E8F2
Pressure Sensor
“Cube-Type” Pressure Sensor, with
LED Display, Offers High-Precision
Sensing
H New psi version available
H Compact style: 28 x 28 x 29 mm
(1.10 x 1.10 x 1.14 in) saves mounting
space
H Easy-to-read LEDs
H Displays both analog bar and digital
pressure values
H Two independent discrete outputs
available—plus one analog output
H Select either NPN and PNP output type
Ordering Information
J SENSORS
Type
Digital output
Analog output
Pressure range
Part number
Positive
pressure
NPN open collector (independent, two outputs)
1 to 5 V
0 to 100 kPa
E8F2-A01C
0 to 1 MPa
E8F2-B10C
0 to 14.5 psi
E8F2-D01C
0 to 145 psi
E8F2-D10C
0 to 100 kPa
E8F2-A01B
0 to 1 MPa
E8F2-B10B
0 to -- 101 kPa
E8F2-AN0C
0 to -14.6 psi
E8F2-DN0C
0 to-101 kPa
E8F2-AN0B
PNP open collector (independent, two outputs)
Negative
pressure
NPN open collector (independent, two outputs)
PNP open collector (independent, two outputs)
J ACCESSORIES (ORDER SEPARATELY)
Description
Part number
Panel-mounting bracket
E89-F4
2
E8F2
E8F2
Application Examples
J CHIP ATTACHMENT
CHECKS
J AIR PRESSURE
CHECKS
J PCB AND WAFER
ATTACHMENT CHECKS
E8F2
E8F2
E8F2
Specifications
J RATINGS/CHARACTERISTICS
Item
E8F2A01C
E8F2B10C
E8F2AN0C
E8F2D01C
E8F2D10C
E8F2DN0C
E8F2A01B
E8F2B10B
E8F2AN0B
Power supply voltage
12 to 24 VDC ± 10% with a ripple (p-p) of 10% max.
Current consumption
70 mA max. (See Note 1.)
Pressure type
Gauge pressure
Rated pressure range
0 to 100
kPa
0 to 1
MPa
0 to
-- 101
kPa
0 to 14.5
psi
0 to 145
psi
0 to
-- 14.6
psi
0 to 100
kPa
0 to 1
MPa
0 to
-- 101
kPa
Pressure setting range
0 to 100
kPa
0 to 1
MPa
0 to
-- 101
kPa
0 to 14.5
psi
0 to 145
psi
0 to
-- 14.6
psi
0 to 100
kPa
0 to 1
MPa
0 to
-- 101
kPa
Withstand pressure
400 kPa
1.5 MPa
400 kP
58 psi
217.6
psi
58 psi
400 kPa
1.5 MPa
400 kPa
Applicable fluid
Non-corrosive gas and non-flammable gas
Operating mode(s)
Hysteresis mode
Window mode
Auto-teaching mode
Repeat accuracy (ON/OFF output)
±1% FS max.
Linearity
±1% FS max.
Response time (ON/OFF output)
5 ms max.
Linear output
1 to 5 V± 5% FS with an output impedance of 1 kΩ and a permissible resistive load of 500 kΩ min.
ON/OFF output
NPN open collector (NO/NC)
Load current: 30 mA max.
Output applied voltage: 30 VDC max.
Residual voltage: 1 V max. with a load current of 30 mA
Display (See Note 2.)
3.5-digit red LED
Green LED bar indicator
The orange LED is lit for two independent outputs with output transistor turned ON
Green unit indicator
Display accuracy
±3% FS ± 1 digit max.
Circuit protection
Reverse polarity connection, load short-circuiting
3
E8F2
E8F2
Item
E8F2A01C
E8F2B10C
E8F2AN0C
E8F2D01C
Temperature influence
±3% FS max.
Ambient temperature
Operating: 0°C to 55°C (32°F to 131°F)
E8F2D10C
E8F2DN0C
E8F2A01B
E8F2B10B
E8F2AN0B
Storage: -- 10°C to 60°C (14°F to 140°F) with no icing
Ambient humidity
Operating/Storage: 35% to 85% (with no condensation)
Voltage influence
±1.5% FS max.
Insulation resistance
100 MΩ min. (at 500 VDC) between current-carry parts and case
Dielectric strength
1,000 VAC at 1 min
Vibration resistance
Destruction: 10 to 500 Hz, 1.0-mm double amplitude or 150 m/s2, 3 times each for 11 min in X,
Y,and Z directions
Shock resistance
300 m/s2 (30G) 3 times each in X, Y, and Z directions
Degree of protection
IEC60529, IP50
Pressure port
1/8 NPT male screw and M5 female screw
Connection method
Pre-wired (standard length: 2 m)
Cable
Approved by UL
Weight (incl. packing material)
Approx. 110 g (3.88 oz)
Material
Pressure port: aluminum die cast
Case: heat-resistant ABS
Accessories
Mounting bracket
Instruction sheet
Note: 1. The current consumption is approximately 43 mA in energy-saving mode.
