Wiring Systems
Introduction to I/O Blocks, I/O Terminals, and I/O Block Bases
G70D, G7TC, and G70A-ZOC16
Unify Wiring with One Connecting Cable.
Simplify Connections to the Controller and Reduce Wiring in the Control Panel.
Improve Surge Suppression and Increase Capacity at the Same Time.
G70D
Compact Output Terminals Save Control Panel Space
• The G70D Series consists of 16-point Relay Output Terminals.
• Two configurations are available: The standard low-profile version is just 156 × 51 × 39 mm (W×D×H) and the vertical version
is just 135 × 46 × 81 mm (W×D×H).
• Relay output models are equipped with G6D power relays (low-profile: SPST-NO 3 A/common; vertical: SPST-NO 3 A/output)
and power MOSFET relay models are equipped with G3DZ power MOSFET relays (SPST-NO 0.3 A/output).
• The flat models have 2 common terminals. The vertical models have 16 independent outputs.
Note: See page 389 and page 392 for more details.
Vertical models
(G70D-VSOC16/VFOM16)
Low-profile models
(G70D-SOC16/FOM16)
G7TC
Both Input Blocks and Output Blocks are Available. G7TC I/O Blocks are Ideal as Controller Interfaces.
• Output Blocks with 8 or 16 outputs are available. Input Blocks
with 16 inputs are available.
• The 16-point Output Blocks are available with PNP circuits.
• The 16-point models are just 182 × 85 × 68 mm (W×D×H)
and the 8-point models are just 102 × 85 × 68 mm
(W×D×H).
• Equipped with G7T I/O Relays (SPST-NO 5 A/output).
• G7TC models conform to UL and CSA standards.
• 16-point models with independent terminals.
• Models are also available with G3TA Solid State Relays.
8-point model
16-point model
Note: See page 394 for more details.
G70A-ZOC16
High-capacity Relay Sockets can be Equipped with G2R (SPDT) Relays.
• Sixteen relay terminal sockets for output relays only.
• Models are available with PNP circuits.
• Compact case is just 234 × 75 × 64 mm (W×D×H).
• Install OMRON G2R Power Relays, G3R Solid State Relays,
G3RZ Power MOSFET Relays, and H3RN Timers as
required. (Relays and Timers are sold separately.)
• High-capacity 10-A Terminal Block
• Conforms to VDE standards.
• Sixteen independent terminals
Note: See page 397 for more details.
386
*Relays are sold separately.
Programmable Controllers
Programmable
Controllers
G70D-SOC08
Space-saving and Labor-saving 8-point Output Block
• Compact terminal block is just 68 × 80 × 44 mm (W × H × D,
when mounted upright).
• Independent contacts and shorting bars allow easy common
connections.
• The common can now be connected with a shorting bar in the
G70D-SOC08 and G70R-SOC08.
• No tools are required to remove Relays, so Relay replacement is easier than ever.
• The attached terminal cover prevents shocks.
• Equipped with operation indicators.
• Built-in diodes absorb coil surge.
• Mount either to DIN rail or via screws.
Note: See page 398 for details.
G70R-SOC08
Space-saving and Labor-saving 8-point Output Block
• Compact terminal block is just 136 × 80 × 55 mm (W × H × D,
when mounted upright).
• Independent contacts and shorting bars allow easy common
connections.
• The common can now be connected with a shorting bar in the
G70D-SOC08 and G70R-SOC08.
• No tools are required to remove Relays, so Relay replacement is easier than ever.
• The attached terminal cover prevents shocks.
• Built-in diodes absorb coil surge.
• Mount either to DIN rail or via screws.
Note: See page 401 for details.
G70D, G7TC, and G70A-ZOC16
387
System Configurations
Connector-equipped cables can be used as shown below to quickly connect I/O Blocks to I/O Units.
Connecting Cables with Three Connectors
CS1W-ID291
CS1W-OD291
CS1W-MD291
G70A-ZOC16 (output only) + Relays
or G7TC
or G70D (output only)
G79
Connecting Cable with
Three Connectors
Connecting Cables with Two Connectors
C500-ID219
C500-OD213
C200H-ID216
C200H-ID217
C200H-OD218
C200H-OD219
CQM1-ID213
CQM1-OD213
G70A-ZOC16 (output only) + Relays
or G7TC or G70D (output only)
CN1-A
II
CN2-A
IV
CN1-B
I
CN2-B
G79
III
Connecting Cable with
Two Connectors
Note: In the diagram above, symbols CN1-A/-B and CN2-A/-B indicate the column numbers for C200H I/O Unit connector pins and symbols
I to IV indicate the column numbers for C500 I/O Unit connector pins.
Connecting Cables with One Connector
C200H-ID215
C200H-OD215
C200H-MD215
G79
Connecting Cable
with One Connector
388
G70A-ZOC16 (output only)
+ Relays
or G7TC
or G70D (output only)
C500-ID218CN
C500-OD415CN
C500-MD211CN
G70A-ZOC16 (output only)
+ Relays
or G7TC
or G70D (output only)
G79
Connecting Cable
with One Connector
Programmable Controllers
Relay output terminal blocks
Easy-to-use, Space-saving 16-point Output
Block
• Slim terminal block is just 135 × 40 mm (W × D).
• Independent contacts and short bars allow easy
common connections.
• An Expansion Terminal Block can be mounted for
power line connections.
• M3.5 fork-type crimp terminals (with a maximum terminal width of 6.2 mm) can be used.
• Lever mechanism allows Relays to be installed and
removed easily without tools.
• Relay models and power MOSFET Relay models
are available.
• Equipped with operation indicators.
• Can be combined with a DRT1-OD32ML I/O Terminal for DeviceNet connectivity or an SRT2VOD16ML Connector Terminal for CompoBus/S
connectivity.
• Built-in diode absorbs coil surge.
• Mount either to DIN rail or via screws.
Ordering Information
Classification
Points
Relay outputs
Power MOSFET Relay outputs
16 points (SPST-NO × 16)
Internal output circuit
common
NPN compatible
(+ common)
Rated voltage
Model
24 V DC
G70D-VSOC16
G70D-VFOM16
These are all non-standard model and require a special order. Contact your OMRON representative for details on availability.
Specifications
Ratings
Relay Specifications
Note: The following specifications apply to G6D Relays mounted in a G70D Output Block and not the G6D Relay itself.
Coil Ratings (per G6D Relay)
Rated voltage
Rated current
Coil resistance
Must-operate voltage
Release voltage
Max. allowable voltage
Power consumption
Relay output terminal blocks
24 V DC
10.5 mA
2,880 Ω
70% max. of rated voltage
10% min. of rated voltage
130% of rated voltage
Approx. 200 mW
Note: 1. The must-operate voltage is 75% max. of the rated voltage if
the Relay is mounted upside down.
2. Rated current and coil resistance were measured at a coil
temperature of 23°C with a tolerance of ±10%.
3. Operating characteristics were measured at a coil temperature of 23°C.
4. The maximum allowable voltage is the maximum value of the
allowable voltage range for the relay coil operating power
supply. There is no continuous allowance.
5. The rated current includes the current consumption of the operation indicator.
389
Programmable
Controllers
G70D-VSOC16/-VFOM16
Power MOSFET Relay Specifications
Contact Ratings (per G6D Relay)
Load
Rated load
Rated carry current
Max. switching voltage
Max. switching current
Max. switching capacity
Min. permissible load (reference value)
(See note .2)
Life expectancy
Resistive load (cosφ = 1)
3 A at 250 V AC, 3 A at 30 V DC
5 A (see note 1)
250 V AC, 30 V DC
5A
1,250 VA, 150 W
5 V DC, 1 mA
Note: The following values apply to G3DZ Relays mounted in a G70D
Output Block and not the G3DZ Relay itself.
Electrical: 100,000 operations min. (under and at the rated load at 1,800 operations/hr), Mechanical: 20,000,000
operations min. (at 18,000 operations/
hr)
Input impedance
Rated current
Note: 1. Up to 5 A can be carried when 8 or fewer outputs are ON.
2. This value is for a switching frequency of 120 times per
minute.
Input (per G3DZ Power MOSFET Relay)
Rated voltage
Operating voltage
Voltage level
24 V DC
19.2 to 28.8 V DC
19.2 V DC max.
1 V DC min.
4 kΩ±20%
8.2 mA±20%
Must operate
Must release
Note: The rated current includes the current consumption of the operation indicator.
Output (per G3DZ Power MOSFET Relay)
Load voltage
Load current
Inrush current
3 to 264 V AC, 3 to 125 V DC
100 µA to 0.3 A
6 A (10 ms)
Characteristics
Item
Contact form
Contact mechanism
Contact resistance
Isolation method
Must-operate time
Release time
Output ON-resistance
Open-circuit leakage current
Max. switching frequency
Insulation resistance
Dielectric strength
Noise immunity
Vibration resistance
Shock resistance
Operating voltage range
Current consumption
Cable length
LED color
Coil surge absorber
Ambient temperature
Ambient humidity
Mounting strength
Terminal strength
Weight (see note 6)
G70D-VSOC16
G70D-VFOM16
Relay outputs
Power MOSFET Relay outputs
16 points (SPST-NO × 16)
Single
--100 mΩ max. (see note 2)
----Photocoupler
10 ms max. (see note 3)
6 ms max.
10 ms max. (see note 3)
10 ms max.
--2.4 Ω max.
--10 µA max. (at 125 V DC)
Mechanical:18,000 operations/hr
--Rated load:1,800 operations/hr
100 MΩ min. (at 500 V DC)
2,000 V AC for 1 min between coil and contact
2,000 V AC for 1 min between input and output terminals
Power input (normal mode): 600 V for 10 min with a pulse width of 100 ns to 1 µs
Power input (common mode): 1.5 kV for 10 min with a pulse width of 100 ns to 1 µs
Input cable (coiling): 1.5 kV for 10 min with a pulse width of 100 ns to 1 µs
Unit body (coiling): 600 V for 10 min with a pulse width of 100 ns to 1 µs
Destruction: 10 to 55 to 10 Hz, 0.5-mm amplitude (1.0-mm double)
Malfunction: 10 to 55 to 10 Hz, 0.375-mm amplitude (0.75-mm double)
Destruction: 300 m/s2, Malfunction: 100 m/s2
24 V DC +10%/–15%
Approx. 170 mA at 24 V DC (see note 4)
Approx. 125 mA at 24 V DC (see note 5)
Between block and controller:5 m max. (reference value for AWG28)
Between block and external device:Dependent on load
Operation indicator: orange
Diode (600 V, 1 A)
Operating: –25°C to 55°C (with no icing or condensation)
Operating: 45% to 85%
No damage when 49 N pull load was applied for 1 s in all directions (except for 9.8 N min. in direction of rail)
Tightening torque: 0.78 to 1.18 N·m,
Tightening torque: 0.78 to 0.98 N·m,
Pull strength: 49 N for 1 min
Pull strength: 49 N for 1 min
Approx. 280 g
Note: 1.
