Compact Non-Contact Door Switch/Non-Contact Door Switch Controller
D40A/G9SX-NS
Electronic Detection Mechanism for
Better Stability in Non-contact Door
Switch Operation
For the most recent information on models that have been certified for
safety standards, refer to your OMRON website.
Be sure to read the “Safety Precautions” on page 32.
Features
● Easy-to-see 2-Color Indicators
● Mount from Either Side
Switch status is easy to see at a glance with
these red/yellow LED indicators.
Red:
Open door
detected.
Yellow:
Closed door
detected.
Not lit:
Power OFF
or failure
Swinging doors
● Small Actuator
Sliding doors
● Save Labor with Connector and Reduce Inventory
An actuator that is smaller than the switch
saves space, even inside the door.
Even when mounted with an L-bracket, the
actuator's height will not hinder installation or
operation.
Compact
Switch
Mount from whichever side provides the
easiest wiring path to enable mounting to all
types of doors.
Wiring time can be reduced with the connector.
Cable lengths can be selected, and only cables of
required lengths can be purchased.
Switches can be integrated into a single Switch
with a connector when installing in a machine with
multiple doors or various types of machines,
which can reduce inventory.
Actuator
● Connect Up to 30 Switches to a Single Controller
Reduce costs by connecting up to 30 Switches to a single Controller.
Up to 30 Switches
1
D40A/G9SX-NS
Solves Conventional Switch Issues to Provide Stable Detection
Issue 1
The Switch does not accurately detect the door when it is closed slowly, resulting in an error.
Conventional switch
An error can occur
if the door is closed
slowly with
conventional
switches.
Door
closed
slowly.
Solution 1
Conventional Switches
The D40A does not use reed switches and
provides stable detection with electronic switches.
Slow
Slow
Magnet
Magnet
Reed switch contacts
Reed switch contacts
Error
Issue 2
If the switching timing of reed
switch contacts 1 and 2 varies
too much, the Controller
detects an error and turns OFF
the output to maintain safety.
Stable Detection
with the D40A's
New System
Note: The figure is intended
only as an illustration.
Detects slow lateral operation.
Detects slow rotating operation.
It is nearly impossible to tell which door is open in a multi-door application.
If an error occurs...
The system cannot be started because the Controller has turned
OFF the output even though all doors appear to be closed.
It's impossible to tell if there is a door open or if an error has occurred.
All doors must be opened and closed before operation can be started.
Solution 2
With the D40A...
The auxiliary outputs can be used to easily indicate which door is
open.
And with two-color indicators, mounting adjustments are also easy.
The D40A is the first Non-contact Door Switch to combine 2-color
indicators, auxiliary outputs, and 30-switch connection capacity,
allowing you to create a better safety environment.
Issue 3
Various cable lengths and complex wiring are required for multiple doors.
Solution 3
The model with a connector allows you to select the cable lengths that are connected and purchase the
cables of required lengths. Switches can be integrated into a single Switch with a connector.
Downtime can be reduced by replacing the cable and switch partially at maintenance time.
2
D40A/G9SX-NS
Two Types of Controller to Solve Productivity, Expandability, and Maintenance Issues
The G9SX-NS and G9SX-NSA are designed specifically for use with Non-contact door switch, and with the G9SX-NSA you can also connect
mechanical safety door switches. Among other features, these Controllers support logical AND connections that enable partial stops. These
Controllers make the most of D40A Switches.
● Two Different Controllers
G9SX-NS
G9SX-NSA
@Logical AND
connection input
@Logical AND
connection input
@D40A input
@D40A plus mechanical
safety door switch input,
channel 1 or 2
@Two instantaneous
safety outputs
@Two instantaneous safety
outputs
@Two OFF-delay safety
outputs
@Logical AND
connection output
@Logical AND
connection output
● Indicators That Make Maintenance Easier
The indicators show the location
and cause of wiring errors and
any other errors that are detected.
Auxiliary outputs for errors also
contribute to reducing down time.
Input error
Logical AND
connection error
Output error
● Mechanical Safety Door Switches Can Also Be Connected with the G9SX-NSA
Inputs can be accepted
D40A
from both D40A Switches
and mechanical switches to
reduce the number of
Safety Door
Switches
Controllers and costs.
● Expansion Units to Easily Increase the Number of Outputs with the G9SX-NSA
The number of outputs
can be easily increased
using connectors.
Up to 25 outputs can be
Up to 25 Outputs
configured.
G9SX-EX Expansion Unit
3
D40A/G9SX-NS
Reduce Costs with these New-Concept Controllers
Issue 1
Two Controllers are required for emergency stop switches and
non-contact door switches.
Application
●One hazard.
●The system must be stopped
when either a door is opened
or an emergency stop switch
is pressed.
D40B
Emergency
stop switch *
D40A
Solution 1
D40B-J1
Emergency
stop switch *
The D40A
Simplifies the
Configuration
The G9SA must be
added to connect the
G9SA
emergency stop
switch.
Two
Controllers
Issue 2
G9SX-NSA
With only one
G9SX-NSA222-T03@
Controller, both a
Non-contact Door Switch
and an emergency stop
switch can be connected.
One
Controller
Another Controller has to be added to use an OFF-delay timer.
Application
●Two hazards.
●The power supply must be
turned OFF immediately when
the emergency stop switch is
pressed.
●When a door is opened, a stop
signal is sent to only
servomotor B and then the
power supply is turned OFF.
Emergency
stop switch *
D40B
Solution 2
D40B-J1
Emergency
stop switch *
The D40A
Simplifies the
Configuration
Wiring
G9SX-NSA
G9SX-BC
The G9SA must be
Logical AND
connection
G9SA-321-T@
OFF-delay
output
G9SA
added to use an
OFF-delay timer.
Three
A
B
Controllers
A Controller can be
eliminated because the
G9SX-NSA222-T03@
provides an OFF-delay
output.
* Always use a manual reset when using an emergency stop.
Refer to G9SX for the features of the G9SX Series.
4
D40A
A
B
Two
Controllers
D40A/G9SX-NS
Selection of Safety Controllers for D40A
[Connectable Controllers]
Safety Controller G9SP
Non-contact Door Switch Controller G9SX-NS@
Safety Controller
G9SP
Non-contact Door Switch Controller
G9SX-NS@
• Flexible programming by combining function blocks
• Extensive system configurations
• Decreased work hours by convenient configurator
• Easy expansion of output points by an expansion unit
• Improved maintainability by LED display
• No special programming required
Function Blocks
* G9SP Series Catalog
Catalog No.: F090
* For details on G9SX-NS@, refer to page 12
and the subsequent pages.
Note: For product information, refer to your OMRON website.