2. Display Example of Digital Indicator
Model
Setting unit
kPa
psi
Applied
Digital display
pressure
Applied
Digital display
pressure
E8F2-A01C/E8F2-A01B
E8F2-B10C/E8F2-B10B
100
1,000
1
1
0
0
0
0
0
0
E8F2-AN0C/E8F2-AN0B
-- 101
-- 1
0
1
0
E8F2-D01C
14.5
1
4
5
0
E8F2-D10C
145
1
4
5
0
E8F2-DN0C
-14.5
-1
4
6
0
Note: The “.” in the display indicates the decimal point. Its position will not change unless the setting unit is changed.
4
E8F2
E8F2
Engineering Data
E8F2-A01C
E8F2-A01C
Pressure 0
Operating pressure fluctuation (% FS)
J TEMPERATURE VS. OPERATING
PRESSURE FLUCTUATION (TYPICAL)
Linear output fluctuation (% FS)
J TEMPERATURE VS. LINEAR OUTPUT
CURRENT FLUCTUATION (TYPICAL)
Rated pressure
Temperature (°C)
Temperature (°C)
J LINEARITY (TYPICAL)
E8F2-A01C
E8F2-A01C
Linear output voltage (V)
Linearity deviation (%FS)
J PRESSURE VS. LINEAR OUTPUT
(TYPICAL)
Pressure (kPa)
Pressure (kPa)
5
E8F2
E8F2
Nomenclature
J E8F2 PRESSURE SENSOR (PSI TYPE)
(1)
(2)
(3)
(4)
OUT1
OUT2 kPa Torr Psi
(5)
(6)
(7)
(8)
Display Panel
1. Bar indicator (green)
Indicates the degree of the measured pressure according to the the set pressure.
2. Numeric and menu display (red)
Indicates measurement values and menu setting items.
3. Unit indicator (green)
Indicates the unit used for detection; the indicator shows which unit is the one currently set.
4. OUT1 indicator (orange)
OUT1 indicator turns ON when OUT1 is turned ON.
5. OUT2 indicator (orange)
OUT2 indicator turns ON when OUT2 is turned ON.
Operation
6. Up key
7. Down key
Both the Up and the Down key are used to select or change the set items, set contents, and set values in setting
mode.
• Press either key (Up or Down key) to check the ON and OFF points in measurement mode. The values are reset by
pressing both keys simultaneously.
• Use either the Up or the Down key (as necessary) together with the SET key for setting the Sensor to a special setting
mode or energy-saving mode.
8. SET key
• Used for entering the set contents and set values in setting mode.
• Used for setting the Sensor to basic setting mode or pressure setting mode.
•
6
E8F2
E8F2
Operation
J OUTPUT STAGE CIRCUIT
Output type
NPN output (normally open)
Model
E8F2-A01C
E8F2-B10C
E8F2-AN0C
Timing
chart
Hysteresis
mode
Pressure
Pressure
ON point
ON point
OFF point
OFF point
Output
OUT
indicator
(orange)
Window
mode
NPN output (normally closed)
ON
Output
OFF
OUT
ON
indicator
(orange) OFF
ON
OFF
Pressure
Pressure
OFF point
OFF point
OFF point - 10% FS
max.
ON point - 10% FS
max.
ON point
Output
OUT
indicator
(orange)
ON
Output
OFF
OUT
ON
indicator
(orange) OFF
ON
OFF
Output circuit
12 to 24 V
Brown
Load
30 mA
max.
Black
Load
(ON/OFF1)
Pressure
Sensor
main
circuit
ON point
30 mA
max.
White (ON/OFF2)
Gray
1 to 5 V
(linear)
Load
Blue
0V
7
OFF point - 10% FS
max.
ON point - 10% FS
max.
E8F2
E8F2
J FUNCTIONS AND SETTINGS
Function/Setting
Description
Zero-reset function
Sets the measurement value to 0 when the Sensor is exposed to the air.
Basic setting
mode
Unit setting
Changes the unit for detection.
Pressure setting method
---
Output-type setting
Selects normally-open or normally-closed output.
Pressure
setting mode
Manual setting
Sets the ON and OFF points manually.
Auto-teaching setting
Automatically sets the ON and OFF points depending upon the actual sensing of
objects.
Special setting
mode
Key-protect setting
Protects the set value against the incorrect operation of the keys.