2.
3.
4.
These values are initial values.
Measurement condition: 1 A at 5 V DC
Ambient temperature: 23°C
Current consumption is when all points are ON and includes
G6D Relay coil current but does not include any external load
current.
5. Current consumption is when all points are ON and includes
G3DZ input current but does not include any external load
current.
6. The Unit weighs approximately 315 g with the Expansion Terminal Block mounted.
390
Programmable Controllers
Short Bar
G79 Connecting Cables
Cable Type
Cable with Loose Wire and
Crimp Terminals
Cable with Loose Wires
Cable with Three Connectors (1:3)
Cable with Two Connectors (1:2)
Cable with One Connector (1:1)
Model
G79-Y@C
Applicable Output Block Appearance
G70D-VSOC16
G70D-VFOM16
Model
G6D-4-SB
G79-A@C
G79-@C-@-@
G79-@C-@
G79-@C
Note: See page 404 for details.
Replacement Relays
Expansion Terminal Block
Applicable Output Block Appearance
G70D-VSOC16
G70D-VFOM16
Model
G70D-ET (see note)
Note: This is a non-standard model and requires a special order.
Contact your OMRON representative for details on availability.
Relay output terminal blocks
Programmable
Controllers
Accessories (Sold Separately)
Applicable Output Block
G70D-VSOC16
G70D-VFOM16
Rated voltage
Model
24 V DC
24 V DC
24 V DC
G6D-1A (see note 1)
G6D-1A-AP (see notes 2 and 3)
G3DZ-2R6PL (see note 3)
Note: 1. The minimum permissible load (reference value) for the
G6D-1A is 10 mA at 5 V DC.
2. The minimum permissible load (reference value) for the
G6D-1A-AP is 1 mA at 5 V DC.
3. These are non-standard models and require a special
order. Contact your OMRON representative for details
on availability.
391
G70D
Relay output terminal blocks
Compact, Low-profile 16-point Output Block
• Compact terminal block is just 156 × 51 × 39 mm
(W × D × H)
• Models with Power MOSFET Relays are available
for high-frequency switching of AC or DC loads.
• Wire loads directly from terminal blocks; no need for
relaying.
• Operation indicators show each I/O signal’s
ON/OFF status at a glance.
• The G70D-SOC16 and G70D-FOM16 can be
combined with a DRT1-OD32ML I/O Terminal for
DeviceNet connectivity or an SRT2-VOD16ML
Connector Terminal for CompoBus/S connectivity.
• Equipped with surge-absorbing diodes.
• Relay Removal Tool included.
• Mount either to DIN rail or via screws.
Ordering Information
Classification
Relay outputs
Points
16 points (SPST-NO × 16)
Power MOSFET relay outputs
Internal output circuit common Rated voltage
NPN compatible (+common)
24 V DC
PNP compatible (– common)
NPN compatible (+ common)
PNP compatible (– common)
Model
G70D-SOC16
G70D-SOC16-1
G70D-FOM16
G70D-FOM16-1
These are all non-standard model and require a special order. Contact your OMRON representative for details on availability.
Specifications
Ratings
Contact Ratings (per G6D Relay)
Relay Specifications
Load
Rated load
Rated carry current
Max. switching voltage
Max. switching current
Min. permissible load (reference value)
(see note 2)
Life expectancy
Note: The following specifications apply to G6D Relays mounted in a
G70D Output Block and not the G6D Relay itself.
Coil Ratings (per G6D Relay)
Rated voltage
Rated current
Coil resistance
Must-operate voltage
Must release voltage
Max. voltage
Power consumption
24 V DC
10.5 mA
2,880 Ω
70% max. of rated voltage
10% min. of rated voltage
130% of rated voltage
Approx. 200 mW
Note: 1. The must-operate voltage is 75% or less of the rated voltage
if the relay is mounted upside down.
2. Rated current and coil resistance were measured at a coil
temperature of 23°C with a tolerance of ±10%.
3. Operating characteristics were measured at a coil temperature of 23°C.
4. The maximum allowable voltage is the maximum value of the
allowable voltage range for the relay coil operating power supply. There is no continuous allowance.
5. The rated current includes the terminal’s LED current.
392
Resistive load (cosφ = 1)
3 A at 250 V AC, 3 A at 30 V DC
3A
250 V AC, 30 V DC
3A
10 mA at 5 V DC
Electrical: 100,000 operations min. (under and at the rated load at 1,800 operations/hr)
Mechanical: 20,000,000 operations
min. (at 18,000 operations/hr)
Note: 1. Up to 3 A can be carried by the power supply terminals for
outputs (terminals B0 to B7.)
2. This value is for a switching frequency of 120 times per
minute.
Programmable Controllers
Input (per G3DZ Power MOSFET Relay)
Rated voltage
Operating voltage
Voltage level
Output (per G3DZ Power MOSFET Relay)
24 V DC
19.2 to 28.8 V DC
19.2 V DC max.
1 V DC min.
4 kΩ±20%
8.2 mA±20%
Must-operate
Must release
Input impedance
Rated current
Programmable
Controllers
Power MOSFET Relay Specifications
Load voltage
Load current
Inrush current
3 to 264 V AC, 3 to 125 V DC
100 µA to 0.3 A
6 A (10 ms)
Note: The rated current includes the terminal’s LED current.
Characteristics
Item
Classification
Contact form
Contact mechanism
Contact material
Contact resistance
Isolation method
Must-operate time
Release time
Output ON-resistance
Open-state leakage current
Max. switching frequency
Insulation resistance
Dielectric strength
Noise immunity
Vibration resistance
Shock resistance
Operating voltage range
Current consumption
Cable length
LED color
Coil surge absorber
Ambient temperature
Ambient humidity
Mounting strength
Terminal strength
Weight
Note: 1.
2.
3.
4.
5.
G70D-SOC16(-1)
G70D-FOM16(-1)
Relay outputs
Power MOSFET relay outputs
16 points (SPST-NO × 16)
Single
--AgCdO
--100 mΩ max. (see note 2)
----Photocoupler
10 ms max. (see note 3)
6 ms max.
10 ms max. (see note 3)
--2.4 Ω max.
--10 µA max. (at 125 V DC)
Mechanical:18,000 operations/hr
--Rated load:1,800 operations/hr
100 MΩ min. (at 500 V DC)
2,000 V AC for 1 min between coil and contact
2,000 V AC for 1 min between input and output terminals
Power input (normal mode): 600 V for 10 min with a pulse width of 100 ns to 1 µs
Power input (common mode): 1.5 kV for 10 min with a pulse width of 100 ns to 1 µs
Input cable (coiling): 1.5 kV for 10 min with a pulse width of 100 ns to 1 µs
Unit body (coiling): 600 V for 10 min with a pulse width of 100 ns to 1 µs
Destruction: 10 to 55 to 10 Hz, 0.5-mm amplitude (1.0-mm double)
Malfunction: 10 to 55 to 10 Hz, 0.375-mm amplitude (0.75-mm double)
Destruction:300 m/s2 (approx. 30G), Malfunction:100 m/s2 (approx. 10G)
24 V DC +10%/–15%
Approx. 300 mA at 24 V DC (see note 4)
Approx. 300 mA at 24 V DC (see note 5)
Between block and controller: 5 m max. (reference value for AWG28)
Between block and external device: Dependent on load
Operation indicator: orange; power supply: green
Diode (400 V, 300 mA)
Operating: 0°C to 55°C
Operating: 35% to 85%
No damage when 5 kgf (49 N) pull load was applied for 1 s in all directions
(except for 1 kgf (9.8 N) in direction of rail)
Tightening torque: 0.78 to 0.98 N·m), Pull strength: 49 N for 1 min
Approx. 200 g
These values are initial values.
Measurement condition: 1 A at 5 V DC
Ambient temperature: 23°C
Current consumption is when all points are ON and includes G6D Relay coil current but does not include any external load current.
Current consumption is when all points are ON and includes G3DZ input current but does not include any external load current.
Accessories (Order Separately)
Replacement Relays
G79 Connecting Cables
Cable Type
Cable with Loose Wire and Crimp Terminals
Cable with Loose Wires
Cable with Three Connectors (1:3)
Cable with Two Connectors (1:2)
Cable with One Connector (1:1)
Note: See page 404 for details.
Relay output terminal blocks
Model
G79-Y@C
G79-A@C
G79-@C-@-@
G79-@C-@
G79-@C
Applicable Output
Block
G70D-SOC16
G70D-SOC16-1
G70D-FOM16
G70D-FOM16-1
Rated voltage
Model
24 V DC
G6D-1A
24 V DC
G3DZ-2R6PL (see note)
Note: This is a non-standard model and requires a special order.
Contact your OMRON representative for details on availability.
393
G7TC
Relay I/O terminal blocks
Unify PLC Wiring to a Single Cable to Reduce
Wiring in the Control Panel and Save Space
• The 16-point Input and Output Blocks are just
182 × 85 × 68 mm (W × D × H) and the 8-point
Output Block is just 102 × 85 × 68 mm (W × D × H).
• Also connects to an SBC with a simple snap-in
connector.
• Surge suppressor circuit built-in.
• Operation indicators show each I/O signal’s
ON/OFF status at a glance.
• Mount to DIN rail.
• The G7TC-OC16 and G7TC-OC08 can be
combined with a DRT1-OD32ML I/O Terminal for
DeviceNet connectivity or an SRT2-VOD16ML
Connector Terminal for CompoBus/S connectivity.
• G3TA I/O Solid-state Relays can be mounted.
• Conforms to UL and CSA standards.
Ordering Information
I/O classification
Input
Output
I/O points
16
16
Internal I/O circuit common
NPN compatible (– common)
NPN compatible (+ common)
PNP compatible (– common)
8
NPN compatible (+ common)
PNP compatible (+ common)
PNP compatible (- common)
Rated voltage
12 V DC
24 V DC
100/110 V DC
100/110 V AC
200/220 V AC
12 V DC
24 V DC
12 V DC
24 V DC
12 V DC
24 V DC
24 V DC
24 V DC
Model
G7TC-ID16*
G7TC-IA16*
G7TC-OC16
G7TC-OC16-1*
G7TC-OC08*
G7TC-OC08-1*
* This is a non-standard model and requires a special order. Contact your OMRON representative for details on availability.
