9
Technical Reference Data
G730
The following information applies to all G730 Remote I/O Modules
1 Application examples
1 Connecting to Wired Remote I/O Master
1 Cables
1 Precautions
modules
1 Troubleshooting and alarm list
Application Examples
3 G730 COMBINES WITH OMRON’S OTHER REMOTE I/O PRODUCTS
(Maximum of two Modules can be mounted.)
C200H-RM201
Wired Remote I/O Master
Module
RM
IN
C200H
C200H-RT201/RT202
Remote I/O Slave Module
Slave Rack
SYSMAC BUS
#0
Word 200
200 m max.
#2
#3
#1
G730-VID08 G730-VID08
G730-VID08
word 201
word 202
word 203
C200H-BCPP1-V2
Backplane
G730-ROC04
Valve, solenoid, or lamp
C500 Slave Rack
Sensor or switch
(One C500 Remote
Slave Module counts
as two
C200HX/HG/HE
Modules)
32 modules max. (512 points)
5 Slave
Racks
max.,
C500
Slave
Rack
counted
as 2.
C500-RT201
Remote I/O Slave Module
Twistedpair
cable
G7TC I/O Block
G71 Remote
Interface Module
G72C I/O Terminal
32 modules
max. (512 points)
G730-ROC08
Remote Relay
Output Module
G730-VID16
Remote Transistor
Input module
To other Slaves (NT-Series Opeator Interface Terminals,
G7TC, G70A, G70D I/O Relay Blocks, etc.)
G730
G730
Installation
3 CONNECTING TO REMOTE I/O MASTER MODULES (WIRED SYSMAC BUS)
The G730-V and G730-R can be connected to a Wired Remote I/O Master. In this case, conventional G71 and G72C models can be used
in the same system.
Although the G730-V and the G730-R are 16/8/4-point terminasl, each of them occupies one word as an actual allocated word. The
G730-ROC04-A (with an error detecting function), however, occupies two words because it must transmit error information to the PLC.
The following tables list the actual word allocations of Remote Terminals on PLCs.
Remote Terminals (other than the G730-ROC04-A)
PLC Model
Actual word allocation
C500
Switch setting word
C1000H/C2000H
(32 words x Remote I/O Master backplane no.) + switch setting word
C200H
200 words + switch setting word
Note: For other PLCs, refer to the operation manuals of those PLCs.
G730-ROC04-A (Two Words are Occupied)
PLC Model
Error information word
Actual word allocation
C500
Switch setting word
Error information word + 1
C1000H/C2000H
(32 words x Remote I/O Master backplane no.) + switch setting word
Error information word + 1
C200H
200 words + switch setting word
Error information word + 1
Note: Refer toError Detecting Function of the G730-ROC04-A.
Example: A C200H PLC is used with the following settings.
• G730-VOD08 set to word 0.
• G730-RIA04 set to word 1.
• G730-ROC04--A (with error detecting function) set to word 2)
15 14 13 12 11 10 9 8 7 6 5 4
3 2 1
0
Word 200
Not used even as internal
relays.
Used as relays for the
G730-VOD08.
15 14 13 12 11 10 9 8 7 6 5 4
3 2 1
0
Word 201
Not used even as internal
relays.
Used as relays for the
G730-RIA04.
15 14 13 12 11 10 9 8 7 6
5 4
3 2 1
0
Word 202
Not used even as internal Used as error data area
relays.
for the G730-ROC04-A.
15 14 13 12 11 10 9 8 7 6 5 4
3 2 1
Word 203
Not used even as internal
relays.
2
Used as relays for the
G730-ROC04-A.
0
G730
G730
3 TROUBLESHOOTING AND ALARM LIST
Master Module (Master)
Abnormal
Expansion
Unit/Slave
PWR
Cause of error
Remedy
PWR
END
T/R
ALM
NODE
Before
eoe
and
d after
ft
normal
operation
Not lit
Not lit
Not lit
Not lit
Not lit
------
------
T/R
The G730-M is not turned on.
Turn on the G730-M.
Lit
Not lit
Not lit
Not lit
Not lit
------
------
CPU abnormality.
Turn off and on the G730-M Master. If the
CPU has abnormality again after the
G730-M Master is turned on, replace the
G730-M Master.
Before
normal
operation
ti
Lit
Lit
Flashing
------
Lit/
Not lit
Lit
Lit
Slaves are set to words 28 to
30.
Slaves must be set to an word range of 0
to 27.
Lit
Lit
Flashing
------
Not lit
Lit
Lit
No terminator is set.
The terminator switch of the Slave
located farthest from the G730-M Master
on the transmission path must be set to
ON.
There is more than one G730-M
Master in the system.
There must be only one G730-M Master
in a single system. If more I/O points are
required, connect one to three Expansion
Units according to the number of I/O
points required.
A Master Unit different in
communication configuration
exists.
A different Master Unit in communication
configuration cannot be used together
with the G730-M/N.
The transmission path is
short-circuited.
The transmission path is
disconnected.
The positive and negative wiring
of the transmission path is
reversed.
Wire the transmission path correctly.
The expansion numbers of two
Expansion Units with the same
I/O configuration are identical.
Assign different words to all Units.
The words of two Slaves with
the same I/O configuration are
identical.
Lit
Lit
Flashing
------
Not lit
Not lit
Not lit
The terminator has power
failure.
Turn on the terminator.
Lit
Flashing
Flashing
------
Not lit
Lit
Lit
There is more than one
terminator.
The terminator switch of only the Slave
located farthest from the G730-M Master
on the transmission path must be set to
ON.
Lit
Not lit
Flashing
------
Flashing
Lit
Lit
The I/O type of the Master Unit
and that of the Slaves do not
correspond.
