Temperature Controllers
E5CSV
CSM_E5CSV_DS_E_7_6
Easy Setting Using DIP Switch and Simple
Functions in DIN 48 × 48 mm-size Temperature
Controllers
• Easy setting using DIP switch.
• Models with two alarms added to Series, ideal for temperature
alarm applications.
• Universal-input (thermocouple/platinum resistance thermometer)
models also available.
• Clearly visible digital display with character height of 13.5 mm.
• Models available with black in addition to white cases.
• RoHS compliant.
For the most recent information on models that have been certified for
safety standards, refer to your OMRON website.
Refer to Safety Precautions for All Temperature
Controllers.
Refer to E5CS/E5CSV Operation for
operating procedures.
Model Number Structure
■ Model Number Legend
Models with Terminal Blocks
E5CSV-@@@@-@
1 2 3 4
5
1. Control Outputs
R: Relay
Q: Voltage for driving SSR
2. Alarm Outputs
Blank: No alarm
1:
1 alarm
2:
2 alarms
3. Input
KJ: Thermocouple
P: Platinum resistance thermometer
T: Thermocouple/platinum resistance
thermometer (universal-input)
4. Power Supply Voltage
Blank: 100 to 240 VAC
D:
24 VAC/VDC
5. Case Color
Blank: Black
W:
Light gray
Note: A functional explanation is provided here for illustration, but models are not necessarily available for all possible combinations. Refer to
Ordering Information when ordering.
Examples
• Relay control output, without alarm, thermocouple/platinum-resistance thermometer multi input, black case : E5CSV-RT
• Relay control output, one alarm output, platinum resistance thermometer input, black case, light gray case
: E5CSV-R1P-W
1
E5CSV
Ordering Information
■ List of Models
Case Color: Light Gray, Thermocouple or Platinum Resistance Thermometer,
Power Supply Voltage: 100 to 240 VAC
Size
E5CSV
48 × 48mm
Type
Control
modes
Terminal block ON/OFF or
PID
Alarms
1
Outputs
Model with
thermocouple
Relay
Voltage (for driving SSR)
E5CSV-R1KJ-W
E5CSV-Q1KJ-W
Model with platinum
resistance
thermometer
E5CSV-R1P-W
E5CSV-Q1P-W
Case Color: Light Gray, Thermocouple, Power Supply Voltage: 24 VAC/VDC
Size
E5CSV
48 × 48mm
Type
Control
modes
Terminal block ON/OFF or
PID
Alarms
1
Outputs
Model with
thermocouple
E5CSV-R1KJD-W
Relay
Case Color: Light Gray, Universal-input, Power Supply Voltage: 100 to 240 VAC
Type
Size
E5CSV
48 × 48mm
Control
modes
Terminal block ON/OFF or
PID
Alarms
0
1
2 (See note.)
Outputs
Relay
Voltage (for driving SSR)
Relay
Voltage (for driving SSR)
Relay
Voltage (for driving SSR)
Model with universalinput (thermocouple
or platinum resistance
thermometer)
E5CSV-RT
E5CSV-QT
E5CSV-R1T
E5CSV-Q1T
E5CSV-R2T
E5CSV-Q2T
Note: There is no alarm output 2 mode switch. The default setting for alarm output 2 is for the upper limit alarm mode. To change the setting,
change the alarm type for alarm output 2 in initial setting level 5. For details, refer to the “E5CSV/E5CS-U Digital Temperature Controller
User’s Manual” (Cat. No. H140-E1-01).
Case Color: Black, Universal-input, Power Supply Voltage: 24 VAC/VDC
Type
Size
E5CSV
48 × 48mm
Control
modes
Terminal block ON/OFF or
PID
Alarms
0
1
2 (See note.)
Outputs
Relay
Voltage (for driving SSR)
Relay
Voltage (for driving SSR)
Relay
Voltage (for driving SSR)
Model with universalinput (thermocouple
or platinum resistance
thermometer)
E5CSV-RTD
E5CSV-QTD
E5CSV-R1TD
E5CSV-Q1TD
E5CSV-R2TD
E5CSV-Q2TD
Note: There is no alarm output 2 mode switch. The default setting for alarm output 2 is for the upper limit alarm mode. To change the setting,
change the alarm type for alarm output 2 in initial setting level 5. For details, refer to the “E5CSV/E5CS-U Digital Temperature Controller
User’s Manual” (Cat. No. H140-E1-01).