394
Programmable Controllers
Programmable
Controllers
Specifications
Coil Ratings (Common to Input/Output per Relay)
Item
Rated current (mA)
Rated voltage (V)
AC
DC
100/110
200/220
12
24
100/110
50 Hz
8.2
4.1
42
21
5
60 Hz
7/7.7
3.5/3.88
Coil resistance (Ω) Must operate Must release Maximum
voltage
of rated voltage
8,700
80% max.
30% min.
105%
33,300
290
80% max.
10% min.
105%
1,150
20,000
Power consumption
per Relay
0.7 VA
per 16 Relays
11 VA
0.5 W
8W
Note: 1. The rated current and coil resistance are measured at a coil temperature of +23°C with a tolerance of +15%/–20% for AC rated current
and ±15% for coil resistance.
2. The operating characteristics are measured at a coil temperature of +23°C.
3. The value for maximum voltage is the maximum value within the allowable voltage fluctuation range for the relay coil’s operating power
supply. Continuous operation at this voltage is not within product specifications.
4. Approx. 4 mA flows into each LED indicator. To calculate the power supply capacity, add the current value of each LED indicator.
Contact Ratings (G7T I/O Relay)
Classification
Item
Rated load
Rated carry current
Max. switching voltage
Max. switching current
Min. permissible load
(reference value)
(See note.)
Electrical life expectancy
Mechanical life expectancy
For input
Resistive load (cosφ=1)
1 A at 24 V DC
1A
250 V AC, 125 V DC
1A
100 µA at 1 V
10,000,000 operations (at 10 mA)
50,000 operations (at 1 A)
50,000,000 operations
Inductive load
(cosφ=0.4 L/R=7 ms)
0.5 A at 24 V DC
For output
Resistive load
(cosφ=1)
5 A at 24 V DC
2 A at 220 V AC
5A
Inductive load
(cosφ=0.4 L/R=7 ms)
2 A at 24 V DC
1 A at 220 V AC
0.5 A
5A
10 mA at 5 V
2A
2,500,000 operations (at 10 mA)
20,000 operations (at 1 A)
1,000,000 operations (under rated load)
Note: The above values are for a switching frequency of 120 operations/min.
Characteristics
Model
Item
Contact form
Contact mechanism
Contact material
Contact resistance (See note 2.)
Must Operate time (See note 3.)
Release time (See note 3.)
Max. switching fre- Mechanical limit
quency
At rated load
Insulation resistance
Dielectric strength
Between coil and contact
Between same polarity contacts
Between paired connectors
Vibration resistance
Shock resistance
Noise immunity
Rated voltage between positive and negative terminal blocks
G7TC-IA16
G7TC-ID16
G7TC-OC16 (-1) (outG7TC-OC08(-1)
(Input, AC coil)
(Input, DC coil)
put, DC coil)
(output, DC coil)
SPST-NO × 16
SPST-NO × 8
Bifurcated crossbar contact
Single contact
Au cladding + Ag
AgInSn
50 mΩ max.
15 ms max.
15 ms max.
18,000 operations/hour
1,800 operations/hour
100 MΩ (at 500 V DC)
2,000 V AC, 50/60 Hz for 1 minute
1,000 V AC, 50/60 Hz for 1 minute
250 V AC, 50/60 Hz for 1 minute
10 to 55 to 10 Hz with 0.5-mm single amplitude (1.0-mm double amplitude)
200 m/s2
Noise level: 1.5 kV; pulse width: 100 ns to 1 µs
Rated voltage of controller’s (PLC or other) input cir- 12 V DC ± 5% (See note 5.)
cuit
24 V DC ± 5%
Rated current between positive and negative terminal blocks Input circuit current of controller (PLC or other) ×
12 V DC: 46 mA × number of ON points
number of ON points
24 V DC: 25 mA × number of ON points
Cable length
To controller
5 m max. (reference value)
(See note 4.)
To I/O devices
50 m max. (reference value, for 2-mm2 CVV cable) Dependent on load
Ambient operating temperature
0 to 55°C
Ambient operating humidity
35% to 85% (with no icing or condensation)
Tightening torque for external connections
0.78 to 1.18 N⋅m
Tensile strength
No damage when a tensile force of 49 N is applied in each direction.
In the direction of the track, the tensile strength is 9.8 N min.
I/O terminal tightening torque
Tightening strength: 0.98 N⋅m; Tensile strength 49 N for 1 minute
LED color
Red
Green
Case color
Transparent red
Transparent green
Transparent
Coil surge absorber
Varistor
Diode (1 A, 400 V)
Weight
Approx. 640 g
Approx. 630 g
Approx. 670 g
Approx. 350 g
Note: 1.
2.
3.
4.
5.
These are initial values.
Measurement condition: 1 A at 5 V DC.
Ambient temperature: 23°C.
Connecting cables up to 5 m are available as standard products. (See page 404.) For longer cables, enquire separately.
G7TC-OC08-01 is not available in 12 V DC type.
Relay I/O terminal blocks
395
Accessories (Order Separately)
G79 Connecting Cables
Cable Type
Cable with Loose Wire and Crimp Terminals
Cable with Loose Wires
Cable with Three Connectors (1:3)
Cable with Two Connectors (1:2)
Cable with One Connector (1:1)
Specifications
Contact resistance
Model
G79-Y@C
10 mΩ max.
(measured at 5 V DC, 1 A)
2,000 V AC for 1 minute
100 MΩ (at 500 V)
10 to 55 to 10 Hz with 0.5-mm single
amplitude (1.0-mm double amplitude)
200 m/s2
Operating: 0 to 55°C
35% to 85%
Approx. 28 g
Dielectric strength
Insulation resistance
Vibration resistance
G79-A@C
G79-@C-@-@
G79-@C-@
G79-@C
Shock resistance
Ambient temperature
Ambient humidity
Weight
Note: See page 404 for more details.
G78-04 Shorting Bar
Use this piece to short-circuit adjacent
terminals.
Max. current flow: 20 A
P70 Indicator Module and Surge Suppressor
G77-S Output Short-Circuit Module
Remove the transparent style strip of the P7TF-05 socket
and mount this module and it will function as an operation
indicator and surge suppressor.
A G77-S Output Short-Circuit Module can be used
to output directly without a relay. The G77-S Output
Short-Circuit Module cannot be used for inputs.
Ordering Information
P7TF-05 Socket
Model
The G7T (SPST-NO, SPST-NC, and SPDT types)
and the G3TA I/O Relays can be mounted on the
P7TF-05 Socket.
The P7TF-05 can be used for applications involving sequences that require slim relays, or to
enable use of SPDT relays with the I/O Block. To
use part of the I/O Block with SPDT specifications,
insert an Output Short-Circuit Module into the I/O
Block, and use the P7TF-05 Socket in combination with an SPDT Relay for the Module’s output.
For AC relay
P70A
For DC relay
P70D
Applicable relay
coil voltage
100 (110) V AC
200 (220) V AC
12/24 V DC
Remarks
Varistor surge
suppression
Diode surge
suppression
Note: 1. Order the indicator module suitable for the relay coil voltage.
2. The indicator module for DC relays can be used with a 12-V
or 2- V DC power supply.
Precautions
General
I/O Relays and I/O Block Bases can be combined as follows to form I/O Blocks:
DC output
DC input
AC input
Combinations
(See note.)
G7TC-OC16
G7TC-OC16-1
G7TC-OC08
G7TC-OC08-1
Block Base
I/O Relay
I/O SSR
P7TF-OS16
P7TF-OS16-1
P7TF-OS08
P7TF-OS08-1
G7T-1112S
AC
G7TC-ID16
G7TC-IA16
P7TF-IS16 (DC type)
P7TF-IS16 (AC type)
G7T-1122S
DC
DC
AC
G3TA-OA202SZ
G3TA-OA202SL
G3TA-ODX02S
G3TA-OD201S
G3TA-IDZR02S (M)
G3TA-IAZR02S
Note: The model numbers given under “Combinations” are for combinations with I/O Relays. To use I/O SSRs, either replace an I/O Relay with
the SSR, or purchase an I/O Terminal (Block Base) and an I/O SSR (i.e., not the combined Unit).
• AC Input Relays/SSRs and DC Input Relays/SSRs cannot be used
together in the same Terminal because of the specifications for coil
surge suppression elements are different.
Furthermore, Relays/SSRs with different voltage specifications cannot be used together in the same Terminal because the specifications of operation indicator circuits are different. (For example, a 100V AC Input Relay and a 200-V AC Input Relay, or a 12-V DC Output
Relay and a 24-V DC Output Relay cannot be used in the same Terminal.)
396
• Only use I/O Terminals, I/O Relays, and I/O SSRs with the same
specifications for rated voltage.
Programmable Controllers
Programmable
Controllers
G70A-ZOC16
I/O Terminal Bases
16-point I/O Block accepts Various Devices
such as G2R Relays, Solid State Relays, and
Timers for More System Flexibility
• Connects to a PLC or SBC with a simple snap-in
connector.
• The G70A-ZOC16-3 can be combined with a DRT1OD32ML I/O Terminal for DeviceNet connectivity or
an SRT2-VOD16ML Connector Terminal for CompoBus/S connectivity.
• SPDT relays can be mounted.
• Conforms to VDE (VDE0106) and CE standards.
• Electric-shock preventive (finger-touch protection)
terminal block
• DIN rail mountable
• High-capacity (10 A) terminal block
• Excellent noise resistance characteristics
• Built-in diodes for coil surge suppression
Ordering Information
Internal I/O circuit common
NPN compatible (+ common)
PNP compatible (– common)
Rated voltage
24 V DC
24 V DC
Model
G70A-ZOC16-3
G70A-ZOC16-4
Compatible Relays/Timers (sold separately)
G2R-1-S (SPDT), G2R-1-SN (SPDT with indicator), G3ROA202SZN, G3R-OA202SLN, G3R-ODX02SN, G3R-OD201SN,
G3RZ-201SLN, H3RN-1, and H3RN-11
Note: Each relay to be mounted must incorporate a coil that has proper specifications within the maximum rated voltage range.