Prevents the set value against the careless operation of the keys.
Hysteresis width setting
Changes the hysteresis range.
Window range setting
Changes the window mode setting.
Display refresh interval setting
Changes the display refresh interval to make the displayed value easier to see.
Measurement value averaging
time setting
Prevents incorrect output due to sudden, instantaneous changes that may occur
with pressure.
Special setting
mode
LED bar indicator range setting
Changes the display range of the LED bar indicator in hysteresis mode.
Energy saving
Energy-saving
mode
Energy-saving function 1
Displays the LED bar indicator but turns the red LED display OFF.
Energy-saving function 2
The LED bar indicator and red LED display flash in window mode if the measured
value exceeds the set range.
ON/OFF set value check function
Checks the set ON and OFF points.
J SETTINGS
Digital Display
The E8F2 displays alphanumeric characters, such as the
measurement values and menu items, with 7-segment LEDs.
Refer to the examples shown below.
The following abbreviations are used for the digital display of the
Controller.
Abbreviation
Meaning
Abbreviation
Meaning
Unt
Unit
DSP
Display
In output operation
M-A
Manual/Auto
AVE
Average
Unit (kPa)
OPE
Operation
BAR
Bar
Width
PRT
Protect
AUT
Auto
HYS
Hysteresis
ECO
Economy
WID
Width
Display
Meaning
ope
kpa
wid
a
b
c
d
e
f
g
h
i
j
k
l
m
n
o
p
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
8
Q
r
s
t
u
U
w
x
y
=
R
S
T
U
V
W
X
Y
Z
E8F2
E8F2
J MODES
In addition to displaying measurement values, the E8F2 has a variety of functions. These functions are available in four main modes as
described below: Measurement Mode, Basic Setting Mode, Pressure Setting Mode, Special Setting Mode. Three functions are available
in measurement mode. For the relationships among each mode and for switching methods, refer to the following figure.
Power ON
Zero-reset function
Energy-saving function 1
No key operation
or
ON- and OFF-point
check function
Measurement
Mode
No key operation
Energy-saving function 2
or
or
or
Pressure Setting Mode
Basic Setting Mode
Manual setting
unt: Measurement unit selection
m-a: Pressure setting method
selection
ope: Output-type selection
Special Setting Mode
Auto-teaching setting
on: OUT1 ON-point setting
t.h1: OUT1 two-point teaching
off: OUT1 OFF-point setting
t.w: OUT1 one-point teaching
on: OUT2 ON-point setting
t.h1: OUT2 two-point teaching
off: OUT2 OFF-point setting
t.w: OUT2 one-point teaching
prt: Key-protect setting
hys: Hysteresis width setting
wid: Window width setting
dsp: Measurement value display
refresh interval setting
aUe: Number of measurement times
setting for measurement value averaging
bar: LED bar indicator range setting
Note: 1.
and
indicate that the key must be pressed for approximately 2 or 3 s respectively.
2. The following will result when the E8F2 in basic, pressure setting, or special setting mode is reset to measurement mode.
:
The set values are entered.
: The set values are not entered (left as they are).
*1.Manual setting is available by selecting m (manual) in the pressure setting method selection in basic setting mode.
*2.Auto-teaching setting is available by selecting a (auto-teaching) in the pressure setting method selection in basic setting mode.
9
E8F2
E8F2
Zero-reset Function
Use the zero-reset function with the Sensor exposed to the air.
OUT1 OUT2 kPa Torr Psi
OUT1 OUT2 kPa Torr Psi
Normal
Measurement mode
OUT1 OUT2
kPa Torr Psi
Error
The displayed measurement value is reset to 0 by pressing the Up and Down keys simultaneously. The reset range is within ±5% (FS)
of the rated pressure. If the value is not within the range, an error will be displayed and the reset will not be enabled.
Basic Setting Mode
The unit of measurement, pressure setting method, and output type are set in basic setting mode.
Setting item
Measurement
mode
OUT1 OUT2
kPa Torr Psi
Setting item
Unit setting
OUT1 OUT2
kPa Torr Psi
Pressure setting method selection
OUT1
OUT2
kPa Torr Psi
Output-type setting
OUT 1
OUT 2
kPa Torr Psi
kPa Torr Psi
1. Press the SET key for approximately 2 s so that the E8F2 will be set to basic setting mode and unt will be displayed.
2. Set the items unt, m--a, and ope with Up or Down key.
10
E8F2
E8F2
Unit Setting
Unit setting in E8F2-AN0C
kPa
OUT1 OUT2 kPa Torr Psi
OUT1 OUT2 kPa Torr Psi
OUT1 OUT2 kPa Torr Psi
OUT1 OUT2 kPa Torr Psi
1. Press the SET key while unt is displayed to display the unit presently set.
2. Press the Up or Down key to select the unit.
3. Press the SET key to select the displayed unit and display unt again.
4. Press the Up and Down keys simultaneously, to display unt again without selecting the unit.
Pressure Setting Method Selection
Pressure setting
Setting item
Manual setting
OUT1 OUT2 kPa Torr Psi
OUT1 OUT2 kPa Torr Psi
Auto-teaching
OUT1 OUT2 kPa Torr Psi
or
m: Manual setting (The ON and
OFF points are manually set.)
a: Auto-teaching (The ON and OFF
points are set automatically.)