■ Accessories (Order Separately)
Protective Cover
DIN Track Mounting Adapter
Type
Hard Protective Cover
Model
Y92A-48B
Terminal Cover
Model
Y92F-52
Rubber Packing
Model
E53-COV17
Note: The E53-COV10 cannot be used.
Model
Y92S-29
Note: The Rubber Packing is provided with the Digital Controller.
2
E5CSV
Specifications
■ Ratings
Supply voltage
100 to 240 VAC, 50/60 Hz
24 VAC, 50/60 Hz; 24 VDC
Operating voltage range
85% to 110% of rated supply voltage
Power consumption
100 to 240 VAC: 5 VA
24 VAC: 3 VA, 24 VDC: 2 W
Sensor input
Thermocouple input type:
K, J, L
Platinum resistance thermometer input type:
Pt100, JPt100
Universal-input (thermocouple/platinum resistance thermometer) type: K, J, L, T, U, N, R, Pt100, JPt100
Control
output
SPST-NO, 250 VAC, 3A (resistive load)
Relay output
Voltage output (for driving the SSR) 12 VDC, 21 mA (with short-circuit protection circuit)
Control method
ON/OFF or 2-PID (with auto-tuning)
Alarm output
SPST-NO, 250 VAC, 1A (resistive load)
Setting method
Digital setting using front panel keys
Indication method
7-segment digital display (character height: 13.5 mm) and deviation indicators
Other functions
• Setting change prohibit (key protection)
• Input shift
• Temperature unit change (°C/°F)
• Direct/reverse operation
• Temperature range, Sensor switching (K/J/L, Pt100/JPt100)
• Switching is performed between a thermocouple and platinum resistance thermometer for universal-input models.
• Control period switching
• 8-mode alarm output
• Sensor error detection
Ambient operating temperature
−10 to 55°C (with no condensation or icing); with 3-year guarantee: −10 to 50°C
Ambient operating humidity
25% to 85%
Storage temperature
−25 to 65°C (with no condensation or icing)
Note: 1. Do not use an inverter output as the power supply. (Refer to Safety Precautions for All Temperature Controllers.)
2. Models for 24 VAC/DC can also be manufactured.
■ Characteristics
Setting accuracy
Indication accuracy
(ambient temperature of 23°C)
Influence of temperature
Influence of voltage
Influence of EMS. (at EN61326-1)
Hysteresis (for ON/OFF control)
Thermocouple (See note 1.):
(±0.5% of indication value or ±1°C, whichever is greater) ±1 digit max.
Platinum resistance thermometer (See note 2.): (±0.5% of indication value or ±1°C, whichever is greater) ±1 digit max.
R thermocouple inputs:
(±1% of PV or ±10°C, whichever is greater) ±1 digit max.
Other thermocouple inputs:
(±1% of PV or ±4°C, whichever is greater) ±1 digit max.
Platinum resistance thermometer inputs: (±1% of PV or ±2°C, whichever is greater) ±1 digit max.
0.2% FS (0.1% FS for universal-input (thermocouple/platinum resistance thermometer) models)
Proportional band (P)
1 to 999°C (automatic adjustment using auto-tuning/self-tuning)
Integral time (I)
1 to 1,999 s (automatic adjustment using auto-tuning/self-tuning
Derivative time (D)
1 to 1,999 s (automatic adjustment using auto-tuning/self-tuning)
Alarm output range
Absolute-value alarm: Same as the control range
Other:
0 to input setting range full scale (°C or °F)
Alarm hysteresis:
0.2°C or °F (fixed)
Control period
2/20 s
Sampling period
500 ms
Insulation resistance
20 MΩ min. (at 500 VDC)
Dielectric strength
2,000 VAC, 50/60 Hz for 1 min between current-carrying terminals of different polarity
Vibration
resistance
Shock resistance
Malfunction 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions
Destruction 10 to 55 Hz, 0.75-mm single amplitude for 2 hr each in X, Y, and Z directions
Malfunction 100 m/s2 min., 3 times each in 6 directions
Destruction 300 m/s2 min., 3 times each in 6 directions
Life expectancy
Electrical
100,000 operations min. (relay output models)
Weight
Approx. 120 g (Controller only)
Degree of protection
Front panel: Equivalent to IP66; Rear case: IP20; Terminals: IP00
Memory protection
EEPROM (non-volatile memory) (number of writes: 1,000,000)
EMC
EMI Radiated:
EMI Conducted:
ESD Immunity:
Approved standards
UL 61010-1 (listing)
CSA C22.2 No.1010-1
Conformed standards
EN61326-1 (See note 3.), EN61010-1, IEC61010-1
VDE 0106 Part 100 (finger protection), when the terminal cover is mounted.
