Solid State Relays
G3PA
Extremely Thin Relays Integrated with Heat Sinks
• Downsizing achieved through optimum design of heat sink.
• Mounting possible via screws or via DIN track.
• Close mounting possible for linking terminals. (Except for
G3PA-260B-VD and G3PA-450B-VD-2.)
• Applicable with 3-phase loads.
• Replaceable power element cartridges.
• Complies with VDE 0160 (finger protection), with a dielectric strength of 4,000 V between input and load.
• Complies with VDE 0805, IEC 950.
• Certified by UL, CSA, and VDE (reinforced insulation).
Ordering Information
List of Models
To Order: Select the part number and add the rated input voltage range. (e.g., G3PA-430B-VD-2 DC12-24)
Isolation
Phototriac
coupler
Zero cross function
Yes
No
Indicator
Yes
Rated output load
10 A at 24 to 240 VAC
Rated input voltage
5 to 24 VDC
20 A at 24 to 240 VAC
G3PA-220B-VD
40 A at 24 to 240 VAC
G3PA-240B-VD
60 A at 24 to 240 VAC
G3PA-260B-VD
10 A at 24 to 240 VAC
G3PA-210BL-VD
20 A at 24 to 240 VAC
G3PA-220BL-VD
40 A at 24 to 240 VAC
G3PA-240BL-VD
60 A at 24 to 240 VAC
Yes
Model
G3PA-210B-VD
10 A at 24 to 240 VAC
G3PA-260BL-VD
24 VAC
G3PA-210B-VD
20 A at 24 to 240 VAC
G3PA-220B-VD
40 A at 24 to 240 VAC
G3PA-240B-VD
60 A at 24 to 240 VAC
20 A at 180 to 400 VAC
G3PA-260B-VD
12 to 24 VDC
G3PA-420B-VD
30 A at 180 to 400 VAC
G3PA-430B-VD
20 A at 200 to 480 VAC
G3PA-420B-VD-2
30 A at 200 to 480 VAC
G3PA-430B-VD-2
50 A at 200 to 480 VAC
G3PA-450B-VD-2
Solid State Relays
G3PA
455
Replacement Parts
Name
Carry current
Power Device
Cartridge
10 A
Load voltage range
19 to 264 VAC
Applicable SSR
Model
VDE
certification
G3PA-210B-VD DC5-24
G32A-A10-VD DC5-24
G3PA-210BL-VD DC5-24
G32A-A10L-VD DC5-24
G3PA-210B-VD AC24
G32A-A10-VD AC24
G3PA-220B-VD DC5-24
G32A-A20-VD DC5-24
G3PA-220BL-VD DC5-24
G32A-A20L-VD DC5-24
G3PA-220B-VD AC24
G32A-A20-VD AC24
G3PA-240B-VD DC5-24
G32A-A40-VD DC5-24
G3PA-240BL-VD DC5-24
G32A-A40L-VD DC5-24
G3PA-240B-VD AC24
G32A-A40-VD AC24
G3PA-260B-VD DC5-24
G32A-A60-VD DC5-24
G3PA-260BL-VD DC5-24
G32A-A60L-VD DC5-24
G3PA-260B-VD AC24
G32A-A60-VD AC24
G3PA-420B-VD DC12-24
G32A-A420-VD DC12-24
G3PA-430B-VD DC12-24
G32A-A430-VD DC12-24
G3PA-420B-VD-2 DC12-24
G32A-A420-VD-2 DC12-24
30 A
G3PA-430B-VD-2 DC12-24
G32A-A430-VD-2 DC12-24
50 A
G3PA-450B-VD-2 DC12-24
G32A-A450-VD-2 DC12-24
20 A
40 A
60 A
20 A
150 to 440 VAC
30 A
20 A
180 to 528 VAC
Yes
Specifications
■ Ratings (at an Ambient Temperature of 25°C)
Input
Model
G3PA-2❏❏B-VD
Rated voltage
Operating Voltage
range
Input current
impedance
Voltage level
Must operate voltage
4 to 30 VDC
7 mA max.
G3PA-2❏❏B-VD
24 VAC
19.2 to 26.4 VAC
1.4 kΩ±20%
19.2 VAC max.
4.8 VAC min.
G3PA-4❏❏B-VD(-2)
12 to 24 VDC
9.6 to 30 VDC
7 mA max.