1. Press the SET key while m--a is displayed to display the pressure setting method presently set.
2. Press the Up or Down key to select the pressure setting method.
3. Press the SET key to select the displayed pressure setting method and display m--a again.
4. Press the Up and Down keys simultaneously to display m--a without selecting the unit.
11
E8F2
E8F2
Output-Type Setting
or
Output-type setting
Setting item
OUT1
OUT1 N.O
OUT2 kPa Torr Psi
OUT1
OUT2 N.O
OUT2 kPa Torr Psi
OUT1
OUT2 kPa Torr Psi
or
or
OUT1 N.C
OUT1
OUT2 N.C
OUT2 kPa Torr Psi
OUT1
OUT2 kPa Torr Psi
no: Normally open
nc: Normally closed
1. Press the SET key while ope is displayed to display the output type of OUT1 presently set.
2.
3.
4.
5.
6.
Press the Up or Down key to select the output type.
Press the SET key to select the displayed output type and display the output type of OUT2 presently set.
Press the Up or Down key to select the output type.
Press the SET key to select the displayed output type and display ope again.
Press the Up and Down keys simultaneously to display ope again without selecting the unit.
Returning to Measurement Mode
Setting item
Unit setting
OUT1 OUT2 kPa Torr Psi
Pressure setting
or
OUT1 OUT2 kPa Torr Psi
Output configuration
or
Entered
OUT1 OUT2 kPa Torr Psi
Not entered
•
Entering the Setting Item:
Press the SET key for approximately 2 s to enter the item that has been set.
•
Not Entering the Setting Item:
Press the Up and Down keys simultaneously so that the item set will not be entered.
12
Measurement
mode
E8F2
E8F2
Pressure Setting Mode
The E8F2 provides output according to the measured values to control external devices, such as valves and pumps. In order to control
the external devices, a reference value can be set so that the output will be ON or OFF if the measured values are above or below the
reference value. The output ON- and OFF-point settings are described below, provided that the output is normally open.
Note: The ON and OFF points are set in pressure setting mode manually or through auto-teaching.
Normally Open
Window mode
ON
Output
Output
Hysteresis mode
OFF
OFF-point ON-point
set value set value
ON
OFF
ON-point OFF-point
set value set value
Pressure
value
Pressure
value
Normally Closed
Window mode
ON
Output
Output
Hysteresis mode
OFF
OFF-point ON-point
set value set value
ON
OFF
Pressure
value
ON-point OFF-point
set value set value
Pressure
value
Manual Setting
Note: Manual setting will be possible if m is selected in pressure setting method selection in basic setting mode.
Manual setting
Measurement
mode
Torr Psi
Torr Psi
Torr Psi
Torr Psi
or
Displayed
alternately
OUT1 ON
Torr Psi
Displayed
alternately
OUT1 OFF
Torr Psi
Displayed
alternately
Displayed
alternately
OUT12 ON
OUT12 OFF
Torr Psi
Press the Up or Down key
to change the set value.
1.
2.
3.
4.
5.
6.
7.
8.
9.
Press the SET key, to set the E8F2 to pressure setting mode and display the OUT1 ON point and on alternately.
Press the Up or Down key to change the OUT1 ON point.
Press the SET key to select the ON point and display the OUT1 OFF point and off alternately.
Press the Up or Down key to change the OUT1 OFF point.
Press the SET key to select the displayed OFF point and display the OUT2 ON point and on alternately.
Press the Up or Down key to change the OUT2 ON point.
Press the SET key to select the ON point and display the OUT2 OFF point and off alternately.
Press the Up or Down key to change the OUT2 OFF point.
Press the SET key to select the OFF point and display the OUT1 ON point and on alternately.
Returning to Measurement Mode
• Entering the Setting Item: Press the SET key for approximately 2 s to enter any item that has been “set.”
• Not Entering the Setting Item: Press the Up and Down keys simultaneously, so any item “set” will not be entered.