Specifications
Ratings/Characteristics
Item
Contact resistance
Permissible current
Max. operating voltage
Terminal
Dielectric strength
block
G70A-ZOC16-3 and G70A-ZOC16-4
10 mΩ (excluding the resistance of the relay to be used)
10 A
380 V AC, 125 V DC
4,000 V AC, 50/60 Hz for 1 min between connector and output terminals
2,000 V AC, 50/60 Hz for 1 min between output terminals
250 V AC, 50/60 Hz for 1 min between connectors
1,000 MΩ (at 250/500 V)
Malfunction: 10 to 61.2 to 10 Hz, 0.1-mm double amplitude 0.2; 61.2 to 150 to 61.2 Hz, 14.7 m/s2
Malfunction: 200 m/s2 (approx. 20G)
Noise level: 2.0 kV; pulse width: 100 ns to 1 µs
Operating: 0°C to 55°C (with no condensation or icing)
Operating: 35% to 85%
Diode: 1 A, 400 V
Diode (2 A, withstand inverse voltage: 40 V)
No damage when a tensile force of 49 N is applied for 1 second in any direction
Tightening strength: 0.59 N⋅m; Tensile strength 49 N for 1 min
Approx. 400 g
Insulation resistance
Vibration resistance
Shock resistance
Noise immunity
Ambient temperature
Ambient humidity
Coil surge absorption element
Protection against reversed connection
Tensile strength
I/O terminal tightening torque
Weight
Accessories (Order Separately)
Short Bar
G79 Connecting Cables
Cable Type
Cable with Loose Wire and Crimp
Terminals
Cable with Loose Wires
Cable with Three Connectors (1:3)
Cable with Two Connectors (1:2)
Cable with One Connector (1:1)
Model
G79-Y@C
Applicable I/O block
G70A-ZOC 16-4
Model
G78-16-E
G79-A@C
G79-@C-@-@
G79-@C-@
G79-@C
Note: See pages page 404 for details.
I/O Terminal Bases
397
G70D-SOC08
Relay Output Terminal Block
Space-saving and Labor-saving 8-point
Output Block
• Compact terminal block is just 68 × 80 × 44 mm
(W × H × D, when mounted upright)..
• Independent contacts and shorting bars allow easy
common connections.
• The common can now be connected with a shorting
bar in the G70D-SOC08 and G70R-SOC08.
• No tools are required to remove Relays, so Relay
replacement is easier than ever.
• The attached terminal cover prevents shocks.
• Equipped with operation indicators.
• Built-in diodes absorb coil surge.
• Mount either to DIN rail or via screws.
Ordering Information
Classification
Relay outputs
Points
8 points (SPST-NO × 8)
Internal output circuit common
NPN compatible (+ common)
Rated voltage
24 V DC
Model
G70D-SOC08
This is a non-standard model and requires a special order. Contact your OMRON representative for details on availability.
Specifications
Ratings
Contact Ratings (per G6D Relay)
The following specifications apply to G6D Relays mounted in a G70D
Output Block and not the G6D Relay itself.
Item
Load
Rated load
Rated carry current
Max. switching voltage
Max. switching current
Max. switching capacity
(reference value)
Min. permissible load
(reference value; see note.)
Life expectancy
Electrical
Coil Ratings (per G6D Relay)
Rated
Rated
voltage current
Coil resistance
24 V DC 10.5 mA 2,880 Ω
Must-operate voltage
70% max.
of rated
voltage
Release
voltage
Max. allowable
voltage
10% min. 130%
of rated
voltage
Power
consumption
Approx.
200 mW
Note: 1. The must-operate voltage is 75% max. of the rated voltage if
the Relay is mounted upside down.
2. Rated current and coil resistance were measured at a coil
temperature of 23°C with a tolerance of ±10%.
3. Operating characteristics were measured at a coil temperature of 23°C.
4. The maximum allowable voltage is the maximum value of the
allowable voltage range for the relay coil operating power
supply. There is no continuous allowance.
5. The rated current includes the current consumption of the operation indicator.
398
Mechanical
Resistive load (cosφ = 1)
5 A at 250 V AC, 5 A at 30 V DC
5A
250 V AC, 30 V DC
5A
1,250 VA, 150 W
5 V DC, 10 mA
100,000 operations min. (at or below
the rated load at 1,800 operations/hr)
20,000,000 operations min.
(at 18,000 operations/hr)
Note: This value is for a switching frequency of 120 times per minute.
Programmable Controllers
Model
Item
Contact form
Contact mechanism
Contact resistance (See note 1.)
Must-operate time (See note 2.)
Release time (See note 3.)
Max. switching frequency Mechanical
Rated load
Insulation resistance
Dielectric strength
Between coil and contact
Between contacts of same polarity
Between contacts of different polarity
Vibration resistance
Destruction
Malfunction
Shock resistance
Destruction
Malfunction
Noise immunity
Power input (normal mode)
Power input (common mode)
Input cable (coiling)
Unit body (coiling)
Allowable power supply voltage fluctuation
Current consumption (See note 3.)
Cable length
Between block and controller
Between block and external device
LED indicator color
Coil surge absorber
Ambient operating temperature
Ambient storage temperature
Ambient operating humidity
Mounting strength
Terminal strength
G70D-SOC08
Relay outputs
8 points (SPST-NO × 8)
Single
100 mΩ max.
100 ms max.
10 ms max.
18,000 operations/hr
1,800 operations/hr
100 MΩ min. (at 500 V DC)
2,000 V AC for 1 min
750 V AC for 1 min
1,500 V AC for 1 min
10 to 55 to 10 Hz, 0.5-mm amplitude (1.0-mm double)
10 to 55 to 10 Hz, 0.5-mm amplitude (1.0-mm double)
300 m/s2
100 m/s2
600 V for 10 min with a pulse width of 100 ns to 1 µs
1.5 kV for 10 min with a pulse width of 100 ns to 1 µs
1.5 kV for 10 min with a pulse width of 100 ns to 1 µs
600 V for 10 min with a pulse width of 100 ns to 1 µs
24 V DC +10%/−15%
Approx. 80 mA at 24 V DC
5 m max. (reference value for AWG 28)
Determine appropriate length for the connected load.
Orange
Diode
−10 to 55°C
35% to 85%
−20 to 65°C
No damage when 49 N pull load was applied for 1 s in all directions
(except for 9.8 N min. in direction of track)
9.8 N·m
49 N for 1 min
Approx. 145 g
Tightening torque
Pull strength
Weight
Note: 1.
2.
3.
4.
Programmable
Controllers
Characteristics
These values are initial values.
Measurement conditions: 1 A at 5 V DC
Ambient temperature: 23°C
The current consumption is the value when all points are ON and includes the G6D Relay coil current.
Engineering Data
500
Current (A)
Number of operations (x104)
Life expectancyMaximum switching capacity
300
6
Note: The data shown in these graphs is
based on actual values sampled
from a production line; please use
this data for reference only. As a
general rule, allow for slight variations in the Relays because the
Relays are mass produced.
5
100
4
250 V AC or 30 V DC resistive load
50
30
3
10
5
2
250 V AC or 30 V DC resistive load
(cosφ = 0.4; L/R = 7 ms)
3
0
1
1
2
3
4
5
6
7
8
9
10
Switching current (A)
0
1
2
3
4
5
6
7
8
9
10
Number of ON contacts
• When using with a carry current of 5 A, no
more than 4 contacts may be ON.
• The carry current is 3 A when all contacts
are ON.
Relay Output Terminal Block
399
Accessories for the G70D-SOC08 (Order Separately)
Shorting Bar
8.5
8.5
8.5
6.8
3.6
11.5 9.5
6.8
(32.3)
Applicable Output Block
G70D-SOC08
Model
G6B-4-SB
Replacement Relays
Applicable Output
Block
G70D-SOC08
Rated voltage
Model
24 V DC
G6D-1A (See note.)
G6D-1A-AP (See note.)
Note: The minimum permissible load (reference value) for the
G6D-1A is 10 mA at 5 V DC.
400
Programmable Controllers
Programmable
Controllers
G70R-SOC08
Relay output terminal block
Space-saving and Labor-saving 8-point
Output Block
• Compact terminal block is just 136 × 80 × 55 mm
(W × H × D) when mounted upright).
• Independent contacts and shorting bars allow easy
common connections.
• The common can now be connected with a shorting
bar in the G70D-SOC08 and G70R-SOC08.
• No tools are required to remove Relays, so Relay
replacement is easier than ever.
• The attached terminal cover prevents shocks.
• Built-in diodes absorb coil surge.
• Mount either to DIN rail or via screws.
Ordering Information
Classification
Relay outputs
Points
8 points (SPST-NO × 8)
Internal output circuit common
NPN compatible (+ common)
Rated voltage
24 V DC
Model
G70R-SOC08
This is a non-standard model and requires a special order. Contact your OMRON representative for details on availability.
Specifications
Ratings
The following specifications apply to G2R Relays mounted in a G70R Output Block and not the G2R Relay itself.
Coil Ratings (per G2R Relay)
Rated
voltage
Rated
current
Coil
Mustresistance operate
voltage
24 V DC 25.8 mA 1,100 Ω
70% max.
of rated
voltage
Contact Ratings (per G2R Relay)
Release
voltage
Max.
allowable
voltage
15% min. 130%
of rated
voltage
Power
consumption
Approx.
530 mW
Note: 1. The must-operate voltage is 75% max. of the rated voltage if
the Relay is mounted upside down.
2. Rated current and coil resistance were measured at a coil
temperature of 23°C with a tolerance of ±10%.
3. Operating characteristics were measured at a coil temperature of 23°C.
4. The maximum allowable voltage is the maximum value of the
allowable voltage range for the relay coil operating power
supply. There is no continuous allowance.
5. The rated current includes the current consumption of the operation indicator.
Relay output terminal block
Item
Load
Rated load
Rated carry current
Max. switching voltage
Max. switching current
Max. switching capacity (reference
value)
Min. permissible load (reference value; see note.)
Life expectancy
Electrical
Mechanical
Resistive load (cosφ = 1)
10 A at 250 V AC, 10 A at 30 V DC
10 A
380 V AC, 125 V DC
10 A
2.50 VA, 300 W
5 V DC, 10 mA
100,000 operations min. (at the rated
load and 1,800 operations/hr)
10,000,000 operations min.
(at 18,000 operations/hr)
Note: This value is for a switching frequency of 120 times per minute.
401
Characteristics
Model
Item
Contact form
Contact mechanism
Contact resistance (See note 1.)
Must-operate time (See note 2.)
Release time (See note 3.)
Max. switching freMechanical
quency
Rated load
Insulation resistance
Dielectric strength
Between coil and contact
Between contacts of same polarity
Between contacts of different polarity
Vibration resistance
Destruction
Malfunction
Shock resistance
Destruction
Malfunction
Noise immunity
Power input (normal mode)
Power input (common mode)
Input cable (coiling)
Unit body (coiling)
Allowable power supply voltage fluctuation
Current consumption (See note 3.)