5
Compact Non-Contact Door Switch
D40A
Electronic Detection Mechanism for
Better Stability
• Up to 30 units can be connected to a G9SX-NS@ or G9SP.
(The G9SP supports 2 channels and up to 15 units per channel.)
• Compact Non-contact Door Switch can be mounted from both
sides.
• The cable length can be selected, reducing wiring restrictions,
and Switches can be integrated into a single Switch with a
connector, reducing inventory.
• Easy maintenance with color LEDs identifying opening/closing
of the door and breaking of cable.
• Complies with EN ISO 13849-1 (PLd/Safety Category 3).
For the most recent information on models that have been certified for
safety standards, refer to your OMRON website.
Be sure to read the “Safety Precautions” on page 32.
Model Number Structure
Model Number Legend
Non-Contact Door Switch (Switch/Actuator)
D40A - @@@
1 2 3
1. Type
1: Standard model
2. Auxiliary outputs
C: 1NO (PNP transistor output)
3. Cable length
2: 2 m
5: 5 m
015-F: Connector type
(Cable length :15cm)
Note: The Switch must be used in combination with a Non-Contact Door Switch Controller (G9SX-NS@) or Safety Controller (G9SP).
For details on G9SX-NS@, refer to page 14 or subsequent pages, and for details on G9SP series, refer to "G9SP Series Catalog"
(Cat. No. F090).
6
D40A
Ordering Information
List of Models
Non-Contact Door Switches (Switch/Actuator)
Classification
Appearance
Auxiliary outputs
Cable length
Model
2m
D40A-1C2
5m
D40A-1C5
Standard models
Semiconductor
outputs *1
Connector model
0.15 m
D40A-1C015-F *2
Note: The Switch must be used in combination with a Non-Contact Door Switch Controller (G9SX-NS@) or Safety Controller (G9SP).
*1. PNP open-collector semiconductor output.
*2. The model with a connector is not KOSHA certified.
Cable with connector
Connector
Type
Single-end
Cable
Length
Model
Packing
Unit
2m
XS2F-D521-DG0-A
5m
XS2F-D521-GG0-A
10 m
XS2F-D521-JG0-A
1
15 m
XS2F-D521-KG0-A
20 m
XS2F-D521-LG0-A
Connector
Type
Cable
Length
Model
Packing
Unit
5
2m
XS2W-D521-DG1-A
5
5
5m
XS2W-D521-GG1-A
5
10 m
XS2W-D521-JG1-A
1
1
15 m
XS2W-D521-KG1-A
1
1
20 m
XS2W-D521-LG1-A
1
Double-end
Controllers
Non-Contact Door Switch Controllers G9SX-NS@
Safety outputs *1
Instantaneous
2
(Semiconductors)
Logical
AND
connection
input
Auxiliary
outputs *3
OFF-delayed
*2
0
2
(Semiconductors)
Logical
AND
connection
output
Max. OFF delay
time *4
Rated
voltage
---
2
(Semiconductors)
1
1
24 VDC
3.0 s
Terminal block type
Model
Screw terminals
G9SX-NS202-RT
Spring-cage terminals
G9SX-NS202-RC
Screw terminals
G9SX-NSA222-T03-RT
Spring-cage terminals
G9SX-NSA222-T03-RC
Note: For details, refer to page 12 or subsequent pages.
*1. P channel MOS FET transistor output
*2. The OFF-delayed output becomes an instantaneous output by setting the OFF-delay time to 0 s.
*3. PNP transistor output
*4. The OFF-delay time can be set in 16 steps as follows:
0/0.2/0.3/0.4/0.5/0.6/0.7/0.8/0.9/1.0/1.2/1.4/1.8/2.0/2.5/3.0 s
Safety Controller G9SP Series
No. of I/O points
Name
Safety Controller
Safety
inputs
Test
outputs
Safety outputs
Standard
outputs
10
4
Semiconductor outputs: 4
4
10
6
Semiconductor outputs: 16
--
20
6
Semiconductor outputs: 8
--
Unit version
Model
G9SP-N10S
Ver.2.0
G9SP-N10D
G9SP-N20S
Note: For details, refer to the G9SP Series Catalog (Catalog No. F090).
7
D40A
Specifications
Non-contact Door Switches
Ratings and Characteristics
Item
Interlock type
Coding level
Model
Operating distance OFF→ON
Operating distance ON→OFF
Operating
Differential travel
characteristics *2
Influence of temperature (max.)
Repeat accuracy
Ambient operating temperature
Ambient operating humidity
Insulation resistance (between charged parts and
case)
Dielectric strength (between charged parts and case)
Pollution degree
Electromagnetic compatibility
D40A-1C@
Type 4 (EN ISO 14119)
Low level coded (EN ISO 14119)
5 mm min. *1
15 mm max. *1
20% or less of operating distance at 23°C (maximum 2.5 mm)
±20% of operating distance at 23°C, within temperature range of −10 to 55°C
±10% or less of operating distance at 23°C
−10 to 55°C (no icing or condensation)
25% to 85%
50 MΩ max. (at 500 VDC)
1,000 VAC for 1 min
3
IEC/EN 60497-5-3 compliant
10 to 55 to 10 Hz (single amplitude: 0.75 mm, double
amplitude: 1.5 mm)
300 m/s2 min.
IP67
PBT resin
M4 screws
1 N·m
24 VDC +10%/−15%
0.6 W max.
24 VDC, 10 mA (PNP open-collector outputs)
Actuator not detected (red); actuator detected (yellow)
2 m, 5 m, 0.15m (Connector type)
30 max. (wiring length: 100 m max.) *4
Switch: approx. 145 g, actuator: approx. 20 g (D40A-1C2)
Vibration resistance
Shock resistance
Degree of protection
Material
Mounting method
Terminal screw tightening torque
Power supply voltage
Power consumption
Auxiliary outputs *3
LED indicators
Connection cables
Number of connectable switches
Weight
*1. The condition of this distance are that the switch and actuator target marks are on the same axis and the sensing surfaces are exactly parallel
condition. OFF to ON distance shows the switch approaching (Point A in the engineering data graph) and ON to OFF distance shows the switch
separating away (Point B in the engineering data graph).
*2. For details on response time and operating time, refer to the catalog or manual of a safety controller to be connected.
*3. Turns ON when the actuator is approaching. The G3R series of the SSR can be driven at an auxiliary output of 10 mA. Contact your OMRON
representative for details.
*4. For details, refer to item 5 on page 33.
Engineering Data
5mm (point A)
Note: 1. The operating distance is the distance between the switch and actuator sensing surfaces.