EN 55011 Group 1 Class A
EN 55011 Group 1 Class A
EN 61000-4-2: 4 kV contact discharge (level 2)
8 kV air discharge (level 3)
Radiated Electromagnetic Field Immunity:
EN 61000-4-3: 10 V/m (80-1000 MHz, 1.4-2.0 GHz amplitude modulated) (level 3)
10 V/m (900 MHz pulse modulated)
Conducted Disturbance Immunity:
EN 61000-4-6: 3 V (0.15 to 80 MHz) (level 2)
Noise Immunity (First Transient Burst Noise): EN 61000-4-4
Burst Immunity:
2 kV power-line (level 3), 1 kV I/O signal-line (level 3)
Surge Immunity:
EN 61000-4-5: Power line:
Normal mode 1 kV; Common mode 2 kV
Output line (relay output): Normal mode 1 kV; Common mode 2 kV
Voltage Dip/Interrupting Immunity:
EN 61000-4-11 0.5 cycle, 100% (rated voltage)
Note: 1. The following exceptions apply to thermocouples.
• U, L: ±2°C ±1 digit max.
• R: ±3°C ±1 digit max. at 200°C or less
2. The following exceptions apply to platinum resistance thermometers.
Input set values 0, 1, 2, 3 for E5CSV: 0.5% FS ±1 digit max.
3. Industrial electromagnetic environment (EN/IEC 61326-1 Table 2)
3
E5CSV
■ Temperature Range
Thermocouple Input Models
Input
9
0 1
7 8
2 3
Temperature
range
(selected
using switch)
4 5 6
(Default setting: 2)
1,000
900
800
700
600
500
400
300
200
100
0
Setting number
K
J/L
999
600
500
500
400
400
300
300
200
200
0
0
0
0
0
0
0
0
0
0
0
1
2
3
4
5
6
7
8
9
Minimum setting unit
1°C
1°C
The shaded value indicates the default
setting status.
Platinum Resistance Thermometer Input Models
9
0 1
7 8
2 3
Temperature
range
(selected
using switch)
4 5 6
(Default setting: 3)
Input
500
400
300
200
100
0
−100
Setting number
Minimum setting unit
JPt100/Pt100
400
300
400
300
200
50
50.0
0.0
−50
80
199.9
99.9
−20
0.0
0
0
4
5
0
1
2
3
1°C
0.1°C
1°C
0.1°C
0
0
0
6
7
8
1°C
0.0
9
0.1°C
The shaded value indicates the default
setting status.
Universal-input (Thermocouple/Platinum Resistance Thermometer) Models
• Using Thermocouple Sensors, Control Mode Switch 5: OFF
Input
9
0 1
7 8
2 3
Temperature
range
(selected
using switch)
4 5 6
(Default setting: 0)
1,700
1,600
1,500
1,400
1,300
1,200
1,100
1,000
900
800
700
600
500
400
300
200
100
0
−100
Setting number
Minimum setting unit
K
J
L
T
U
N
R
1,700
1,300
1,300
850
850
400
199.9
−99
0.0
199.9
−99
0.0
−99
0
1
2
3
1°C
0.1°C
1°C
0.1°C
400
199.9
−99
4
5
1°C
0.0
6
−99
7
0.1°C
−99
8
0
9
1°C
The shaded value indicates the default
setting status.
• Using Platinum Resistance Thermometers, Control Mode Switch 5: ON
Input
9
0 1
7 8
2 3
Temperature
range
(selected
using switch)
4 5 6
(Default setting: 0)
1,000
900
800
700
600
500
400
300
200
100
0
−100
Setting number
Minimum setting unit
Pt100
JPt100
850
500
400
199.9
400
200
199.9
99
−99
0.0
0
1
1°C
0.1°C
−99
2
200
99
0
0
3
4
1°C
−99
5
0.0
6
0.1°C
−99
7
0
0
8
9
1°C
The shaded value indicates the default
setting status.
4
E5CSV
External Connection Diagram
Voltage output
models
(See note 1.)
Relay output
models
Voltage output
Relay output
Alarm output
1
1
6
2
2
7
3
3
8
4
4
9
5
5
10
12 VDC,
21 mA
Alarm output 2 (See note 3
Alarm output 1 (See note 3
A
B
B
Platinum resistance
thermometer input
100 to 240 VAC, 50/60 Hz
(24 VAC/VDC)
(See note 2.)