Cable length
Between block and controller
Between block and external device
Coil surge absorber
Ambient operating temperature
Ambient operating humidity
Ambient storage temperature
Mounting strength
Terminal strength
G70R-SOC08
Relay outputs
8 points (SPST-NO × 8)
Single
30 mΩ max.
15 ms max.
15 ms max.
18,000 operations/hr
1,800 operations/hr
100 MΩ min. (at 500 V DC)
2,000 V AC for 1 min
750 V AC for 1 min
1,500 V AC for 1 min
10 to 55 to 10 Hz, 0.5-mm amplitude (1.0-mm double)
10 to 55 to 10 Hz, 0.5-mm amplitude (1.0-mm double)
300 m/s2
100 m/s2
600 V for 10 min with a pulse width of 100 ns to 1 µs
1.5 kV for 10 min with a pulse width of 100 ns to 1 µs
1.5 kV for 10 min with a pulse width of 100 ns to 1 µs
600 V for 10 min with a pulse width of 100 ns to 1 µs
24 V DC +10%/−15%
Approx. 185 mA at 24 V DC
5 m max. (reference value for AWG 28)
Determine appropriate length for the connected load.
Diode
−10 to 55°C
35% to 85%
−20 to 65°C
No damage when 49 N pull load was applied for 1 s in all directions
(except for 9.8 N min. in direction of track)
0.98 N·m
49 N for 1 min
Approx. 350 g
Tightening torque
Pull strength
Weight
Note: 1.
2.
3.
4.
These values are initial values.
Measurement conditions: 1 A at 5 V DC
Ambient temperature: 23°C
The current consumption is the value when all points are ON and includes the G2R Relay coil current.
Engineering Data
1,000
500
250 V AC resistive load
30 V DC resistive load
300
Current (A)
Number of operations (x104)
Life expectancyMaximum switching capacity
Note: The data shown in these graphs is
based on actual values sampled
from a production line; please use
this data for reference only. As a
general rule, allow for slight variations in the Relays because the
Relays are mass produced.
12
11
10
9
100
8
250 V AC inductive load (cosφ = 0.4)
50
30
7
6
5
10
5
4
30 V DC inductive load (L/R = 7 ms)
3
3
2
1
0
2
4
5
6
7.5 8
10
12
14
Switching current (A)
0
1
2
3
4
5
6
7
8
9 10
Number of ON contacts
• When using with a carry current of 10 A, no
more than 4 contacts may be ON.
• The carry current is 8 A when all contacts
are ON.
402
Programmable Controllers
Programmable
Controllers
Accessories for the G70R-SOC08 (Order Separately)
Shorting Bar
8.5
8.5
8.5
6.8
3.6
11.5 9.5
6.8
(32.3)
Applicable Output Block
G70R-SOC08
Model
G6B-4-SB
Replacement Relays
Applicable Output
Block
G70R-SOC08
Rated voltage
Model
24 V DC
G2R-1-S
G2R-1-SN
Relay output terminal block
403
G79
I/O Block Connecting Cables
G79 Connecting Cables
Connecting Cables with Crimp Terminals (G79-Y@C)
Connecting Cables with One Connector (G79-@C)
This Cable is convenient for connecting I/O Blocks to devices equipped
with screw terminals.
This Cable is convenient for connecting an I/O Block to a single device
equipped with one connector socket.
Length (l)
1,000 mm
1,500 mm
2,000 mm
3,000 mm
5,000 mm
Length (l)
1,000 mm
1,500 mm
2,000 mm
3,000 mm
5,000 mm
Model
G79-Y100C*
G79-Y150C*
G79-Y200C*
G79-Y300C*
G79-Y500C*
End A
End B
Connect
to I/O
Block
Connect
to I/O
devices
300
L
L
Note: 1. The power line capacity is 50 mA max. per I/O point. Also, always check the driver capacity and I/O relay power consumption when using an Output Block.
2. The crimp terminals are labeled with the corresponding connector pin numbers in parentheses.
3. Connect terminals 9 and 19 and terminals 10 and 20 together
when using the G7TC-OC08.
4. The wire gauge of the wires in the cable is 28 AWG (10/0.38).
Loose-wire Connecting Cables (G79A@C)
This Cable has loose wires at the device end.
Length (l)
2,000 mm
5,000 mm
Model
G79-100C*
G79-150C*
G79-200C*
G79-300C*
G79-500C*
Model
G79-A200C*
G79-A500C*
End A
End B
Connect
to I/O
Block
Connect
to I/O
devices
300
Connecting Cables with Two Connectors
(G79-O@C-@ and G79-I@C-@)
Cables for both Output Blocks (for connection to SYSMAC I/O Units;
tape color: red) and Input Blocks (for connection to SYSMAC I/O Units;
tape color: yellow) are available.
Length
A
1,000 mm
1,500 mm
2,000 mm
3,000 mm
5,000 mm
B
750 mm
1,250 mm
1,750 mm
2,750 mm
4,750 mm
Cables for Input
Blocks
Cables for Output
Blocks
G79-I100C-75*
G79-I150C-125*
G79-I200C-175*
G79-I300C-275*
G79-I500C-475*
G79-O100C-75*
G79-O150C-125*
G79-O200C-175
G79-O300C-275*
G79-O500C-475*
Note: The 32-point card-type connectors for the Input Block Cables
and and Output Block Cables have different pin arrangements.
L
Note: 1. The wire gauge of the wires in the cable is 24 AWG (7/0.203).
2. Connect terminals 9 and 19 and terminals 10 and 20 together
when using the G7TC-OC08.
* This is a non-standard model and requires a special order. Contact your OMRON representative for details on availability.
404
Programmable Controllers
Programmable
Controllers
Connecting Cables for Mitsubishi PLCs
The following cables can be used to connect a Mitsubishi PLC
(with a 32-point connector) to I/O Blocks.
Length
A
1,000 mm
B
750 mm
1,500 mm
1,250 mm
2,000 mm
3,000 mm
1,750 mm
2,750 mm
Model
Model
G79-I100C-75-MN
(See note.)
G79-I150C-125-MN
(See note.)
G79-I200C-175-MN
G79-I300C-275-MN
G79-O100C-75-MN
G79-O150C-125-MN
G79-O200C-175-MN
G79-O300C-275-MN
These are all non-standard model and require a special order.
Contact your OMRON representative for details on availability.
Note: 1. Applicable Mitsubishi PLC models
Inputs: AX42, A1SX41, and A1SX42
Outputs: AY42, A1SY41, and A1SY42
A
(120)
B
Direct-wiring length
(without bends)
Connecting Cables with Three Connectors
(G79-@C-@-@)
Length
A
1,500 mm
2,000 mm
3,000 mm
Model
B
1,250 mm
1,750 mm
2,750 mm
C
1,000 mm
1,500 mm
2,500 mm
G79-150C-125-100
G79-200C-175-150
G79-300C-275-250
These are all non-standard model and require a special order.
Contact your OMRON representative for details on availability.
A
B
CN1
CN4
(120)
CN3
(270)
CN2
C
Direct-wiring length
(without bends)
I/O Block Connecting Cables
405
XW2@
I/O terminal blocks and cables
Ideal for Reducing Wiring to PLCs and Other Equipment in the Control Panel
Connecting Components (PLC Units, Connector-Terminal Conversion Units, and Cables)
Use the XW2D for Connections to Controllers
CJ1 Basic I/O Units
CJ Basic I/O Units with 32-point connectors
CJ Basic I/O Units with 64-point connectors
CJ1W-ID231 (Fujitsu Connector/Input Unit)
CJ1W-OD231 (Fujitsu Connector/Output Unit)
CJ1W-ID232 (MIL Connector/Input Unit)
CJ1W-OD232/OD233 (MIL Connector/Output Unit)
CJ1W-ID261 (Fujitsu connector/Input Unit)
CJ1W-OD261 (Fujitsu connector/Output Unit)
CJ1W-MD261 (Fujitsu connector/I/O Unit)
CJ1W-ID262 (MIL Connector/Input Unit)
CJ1W-OD263 (MIL Connector/Output Unit)
CJ1W-MD263 (MIL Connector/I/O Unit)
CJ1W-MD563 (MIL Connector/I/O Unit)
CJ1M CPU Unit
CJ1M-CPU22/CPU23 (MIL Connector/Built-in I/O)
Fujitsu Connector
MIL Connector
MIL Connector
Fujitsu Connector
Connecting Cables
Connecting Cables
XW2Z-@@@B (Fujitsu connector)
XW2Z-@@@K (MIL Connector)
XW2Z-@@@B (Fujitsu connector)
XW2Z-@@@K (MIL Connector)
Connector-Terminal Conversion Unit
Connector-Terminal Conversion Unit
(2 required)
XW2B-40G4
XW2B-40G5
XW2D-40G6
XW2D-40G6-RF (with built-in bleeder resistor)
(ID261, MD261 input side only)
XW2D-40G6-RM (with built-in bleeder resistor)
(MD263 input side only)
XW2B-40G4
XW2B-40G5
XW2D-40G6
XW2D-40G6-RF (with built-in bleeder resistor) (ID231 only)
XW2D-40G6-RM (with built-in bleeder resistor) (ID232 only)
CJ Basic I/O Unit with 32-point Connectors
CJ Basic I/O Unit with 64-point Connectors
CJ1W-ID231 (Fujitsu Connector/Input Unit)
CJ1W-OD231 (Fujitsu Connector/Output Unit)
CJ1W-ID232 (MIL Connector/Input Unit)
CJ1W-OD232/OD233 (MIL Connector/Output Unit)
Fujitsu Connector
MIL Connector
CJ1W-ID261 (Fujitsu Connector/Input Unit)
CJ1W-OD261 (Fujitsu Connector/Output Unit)
CJ1W-MD261 (Fujitsu Connector/I/O Unit)
CJ1W-ID262 (MIL Connector/Input Unit)
CJ1W-OD263 (MIL Connector/Output Unit)
CJ1W-MD263 (MIL Connector/I/O Unit)
CJ1W-MD563 (MIL Connector/I/O Unit)
MIL Connector
Fujitsu Connector