2. The graph indicates shifting to X or Z direction from following condition that the switch and
actuator target marks are on the same axis and the sensing surfaces are exactly parallel
condition.
Dashed lines indate reference value for maximum and minimun oprating distance at abient
temperature +23°C. The solid line indicates reference values of the maximum and
minimum operating distances.
3. The operating distance may be affected by ambient metal, magnet catches, and
temperature.
15mm (point B)
Y-direction movement
ON
Unstable
range
OFF
18
OFF range
16
Maximum
operating distance
(ON to OFF)
B
14
Sensing
surface
Engineering Data
(ON to OFF)
12
Engineering
Data
(OFF to ON)
10
Y
8
Minimum
operating distance
(OFF to ON)
6
A
4
0
−6
−4
−2
0
Target marks
OFF range
16
14
Engineering Data
(ON to OFF)
12
10
Engineering
Data
(OFF to ON)
8
4
Distance from the target mark on the switch X (mm)
6
A
ON range
0
−15
−10
−5
0
Z
Minimum
operating distance
(OFF to ON)
6
2
2
Sensing
surface
Maximum
operating distance
(ON to OFF)
B
4
ON range
2
8
X
Operating distance Y (mm)
Operating distance Y (mm)
18
5
10
15
Distance from the target mark on the switch Z (mm)
Y
Target marks
D40A
Cable with connector
Ratings and Characteristics
Rated current
4A
Rated voltage
250 VAC/VDC
Contact resistance (Connector)
40 mΩ max. (20 mV max., 100 mA max.)
Insulation resistance
1,000 MΩ min. (at 500 VDC)
Dielectric strength (Connector)
1,500 VAC for 1 min (leakage current: 1 mA max.).
Degree of protection
IP67 (IEC60529)
Insertion tolerance
200 times min.
Cable holding strength
Cable diameter: 6 mm
Ambient operating temperature range
Operating: − 25°C to 70°C
Ambient humidity range
20% to 85%
98 N/15 s
Materials and Finish
Item
Contacts
Thread bracket
Pin block
XS2F/H/W
Materials
Phosphor bronze
Finish
Nickel base, 0.4-μm gold plating
Materials
Brass
Finish
Nickel plated
Materials
PBT resin (UL94V-0)
Finish
For DC: light gray; for AC: dark gray
O-ring/rubber bushing
Rubber
Cover
PBT resin (UL94V-0)
9
D40A
Connections
Internal Circuit Diagram
D40A-1C@
Brown
Internal circuit
Blue
White
Black
Yellow
D40A and G9SX-NS@ Wiring
Example: Wiring a Single Switch
Example: Wiring Multiple Switches
Connect Up to 30 Non-contact Door Switches
Blue
Brown
Black
White
Blue
Brown
Black
White
Blue
Brown
A2
Black
D1 D2 D3 D4
Auxiliary output load *1
White
Blue
*2
Yellow
Black
Brown
White
D40A-1C@
G9SX-NS202-@
G9SX-NSA222-T03-@
*1. The auxiliary output load current must be 10 mA max.
*2. When connecting a XS2F series connector with cable to a
connector type, the color of the auxiliary output cable is gray.
D1 D2 D3 D4
G9SX-NS202-@
G9SX-NSA222-T03-@
Wiring of Inputs and Outputs
Signal name
Wire color
Pin No. of
connector type
Description of operation
+
Brown
1
-
Blue
3
Non-contact Door Switch input
White
2
Inputs signals from the G9SX-NS@.
The Non-contact Door Switch input must be ON as a required condition for
the Non-contact Door Switch output to be ON.
Non-contact Door Switch
output
Black
4
Turns ON and OFF according to actuator detection and the status of the
Non-contact Door Switch input.
Auxiliary output
(PNP open-collector output)
Yellow
5
Turns ON when actuator is detected.
Non-contact Door Switch
power supply input
Supplies power to the D40A.
Connect to the D3 and D4 terminal of the G9SX-NS@.
Note: When connecting a XS2F series connector with cable to a connector type, the color of the auxiliary output cable is gray.
4
3
5
1
2
Pin arrangement of connector type
For more information on connection terminal and wiring of G9SP, refer to G9SP Series Safety Controller
OPERATION MANUAL (Man. No. Z922).
10
D40A
Dimensions and Terminal Arrangement
(Unit: mm)
Non-contact Door Switch (Switch/Actuator)
D40A-1C2
D40A-1C5
D40A-1C015-F
Indicator
(1.5)
2-4.2 dia.
9.5
7.2 dia.
38
7.2 dia.
48
48
7.2 dia.
12
7.2 dia.
Sensing
surface
(150)
6
13
17
38
(2)
2-4.2 dia.
20
25
Vinyl-insulated round cable:
Diameter 4 mm, 5-wire
(Conductor cross-sectional area: 0.2 mm2/
Insulator diameter: 1.0 mm)
Standard length: 2 m/5 m
(46) (15 dia.)
M12
13
(Actuator)
(Switch)
Accessories (Sold separately)
Socket on One Cable End
(5-pole Connectors)
XS2F-D521-DG0-A (L=2m)
XS2F-D521-GG0-A (L=5m)
XS2F-D521-JG0-A (L=10m)
XS2F-D521-KG0-A (L=15m)
XS2F-D521-LG0-A (L=20m)
(Unit: mm)
Straight Connectors
M12
5 dia.
45°
6 dia.
14.9 dia.
30
40.7
L
Pin Arrangements
(Engagement Side)
Wiring Diagram
Cable lead
colors
Contact No.
2
4
Brown
White
Blue
Black
Gray
1
3
5
Sockets and Plugs on Cable Ends
(5-pole Connectors)
XS2W-D521-DG1-A (L=2m)
XS2W-D521-GG1-A (L=5m)
XS2W-D521-JG1-A (L=10m)
XS2W-D521-KG1-A (L=15m)
XS2W-D521-LG1-A (L=20m)
5
50
2
5
3
1
4
Straight/Straight Connectors
6 dia.
14.9 dia.
14.9 dia.
40.7
44.7
L
Wiring Diagram for 5 Cores
Contact No.
1
2
3
4
5
Cable lead
colors
1
Brown
2
White
3
Blue
4
Black
5
Gray
11
Non-Contact Door Switch Controller
G9SX-NS
Dedicated controller for Non-Contact
Door Switch with programless and
safety circuit configuration
• Up to 30 units of D40A/D40Z Compact Non-Contact Door Switch
can be connected to a single Controller.
• Logical AND connection function provides easy system
configuration for partial stop and complete stop.
• Programless.
• G9SX-NSA provides simultaneous inputs of a Non-Contact Door
Switch and a conventional key-insertion type Safety Door Switch.