9.2 VDC max.
1 VDC min.
G3PA-2❏❏BL-VD
4 VDC max.
Must release voltage
5 to 24 VDC
1 VDC min.
20 mA max.
Output
Model
Applicable load
Rated load voltage
G3PA-210B(L)-VD
Inrush current
150 A (60 Hz, 1 cycle)
G3PA-220B(L)-VD
0.1 to 20 A
220 A (60 Hz, 1 cycle)
G3PA-240B(L)-VD
0.5 to 40 A
440 A (60 Hz, 1 cycle)
G3PA-260B(L)-VD
0.5 to 60 A
440 A (60 Hz, 1 cycle)
180 to 400 VAC (50/60 Hz)
19 to 264 VAC (50/60 Hz)
Load current
0.1 to 10 A
G3PA-420B-VD
24 to 240 VAC (50/60 Hz)
Load voltage range
150 to 440 VAC (50/60 Hz)
G3PA-430B-VD
G3PA-420B-VD-2
200 to 480 VAC (50/60 Hz)
220 A (60 Hz, 1 cycle)
0.5 to 30 A
440 A (60 Hz, 1 cycle)
0.5 to 20 A
220 A (60 Hz, 1 cycle)
G3PA-430B-VD-2
0.5 to 30 A
440 A (60 Hz, 1 cycle)
G3PA-450B-VD-2
0.5 to 50 A
440 A (60 Hz, 1 cycle)
Refer to Engineering Data for further details.
456
Solid State Relays
G3PA
180 to 528 VAC (50/60 Hz)
0.5 to 20 A
■ Characteristics
Item
G3PA210B(L)-VD
G3PA220B(L)-VD
G3PA240B(L)-VD
G3PA260B(L)-VD
G3PA420B-VD
G3PA420B-VD-2
G3PA430B-VD
G3PA430B-VD-2
G3PA450B-VD-2
Operate time 1/2 of load power source cycle + 1 ms max. (DC Input, -B models)
1 1/2 of load power source cycle + 1 ms max. (AC Input)
1 ms max. (-BL models)
Release time 1/2 of load power source cycle + 1 ms max. (DC Input)
1 1/2 of load power source cycle + 1 ms max. (AC Input)
Output ON
1.6 V (RMS) max.
voltage drop
1.8 V (RMS) max.
Leakage
current
5 mA max. (at 100 VAC)
10 mA max. (at 200 VAC)
10 mA max. (at 100 VAC)
20 mA max. (at 200 VAC)
20 mA
max. (at
400 VAC)
20 mA max. (at 20 mA
480 VAC)
max. (at
400 VAC)
I2 t
260 A2s
1,260 A2s
260 A2s
1,800 A2s
Insulation
resistance
100 MΩ min. (at 500 VDC)
Dielectric
strength
4,000 VAC, 50/60 Hz for 1 min
Vibration
resistance
Malfunction: 10 to 55, 0.75–mm double amplitude (Mounted to DIN track)
Shock
resistance
Malfunction: 300 m/s2 (mounted to DIN track)
Ambient
temperature
Operating:–30°C to 80°C (with no icing or condensation)
Storage:–30°C to 100°C (with no icing or condensation)
Certified
standards
UL, CSA, EN60950 File No. 5915ÜG
Ambient
humidity
Operating: 45% to 85%
Weight
Approx.
260 g
Approx.
340 g
Approx.
460 g
Approx.
900 g
20 mA max. (at 480 VAC)
1,800 A2s
1,800 A2s
UL, CSA ,
EN609474-3 File
No.
6642ÜG
UL, CSA,
EN60947-4-3
File No.
133127ÜG
UL, CSA, UL, CSA, EN60947-4-3 File
EN60947- No. 133127ÜG
4-3 File
No.
6642ÜG
Approx.
290 g
Approx.
290 g
Approx.
410 g
Approx.
410 g
Solid State Relays
Approx.
900 g
G3PA
457
Operation
■ Replacement Parts
G32A-A Power Device Cartridge
The G32A-A Power Device Cartridge (a Triac Unit) can be replaced with a new one. When the temperature indicator has changed from pink to red,
the triac circuitry may have malfunctioned possibly by an excessive flow of current, in which case, dismount the damaged cartridge for replacement.