MIL Connector
Connecting Cables
XW2Z-@@@D (Fujitsu connector/Input Unit)
XW2Z-@@@L (Fujitsu connector/Output Unit)
XW2Z-@@@N (MIL Connector)
Connecting Cables
(2 required)
XW2Z-@@@D (Fujitsu connector/Input Unit)
XW2Z-@@@L (Fujitsu connector/Output Unit)
XW2Z-@@@N (MIL Connector)
Connector-Terminal Conversion Unit
XW2B-20G4
XW2B-20G5
XW2D-20G6
XW2C-20G6-IO16
XW2C-20G5-IN16 (Input side only)
XW2E-20G5-IN16 (Input side only)
406
Connector-Terminal Conversion Unit
XW2B-20G4
XW2B-20G5
XW2D-20G6
XW2C-20G6-IO16
XW2C-20G5-IN16 (Input side only)
XW2E-20G5-IN16 (Input side only)
Programmable Controllers
Programmable
Controllers
CJ Basic I/O Unit with 32-point Connectors
CJ1W-MD231 (Fujitsu Connector/Input Unit)
CJ1W-MD233 (MIL Connector/I/O Unit)
Fujitsu Connector
MIL Connector
Connecting Cables
XW2Z-@@@A (Fujitsu Connector)
G79-O@@C (MIL Connector)
Connector-Terminal Conversion Unit
(2 required)
XW2B-20G4
XW2B-20G5
XW2D-20G6
XW2C-20G6-IO16
XW2C-20G5-IN16 (input side only)
XW2E-20G5-IN16 (input side only)
CS1 Basic I/O Units with 96-point and Two 48-point Connectors
CS1 I/O Unit
CS1W-ID291 (96 inputs)
CS1W-OD291 (96 outputs)
CS1W-OD292 (96 outputs)
CS1W-MD291 (48 inputs, 48 outputs)
CS1W-MD292 (48 inputs, 48 outputs)
CS1 I/O Unit
CS1W-ID291 (96 inputs)
CS1W-OD291 (96 outputs)
CS1W-OD292 (96 outputs)
CS1W-MD291 (48 inputs, 48 outputs)
CS1W-MD292 (48 inputs, 48 outputs)
CS1 I/O Unit
CS1W-ID291 (96 inputs)
CS1W-OD291 (96 outputs)
CS1W-OD292 (96 outputs)
CS1W-MD291 (48 inputs, 48 outputs)
CS1W-MD292 (48 inputs, 48 outputs)
XW2Z-@@@H-2
Connecting Cables
(2 required)
XW2Z-@@@H-3
Connecting Cables
(2 required)
XW2Z-@@@H-1
Connecting Cables
(2 required)
XW2B-60G4 or XW2B-60G5
Connector-Terminal Conversion Unit
I/O Units with 32-point Connectors
C200H-ID215
C200H-OD215
C200H-MD115
C200H-MD215
C200H-MD501
C200H-ID501
C200H-OD501
C500-ID218CN
C500-ID501CN
C500-OD415CN
C500-MD211CN
C500-OD501CN
XW2Z-@@@A
Connecting Cables
XW2D-20G6,
XW2B-20G5,
or XW2B-20G4
Connector-Terminal
Conversion Unit
XW2D-20G6,
XW2B-20G5,
or XW2B-20G4
Connector-Terminal
Conversion Unit
XW2D-40G6,
XW2B-40G5,
or XW2B-40G4
Connector-Terminal
Conversion Unit
XW2D-20G6,
XW2B-20G5,
or XW2B-20G4
Connector-Terminal
Conversion Unit
XW2D-20G6,
XW2B-20G5,
or XW2B-20G4
Connector-Terminal
Conversion Unit
I/O Units with 32-point Connectors (Group-2) I/O Units
with 64-point Connectors
CS1W-ID231*
CS1W-OD231*
CS1W-OD232*
CS1W-ID261
CS1W-OD261
CS1W-OD262
CS1W-MD261
CS1W-MD262
CJ1W-ID231*
CJ1W-OD231*
CJ1W-ID261
CJ1W-OD261
CQM1-ID213*
CQM1-OD213*
C200H-ID216*
C200H-OD218*
C200H-ID217
C200H-OD219
C500-ID114
C500-ID219
C500-OD213
XW2Z-@@@B
Connecting Cables
*These I/O Units have
just one connector.
XW2D-20G6
Connector-Terminal
Conversion Unit
XW2D-40G6
Connector-Terminal
Conversion Units
I/O terminal blocks and cables
407
Use the XW2C-20G5-IN16 when a Power Supply Common Terminal is Required.
I/O Units with 32-point Connectors
C200H-ID215
C200H-MD215
C200H-MD115
I/O Units with 32-point Connectors (Group-2)
I/O Units with 64-point Connectors
C500-ID218CN
C500-MD211CN
CS1W-ID231
CS1W-ID261
CJ1W-ID231
CJ1W-ID261
XW2Z-@@@A
Connecting Cables
CQM1-ID213
C200H-ID216
C200H-ID217
C500-ID114
C500-ID219
XW2Z-@@@D
Connecting Cables
XW2C-20G5-IN16
Connector-Terminal
Conversion Units
XW2C-20G5-IN16
Connector-Terminal
Conversion Units
Connecting a PLC’s Position Control Unit with
a Servo Driver
Connecting to a PLC via Host Link
XW2Z Host Link Cable
XW2B Servo Relay Units
Position Control Units and Servo Drivers
SYSMAC PLC:
CQM1-series, C-series,
CV-series, or CVM1
PLC Position Control Unit
C200H-NC112
C200HW-NC113
C200H-NC211
C200HW-NC213
C200HW-NC413
CQM1-CPU43
XW2Z-@@@J-A@
Connecting Cable
Peer Device:
Personal computer,
Factory Intelligent Terminal,
or Programmable Terminal
XW2Z-@@@P/R/S/T
Host Link Cable
XW2Z-@@@J-B@
Connecting Cable
Servo Driver
R88D-UP@@@
R88D-UT@@@
R88D-UEP@@@
R88D-MT@@@
R88D-H@@@
XW2B-@@J6-@B
Servo Relay Unit
408
Programmable Controllers
Programmable
Controllers
XW2B
I/O terminal block
Easily wire connectors to Terminal Blocks
and Reduce Control Panel Wiring
• Can be mounted with screws or snapped onto DIN
rail.
• Standard models are available with MIL flat cable
connectors and multipole rectangular connectors.
• Terminal Blocks are available with M2.5 or M3.5
screws.
• Cables are available for OMRON PLC connectors.
Ordering Information
Poles
20
34
40
50
60
20
34
40
50
60
Model
XW2B-20G5
XW2B-34G5*
XW2B-40G5
XW2B-50G5*
XW2B-60G5*
XW2B-20G4
XW2B-34G4*
XW2B-40G4
XW2B-50G4*
XW2B-60G4*
* This is a non-standard model and requires a special order.
Contact your OMRON representative for details on availability.
Specifications
Ratings/Characteristics
Rated current
Rated voltage
Insulation resistance
Dielectric strength
Ambient temperature
I/O terminal block
1A
125 V AC
100 MΩ min. (at 500 V DC)
500 V AC for 1 min (with a leakage current
of 1 mA max.)
Operating: −25 to 80 °C
409
Dimensions
Note: All dimensions are in mm.
XW2B-@@G5
(M3.5 Screws)
XW2B-@@G4
(M2.5 Screws)
Flat Cable Connector (MIL plug)
Flat Cable Connector (MIL plug)
Two,
3.5 dia.
Two,
3.5 dia.
Terminal
block
Terminal block
Connection Diagram
Connection Diagram
Terminal
Block
(front view)
Flat Cable
Connector
(front view)
Triangle mark
Triangle mark
Dimensions
Model
XW2B-20G5
XW2B-34G5
XW2B-40G5
XW2B-50G5
XW2B-60G5
410
Terminal
Block
(front view)
Flat Cable
Connector
(front view)
Dimensions
Poles
20
34
40
50
60
Dimension A (mm)
112.5
180.0
202.5
247.5
292.5
Model
XW2B-20G4
XW2B-34G4
XW2B-40G4
XW2B-50G4
XW2B-60G4
Poles
20
34
40
50
60
Dimension A (mm)
67.5
112.5
135.0
157.5
180.0
Programmable Controllers
Programmable
Controllers
XW2B
Servo I/O terminal block
Combines Connectors and the Terminal
Block to Reduce Wiring between Servo
Drivers and Position Control Units
• Allows simple terminal block wiring of control signals
between a Servo Driver and a Position Control Unit
or CQM1 PLC (with built-in pulse I/O function).
• No need to solder connections; all you need is a
screwdriver.
• Special cables are available to connect various
Units.
• Only a 24-V DC power supply is required for control
signals.
• Space-saving terminal blocks use M3.0 screws.
• Can be mounted with screws or snapped onto DIN
rail.
Ordering Information
Compatible Servo Drivers
SMARTSTEP Series:
R7D-AP@@@
W Series:
R88D-WT@@@@
U Series:
R88D-UP@@@
R88D-UT@@@
R88D-UEP@@@
M Series:
R88D-MT@@@
H Series:
R88D-H@@@
Compatible Position Control Units
NC Units (Communications functions are not supported.)
CS1W-NC113/133CJ1W-NC113/133
C200HW-NC113
C200H-NC112
3F88M-DRT141
NC Units (Communications functions are not supported.)
CS1W-NC213/233/413/433
CJ1W-NC213/233/413/433
C200HW-NC213/413
C200H-NC211
Other Units (Communications functions are not supported.)
CS1W-HCP22
CQM1H-PLB21
CQM1-CPU43-V1
NC Units (Communications functions are supported.)
CS1W-NC213/233/413/433
CJ1W-NC213/233/413/433
CPU units (Communications functions are not supported)
CJ1M-CPU22/23
CPU units (Communications functions are not supported)
CJ1M-CPU22/23
Model number
XW2B-20J6-1B
XW2B-40J6-2B
XW2B-20J6-3B
XW2B-40J6-4A
XW2B-20J6-8A (one axis)
WX2B-20J6-9A (two axis)
Connection Example
Servo Driver
Position Control Unit
Servo I/O terminal block
Power
supply
Switches/sensors
• Simple terminal block wiring of control signals between Servo Driver and Position Control Unit.
• No need to solder connections; all you need is a screwdriver
• Special cables are available to connect the Units.
Servo I/O terminal block
411
XW2C
Input terminal block
Equipped with Power Supply Common and
Operation Indicators and Reduces Control
Panel Wiring to Input Devices
• Equipped with a power supply common for input
devices.
• Operation indicators show each I/O signal’s ON/
OFF status at a glance.
• Can be mounted on DIN rail or screw-mounted.
• Compatible Connecting Cables are available (sold
separately.)