For the most recent information on models that have been certified for
safety standards, refer to your OMRON website.
Be sure to read the “Safety Precautions” on page 32.
Model Number Structure
Model Number Legend
Non-Contact Door Switch Controller
G9SX - @@@@@@ - @@@ - @@
1
2 3 4
5
1. Functions
NS/NSA: Controller
EX:
Expansion Unit
2. Output Configuration
(Instantaneous Safety Outputs)
2: 2 outputs
4: 4 outputs
3. Output Configuration
(OFF-delayed Safety Outputs)
0: None
2: 2 outputs
12
6
4. Output Configuration
(Auxiliary Outputs)
1: 1 output
2: 2 outputs
5. Max. OFF-delay Time
Controller
T03: 3 s (Variable)
Expansion Unit
Blank: No OFF delay
T:
OFF delay
6. Terminal Block Type
RT: Screw terminals
RC: Spring-cage terminals
G9SX-NS
Ordering Information
List of Models
Non-Contact Door Switch Controllers
Safety outputs *1
Instantaneous
2
(Semiconductors)
*1.
*2.
*3.
*4.
Logical
AND
connection
input
Auxiliary
outputs *3
OFF-delayed
*2
0
2
(Semiconductors)
2
(Semiconductors)
Logical
AND
connection
output
Max. OFF delay
time *4
Rated
voltage
--1
1
24 VDC
3.0 s
Terminal block type
Model
Screw terminals
G9SX-NS202-RT
Spring-cage terminals
G9SX-NS202-RC
Screw terminals
G9SX-NSA222-T03-RT
Spring-cage terminals
G9SX-NSA222-T03-RC
P channel MOS FET transistor output
The OFF-delayed output becomes an instantaneous output by setting the OFF-delay time to 0 s.
PNP transistor output
The OFF-delay time can be set in 16 steps as follows:
0/0.2/0.3/0.4/0.5/0.6/0.7/0.8/0.9/1.0/1.2/1.4/1.8/2.0/2.5/3.0 s
Expansion Units
Safety outputs
Instantaneous
OFF-delayed
4PST-NO
---
Auxiliary
outputs
OFF-delay time
---
1
(Semiconductor) *1
---
Rated
voltage
24 VDC
*2
4PST-NO
Terminal block type
Model
Screw terminals
G9SX-EX401-RT
Spring-cage terminals
G9SX-EX401-RC
Screw terminals
G9SX-EX041-T-RT
Spring-cage terminals
G9SX-EX041-T-RC
*1. PNP transistor output
*2. The OFF-delay time is synchronized to the OFF-delay time setting in the connected Controller (G9SX-NSA222-T03-@).
Accessories
Terminal Block
Appearance *
Specifications
Applicable units
Model
Remarks
Terminal Block with screw
terminals (3-pin)
G9SX-NSA
Y9S-03T1B-02A
Two Terminal Blocks (black) with screw
terminals, and a set of six code marks to
prevent erroneous insertion.
Terminal Block with screw
terminals (4-pin)
G9SX-NS
G9SX-EX-@
Y9S-04T1B-02A
Two Terminal Blocks (black) with screw
terminals, and a set of six code marks to
prevent erroneous insertion.
Terminal Block with springG9SX-NSA
cage terminals (3-pin)
Y9S-03C1B-02A
Two Terminal Blocks (black) with spring-cage
terminals, and a set of six code marks to
prevent erroneous insertion.
Terminal Block with spring- G9SX-NS
cage terminals (4-pin)
G9SX-EX-@
Y9S-04C1B-02A
Two Terminal Blocks (black) with spring-cage
terminals, and a set of six code marks to
prevent erroneous insertion.
Note: The G9SX main unit comes with a terminal block as standard equipment. The accessories shown here can be ordered as a replacement.
* The illustrations show 3-pin types
13
G9SX-NS
Specifications
Non-contact Door Switch Controllers
Ratings
Power input
Item
Model
G9SX-NS202-@
G9SX-NSA222-T03-@
Rated supply voltage
24 V DC
Operating voltage range
−15% to 10% of rated supply voltage
Rated power consumption *
3 W max.
4 W max.
G9SX-EX-@
2 W max.
* Power consumption of loads not included.
Inputs
Item
Model
Safety input *1
G9SX-NS202-@/G9SX-NSA222-T03-@
Operating voltage: 20.4 VDC to 26.4 VDC, internal impedance: approx. 2.8 kΩ *2
Feedback/reset input
*1. Only applies to the G9SX-NSA222-T03-@. Refers to input other than that from the Non-contact Door Switch.
*2. Provide a current equal to or higher than that of the minimum applicable load of the connected input control device.
Outputs
Item
Model
G9SX-NS202-@/G9SX-NSA222-T03-@
Instantaneous safety output *1
OFF-delayed safety output *1
P channel MOS FET transistor output
Load current: 0.8 A DC max. *2
Auxiliary output
PNP transistor output
Load current: 100 mA max.
*1. While safety outputs are in the ON state, the following signal sequence is output continuously for diagnosis.
When using the safety outputs as input signals to control devices (i.e. Programmable Controllers), consider the OFF pulse shown below.
Approx.100 ms
ON
OFF
360 μs max.
*2. The following derating is required when Units are mounted side-by-side.
G9SX-NS202-@/G9SX-NSA222-T03-@: 0.4 A max. load current
Expansion Unit
Item
Model
G9SX-EX-@
Rated load
250 VAC, 3 A/30 VDC, 3 A (resistive load)
Rated carry current
3A
Maximum switching voltage 250 VAC, 125 VDC
14
G9SX-NS
Characteristics
Item
Model
Over-voltage category
(IEC/EN 60664-1)
G9SX-NS202-@
G9SX-NSA222-T03-@
G9SX-EX-@
II (Relay outputs 13 to 43
and 14 to 44: III)
II
Logical AND connection input:
100 ms max.
Operating time (OFF to ON state) *1
D40A connected: 100 ms max.
D40Z connected: 200 ms max.
Safety input: 50 ms max. *2
Logical AND connection input:
100 ms max. *3
D40A connected: 100 ms max. *3
D40Z connected: 200 ms max. *3
30 ms max. *4
15 ms max. (Logical AND
connection input: OFF)
Logical AND connection input:
Response time (ON to OFF state) *1
15 ms max.
D40A connected: 20 ms max. *6
D40Z connected: 45 ms max.
15 ms max. (Logical AND
connection input: OFF)
Safety input: 15 ms max.
Logical AND connection input:
15 ms max.
D40A connected: 20 ms max. *6
D40Z connected: 45 ms max.