Thermocouple
input
Thermocouple/
platinum resistance thermometer universal-input
Note: 1. The voltage output (12 VDC, 21 mA) is not electrically isolated from the internal circuits. When using a grounding thermocouple, do not
connect output terminals 1 or 2 to ground. Otherwise, unwanted current paths will cause measurement errors.
2. Models with 100 to 240 VAC and 24 VAC/VDC are separate. Models using 24 VDC have no polarity.
3. The number of alarm outputs depends on the model.
Nomenclature
E5CSV Models with Terminal Blocks
Output indicator
Deviation indicators
Mode indicators
Mode Key
Lock Release Key
Temperature display
Alarm indicators
Up Key
Down Key
5
E5CSV
Dimensions
Note: All units are in millimeters unless otherwise indicated.
■ Controller
E5CSV
Panel Cutout Dimensions
84
78
6
48×48
45
+0.6
0
L
45
+0.6
0
45
+0.6
0
44.8×44.8
+1
60 min.
L = (48 × N−2.5) 0
Mounting side-by-side
(group mounting of N Controllers)
Note: Terminals cannot be removed.
E5CSV + Adapter for Flush Mounting
(Provided)
Panel
Adapter for flush mounting
Y92F-30 Adapter for flush mounting
58
Tightening
screws
48
76.5
7.5
Note: 1. The recommended panel thickness is 1 to 4 mm.
2. Group mounting is possible in one direction only.
DIN Track Mounting Adapter
Y92F-52 Note: This Adapter cannot be used together with the Terminal Cover.
Remove the Terminal Cover to use the Adapter.
61
3.5
38
50
Mounted to E5CSV
48
100.5
6
E5CSV
■ Accessories (Order Separately)
Hard Protective Cover
The Y92A-48B Protective Cover (hard type) is available for the following applications.
°C
• To protect the set from dust and dirt.
• To prevent the panel from being accidentally touched causing displacement of set values.
• To provide effective protection against water droplets.
Terminal Cover
92A -48
B
Rubber Packing
E53-COV10
48
Order the Rubber Packing separately if it becomes lost
or damaged. The Rubber Packing can be used to
achieve an IP66 degree of protection for models with
terminal blocks.
48.8
22
9.1
E53-COV17
Y92S-29 (for DIN48 × 48)
48
48.8
(Deterioration, shrinking, or hardening of the rubber
packing may occur depending on the operating
environment. Therefore, periodic replacement is
recommended to ensure the level of waterproofing
specified in NEMA4. The time for periodic replacement
depends on the operating environment. Be sure to
confirm this point at your site. Consider one year a
rough standard. OMRON shall not be liable for the level
of water resistance if the customer does not perform
periodic replacement.)
The Rubber Packing does not need to be attached if a
waterproof structure is not required.
22
(For Controllers after the
design change scheduled
for October 2010)
9.1
Safety Precautions
Refer to Safety Precautions for All Temperature Controllers.
Refer to E5CS/E5CSV Operation for operating procedures.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
In the interest of product improvement, specifications are subject to change without notice.
7
Terms and Conditions Agreement
Read and understand this catalog.
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you
have any questions or comments.
Warranties.
(a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship
for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron
disclaims all other warranties, express or implied.
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT
NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS. BUYER
ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE
PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.
Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the
Products or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at
Omron’s election, to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or
replacement thereof) the non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount
equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsible for warranty,
repair, indemnity or any other claims or expenses regarding the Products unless Omron’s analysis confirms that the Products
were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate
modification. Return of any Products by Buyer must be approved in writing by Omron before shipment. Omron Companies shall
not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or
electronic components, circuits, system assemblies or any other materials or substances or environments. Any advice,
recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above
warranty.
See http://www.omron.com/global/ or contact your Omron representative for published information.
Limitation on Liability; Etc.
OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,
WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.
Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted.
Suitability of Use.
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the
combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable
third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself
is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine,
system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product
with respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE
QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS,
AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
OVERALL EQUIPMENT OR SYSTEM.
Programmable Products.
Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence
thereof.
Performance Data.
Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining
suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate
it to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability.
Change in Specifications.
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our
practice to change part numbers when published ratings or features are changed, or when significant construction changes are
made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers
may be assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at
any time to confirm actual specifications of purchased Product.
Errors and Omissions.
Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is
assumed for clerical, typographical or proofreading errors or omissions.
2020.5
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2020 All Right Reserved.