The damaged cartridge can be replaced with a new one without disconnecting the wires from the G3PA.
Improve the heat radiation efficiency of the G3PA before replacing the cartridge.
The G32A-A Power Device Cartridge can withstand an excessive current for a short period of time, such as may be caused accidentally by the
short circuitry of the load, in which case the temperature indicator will not turn red.
Be sure to turn OFF the power supply when replacing the Cartridge. Supplying power with the Cartridge removed may result in malfunction.
Appearance
G32A-A10(L)-VD G32A-A20(L)-VD
G32A-A420-VD(-2)
G32A-A40(L)-VD
G32A-A430-VD(-2)
G32A-A60(L)-VD
G32A-A450-VD-2
Replacing Power Device Cartridges
When replacing Power Device Cartridges, use the specified model. Using a Power Device Cartridge other than the specified one will result in faulty
operation and destruction of the elements.
458
Solid State Relays
G3PA
■ Replacement Procedure
G32A-A10(L)-VD/G32A-A20(L)-VD/G32-A420-VD(-2)
Use the special tool (provided) to extract the cartridge for replacement with a new one.
Extraction
Follow the procedures below to remove the Power Device Cartridge
from the G3PA.
1. Switch off the power.
2. Remove the terminal cover.
3. Hook the indented part of the cartridge with the tool (supplied with
a new cartridge) and pull up on the cartridge to remove it.
Remover
Hook here with
Remover.
Apply silicone grease here.
2. Make sure that there is no dust or pieces of wire on the heat sink
of the G32A-A or the G3PA.
3. Insert the cartridge into the opening of the G3PA so that the letters on the cartridge and those on the G3PA are in the same
direction and side A and side B are even.
Side A
Side B
Installation
Follow the procedures below to Install the Power Device Cartridge on
the G3PA.
1. Apply silicone grease (provided with the G32A-A) to the entire
surface of the heat sink.
4. Attach the terminal cover.
5. Switch on the power and check the G3PA to be sure it works
properly.
G32A-A40(L)-VD/G32A-A60(L)-VD/G32A-A430-VD(-2)/G32A-A450-VD-2
The G32A Power Device Cartridge is mounted and secured with screws to the G3PA Unit.
Extraction
Installation
Follow the procedures below to remove the G32A-A Power Device
Cartridge from the G3PA.
Follow the procedures below to Install the Power Device Cartridge on
the G3PA.
1. Switch off the power.
2. Remove the terminal cover.
3. Loosen the two centered screws on the sides to dismount the cartridge. The screws are connected to terminals 1 and 2.
1. Apply silicone grease to the entire surface of the heat sink.
Loosen
Apply silicone grease here.
Loosen
2. Make sure that there is no dust or pieces of wire on the heat sink
of the G32A-A or the G3PA.
4. Loosen the screws on both the corners.
Loosen
Loosen
5. Hold the indented part of both the corners to remove
the cartridge.
Solid State Relays
G3PA
459
3. Insert the cartridge into the opening of the G3PA so that side A
and side B are even.
Side A
4. Tighten the screws on both the corners with a tightening torque of
0.59 to 0.78 N•m.
5. Tighten the screws on both the sides with a tightening torque of
0.59 to 0.78 N•m.
6. Attach the terminal cover.
7. Switch on the power and check the G3PA to be sure it works
properly.
Side B
■ Linking Terminal Connection
• Connecting with linking terminal for G3PA-210B(L)-VD, -220B(L)VD, -240B(L)-VD and G3PA-420B-VD(-2), G3PA-430B-VD(-2).
SSR1
SSR2
SSR1
SSR2
• Connecting with linking terminal to “G32A-D” series short circuit
unit. (Order short circuit units seperately.)
SSR
G32A Unit
SSR
G32A Unit
*
1. When SSRs are close
mounted, loosen the
M3.5 Sems screw and
flip the linking terminal
down.
2. Insert the linking
terminal securely
into the center of
the screw and
tighten the screw.
* The cover will not fit if
the terminal protrudes.
1. When SSR are close
mounted, loosen the
M3.5 Sems screw on
the G32A and flip the
linking terminal down.
2. Insert the linking terminal
securely into the center
of the screw and tighten
the screw. Ensure that
the linking terminal does
not protrude.
Connect the terminal with power off.