10 ms max. *4
ON-state residual voltage
3.0 V max. (safety output, auxiliary output)
OFF-state leakage current
0.1 mA max. (safety output, auxiliary output)
Maximum wiring length of safety
input, logical AND connection input,
and Non-contact Door Switch input
100 m max. (External connection impedance: 100 Ω max. and 10 nF max.)
Reset input time
(Reset button pressing time)
100 ms min.
Accuracy of OFF-delay time *5
---
Within ±5% of the set value
Between logical AND
connection terminals,
and power supply input
terminals and other input
Insulation and output terminals
20 MΩ min. (at 100 VDC)
resistance connected together
---
Between all terminals
connected together and
DIN rail
100 MΩ min.
(at 500 VDC)
Between logical AND
connection terminals,
and power supply input
terminals and other input
and output terminals
500 VAC for 1 min.
connected together
Dielectric
strength
Within ±5% of the set value
---
Between all terminals
connected together and
DIN rail
1,200 VAC for 1 min
Between different poles
of outputs
Between relay outputs
connected together and
other terminals
connected together
Vibration resistance
Destruction
Shock
resistance Malfunction
--2,200 VAC for 1 min
10 to 55 to 10 Hz, 0.375 mm single amplitude (0.75 mm double amplitude)
300 m/s2
100 m/s2
Electrical
---
100,000 cycles min. rated
load, switching frequency:
1,800 cycles/hour)
Mechanical
---
5,000,000 cycles min.
(switching frequency:
7,200 cycles/hour)
Durability
Ambient operating temperature
−10 to 55°C (no icing or condensation)
Ambient operating humidity
25% to 85%
Terminal tightening torque
0.5 N·m (For the G9SX-NS@-RT (with screw terminals) only)
Weight
Approx. 125 g
Approx. 200 g
Approx. 165 g
*1. When two or more Units are connected by logical AND, the operating time and response time are the sum total of the operating times and
response times, respectively, of all the Units connected by logical AND.
The operating time/response time of the Non-contact Door Switch are included of the time with the D40A/D40Z.
*2. Represents the operating time when the safety input turns ON with all other conditions set.
*3. Represents the operating time when the logical AND input and the Non-contact Door Switch input turn ON with all other conditions set.
*4. This does not include the operating time or response time of G9SX-NS@ that are connected.
*5. This does not include the operating time or response time of internal relays in the G9SX-EX-@.
*6. The failure detection time for 24 V short-circuit failure on the input to Non-contact Door Switches is 35 ms max.
If using the Switch for an application other than as a Door Switch, calculate the safe distance using a failure detection time of 35 ms.
15
G9SX-NS
Logical AND Connection
Item
Model
G9SX-NS202-@
G9SX-NSA222-T03-@
G9SX-EX-@
Number of Units connected per logical
4 Units max.
AND output
---
Total number of Units connected by
logical AND *1
20 Units max.
---
Number of Units connected in series
by logical AND
5 Units max.
---
Max. number of Expansion Units
connected *2
Maximum cable length for logical AND
input
---
5 Units max.
100 m max.
---
Note: See Logical AND Connection Combinations below for details.
*1. The number of G9SX-EX401-@ Expansion Units or G9SX-EX041-T-@ Expansion Units (OFF-delayed Model) not included.
*2. G9SX-EX401-@ Expansion Units and G9SX-EX041-T-@ Expansion Units (OFF-delayed Model) can be mixed.
Logical AND Connection Combinations
1. One logical AND connection output from a G9SX-NS@ Controller
can be logical AND connected to up to four Controllers.
G9SX-NS@
G9SX-NS@
G9SX-NS@
G9SX-NS@
G9SX-NS@
3. The largest possible system configuration contains a total of 20
G9SX-NS@ Controllers, G9SX-AD@ Advanced Units, and
G9SX-BC Basic Units. In this configuration, each Controller or
Advanced Unit can have up to five Expansion Units.
G9SX-@
2. Any G9SX-NS@ Controller that receives a logical AND connection
input can be logically connected to other Controllers on up to five
layers.
G9SX-NS@
G9SX-AD@
or
G9SX-NS@
G9SX-AD@
or
G9SX-NS@
G9SX-AD@
or
G9SX-NS@
G9SX-AD@
or
G9SX-NS@
G9SX-AD@
or
G9SX-NS@
G9SX-AD@
or
G9SX-NS@
G9SX-AD@
or
G9SX-NS@
G9SX-AD@
or
G9SX-NS@
G9SX-AD@
or
G9SX-NS@
G9SX-AD@
or
G9SX-NS@
G9SX-AD@
or
G9SX-NS@
G9SX-AD@
or
G9SX-NS@
G9SX-AD@
or
G9SX-NS@
G9SX-AD@
or
G9SX-NS@
G9SX-AD@
or
G9SX-NS@
G9SX-AD@
or
G9SX-NS@
G9SX-NS@
G9SX-NS@
G9SX-NS@
G9SX-NS@
Note: The G9SX-NS@ in the above diagram can be replaced by the
G9SX-AD@ Advanced Unit.
For details on G9SX-AD@ advanced unit, refer to G9SX
Flexible Safety Unit on your OMRON website.
16
Number of Units connected
in series by logical AND: 5
Units max.
G9SX-AD@
or
G9SX-NS@
Number of Units connected
per logical AND output: 4
Units max.
G9SX-AD@
or
G9SX-NS@
G9SX-AD@
or
G9SX-NS@
Total number of Units
connected by logical AND:
20 Units max.
G9SX-NS
Response Time and Operating Time
1. G9SX-NS@
Logical AND input
Max. response time
Max. operating time
(excluding Expansion Units) *1 (excluding Expansion Units) *2
Non-contact Door
Switch input
Non-contact Door
Switch input
D40A connected: 20 ms max. *3
D40Z connected: 45 ms max. *3
D40A connected: 100 ms max. *4
D40Z connected: 200 ms max. *4
Logical AND input
15 ms
100 ms
*1. The maximum response time is the time it takes the output to switch from ON to OFF after
the input switches from ON to OFF.
*2. The maximum operating time is the time it takes the output to switch from OFF to ON after
the input switches from OFF to ON.
*3. Represents the response time of Non-contact Door Switch (1 to 30 units connected) and
the response time of G9SX-NS added.
*4. Represents the operating time of Non-contact Door Switch (1 to 30 units connected) and
the operating time of G9SX-NS added.
2. G9SX-NSA@
Non-contact Door
Switch input
D4NS
Safety input
Max. response time
Max. operating time
(excluding Expansion Units) *1 (excluding Expansion Units) *2
Non-contact Door
Switch input
Logical AND input
D40A connected: 20 ms max. *3
D40Z connected: 45 ms max. *3
D40A connected: 100 ms max. *4
D40Z connected: 200 ms max. *4
Safety input
15 ms
50 ms
Logical AND input
15 ms
100 ms
*1. The maximum response time is the time it takes the output to switch from ON to OFF after
the input switches from ON to OFF.
