engineering level. Displayed and can be set if the default value is changed on the engineering level. List of Parameters Section 3-3 Display Name Ct Hb Heater current value display Heater burnout alarm value Setting/Display Range Setting before shipping 0.0 to 55.0 A If the current exceeds 55.0 A, ffff will be displayed on the set value display. 0.0 to 50.0 A 0.0 0.0: Always OFF 50.0: Always ON Remarks For models incorporating a heater burnout alarm. Nothing is displayed if the E5J has current control output. For models incorporating a heater burnout alarm. Nothing is displayed if the E5J has current control output. Displayed and can be set when the E5J is in advanced PID operation. P Proportional band 0.1 to 999.9 °C/°F 8.0 (14.4) i Integral time 0 to 3999 s 233 Displayed and can be set when the E5J is in advanced PID operation. 40 Displayed and can be set when the E5J is in advanced PID operation. 50.0 Displayed and can be set if the integral time is set to 0 when the E5J is in advanced PID operation. 8.0 0: No integral operation d Derivative time 0 to 3999 s 0: No derivative operation oFr Manual reset value 0.0 to 100.0 % Note The value in the parentheses is the E5J--F setting before shipping. 21 Parameters on Display Level 0 3-4 Section 3-4 Parameters on Display Level 0 The value set before shipping appears (Set point setting) Displays when the E5J incorporates an alarm function (see note). (Alarm 1 setting) Displays when the E5J incorporates an alarm function (see note). (Alarm 2 setting) Note: The process value will not be displayed if the alarm mode switch is set to 0 or if the E5J does not incorporate any alarm. Set Point Setting (°C or °F) It is possible to alter the present set point (SP0 or SP1). al1 and al2 (°C or °F) The alarm mode is factory-set to the upper limit alarm (deviation). It is possible to change the alarm mode with the alarm mode selector. Refer to 2-3-3 Alarm Mode Setting. The alarm value can be set with the deviation width or absolute value according to the alarm mode. Deviation alarm Upper and lower limit alarm, upper limit alarm, lower limit alarm and upper and lower limit range alarm. Set with the deviation width from the set point Alarm value 10°C/°F Absolute value alarm Absolute value upper limit alarm and absolute value lower limit alarm. Set with the absolute value from 0°C/°F. Alarm value 110°C/°F 0°C/°F Set point (SP) 100°C/°F 22 Parameters on Display Level 1 3-5 Section 3-5 Parameters on Display Level 1 The value set before shipping appears (Output value display) Displays when the E5J in PID control operation has a relay or voltage output. (Control period setting) Displays when the E5J is in ON/ OFF control operation. (Hysteresis setting) Displays if the E5J has an event input. (Set point 0 setting) (Set point 1 setting) Displays only if the event input 2 function is used for set point selection (see note 1). (Set point 2 setting) (Set point 3 setting) Displays if the input shift value display is selected (see note 1). (Input shift value setting) Displays if the heater burnout alarm function is selected. (see note 2). (Heater current value display) (Heater burnout alarm value setting) Displays when the E5J in advanced PID operation. 8.0 (Proportional band setting)* *In case of °F: 14.4 (Integral time setting) (Derivative time setting) Displays if I is 0. (Manual reset value setting) Note 1. Displayed if the initial value is changed on the engineering level. 2. Not displayed if current output is used as control output or a model with no heater burnout alarm function is used. 23 Parameters on Display Level 1 Section 3-5 o Output Value Display The output value is displayed within a range of 0.0% to 100.0%. cp Control Period Setting It is possible to set the control period within a range of 1 to 99 s. The control period is the period required by the E5J to turn ON and OFF its relay output or voltage output. The ON period increases in proportion to the output value. If the control period is short, smooth control operation will be possible although a short control period shortens the life of the relay if relay output is used. Therefore, the control period should not be less than 20 s if relay output is used. The following are output examples with an output value of 50.0 %. 5s 10 s ON ON OFF OFF Control period: 10 s hys Hysteresis Setting (°C or °F) Control period: 20 s It is possible to set the hysteresis for the E5J in ON/OFF control operation within a range of 0.1° to 999.9°C/°F. Hysteresis Heating control (Reverse) ON OFF Low temperature Set point High temperature Hysteresis Cooling ON control OFF (Normal) Low temperature Set point High temperature sp0, sp1, sp2, and sp3 (E5J-B Only) It is possible to set sp-0 (set point 0), sp-1 (set point 1), sp-2 (set point 2), and sp-3 (set point 3) all in Celsius or Fahrenheit regardless of the set point presently selected. To select the set point, open or short-circuit terminals EV1 and EV2. Refer to Section 7 Event Input Function for details. in-s Input Shift Value It is possible to set the input shift value within a range of –199.9° to 999.9°C/°F. When an input shift value is set, the process value will be the input value added with the shift value. Example Input 100°C Input shift value Process value 0 (no compensation) 100°C 10.0 (compensation value) 110°C –10.0 (compensation value) 90°C After the input shift value is set, the it is effective even if the input shift