The I/O type of the Master Unit must
correspond to the I/O type of the Slaves.
Be sure to set them correctly.
The words of two Slaves
different to each other in I/O
type are identical.
Set so that no word will be duplicated.
The expansion numbers of two
Expansion Units different to
each other in I/O type are
identical.
Lit
Not lit
Flashing
------
Not lit
Four-point Units are set to
words 24 to 27, which is an
exclusive area for 8/16-point
Units.
Set 4-point Units to words 0 to 23, and
set 8/16-point Units to words 24 to 27.
The word settings for a
8-point/16-point Unit is beyond
the specified range.
Not all words between word 00 and word
32 can be used for 8-point or 16-point
Units.
The words for Units with
different numbers of points are
duplicated.
Assign different words to all Units.
Lit
Lit
A Slave is set to word 31. There
is a Slave with no Expansion
Unit.
Slaves must be set to words 0 to 27.
Not lit
Not lit
The Slaves except the
terminator or Expansion Unit in
the system are not turned on.
Turn on the Slaves and Expansion Unit.
3
G730
G730
Master Module (Master)
PWR
After
normal
operation
Lit
END
Not lit
T/R
Lit
ALM
------
Abnormal
Expansion
Unit/Slave
NODE
------
PWR
Cause of error
Remedy
T/R
Lit
Lit
The transmission path is
short-circuited.
The transmission path is
disconnected.
Wire the transmission path correctly.
Not lit
Not lit
The Expansion Unit is turned
off.
Turn on the Expansion Unit.
The Slave has power failure.
Turn on the Slave.
Lit
Not lit
Flashing
Lit
Not lit
Lit
Flashing
Relay contact weld, improper
relay contact, or load
disconnection has caused the
Slave to indicate an error
detecting function.
Replace the relay or connect the load.
Lit
Not lit
Lit
------
------
Lit
Not lit
The CPU on the Expansion Unit
for the Slave has abnormality.
Turn off the Slave and Expansion Unit
and turn them on again and check if they
operate normally. If they do not operate
normally, replace them.
Note: 1. Dotted lines mean that the indication of the LEDs have nothing to do with the errors.
2. Refer to C-Series Remote I/O Module (Wired-Type) Operation Manual W120 for details on troubleshooting when the system is
connected to a Remote I/O Master.
Connector Cables
Use G79 Cables to connect G730 Remote I/O Modules to PLC input and output modules. Complete pinout drawings are in the G79
Cables data sheet in the Wiring Solutions section of this catalog. For controllers from any manufacturer, use G79-YPC cables with crimp
hooks or G79-APC cables with tinned leads. For dedicated cables used with Omron PLCs, consult the G79 Cables data sheet.
3 G79 CONNECTING CABLE
G79-YPC with Crimp-style Terminals
Use the G79-YPC Cable to connect the screw
terminals of a controller and the G730-M/N
Master Module.
L: Length
1,000 mm
1,500 mm
2,000 mm
3,000 mm
5,000 mm
G79-Y100C
G79-Y150C
G79-Y200C
G79-Y300C
G79-Y500C
Connecting to peripheral
devices
Connecting to the G730.
300
L
Note: 1. The wire capacity must be 50 mA max. per I/O.
2. Each wire has a pin number as shown in the following table
Connections.
G79-APC with Multi-strand Cable
The G79-APC has a multi-strand cable on the
controller side.
L: Length
2,000 mm
5,000 mm
G79-A200C
G79-A500C
Connecting to peripheral
devices
Connecting to the G730.
300
L
Note: 1. The diameter of each wire is 0.6 mm (AWG24)
2. Each wire has a pin number as shown in the following table
Connections.
4
G730
G730
Precautions
Cleaning
3 CONNECTION
Wiring
Use alcohol to clean the G730. Do not use paint thinner; it will
dissolve or discolor the paint on the panel of the G730.
Do not wire the cable near or in parallel with power lines.
Removing Finger Protection Cover
Pay attention to the polarities of the terminals.
Use a screwdriver to unlock parts (1), (2), and (3).
Be sure to wire the transmission path and power lines correctly.
Provide a distance of 200 mm at least between power lines and
the G730.
Design the whole system with the correct voltage specification for
I/O exchange.
Installation Site
(1)
The following conditions are required to install the G730.
There is no direct sunlight.
The ambient temperature is within a range of 0 to 55 °C.
The relative humidity is within a range of 10% to 90%.
There is no drastic temperature changes that can cause
condensation.
There is no corrosive or inflammable gas.
There is no excessive dust, salinity, or powdered metal.
No vibration or shock is directly imposed on the G730.
No water, oil, or chemical is sprayed on the G730.
(3)
(2)
3 MOUNTING ADAPTER
DIN Track Adapter
Protection from Noise
Do not install the G730 on a panel where high--power equipment
is installed.
G730--V
Power line
200 mm min.
G730
200 mm
min.
G730-Y30
Mounting Screws
Mounting screws must be tightened securely to prevent the G730
from malfunctioning.
Connection Cable Lock
Note: Mount the G730-V to the G730-Y30 so that
the G730-V and G730-Y30 mate securely
with each other.
Before turning on the G730, check that the connectors of each
connection cable are locked properly.
Static Electricity
Excessive static electricity can be generated where the humidity
is low. Before you operate the G730, touch grounded metal so
that your body will be free from static electricity.
NOTE: DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters to inches divide by 25.4.
9
OMRON ELECTRONICS, INC.
OMRON CANADA, INC.
One East Commerce Drive
Schaumburg, IL 60173
885 Milner Avenue
Scarborough, Ontario M1B 5V8
1-800-55-OMRON
416-286-6465
Cat. No. GC RIO-1
04/00
Specifications subject to change without notice.
Printed in U.S.A.