*2. The maximum operating time is the time it takes the output to switch from OFF to ON after
the input switches from OFF to ON.
*3. Represents the response time of Non-contact Door Switch (1 to 30 units connected) and
the response time of G9SX-NS added.
*4. Represents the operating time of Non-contact Door Switch (1 to 30 units connected) and
the operating time of G9SX-NS added.
3. Multiple G9SX-NS@/NSA@ Non-contact Door Switch Controllers
When multiple Controllers are logically connected with AND connections, the response time is the sum of the response times given in 1 and 2
above. (It is the same for the operating time.)
D4NS
Case (a)
Safety input
Response Time from When D40A (1) Turns from ON to OFF until Safety Output (2) Turns from
D40A (1)
ON to OFF
(
20 ms
(D40A (1))
+
15 ms
=
(Logical AND
connection (1))
35 ms
Note: 45 ms + 15 ms = 60 ms when D40Z is connected.
Safety output (1)
Logical AND
(1)
D40A (2)
Case (b)
Response Time from When D4NS Turns from ON to OFF until Safety Output (3) Turns from
ON to OFF
15 ms
(D4NS)
+
15 ms
+
(Logical AND
connection (1))
15 ms
=
(Logical AND
connection (2))
45 ms
Safety output (2)
Logical AND
(2)
D40A (3)
Safety output (3)
17
G9SX-NS
Connections
Internal Connection
G9SX-NS202-@ (Non-contact Door Switch Controller)
A1
D1 D2 D3 D4 T31 T32 T33
T41 T42
Non-contact Door Reset/Feedback
Input
Switch control
*2
Logical AND
input
G9SX-NSA222-T03-@
(Non-contact Door Switch Controller)
A1
Power
supply
circuit
*1
A2
Safety output control
S14 S24
*2
Power
supply
circuit
*1
Auxiliary
output control
L1
X1
A2
G9SX-EX401-@/G9SX-EX041-T-@
(Expansion Unit/Expansion Unit OFF-delayed Model)
13 23 33 43
*1
Exp.
sig.
IN
A2
X2
*2
K1
Exp.
sig.
OUT
K2
14 24 34 44
*1. Internal power supply circuit is not isolated.
*2. Relay outputs are isolated.
18
Safety
input 2
fault Non-contact Door
Reset/Feedback Cross
detection
Input
Switch control
input
Safety output control
Auxiliary
output control
Logical
AND input
Expansion Unit
output control
S14 S24 S44 S54 L1
X1
X2
*3
*1. Internal power supply circuit is not isolated.
*2. Logical AND input is isolated.
*3. Outputs S14 to S24 are internally redundant.
Safety
output
Power control
supply
Auxiliary
circuit
output
control
Safety
input 1
X2
*3
A1
T11 T12 T21 T22 T31 T32 T33 Y1 D1 D2 D3 D4 T41 T42
*1. Internal power supply circuit is not isolated.
*2. Logical AND input is isolated.
*3. Outputs S14 to S54 are internally redundant.
G9SX-NS
D40A, D40Z and G9SX-NS@ Wiring
Example: Wiring a Single Switch
D40A
D40Z
Blue
Black
White
Yellow
D1 D2 D3 D4
Auxiliary output load *1
Brown
D40Z-1C@
*2
Blue
Black
Brown
White
D40A-1C@
D1 D2 D3 D4
A2
G9SX-NS202
G9SX-NSA222
G9SX-NS202-@
G9SX-NSA222-T03-@
*1. The auxiliary output load current must be 10 mA max.
*2. When connecting a XS2F series connector with cable to a
connector type, the color of the auxiliary output cable is gray.
Example: Wiring Multiple Switches
Example of auxiliary outputs of the D40Z
Connect Up to 30 Non-contact Door Switches
The auxiliary output of the D40Z supports the input polarities of both
PNP and NPN.
PNP
Yellow
24 VDC
COM
Blue
Brown
Black
White
Blue
Brown
Black
White
Blue
Brown
Black
White
PLC etc.
Gray
IN
Yellow
IN
NPN
PLC etc.
Gray
COM
24 VDC
Note: The auxiliary output load current must be 10 mA max.
Wrong connection may lead to a failure of the auxiliary
output circuit.
D1 D2 D3 D4
G9SX-NS202-@
G9SX-NSA222-T03-@
Wiring of Inputs and Outputs
Cable color of
D40A/D40Z
Signal name
Pin No. of D40A
connector type
Description of operation
+
Brown
1
-
Blue
3
Non-contact Door Switch input
White
2
Inputs signals from the G9SX-NS@.
The Non-contact Door Switch input must be ON as a required condition for
the Non-contact Door Switch output to be ON.
Non-contact Door Switch
output
Black
4
Turns ON and OFF according to actuator detection and the status of the
Non-contact Door Switch input.
Yellow
---
Gray
5
Non-contact Door Switch
power supply input
Auxiliary output
Supplies power to the D40A or D40Z.
Connect to the D3 and D4 terminal of the G9SX-NS@.
Turns ON when actuator is detected.
When a fault is detected, turns into OFF state regardless of actuator status. *3
Note: 1. When connecting a XS2F series connector with cable to a D40A connector type, the cable color of the auxiliary output is gray.
2. For details, refer to the data sheet of each Non-contact Door Switch.
*3. Only D40Z turns into OFF state when a fault is detected by the actuator.
4
3
5
1
2
Pin arrangement of D40A connector type
19
G9SX-NS
Wiring of Inputs and Outputs
G9SX-NS202-@
Signal name
Power supply
input
Terminal
name
A1, A2
Non-contact
D1, D2,
Door Switch input D3, D4
Description of operation
Connect the power source to the A1 and A2
terminals.
Wiring
Connect the power supply plus (24 VDC) to the A1
terminal.
Connect the power supply minus (GND) to the A2
terminal.
All Non-contact Door Switch inputs connected to the
G9SX-NS@ must be ON as a required condition for
the safety outputs to be ON. Otherwise the safety
outputs cannot be in the ON state.
White
D1
Black
Brown
D2
Blue
D3
D4
Feedback loop
To set the safety outputs in the ON state, the ON state
signal must be input to T33. Otherwise the safety
Auto reset
outputs cannot be in the ON state.
Feedback/reset
input
Logical AND
connection input
T31, T32,
T33
T41, T42
To set the safety outputs in the ON state, the signal
input to T32 must change from the OFF state to the
ON state, and then to the OFF state. Otherwise the
safety outputs cannot be in the ON state.