13
Torr Psi
E8F2
E8F2
Auto-teaching
Auto-teaching allows input measured values to be input as ON- and OFF-point set values instead of key input. One- or two-point autoteaching can be selected.
ON
OFF
Two-point teaching
Output
Output
One-point teaching
ON
Pressure
value
OFF
Pressure
value
Note: Auto-teaching will be possible if a is selected in the pressure setting method selection in basic setting mode.
1. Press the SET key to set the E8F2 to pressure setting mode and to display OUT1 and t.h1.
2. Press the Up or Down key to select the one-point teaching or two-point teaching method of OUT1 and OUT2.
Setting item
Measurement
mode
OUT1 OUT2kPa Torr Psi
Auto-teaching
OUT1 two-point teaching
OUT1 one-point teaching
OUT1 OUT2kPa Torr Psi
OUT1 OUT2
OUT2 two-point teaching
OUT1 OUT2 kPa Torr Psi
kPa Torr Psi
OUT2 one-point teaching
OUT1 OUT2kPa Torr Psi
t.h1: Teach hysteresis mode at first point
t.w: Teach window mode
Two-point Teaching (Hysteresis-mode Teaching)
Present measurement
value is displayed.
Present measurement
value is displayed.
OUT1
OUT1 OUT2 kPa Torr Psi
OUT1 OUT2 kPa Torr Psi
OUT1 OUT2 kPa Torr Psi
OUT1 OUT2 kPa Torr Psi
1. Press the SET key under condition 1 below while t.h1 is displayed to display the present measurement value.
2. Check the measurement value and press the Set key to perform and complete teaching the first point.
3. Press the Set key under condition 2 below to display the present measurement value.
(This list of steps continues on the next page.)
14
E8F2
E8F2
Output
Two-point Teaching
ON
ON point:
(TEACH1 + TEACH2)/2
OFF point: ON point -- 3% FS
(default value) the default
value is changeable.
Condition 2
Condition 1
OFF
Pressure value
OFF point
ON point
Entered
OUT1 OUT2
kPa Torr Psi
TEACH1 and TEACH2 can
be performed in reverse
order. TEACH1 value can
be larger than TEACH2
value or vice versa.
or
Measurement mode
Not entered
4. Check the measurement value and press the Set key to perform and complete teaching the second point.
5. Press the SET key for approximately 2 s while t.h1 is displayed to enter the values and return the E8F2 to measurement mode.
6. Press the Up and Down keys simultaneously to set the E8F2 to measurement mode without selecting the values.
Note: The E8F2 will be automatically set to hysteresis mode by performing two-point teaching.
Two-point teaching is ideal for applications that check for vacuum attachment.
Auto-teaching
• One-point Teaching (Window-mode Teaching) OUT1
Present value
OUT1 OUT2
kPa Torr Psi
OUT1 OUT2 kPa Torr Psi
Entered
OUT1 OUT2 kPa Torr Psi
or
Measurement mode
Not entered
1. Press the SET key under condition 3 below while t.w is displayed to display the present measurement value.
One-Point Teaching
Output
Condition 3
ON point: TEACH1 -- 30% FS
OFF point: TEACH1 + 30% FS
The default value is 10% FS
(changeable).
ON
OFF
ON point
OFF point
Pressure
value
2. Check the measurement value and press the Set key to perform and complete teaching.
3. The values are entered Press the SET key for approximately 2 s while t.w is displayed to enter the values and return the E8F2 to
measurement mode.
4. Press the Up and Down keys simultaneously to return the E8F2 to measurement mode without selecting the values.
Note: The E8F2 will be automatically set to window mode by performing one-point teaching. One-point teaching is ideal for applications
that check original pressure.
15
E8F2
E8F2
Teaching Error
•
Present value not
within set range
Error display for 1 s
OUT1 OUT2 kPa Torr Psi
OUT1 OUT2 kPa Torr Psi
Meaning of display: er.t (Error teach)
If the present value or the result of calculation after teaching is not within the range, the SET key input will not be accepted. In this case
an error will be displayed for 1 s if teaching is performed.
Special Setting Mode
Key-protect, hysteresis width, window width, display refresh interval, number of measurement times for averaging, and bar indicator
range settings are set in special setting mode.
Setting item
Measurement
mode
OUT1 OUT2
kPa Torr Psi
Setting item
Hysteresis width
key-protect
OUT1 OUT2
OUT1 OUT2
kPa Torr Psi
Window width
kPa Torr Psi
OUT1 OUT2
Display refresh interval
kPa Torr Psi
OUT1 OUT2
Number of measurement
times for averaging
kPa Torr Psi
Bar indicator range
OUT1 OUT2 kPa Torr Psi
1. Press the SET key and Up key simultaneously to set the E8F2 to special setting mode and display prt.
2. Set the Up or Down key to select the items prt, hys, wid, dsp, aUe, and bar.
Key-protect Setting
No key-protect
OUT1 OUT2
kPa Torr Psi
OUT1 OUT2
kPa Torr Psi
or
Press the Up or Down key to
change the set value.