Ordering Information
Points
16 inputs
Internal I/O circuit
common
NPN compatible
(+ common)
Model
XW2C-20G5-IN16
This is a non-standard model and requires a special order.
Contact your OMRON representative for details on availability.
Specifications
Ratings/Characteristics
Rated current
Rated voltage
Number of circuits
Input display
Power supply voltage range
LED indicator current
Insulation resistance
Dielectric strength
Ambient temperature
1 A/common
12 to 24 V DC
16 points
LED indicators (orange)
12 to 24 V DC ±5%
10 mA/input max. at 24 V DC
50 MΩ min. (at 500 V DC)
500 V AC for 1 min
Operating: 0 to 55 °C
Dimensions
Note: All dimensions are in mm.
XW2C-20G5-IN16
Flat Cable Connector (MIL plug)
Two, 4.5 dia.
Terminal block
412
DIN Track lock
Programmable Controllers
Programmable
Controllers
XW2D
Slim Input terminal block
Introducing the XW2D Series, a Slim Version
of the I/O terminal block
• Required mounting area reduced by 35% (compared to OMRON’s 40-pole XW2B Unit), allowing
for smaller control panels and automatic equipment.
• Terminal screw mechanism prevents lost terminal
screws.
• Use either round or forked crimp terminals.
• Mount via DIN rail or screws. Unique DIN rail lock to
mount or remove Units from DIN rail while open.
• Terminal cover can be fixed in the open position.
• Easy-count terminal numbers with different colors
every five terminals.
Ordering Information
Mounted connec- Poles
tor
MIL, XG4A
20
34
40
MIL, XG4C
MR Socket
(See note 3.)
MR Plug
(See note 3.)
50
20
34
40
50
20
34
50
20
34
50
Model
Dimension A
Dimension B
XW2D-20G6
XW2D-34G6*
XW2D-40G6
XW2D-40G6-RF* (See note 1.)
XW2D-40G6-RM* (See note 2.)
XW2D-50G6*
XW2D-20C6*
XW2D-34C6*
XW2D-40C6*
XW2D-50C6*
XW2D-20X6*
XW2D-34X6*
XW2D-50X6*
XW2D-20Y6*
XW2D-34Y6*
XW2D-50Y6*
79
128
149
149
149
184
79
128
149
184
79
128
184
79
128
184
57
100
110
110
110
144
57
100
110
144
57
100
144
57
100
144
Mounted connector
model
XG4A-2031
XG4A-3431
XG4A-4031
XG4A-4031
XG4A-4031
XG4A-5031
XG4C-2031
XG4C-3431
XG4C-4031
XG4C-5031
MR-20RFD2
MR-34RFD2
MR-50RFD2
MR-20RMD2
MR-34RMD2
MR-50RMD2
Cable connector
model
XG4M-2030-T
XG4M-3430-T
XG4M-4030-T
XG4M-4030-T
XG4M-4030-T
XG4M-5030-T
XG4M-2030-U
XG4M-3430-U
XG4M-4030-U
XG4M-5030-U
MR-20M
MR-34M
MR-50M
MR-20F
MR-34F
MR-50F
Note: 1. Has a built-in bleeder resistor and is for the CJ1W-ID231/ID261. External dimensions are the same as the XW2D-40G6.
2. Has a built-in bleeder resistor and is for the CJ1W-ID232. External dimensions are the same as the XW2D-40G6.
3. The MR Connectors are manufactured by Honda Tsushin Kogyou Co., Ltd.
Specifications
Ratings /Characteristics
Rated current
Rated voltage
Insulation resistance
Dielectric strength
Ambient temperature
Slim Input terminal block
1A
125 V AC, 24 V DC
100 MΩ max. (at 500 V DC)
500 V AC for 1 min (with a leakage
current of 1 mA max.)
Operating: 0 to 55 °C
413
Dimensions
XW2D-@@G6 with XG4A MIL Connector
Note: In the 20-pole models, there is just one DIN rail lock located at the bottom-center of the Unit.
Connection Diagram (50-pole model)
XG4A MIL Connector
A
B
Two, 4.5 dia.
(39.1)
17.6
Connector pins
2
4
6
46 48 50
1
3
5
45 47 49
A1 A2 A3
A23 A24 A25
6 40
7
DIN Track lock
39
(4.5)
7
5.8
1.2
M3
B1 B2 B3
B23 B24 B25
Terminals
Note: The connector’s odd-numbered poles
connect to the “A” terminals and the
connector’s even-numbered poles connect to the “B” terminals.
7
XW2D-@@C6 with XG4C MIL Connector
Note: In the 20-pole models, there is just one DIN rail lock located at the bottom-center of the Unit.
Connection Diagram (50-pole model)
XG4C MIL Connector
A
Two, 4.5 dia.
(21.1)
B
17.6
Connector pins
2
4
6
46 48 50
1
3
5
45 47 49
A1 A2 A3
A23 A24 A25
640
7
DIN Track Lock
(4.5)
39
7
5.8
1.2
M3
B1 B2 B3
B23 B24 B25
Terminals
7
414
Note: The connector’s odd-numbered poles
connect to the “A” terminals and the
connector’s even-numbered poles connect to the “B” terminals.
Programmable Controllers
Programmable
Controllers
XW2D-@@X6 with MR Socket Connector
Note: In the 20-pole models, there is just one DIN rail lock located at the bottom-center of the Unit.
Connection Diagram (50-pole model)
A
B
Two, 4.5 dia.
(28.2)
17.6
Connector pins
33 34 35
6 40
48 49 50
19 20
7
DIN Track Lock
1
2
3
1
3
5
32
16 17 18
39
(4.5)
7
5.8
1.2
M3
2
4
17 19
45 47 49
46 48 50
16 18 20
6
7
Terminals
Note: The connector’s poles connect to the
MR socket terminals with the same
number.
XW2D-@@Y6 with MR Plug Connector
Note: In the 20-pole models, there is just one DIN rail lock located at the bottom-center of the Unit.
Connection Diagram (50-pole model)
A
B
Two, 4.5 dia.
(25.9)
17.6
Connector pins
1
2
6 40
16 17 18
3
19 20
32
48 49 50
33 34 35
7
DIN Track Lock
39
(4.5)
7
5.8
1.2
M3
1
3
2
7
5
4
17 19
6
16 18
45 47 49
20
46 48 50
Terminals
Note: The pin numbers on the connector correspond directly to the terminal numbers on the terminal block.
Slim Input terminal block
415
XW2E
Input terminal block with Common (3-tier Style)
Easy-to-wire 3-row Terminal Block with
Power Supply Terminals and Common
• Special-purpose Terminal Block for 16 PLC inputs
• The 3-row terminal configuration simplifies wiring
since only one crimp terminal connection to the
power supply is required.
Ordering Information
Points
16 inputs
Poles
20
Model
XW2E-20G5-IN16
Mounted connector model
XG4A-2031
Cable connector model
XG4M-2030-T
These are all non-standard model and require a special order. Contact your OMRON representative for details on availability.
Note: Use a XW2Z-@@@A Cable only.
Specifications
Ratings/Characteristics
Rated current
Rated voltage
Insulation resistance
Dielectric strength
1 A/common
12 to 24 V DC
50 MΩ min. (at 500 V DC)
500 V AC for 1 min
(with a leakage current of 1 mA max.)
Operating: 0 to 55 °C
Ambient temperature
Dimensions
Note: All dimensions are in mm.
XW2E-20G5-IN16
Two, 4.5 dia. (Mounting holes)
XG4A-2031
0/8
1/9
2/1
0
3/1
1
4/1
2
5/1
3
6/1
4
7/1
5
0/8
50
40
1/9
2/1
0
3/1
1
4/1
2
5/1
3
6/1
4
30
7/1
5
11.5
6.3
7.3 (Pitch between terminals)
139
Connection Diagram
Connector pins
2
4
6
8
10
12
14
16
18
20
1
3
5
7
9
11
13
15
17
19
NC
NC
53
+
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
External
power supply
18
See note.
Terminal block
149
Note: No terminals in this example.
416
Programmable Controllers
Connecting Cables for I/O terminal blocks
• Refer to page 422 for connection details.
XW2Z-@@@A Cables for PLC Units with 32-point Connectors
Ordering Information
XW2Z-@@@A
XW2Z-@@@AU (See note.)
*Cable length (mm)
*Cable length (mm)
L
L
*Cable length L (mm)
500 mm
1,000 mm
1,500 mm
2,000 mm
3,000 mm
5,000 mm
*Cable length L (mm)
500 mm
1,000 mm
1,500 mm
2,000 mm
3,000 mm
5,000 mm
Model
XW2Z-050A
XW2Z-100A
XW2Z-150A*
XW2Z-200A
XW2Z-300A*
XW2Z-500A*
Model
XW2Z-050AU*
XW2Z-100AU*
XW2Z-150AU*
XW2Z-200AU*
XW2Z-300AU*
XW2Z-500AU*
XW2Z-@@@B Cables for Group-2 PLC I/O Units with 32-point Connectors and PLC I/O Units
with 64-point Connectors
XW2Z-@@@B
XW2Z-@@@BU (See note.)
*Cable length (mm)
*Cable length (mm)
L
Wiring
Normal wiring
*Cable length L (mm)
500 mm
1,000 mm
1,500 mm
2,000 mm
3,000 mm
5,000 mm
L
Model
XW2Z-050B
XW2Z-100B
XW2Z-150B*
XW2Z-200B
XW2Z-300B
XW2Z-500B
Wiring
Normal wiring
*Cable length L (mm)
500 mm
1,000 mm
1,500 mm
2,000 mm
3,000 mm
5,000 mm
Model
XW2Z-050BU*
XW2Z-100BU*
XW2Z-150BU*
XW2Z-200BU*
XW2Z-300BU*
XW2Z-500BU*
XW2Z-@@@D Cables for Group-2 PLC Input Units with 32-point Connectors and PLC Input Units
with 64-point Connectors
XW2Z-@@@D
*Cable length (mm)
Row Row
A
B
B
(250)
Yellow
A20 B20
Note:
The wiring of the G79-I@C-@ cables
(for the G7TC) is different, so these
cables cannot be used with the XW2C.
A1 B1
CN3
Black
(500)
*Cable lengths (mm)
A
1,000 mm
1,500 mm
2,000 mm
3,000 mm
5,000 mm
Model
B
750 mm
1,250 mm
1,750 mm
2,750 mm
4.750 mm
XW2Z-100D*
XW2Z-150D*
XW2Z-200D*
XW2Z-300D*
XW2Z-500D*
CN2
A
The pins in CN2 (yellow) connect to row A of CN1 and
the pins in CN3 (black) connect to row B of CN1.