A logical AND connection means that one unit (Unit
A) outputs a safety signal “a” to a subsequent unit
(Unit B) and Unit B calculates the logical AND (i.e.,
outputs the AND) of the signal “a” and safety signal
“b”, which is input to Unit B.
Thereby the logic of the safety output of Unit B is
(AND). (An AND of inputs “a” and “b” is output.)
To set the safety outputs of the subsequent Unit in the
ON state, its logical AND connection preset switch
must be set to AND (enable) and the high signal must
be input to T41 of the subsequent unit.
+24 V
T31
T32
T33
Feedback loop
Reset
Switch
Manual reset
KM +24 V
T31
T32
T33
Input a
Unit A
G9SX-NS/NSA
Output (a) L1 A2
Unit B
Logical AND connection sig.
(1st layer)
Input b
T41 T42
G9SX-NS/NSA
Output (a&b) L1 A2
Next unit (4 unit max.)
T41 T42
G9SX-NS/NSA
Logical AND connection sig.
(2nd layer)
Next unit (4 unit max.)
T41 T42
G9SX-NS/NSA
L1 A2
Next unit (5 layers max.)
20
KM
Instantaneous
safety output
S14, S24
Turns ON/OFF according to the state of the safety
inputs, Non-contact Door Switch inputs, feedback/
reset inputs, and logical AND connection inputs.
Keep these outputs open when not used.
Logical AND
connection
output
L1
Outputs a signal of the same logic and at the same
time as the instantaneous safety outputs.
Keep these outputs open when not used.
Auxiliary monitor
output
X1
Outputs a signal of the same logic and at the same
time as the instantaneous safety outputs.
Keep these outputs open when not used.
Auxiliary error
output
X2
Outputs when the error indicator is lit or flashing.
Keep these outputs open when not used.
G9SX-NS
G9SX-NSA222-T03-@
Signal name
Power supply
input
Terminal
name
A1, A2
Description of operation
Connect the power source to the A1 and A2
terminals.
Wiring
Connect the power supply plus (24 VDC) to the A1 terminal.
Connect the power supply minus (GND) to the A2 terminal.
+24 V
Using safety input 1 system
Safety input 1
T11 T12 T21 T22
To set the safety outputs in the ON state, the high
state signals must be input to both safety input 1
and safety input 2. Otherwise the safety outputs
cannot be in the ON state.
Safety input 2
Non-contact
Door Switch
input
+24 V
T11, T12
T21, T22
D1, D2,
D3, D4
Feedback/reset T31, T32,
input
T33
T11 T12 T21 T22
Y1
Using safety input 2 system
(with short-circuit monitoring
between systems)
T11 T12 T21 T22
Y1
White
D1
NC
Black
Brown
D2
Blue
D3
D4
Feedback loop
Auto reset
+24 V
T31
T32
KM
T33
Feedback loop
Reset
Switch
KM +24 V
T31
T32
T33
Input a
Unit A
Logical AND
T41, T42
connection input
+24 V
To set the safety outputs in the ON state, the signal
input to T32 must change from the OFF state to the
Manual reset
ON state, and then to the OFF state. Otherwise the
safety outputs cannot be in the ON state.
A logical AND connection means that one unit (Unit
A) outputs a safety signal “a” to a subsequent unit
(Unit B) and Unit B calculates the logical AND (i.e.,
outputs the AND) of the signal “a” and safety signal
“b”, which is input to Unit B.
Thereby the logic of the safety output “b” is output.)
To set the safety outputs of the subsequent Unit in
the ON state, its logical AND connection preset
switch must be set to AND (enable) and the high
signal must be input to T41 of the subsequent unit.
+24 V
Using safety input 2 system
(without short-circuit
monitoring between
systems)
All Non-contact Door Switch inputs connected to
the G9SX-NS must be ON as a required condition
for the safety outputs to be ON.
Otherwise the safety outputs cannot be in the ON
state.
To set the safety outputs in the ON state, the ON
state signal must be input to T33.
Otherwise the safety outputs cannot be in the ON
state.
+24 V
Y1
G9SX-NS/NSA
Output (a) L1 A2
Unit B
Logical AND connection sig.
(1st layer)
Input b
T41 T42
G9SX-NS/NSA
Output (a&b) L1 A2
Next unit (4 unit max.)
T41 T42
G9SX-NS/NSA
Logical AND connection sig.
(2nd layer)
Next unit (4 unit max.)
T41 T42
G9SX-NS/NSA
L1 A2
Next unit (5 layers max.)
Y1
Selects the mode for the failure detecting (cross
Whether Y1 is connected depends on whether the T11 and
fault detecting) function for the safety inputs of
T21 terminals are used.
G9SX corresponding to the connection of the cross
Refer to wiring information for safety inputs 1 and 2.
fault detection input.
S14, S24
Turns ON/OFF according to the state of the safety
inputs, feedback/reset inputs, and logical AND
connection inputs.
During OFF-delay state, the Instantaneous safety
outputs are not able to turn ON.
OFF-delayed
safety output
S44, S54
OFF-delayed safety outputs.
The OFF-delay time is set by the OFF-delay preset
switch.
Keep these outputs open when not used.
When the delay time is set to zero, these outputs
can be used as non-delay outputs.
Logical AND
connection
output
L1
Outputs a signal of the same logic and at the same
Keep these outputs open when not used.
time as the instantaneous safety outputs.
Auxiliary
monitor output
X1
Outputs a signal of the same logic and at the same
Keep these outputs open when not used.
time as the instantaneous safety outputs.
Auxiliary error
output
X2
Outputs when the error indicator is lit or flashing.
Cross fault
detection input
Instantaneous
safety output
Keep these outputs open when not used.
Keep these outputs open when not used.
21
G9SX-NS
Dimensions and Terminal Arrangement
(Unit: mm)
Non-contact Door Switch Controller
(6) (See note 2.)
G9SX-NS202-@
Terminal arrangement
T31 T32 T33 D3
D1 D2 X1 A1
T31 T32 T33 D3
D1 D2 X1 A1
G9SX-NS202
24VDC
PWR
FB
AND
NS
EI
100 max.
PWR
FB
AND
NS
ERR
EI
ERR
No.
T41 T42 X2
S14 S24 L1
A2
D4
T41 T42 X2 A2
S14 S24 L1 D4
23 max.
115 max.
(22.5) *
(6) (See note 2.)
Note: 1. Above outline drawing is for models with spring-cage terminals (-RC).
2. For models with spring-cage terminals (-RC) only.
* Typical dimension
Non-contact Door Switch Controller
G9SX-NSA222-T03-@
(6) (See note 2.)