value display is turned off on the engineering level. ct Heater Current Value Display (E5J-H Only) It is possible to set the heater current value within a range of 0.0 to 55.0 A. If the current value exceeds 55.0 A, ffff will be displayed on the set value display. The heater current will be processed and displayed if the control output is ON. hb Heater Burnout Alarm Value Setting (E5J-H Only) It is possible to set the heater burnout alarm value within a range of 0.0 to 50.0 A, which will be used to detect heater burnout. If the heater burnout alarm value is set to 0.0 A, the heater burnout alarm output will be always OFF. If the heater burnout alarm value is set to 50.0 A, the heater burnout alarm output will be always ON. Refer to Section 8 Heater Burnout Detection for details. When the E5J is in advanced PID with fuzzy self-tuning mode, the following parameters (p, i, d, ofr) will not be displayed (i.e., there is no need to set the following parameters). The fuzzy self-tuning always adjusts the PID constants to the most suitable values according to the characteristics of the controlled device. 24 Parameters on Display Level 1 Section 3-5 p Proportional Band Setting It is possible to set the proportional band within a range of 0.1 to 999.9°C/°F. i Integral Time Setting It is possible to set the integral time within a range of 0 to 3999 s. d Derivative Time Setting It is possible to set the derivative time within a range of 0 to 3999 s. ofr Manual Reset Value Setting It is possible to set the necessary output value when the E5J is in constant operation within a range of 0.0% to 100.0%. The E5J will be balanced with a deviation between the set point and process value in P or PD control mode. This deviation is called offset. The offset can be removed by changing the manual reset value. 25 SECTION 4 Fuzzy Self-tuning This section provides the procedures required to adjust all PID constants using fuzzy self-tuning according to the characteristics of the device for ideal temperature control. 4-1 4-2 4-3 Fuzzy Self-tuning Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1-1 Step Response Tuning (SRT) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1-2 Disturbance Tuning (DT) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1-3 Hunting Tuning (HT) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Terminology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3-1 Stable Value, Stable Range, and Stability Judgement Time . . . . . . . . . . . . . . . . . 4-3-2 Hunting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3-3 Characteristics and Characteristics Change . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3-4 External Disturbance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3-5 Interference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3-6 Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 28 29 30 31 32 32 33 33 33 33 34 27 Section 4-1 Fuzzy Self-tuning Operation 4-1 Fuzzy Self-tuning Operation The fuzzy self-tuning function has three features, step response tuning (SRT), disturbance tuning (DT), and hunting tuning (HT). 4-1-1 Step Response Tuning (SRT) SRT is used to obtain all PID constants using a step response method when the Temperature Controller starts operations. SRT is also used when the set point changes value exceeding a set range while the Temperature Controller is operating. After SRT has been executed, no SRT will be executed the next time the Temperature Controller starts operating, unless the set point has been changed. Set point P X 1.27 Max. temperature slope R Tuning at startup Dead time L Output (%) 100 100% imposed step-wise control amount. In step response tuning, control is completely imposed stepwise to measure the maximum temperature slope (R) and dead time (L), and the most ideal PID constants for the device are obtained from R and L. Advanced PID Note Be sure to turn on the power supply to the load either before or simultaneously with the start of Temperature Controller operation. When using the E5AJ-A2HB or E5EJ-A2HB, you can change the RUN/STOP setting to RUN via event input 2 after supplying power to the load. Dead time will be measured from the time the Temperature Controller starts operating. If a load such as a heater is turned on after the Temperature Controller is turned on, dead time longer than the actual value will be measured and inappropriate PID constants will be obtained. If an extremely large amount of dead time is measured, the control amount will be set to 0% for a short period of time before being returned to 100%, and the constants will then be retuned. Retuning is performed only for large amounts of dead time, so be sure to follow the precaution given above when starting operation. 28 Section 4-1 Fuzzy Self-tuning Operation SRT Startup Condition SRT will be ON if the following conditions are satisfied simultaneously when the Temperature Controller is turned on or the set point is changed. At the time the Temperature Controller starts operating At the time set point is changed 1) The set point at the time the Temperature Controller starts operating is different from the set point used at the time SRT was last executed (see note). 1) The new set point is different from the set point used at the time SRT was executed last (see note). 2) The difference between the set point and the process value at the time the Temperature Controller starts operating is larger than the present proportional band value (P) x 1.27 + 4. 