Linking terminal
G3PA-420B-VD
Refer to the instruction manual for
the G32A-A Power Device Cartridge
to replace the G3PA's triac part.
Linking terminal
When the temperature indicator has turned from pink to red, the G32-A-A Power Device Cartridge
may have malfunctioned, in which case the cartridge must be replaced with a new one.
460
Solid State Relays
G3PA
Linking
terminal
Linking
terminal
Use the terminal cover to prevent accidents
due to electric shock.
Engineering Data
Load Current vs. Ambient Temperature
Vertical Mounting
Panel
Ground
G3PA-210B(L)-VD, G3PA-220B(L)-VD
G3PA-240B(L)-VD
G3PA-260B(L)-VD
G3PA-220B(L)-VD
80
Load current (A)
G3PA-210B(L)-VD
15
Load current (A)
Load current (A)
25
60
40
25
20
-30 -20
Ambient temperature (°C)
Ambient temperature (°C)
Ambient temperature (°C)
20
40
60
80
100
G3PA-450B-VD-2
Load current (A)
G3PA-430B-VD, G3PA-430B-VD-2
Load current (A)
Load current (A)
G3PA-420B-VD, G3PA-420B-VD-2
0
Ambient temperature (°C)
Ambient temperature (°C)
Ambient temperature (°C)
Note: Close mounting is possible for a maximum of three Units by reducing the load current by 20%. (A minimum clearance of 10 mm must be
provided when mounting four or more Units.)
Solid State Relays
G3PA
461
Input Voltage vs. Input Current
G3PA-4@0-VD, G3PA-4@-VD-2
Input impedance (kΩ)
Input current (mA)
Input impedance (kΩ)
Input current (mA)
G3PA-2@0B-VD
Ta = 25°C
8
6
4
Input current
2
1
0.8
0.6
Input impedance
10
Input
current
4
2
Input impedance
1
0.8
0.6
0.4
0.4
0.2
0.2
0.1
1
T = 25°C
8
6
0.1
2
4
6
8 10
20
1
40
2
4
6
8 10
20
40
Input voltage (V)
Input voltage (V)
Horizontal Mounting
Panel
Ground
G3PA-220B(L)-VD
15
14
11
10
G3PA-210B(L)-VD
7
5.5
5
3.5
G3PA-260B(L)-VD
Load current (A)
20
G3PA-240B(L)-VD
Load current (A)
Load current (A)
G3PA-210B(L)-VD, G3PA-220B(L)-VD
28
11
10
60
42
40
20
18
−30 −20
Ambient temperature (°C)
Ambient temperature (°C)
G3PA-430B-VD
G3PA-420B-VD
G3PA-450B-VD-2
Load current (A)
Load current (A)
G3PA-420B-VD, G3PA-430B-VD
G3PA-420B -VD-2, G3PA-430B-VD-2
Ambient temperature (°C)
462
Solid State Relays
Ambient temperature (°C)
G3PA
0
20
40
60
80
Ambient temperature (°C)
100
Close Mounting (Up to Three)
Panel
Ground
DIN track
G3PA-210B(L)-VD, G3PA-220B(L)-VD
G3PA-240B(L)-VD
G3PA-260B(L)-VD
30
45
27
G3PA-220B-VD
15
13
9
G3PA-210B-VD
7
5
4.5
64
36
Load current (A)
20
18
Load current (A)
Load current (A)
40
30
20
14
48
40
20
10
-30 -20
Ambient temperature (°C)
Ambient temperature (°C)
G3PA-420B-VD, G3PA-420B-VD-2
20
40
60
80
100
G3PA-430B-VD, G3PA-430B-VD-2
30
40
Load current (A)
Load current (A)
0
Ambient temperature (°C)
20
16
10
30
24
20
10
−30
10
30
80
Ambient temperature (°C)
100
−30
10
30
80
Ambient temperature (°C)
Load current (A)
G3PA-450B-VD-2
Ambient temperature (°C)
Solid State Relays
G3PA
463
Inrush Current Resistivity
One cycle, non-repetitive (Keep the inrush current to half the rated value if it occurs repetitively.)