Key-protect Status
0: No Key-Protect.
1: No basic or pressure settings are accepted.
2: No input is accepted other than for checking the pressure value or special settings or setting to energy-saving mode.
1.
2.
3.
4.
Press the SET key while prt is displayed to display the key-protect value presently set.
Press the Up or Down key to change the value.
Press the SET key to select the displayed value and display prt again.
Press the Up and Down keys simultaneously display prt again without selecting the value.
16
OUT1 OUT2 kPa Torr Psi
E8F2
E8F2
Hysteresis Width Setting
The hysteresis width can be changed by taking the following steps.
Hysteresis mode
Output
or
OUT1 OUT2 kPa Torr Psi
ON
Change in
hysteresis width
desired
OFF
OUT1 OUT2 kPa Torr Psi
OUT1 OUT2 kPa Torr Psi
Window mode
Output
Press the Up or
Down Key to
change the set
value.
ON
Change in
hysteresis width
desired
OFF
ON
point
1.
2.
3.
4.
5.
6.
Pressure
value
OFF ON
point point
OFF
point
Pressure
value
Press the SET key while hys is displayed to display the hysteresis width of OUT1 presently set.
Press the Up or Down key to change the set value within a range between 0 and 10.0% FS.
Press the SET key to select the displayed set value and display the hysteresis width of OUT2 presently set.
Press the Up or Down key to change the set value.
Press the SET key to select the displayed set value and display hys again.
Press the Up and Down keys simultaneously to display hys again without selecting the value.
Note: 1. Hysteresis Mode: No manual hysteresis width settings are enabled in hysteresis mode except for those set by auto-teaching.
Window Mode
Hysteresis width settings are enabled when the E8F2 in window mode is set to measurement mode.
2. ON- and OFF-point widths in hysteresis mode are used as hysteresis widths, which cannot be changed in window mode.
Window Range Setting
or
OUT2
Output
OUT1
OUT1 OUT2 kPa Torr Psi
OUT1 OUT2
OUT1 OUT2 kPa Torr Psi
kPa Torr Psi
ON
(0 to 30%)
OFF
Reference value
(TEACH1)
Press Up or Down key
to change set value.
1.
2.
3.
4.
5.
6.
Press the SET key while wid is displayed to display the window width of OUT1 presently set.
Press the Up or Down key to change the set value within a range between 0 and 30% FS of the reference value.
Press the SET key to select the displayed set value and display the window width of OUT2 presently set.
Press the Up or Down key to change the set value.
Press the SET key to select the displayed set value and display wid again.
Press the Up and Down keys simultaneously to display wid again without selecting the set value.
Note: No window width settings will be enabled in hysteresis mode.
17
Pressure
value
E8F2
E8F2
Display Refresh Interval Setting
• The following refresh intervals are selectable.
0.1: The average value is displayed at 0.1-s intervals.
0.5: The average value is displayed at 0.5-s intervals.
1.0: The average value is displayed at 1.0-s intervals.
OUT1 OUT2
OUT1 OUT2
kPa Torr Psi
kPa Torr Psi
or
Press Up or Down key to
change set value.
1. Press the SET key while dsp is displayed to display the display refresh interval presently set.
2. Press the Up or Down key to change the set value.
3. Press the SET key to select the displayed set value and display dsp again.
4. Press the Up and Down keys simultaneously to display dsp again without selecting the set value.
Note: Set the AVE to the number of measurements for obtaining an average value.
Measurement Value Averaging Time Setting
The number of measurements can be set to 1, 8, 32, or 256.
OUT1 OUT2 kPa Torr Psi
OUT1 OUT2 kPa Torr Psi
or
Press Up or Down Key to
change set value.
1. Press the SET key while aUe is displayed to display the set value as the number of measurements for averaging measured values.
2. Press the Up or Down key to change the set value.
3. Press the SET key to select the displayed set value and display aUe again.
4. Press the Up and Down keys simultaneously to display aUe again without selecting the set value.
Note: If the DSP item is set to 0.5 and AVE item is set to 32, the E8F2 will measure 32 times, the average value of which will be treated
as one block. The average block value for 0.5 s will be displayed at 0.5-s intervals.
18
E8F2
E8F2
Bar Indicator Range Setting
The set value is an indication range per LED between 1 and 20% FS. If the E8F2 is set to AUT, the ideal display range will be automatica
set according to the the ON point presently set.