3) The process value at the time the Temperature Controller starts operating is smaller than the set point in reverse operation and larger than the set point in normal operation. 2) The set point changing range is larger than the present proportional band value (P) x 1.27 + 4. 3) The process value is in stable condition before the set point is changed. 4) A larger set point value is set in reverse operation and a smaller set point is set in normal operation. Note The last SRT-executed set point is set to 0 before shipping and when changing from advanced PID control to advanced PID control with fuzzy self-tuning. Imposition Completion Condition of Step Control Amount In order to prevent overshooting, the step controlled amount must be imposed continuously only while the present deviation is the same as or greater than the value obtained from the proportional band (P)1.27. The step control will not be applied when the deviation becomes smaller than this value. PID Constant Refreshing Conditions If the step control amount is applied before the maximum temperature slope (R) is obtained, SRT will not renew any PID constant. If the proportional band obtained from the R and L values that were measured before the imposition had been completed is larger than the present proportional band, the PID constants will be renewed because the measured value is in the direction towards the suitable proportional band value, and the set point at that time will be the SRTexecuted set point. 4-1-2 Disturbance Tuning (DT) DT is used to measure the control waveform and adjust the PID constants when the measured temperature becomes unstable. When there are control characteristic changes after the PID constants are refreshed with SRT or when the PID constants are not suitable to the object to be controlled because SRT was not executed, the PID constants will be adjusted with DT. DT at the Time of Operation Start and Set Value Change If there is overshooting at the time the Temperature Controller restarts operating after SRT has been executed, DT adjusts the PID constants so that the set point response waveform will be as close as possible to the most ideal response waveform after it is deemed that there has been a characteristics change in the control system. Stable range (set to 15.0°C before shipping) Set point Stability judgement time The set point response waveform at the time the Temperature Controller restarts operation will be closer to the most ideal response waveform. Measurement of set point response waveform PID before tuning PID after tuning 29 Section 4-1 Fuzzy Self-tuning Operation After the process value reaches the set point and becomes stable, if the process value is disturbed and the disturbance exceeds the stable range, the disturbance is regarded as external disturbance At the time of disturbance, DT measures the external disturbance waveform and adjusts the PID constants so that the external disturbance waveform will be as close as possible to the most ideal external disturbance response waveform. DT at the Time of External Disturbance Response External disturbance External disturbance Stable range (set to 15.0°C before shipping) Set point Stability judgement time Measurement of external disturbance response waveform PID before tuning Startup Conditions of DT The external disturbance response waveform is approaching to the most ideal response waveform even if the same kind of external disturbance reoccurs. The waveform will not, however, change if the most ideal PID constants are already set. PID after tuning DT is used to monitor the control waveform if there is external disturbance or SRT does not work at the time the Temperature Controller starts operating or at the time of set point change. If the measured waveform is not an ideal waveform, DT will be ON. If either one of the following conditions is satisfied, the control waveform will be monitored. 1, 2, 3... 1. SRT Startup conditions 3 and 4 on page 29 are satisfied but neither 1 nor 2 is satisfied. 2. There has been an external disturbance exceeding the stable range after the process value was in stable condition. Note The stable range is set to 27°F with the E5J--F. 4-1-3 Hunting Tuning (HT) If there is hunting due to characteristics changes of the control system, HT is used to measure the hunting waveform and adjust the PID constants to suppress the hunting. Extreme value Stable range (set to 15.0°C before shipping) Set point Measurement of hunting waveform PID before tuning Startup Conditions of HT PID after tuning HT will be ON when there is hunting with four or more maximum temperature values while SRT is not being executed. Note If the periodic temperature changes of the application exceed the stable range (set to 15.0°C at the factory) due to continuous external disturbance (i.e., the temperature is affected by an external disturbance before stabilizing after a previous external disturbance (refer to figure A below)), the user should change the stable range to a value greater than the temperature changing range, otherwise 30 Troubleshooting Section 4-2 HT may change the PID constants even though the PID constants are ideal for the control system. Refer to 9-1 Engineering Level for details. External disturbance Figure A: Waveform with HT turned ON External disturbance T1 T2 T1
E53-COV03 价格&库存

很抱歉,暂时无法提供与“E53-COV03”相匹配的价格&库存,您可以联系我们找货

免费人工找货