* This is a non-standard model and requires a special order. Contact your OMRON representative for details on availability.
Connecting Cables for I/O terminal blocks
417
Programmable
Controllers
XW2Z
XW2Z-@@@F Cables with Crimp Terminals (20 poles)
XW2Z-@@@F
*Cable length L (mm)
1,000 mm
1,500 mm
2,000 mm
3,000 mm
5,000 mm
Fork Terminals
(M3.5)
Connect
to devices
XG4M-2030-T
Model
XW2Z-100F
XW2Z-150F
XW2Z-200F
XW2Z-300F
XW2Z-500F
These are all non-standard model and require a special order.
Contact your OMRON representative for details on availability.
L
*Cable length (mm)
300
XW2Z-@@@L Cables for Group-2 PLC Output Units with 32-point Connectors and PLC Output Units
with 64-point Connectors
XW2Z-@@@L
*Cable lengths (mm)
Row Row
A
B
B
A20 B20
(250)
Green
A1 B1
White
(500)
CN3
*Cable lengths (mm)
A
1,000 mm
1,500 mm
2,000 mm
3,000 mm
5,000 mm
Model
B
750 mm
1,250 mm
1,750 mm
2,750 mm
4.750 mm
XW2Z-100L
XW2Z-150L
XW2Z-200L
XW2Z-300L
XW2Z-500L
CN2
A
The pins in CN2 (white) connect to row A of CN1 and
the pins in CN3 (green) connect to row B of CN1.
These are all non-standard model and require a special order.
Contact your OMRON representative for details on availability.
XW2Z-@@@H Cables for PLC I/O Units with 96-point Connectors
XW2Z-@@@H-1
XW2Z-@@@H-2
*Cable lengths (mm)
A
*Cable length (mm)
Black
CN1
CN2
L
CN3
Yellow
B
Wiring distance
(not including bends)
Cable length (mm)
500 mm
1,000 mm
1,500 mm
2,000 mm
3,000 mm
5,000 mm
7,000 mm
10,000 mm
Model
XW2Z-050H-1
XW2Z-100H-1
XW2Z-150H-1
XW2Z-200H-1
XW2Z-300H-1
XW2Z-500H-1
XW2Z-700H-1
XW2Z-010H-1
These are all non-standard model and require a special order.
Contact your OMRON representative for details on availability.
418
Cable lengths (mm)
A
1,000 mm
1,500 mm
2,000 mm
3,000 mm
5,000 mm
10,000 mm
Model
B
750 mm
1,250 mm
1,750 mm
2,750 mm
4.750 mm
9,750 mm
XW2Z-100H-2
XW2Z-150H-2
XW2Z-200H-2
XW2Z-300H-2
XW2Z-500H-2
XW2Z-010H-2
These are all non-standard model and require a special order.
Contact your OMRON representative for details on availability.
Programmable Controllers
*Cable lengths (mm)
A
B
Black
CN1
CN2
CN3
Yellow
CN4
Cable lengths (mm)
A
B
1,000 mm
750 mm
1,500 mm
1,250 mm
2,000 mm
1,750 mm
3,000 mm
2,750 mm
5,000 mm
4.750 mm
10,000 mm
9,750 mm
Programmable
Controllers
XW2Z-@@@H-3
Model
C
1,000 mm
1,500 mm
2,000 mm
3,000 mm
5,000 mm
10,000 mm
XW2Z-100H-3
XW2Z-150H-3
XW2Z-200H-3
XW2Z-300H-3
XW2Z-500H-3
XW2Z-010H-3
Gray
Wiring distance
(not including bends)
C
These are all non-standard model and require a special order.
Contact your OMRON representative for details on availability.
XW2Z-@@@K/N Cables for PLC I/O Units with 32-point MIL Connectors
XW2Z-@@@K
*Cable length (mm)
L
Cable length (mm)
1,000 mm
1,500 mm
2,000 mm
3,000 mm
5,000 mm
Model (See note.)
XW2Z-100K
XW2Z-150K*
XW2Z-200K
XW2Z-300K*
XW2Z-500K*
* This is a non-standard model and requires a special order.
Contact your OMRON representative for details on availability.
XW2Z-@@@N
*Cable lengths (mm)
A
(120)
B
Wiring distance
(not including bends)
Connecting Cables for I/O terminal blocks
Cable lengths (mm)
A
1,000 mm
1,500 mm
2,000 mm
3,000 mm
5,000 mm
Model
B
750 mm
1,250 mm
1,750 mm
2,750 mm
4.750 mm
XW2Z-100N
XW2Z-150N
XW2Z-200N
XW2Z-300N
XW2Z-500N
These are all non-standard model and require a special order.
Contact your OMRON representative for details on availability.
419
XW2Z
Host Link Cables
PLC-compatible RS-232C Cables Ideal for Host Link
Connections between a PLC and Host Computer or
other Device
Connection Example
SYSMAC PLC
CQM1, C-series,
CV-series, or CVM1
XW2Z Host Link Cable
Host device
Personal computer, Factory Intelligent
Terminal, or Programmable Terminal
Ordering Information
SYSMAC PLC end
C20-LK201-V1
C500-LK203
C500-LK201-V1
C120-LK201-V1
C200H-LK201
CV500-LK201
(Port 1, full-duplex mode)
C200HS-CPU31/33/21/23
CQM1-CPU21/41/42/43/44
(Units with RS-232C port)
C20H
C28H
C40H
C60H
(Units with built-in Host Link)
C200HS-CPU31/33/21/23
CQM1-CPU21/41/42/43/44
(Units with RS-232C port)
CV500/CV1000/CV2000, CVM1
(Units with built-in Host Link)
CV500-LK201
(Port 2, full-duplex mode)
C200HE-CPU42
C200HG-CPU43/63
C200HX-CPU44/64
C200HW-COM02/04/05/06
CPM1-CIF01
420
XW2Z Host Link Cable (PLC-compatible RS-232C cable)
Wiring configuration
Cable length L
(See note 1.)
2m
25-pin D-Sub Plug
25-pin D-Sub Plug
5m
Host end
PLC end
Connector hood FG
FG
SD
RD
RS
CS
SG
DR
ER
Shield
1
2
3
4
5
7
6
20
1
2
3
4
5
7
6
20
25-pin D-Sub Plug
Host end
Connector hood FG
Shield
1
2
3
4
5
7
6
20
9-pin D-Sub Plug
PLC end
Connector hood FG
--SD
RD
RS
CS
SG
1
2
3
4
5
9
2m
5m
XW2Z-200R*
XW2Z-500R*
2m
5m
XW2Z-200S*
XW2Z-500S*
FG
SD
RD
RS
CS
SG
DR
ER
25-pin D-Sub Plug
Shield
Programmable Terminal:
NT20M, NT600M,
NT610C, or NT610G
FG
SD
RD
RS
CS
SG
DR
ER
PLC end
Connector hood FG
1
2
3
4
5
7
9
XW2Z-200P*
XW2Z-500P*
Connector hood FG
9-pin D-Sub Plug
FG
SD
RD
RS
CS
SG
SG
Host device end
Model number
Host end
Connector hood FG
1
2
3
4
5
7
6
20
FG
SD
RD
RS
CS
SG
DR
ER
Programmable Controllers
C20-LK201-V1
C500-LK203
C500-LK201-V1
C120-LK201-V1
C200H-LK201
CV500-LK201
(Port 1, full-duplex mode)
C200HS-CPU31/33/21/23
CQM1-CPU21/41/42/43/44
CV500/CV1000/CV2000, CVM1
CV500-LK201
(Port 2)
C200HE-CPU42
C200HG-CPU43/63
C200HX-CPU44/64
C200HW-COM02/04/05/06
CPM1-CIF01
XW2Z Host Link Cable (PLC-compatible RS-232C cable)
Wiring configuration
Cable length L
(See note 1.)
2m
25-pin D-Sub Plug
9-pin D-Sub Socket
5m
PLC end
Connector hood FG
FG
SD
RD
RS
CS
DR
SG
--ER
1
2
3
4
5
6
7
--20
1
2
3
4
5
6
7
8
9
9-pin D-Sub Socket
Host end
Connector hood FG
Shield
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
9
9-pin D-Sub Plug
PLC end
Connector hood FG
FG
SD
RD
RS
CS
--DR
ER
SG
Shield
Host end
Connector hood FG
1
2
3
4
5
6
7
8
9
Personal Computer
2m
5m
XW2Z-200S-V
XW2Z-500S-V*
2m
5m
XW2Z-200S-CV*
XW2Z-500S-CV*
2m
5m
XW2Z-200T
XW2Z-500T
--RD
SD
ER
SG
DR
RS
CS
---
9-pin D-Sub Socket
1
2
3
4
5
6
7
8
9
XW2Z-200P-V*
XW2Z-500P-V*
---
PLC end
Connector hood FG
--SD
RD
RS
CS
-------
Host device end
Model number
RD
SD
ER
SG
DR
RS
CS
---
9-pin D-Sub Plug
SG
CS1H-CPU@@-V1
CS1G-CPU@@-V1
CJ1G-CPU@@
CJ1H-CPU@@
CJ1M-CPU@@
Shield
Host end
Connector hood FG
Programmable
Controllers
SYSMAC PLC end
--RD
SD
ER
SG
DR
RS
CS
---
ESD-preventive connectors are used.
CQM1-CPU21/41/42/43/44
(Units with RS-232C port)
C200HS-CPU31/33/21/23
CV500-CPU01, CV1000-CPU01,
CV2000-CPU01
CVM1-CPU01/11
CV500-LK201
(Communications port 2)
C200HE-CPU42
C200HG-CPU43/63
C200HX-CPU44/64
C200HW-COM02/04/05/06
CPM1-CIF01
CPM2A-CPU@@
CQM1H-CPU21/51/61
CS1@-CPU@@
CJ1@-CPU@@
9-pin D-Sub Plug
PLC end
Connector hood FG
--SD
RD
RS
CS
SG
1
2
3
4
5
9
9-pin D-Sub Plug
Shield
Host end
Connector hood FG
1
2
3
4
5
9
Programmable Terminal:
NT20S, NT600S,
NT620S, NT620C,
NT30, or NT30C
NT31, or NT31C,
NT631, or NT 631 C,
NS-series
--SD
RD
RS
CS
SG
Note: 1. The cable length does not include the connectors, as shown in the following diagram.
L
Cable length
* This is a non-standard model and requires a special order. Contact your OMRON representative for details on availability.
Host Link Cables
421