Energized time (ms)
464
Solid State Relays
Energized time (ms)
G3PA
G3PA-240B(L)-VD/260B(L)-VD,
G3PA-430B-VD, G3PA-430B-VD-2,
G3PA-450B-VD-2
Inrush current (A. Peak)
G3PA-220B(L)-VD, G3PA-420B-VD,
G3PA-420B-VD-2
Inrush current (A. Peak)
Inrush current (A. Peak)
G3PA-210B(L)-VD
Energized time (ms)
Dimensions
Note: All units are in millimeters unless otherwise indicated.
G3PA-210B(L)-VD
With Terminal
Cover
Without Terminal
Cover
4.6 dia.
Two, M4
Linking terminal B1
Mounting
Holes
Terminal
Arrangement/
Internal Connections
Two, 4.5 dia. or M4 holes
Input circuit
Trigger circuit
Two,
M3.5
Linking
terminal B2
4.6 x 5.6 elliptical
hole
100 max.
G3PA-220B(L)-VD
Without Terminal
Cover
With Terminal
Cover
4.6 dia.
Linking terminal B1
Mounting
Holes
Two, M4
Terminal
Arrangement/
Internal Connections
Two, 4.5 dia. or M4 holes
Input circuit
Trigger circuit
Two,
M3.5
Linking terminal B2
4.6 x 5.6 elliptical
hole
100 max.
Linking
terminal B1
With Terminal
Cover
4.6 dia.
Two, M5
Mounting
Holes
Two, 4.5 dia. or M4 holes
Terminal
Arrangement/
Internal Connections
Two,
M3.5
Input circuit
Without Terminal
Cover
Trigger circuit
G3PA-240B(L)-VD
Linking
terminal B2
4.6 x 5.6 elliptical
hole
100 max.
Solid State Relays
G3PA
465
G3PA-260B(L)-VD
G3PA-450B-VD-2
With Terminal
Cover
Without Terminal
Cover
Terminal Arrangement/
Internal Connections
Mounting Holes
4.6 dia.
Two, M5
Two, M3.5
4.6 x 5.6
elliptical hole
Input circuit
Trigger circuit
Two, 4.5 dia. or M4 holes
110 max.
100 max.
G3PA-420B-VD, G3PA-420B-VD-2
Without Terminal
Cover
With Terminal
Cover
Mounting Holes
Two, 4.5 dia. or M4
4.6 dia.
Terminal Arrangement/
Internal Connections
Two, M4
7.6
Linking
terminal
−B2
90±0.3
80
Trigger circuit
38 100
max.
Input circuit
90±0.2
Linking
terminal
67+B1
8.6
Two, M3.5
2.2
8.8
25±0.2
4.5 x 5.6 elliptic hole
100 max.
37 max.
4.5
13.2
91
90
G3PA-430B-VD, G3PA-430B-VD-2
Without Terminal
Cover
With Terminal
Cover
Mounting Holes
Terminal Arrangement/
Internal Connections
4.6 dia.
Two, M5
Two, 4.5 dia. or M4
Linking
terminal
+B1
38 100 90±0.2 80
max.
Linking
terminal
−B2
90±0.3
13
18
13
4.6 x 5.6
elliptic hole
89
466
Solid State Relays
G3PA
35±0.2
4.5
100 max.
47 max.
91
35±0.3
Input circuit
67
Trigger circuit
7.6
Safety Precautions
■ Precautions for Correct Use
For a DC or L load, a diode should be connected in parallel the load
to absorb the counter electromotive force of the load.
Please observe the following precautions to prevent failure to operate, malfunction, or undesirable effect on product performance.
Load
Load Connection
For an AC load, use a power supply rated at 50 or 60 Hz.
The maximum operating frequency is 10 Hz.
The G3PA-(VD) has a built-in varistor for overvoltage protection.
Load power
supply
SSR
Input
Noise Terminal Voltage according to
EN55011
At a low applied voltage, such as 24 VAC, the load current is not fully
supplied. When the Unit is switched ON, the voltage required to
power the Unit deprives the output signal of the necessary voltage
level and thus creates loss time. The lower the load voltage is, the
greater the loss time is. This condition, however, will not create any
serious problems.
The G3PA-(VD) complies with EN55011 standards when a capacitor
is connected to the load power supply as shown in the following circuit diagram.
Load
Input
G3PA-(VD)
Output
Recommended Capacitor: 1 μF, 250 VAC
Loss time
Mounting
When attaching a heat sink to the G3PA-(VD), in order to facilitate heat dissipation, apply silicone grease or equivalent heat-conductive grease on
the heat sink. (Toshiba Silicone, Shinetsu Silicone, etc.)