OUT1 OUT2
kPa Torr Psi
OUT1 OUT2
kPa Torr Psi
or
Press Up or Down key to
change set value.
1. Press the SET key while bar is displayed to display the bar display range presently set.
2. Press the Up or Down key to change the set value.
3. Press the SET key to select the displayed set value and display bar again.
4. Press the Up and Down keys simultaneously to display bar again without selecting the set value.
Note: The bar indicator range will be available to OUT1 output and will be enabled in hysteresis mode only.
Bar Indicator
The user can visually sense the measured pressure according to the ON and OFF points from the bar indicator. This indicator is available to OUT1 output only. There is a difference in indication mode between hysteresis mode and window mode.
• Hysteresis Mode
The five LEDs indicate the present pressure provided that the ON point is between the second and third LEDs from the left.
Output
1-MPa Model (with 300 kPa as ON Point)
ON
Condition 1 (350 kPa)
OFF
Pressure
value: kPa
300
(ON point)
The indication range per LED is obtained from the following.
• 300 kPa ≤ 1 MPa x 1/2
• 300 kPa x 1/3 = 100 kPa
The first through third LEDs from the left are all ON under condition 1. The indication range per LED is the set value of the indication
range in special setting mode. If the set value is aut, the following ranges are obtainable.
When ON point ≤ Rated pressure x 1/2
Indication range per LED = ON point x 1/3
When ON point > Rated pressure x 1/2
Indication range per LED = (Rated value -- ON point) x 1/3
Window Mode
The distance between ON and OFF points are divided into five equal portions. The present pressure will be indicated by a single
LED that will be ON. The left LED will flash if the present pressure is below the ON point and the right LED will flash if the present
pressure is above the OFF point.
•
Output
1-MPa Model
(with 300 kPa as ON point and 600 kPa as OFF point)
ON
Condition 2
(450 kPa)
OFF
300 kPa
(ON point)
Condition 3
(700 kPa)
600 kPa
(OFF point)
Pressure
value: kPa
Only LED (a) will be lit under condition 2.
Only LED (b) will be lit under condition 3.
The display range per LED will be the following.
Difference between ON and OFF points x 1/5
Note: No bar indicator settings in special setting mode will be enabled
19
E8F2
E8F2
Returning to Measurement Mode
Key-protect
Setting items
or
OUT1 OUT2
kPa Torr Psi
or
OUT1 OUT2
kPa Torr Psi
or
OUT1 OUT2
Number of measurement
times for averaging
Display refresh
interval
Window width
Hysteresis width
kPa Torr Psi
or
OUT1 OUT2
kPa Torr Psi
Entered
Entering Set Values:
Press the SET key for approximately 2 s
while the value is displayed.
Not entered
Bar indicator
range setting
or
OUT1 OUT2
Measurement
mode
OUT1 OUT2
kPa Torr Psi
kPa Torr Psi
Not Entering Set Values:
Press the Up and Down keys
simultaneously while the value
is displayed.
Energy-saving Mode
The E8F2 has functions to save power by turning OFF the numeric and menu display and leaving the bar indicator turned ON.
Energy-saving Function 1
Normal Measurement Mode
OUT1 OUT2
kPa Torr Psi
OUT1 OUT2
kPa Torr Psi
1. The numeric and menu display is turned OFF by pressing the SET and Down keys simultaneously in measurement mode.
2. The display is turned ON by pressing the SET and Down keys simultaneously again.
Energy-saving Function 2
If the present pressure is not within the set range, the numeric and menu display will flash as a warning.
Pressure beyond
the set range is
imposed.
OUT1 OUT2
kPa Torr Psi
OUT1 OUT2
kPa Torr Psi
OUT1 OUT2 kPa Torr Psi
OUT1 OUT2
kPa Torr Psi
Pressure value flashes.
Displayed for 1 s
1. If the SET and Down keys are pressed simultaneously for approximately 3 s in measurement mode, eco will be displayed for 1 s
and then the numeric and menu display will be turned OFF.
2. Provided that the E8F2 is set to window mode, the numeric and menu display will flash together with the bar indicator if the
present pressure is below ON point or above the OFF point.
3. The numeric and menu display and the bar indicator return to normal condition by pressing the SET and Down keys
simultaneously.
20
E8F2
E8F2
ON- and OFF Set Value Check Function
ON- and OFF-point Set value
or
Measurement
mode
or
or
or
or
Displayed
alternately
Displayed
alternately
OUT1 ON point
Displayed
alternately
Displayed
alternately
OUT2 OFF point
OUT2 ON point
OUT1 OFF point
The ON and OFF points presently set can be checked.
Press the Up or Down Key in measurement mode to display the OUT1 ON point and on alternately.
Press the Up or Down Key again to display the OUT1 OFF point and off alternately.
Press the Up or Down Key after the above to display the OUT2 items.
If no key is input for approximately 2 s during the above operation, the present measurement value will be displayed automatically.
Dimensions
Unit: mm (inch)
J CONTROLLER
E8F2
Display panel
28 (1.10)
27 (1.06)
29
(1.14)
25.5 (1.00)
1.5
(0.06)
2
(0.68)
17
(0.67)
9
8
(0.35) (0.31)
Pressure-introducing
Two-M3 (Depth: 6)
section
1/8 NPT
28
(1.10)
20
(0.79)
27
(1.06)
Vinyl-insulated round cable with five
conductors, 4 dia. (0.08 dia. x 30);
standard length: 2 m
20.5
(0.81)
20
(0.79)
6 (0.24)
Mounting Dimensions
With Mounting Bracket
Two-M3
20.5
(0.81)
29
(1.14)
27 (1.06)
15
(0.59)
5.4
(0.21)
20
(0.79)
20
(0.79)
42
(1.65)
28
(1.10)
15
(0.59)
21
E8F2
E8F2
J ACCESSORIES
E89-F3 Mounting Bracket
15 ±0.4
(0.59)
20.5
(0.81)
9
(0.35)
Two-3.5 (0.14) dia.
27 (1.06)
20 (0.79)
14.5
(0.57)
Four-R1 (R0.04)
13.5
(0.53)
20
(0.79)
26.9
(1.06)
* Provided with E8F2
Two-3.5 (0.14) dia.
4.5
(0.18)
R1.6 (R0.06)
R7.25 (R0.29)
Four-R2.5 (R0.10)
1.6
(0.06)
J E89-F4 PANEL-MOUNTING BRACKET (SOLD SEPARATELY)
Panel Cutout Dimensions
(E89-F4 is available in the following two sizes.)
20.65 (0.81)
Spacer not mounted
0
0
0
(1.42+0.02)
(1.30+0.02)
4
(0.16)
(1.42+0.02)
36+0.5
0
40 (1.57)
36+0.5
0
(1.30+0.02)
0
33+0.5
Panel
Spacer mounted
33+0.5
12.15
(0.48)
0
0
Panel
25 (0.98)
17
(0.67)
41.3 (1.63)
Note: The spacer can be removed from the panelmounting bracket. The panel cutout dimensions can be adjusted as shown above by
attaching or detaching the spacer.
40
(1.57)
11.5
(0.45)
20
(0.79)
Spacer
22
E8F2
E8F2
Precautions
J ENVIRONMENT
•
•
•
J MOUNTING
Do not use the Sensor in locations subject to explosive or
flammable gases.
Do not use the Sensor in an environment subject to corrosive
or combustible gases.
Make sure that the Sensor is free of water.
J AVOID DAMAGE TO THE E8F2
•
•
•
•
•
•
•
Do not impose any voltage exceeding the rated voltage on
the E8F2.
Do not short-circuit the load connected to the E8F2.
When supplying power to the E8F2, make sure that the polarity of the power is correct.
•
•
J WIRING
•
•
Do not wire power lines or high-tension lines adjacent to the
lines of the E8F2.
If no linear output is used, cut the gray lead wire short and
apply insulating tape to the lead wire so that it will not come
into contact with any other terminal.
•
Mount the Sensor so that ultrasonic vibrations will not be
applied directly to the Sensor.
Do not insert any wire into the pressure port. Doing so may
damage the pressure elements and cause a malfunction.
Do not apply a tensile strength in excess of 50 N (11.25 lbs)
to the cords or connectors.
The pressure-introducing section (aluminum die-cast made)
is fixed with tapered 1/8 NPT male screws and M5 female
screws. When using tapered screws, use tapered 1/8 NPT
female screws.
Wrap the tapered 1/8 NPT male screws with sealing tape to
prevent any leakage. Tighten the male screws to a torque of
10 NSm (7.38 ftSlbs) max.
Tighten M5 female screws to a torque of 2 NSm
(1.48 ftSlbs) max.
Tightening each male screw by using a 12-mm wrench to
hold its hexagonal head, not the screw itself.
E8F2
Hexagonal head
•
When attaching the Mounting Bracket to the Sensor, make
sure that each M3 screw is tightened to a torque of
0.5 NSm (0.37 ftSlbs) max.
NOTE: DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters to inches divide by 25.4.
R
OMRON ELECTRONICS LLC
OMRON ON--LINE
OMRON CANADA, INC.
1-800-55-OMRON