Tighten the mounting screws of the heat sink with a torque of 0.78 to 0.98 N•m.
Vertical
↔
• Screw or DIN track
mounting is possible.
• Vertical mounting should
usually be used.
Vertical mounting
G3PA
↔
DIN track
G3PA
80 mm
DIN track
Close mounting
Horizontal mounting
Vertical
The rated ambient
temperature is
40°C. (30°C for
400 V.)
Vertical
↔
Panel
Panel
• Close mounting is also
possible.
• Close mounting is possible for
up to 3 G3PA SSRs. (If there
are 4 or more SSRs, mount at
intervals of 10 mm min.)
Reduce the load current by
10% for G3PA-210B-VD,
-220B-VD, -240B-VD and by
20% for G3PA-260B-VD, 420B-VD(-2), -430B-VD(-2),
-450B-VD-2.
• Leave a distance of 80 mm
• With vertical mounting,
reduce the load current by
30%. (Refer to the Load
Current vs. Ambient
Temperature graph.)
Note: Leave a distance of 60 mm min. between SSRs and ducts (especially above the SSR).
Solid State Relays
G3PA
467
Close Mounting
An SSR uses a semiconductor in the output element. This causes
the temperature inside the control panel to increase due to heating
resulting from the passage of electrical current through the load. To
restrict heating, attach a fan to the ventilation outlet or air inlet of the
control panel to ventilate the panel. This will reduce the ambient temperature of the SSRs and thus increase reliability. (Generally, each
10°C reduction in temperature will double the expected life.)
SSR Mounting Pitch
Panel Mounting
(At a rated ambient temperature of 40°C).
Duct or airflow obstruction
Load current (A)
SSR
Required number of fans
per SSR
60 mm min.
Size of fans: 92 mm2, Air volume: 0.7 m3/min,
If there are instruments that generate heat in the control panel
other than SSRs, additional ventilation will be required.
min.
Relationship between SSRs and Ducts
Countermeasure (1)
Countermeasure (2)
50 mm max.
(A height of no
more than half
the SSR's height is
recommended.)
G3PA
G3PA
Mounting surface
Mounting surface
Mounting surface
Duct or
airflow
obstruction
Vertical
direction
Airflow
Duct or
airflow
obstruction
Do not surround the SSR
with ducts, otherwise the
heat radiation of the SSR
will be adversely affected.
Use short ducts.
If the ducts cannot be
shortened, place the SSR
on a metal base so that it
is not surrounded by the
ducts.
Ventilation
Be aware of air flow
Duct or
air flow
obstruction
Ventilation
outlet
G3PA
G3PA
G3PA
Air inlet
If the air inlet or air outlet has a filter, clean the filter regularly to prevent it from clogging and ensure an efficient flow of air.
Do not locate any objects around the air inlet or air outlet, otherwise
the objects may obstruct the proper ventilation of the control panel.
A heat exchanger, if used, should be located in front of the SSR Units
to ensure the efficiency of the heat exchanger.
Please reduce the ambient temperature of SSRs.
The rated load current of an SSR is measured at an ambient
temperature of 25 or 40°C.
468
60 A
0.93
Thus, 4 fans would be required.
Close Mounting
G3PA
40 A
0.62
Ambient temperature of control panel: 30°C
Space between
SSRs
Duct Height
30 A
0.47
0.31 x 10 = 3.1
30 mm min.
80 mm min.
20 A
0.31
Example: For 10 SSRs with load currents of 20 A,
Between duct
or airflow
obstruction
and SSR
Mounting direction
Vertical direction
10 A
0.16
Solid State Relays
G3PA
MEMO
Solid State Relays
G3PA
All sales are subject to Omron Electronic Components LLC standard terms and conditions of sale, which
can be found at http://www.components.omron.com/components/web/webfiles.nsf/sales_terms.html
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
OMRON ON-LINE
OMRON ELECTRONIC
COMPONENTS LLC
55 E. Commerce Drive, Suite B
Schaumburg, IL 60173
Global - http://www.omron.com
USA - http://www.components.omron.com
847-882-2288
Cat. No. X301-E-1b
Solid State Relays
09/11
G3PA
Specifications subject to change without notice