Terminal arrangement
T31 T32 T33 D1 D2 D3
T11 T12 Y1 X1 X2 A1
T31 T32 T33 D1
T11 T12 Y1 X1
D2
X2
D3
A1
G9SX-NSA222-T03
24VDC
PWR
FB
T1
T2
AND
NS
EI
ED
0.8 0.91.0
0.7
1.2
0.6
1.4
0.5
1.8
0.4
2.0
0.3
2.5
0.2
0 3.0
OFF-DELAY
100 max.
PWR
FB
T1
T2
AND
NS
EI
ED
ERR
ERR
No.
T21 T22
T41 T42
S14 S24 S44 S54 L1
A2
D4
T21 T22
T41 T42 A2
S14 S24 S44 S54 L1 D4
35.5 max.
(35) *
(10)
115 max.
(6) (See note 2.)
Note: 1. Above outline drawing is for models with spring-cage terminals (-RC).
2. For models with spring-cage terminals (-RC) only.
* Typical dimension
Expansion Unit
G9SX-EX401-@
Expansion Unit (OFF-delayed Model)
G9SX-EX041-T-@
Terminal arrangement
G9SX-EX401-@ G9SX-EX041-T-@
(Expansion Unit) (Expansion Unit
with OFF Delay)
(6) (See note 2.)
13 23 33 43
13 23 33 43
PWR
PWR
EI
ED
ERR
ERR
100 max.
23 max.
(22.5) *
115 max.
A1 X2 A2
A1 X2 A2
14 24 34 44
14 24 34 44
(6) (See note 2.)
Note: 1. Above outline drawing is for models with spring-cage terminals (-RC).
2. For models with spring-cage terminals (-RC) only.
* Typical dimension
22
G9SX-NS
Operation
Functions
Logical AND Connection
Connecting Expansion Units
A logical AND connection means that the G9SX outputs a safety
signal “a” to another G9SX, and that G9SX creates the logical AND of
safety signal “a” and safety signal “b.” The safety output of the
G9SX-NSA222-T03-@ with the logical AND connection shown in the
following diagram is “a” AND “b.”
a
b
G9SX-NS202-@
G9SX-NSA222-T03-@
a
• The G9SX-EX and G9SX-EX-T Expansion Units can be connected
to a G9SX-NSA222-T3-@ Non-contact Door Switch Controller to
increase the number of safety outputs. (They cannot be connected
to a G9SX-NS202-@.)
• A maximum of five Expansion Units can be connected to one
G9SX-NSA222-T03-@. This may be a combination of G9SX-EX
instantaneous models and G9SX-EX-T OFF-delayed models.
• Remove the terminating connector from the receptacle on
G9SX-NSA222-T03-@ and insert the Expansion Unit cable
connector into the receptacle. Insert the terminating connector into
the receptacle on the Expansion Unit at the very end (rightmost).
• When Expansion Units are connected to a Controller, make sure
that power is supplied to every Expansion Unit. (Refer to the
following diagram for actual Expansion Unit connection.)
a (AND) b
This is illustrated using the application in the following diagram as an
example. The equipment here has two hazards identified as Robot 1
and Robot 2, and it is equipped with Non-contact Door Switches and
an emergency stop button as safety measures. If the door to Robot 2
is opened, only Robot 2 is stopped (i.e., a partial stop). If the door to
Robot 1 is opened or the emergency stop button is pressed, both
Robot 1 and Robot 2 stop (i.e., a complete stop).
The actual situation using a G9SX for this application is shown in this
example.
Terminating
connector
G9SX-NSA222-T03-@
Expansion Unit
Note: The logical AND setting on the G9SX-NS202-@ must be set to
AND (enabled).
Non-contact Door Switch 2
Non-contact Door Switch 1
Emergency stop button
Robot 2
Robot 1
Emergency
stop switch * D40A
D40A
G9SXNSA222-T03-@
G9SXNS202-@
Robot 1
Robot 2
* A manual reset is required when an emergency stop is used.
23
G9SX-NS
Setting Procedure
1. Cross Fault Detection (G9SX-NSA222-T03-@)
Set the cross fault detection mode for safety inputs by shorting Y1
to 24 V or leaving it open.
When cross fault detection is set to ON, short-circuit failures are
detected between safety inputs T11-T12 and T21-22. When a
cross fault is detected, the following will occur.
(1) The safety outputs and logical AND outputs lock out.
(2) The LED error indicator is lit.
(3) The error output (auxiliary output) turns ON.
3. Setting Logical AND Connection (G9SX-NS202-@/
NSA222-T03-@)
When connecting two or more Non-contact Door Switch
Controllers by logical AND connection, set the logical AND
connection preset switch on the Controller that is on the input side
(Unit B in the following diagram) to AND. The default setting of the
logical AND connection preset switch is set to OFF.
Back
Unit A
Cross fault
detection
Wiring
AND
L1
A2
T41
T42
OFF
+24 V
Using safety input 1
system
+24 V
Switch
AND
OFF
T11
OFF
T12
T21
+24 V
T22
Unit B
Y1
+24 V
Note: A setting error will occur and Unit B will lock out if the logical
AND setting switch on the Unit B is set to OFF.
+24 V
T11
T12
T21
T22
Y1
T11
T12
T21
T22
Y1
Using safety input 2
system
ON
4. Setting the OFF-delay Time (G9SX-NSA222-T03-@)
The OFF-delay preset time on G9SX-NSA222-T03-@ is set from
the OFF-delay time preset switch (1 each on the front and back of
the Unit).
Normal operation will only occur if both switches are identically set.
An error will occur if the switches are not identically set. The default
setting of the OFF-delay time preset switch is set to 0 s.
Front
Back
2. Reset Mode (G9SX-NS202-@/NSA222-T03-@)
Set the reset mode using feedback/reset input terminals T31, T32,
and T33.
Auto reset mode is selected when terminal T32 is shorted to 24 V
and manual reset mode is selected when terminal T33 is shorted
to 24 V.
Auto reset mode
Manual reset mode
KM1
KM2
+24 V
T31
T32
Reset
switch
KM1
Refer to the following illustration for details on setting switch positions.
KM2
G9SX-NSA222-T03-@
KM3
KM3
KM4
KM4
KM5
KM5
T33
Switch
Switch
T31
T32
+24 V
T33
0.7
0.6
0.5
0.4
0.3
0.2
0.8 0.91.0
1.2
1.4
1.8
2.0
2.5
0 3.0
OFF-DELAY
Example 1: 0-second
24
0.7
0.6
0.5
0.4
0.3
0.2
Notch
0.8 0.91.0
1.2
1.4
1.8
2.0
2.5
0 3.0
OFF-DELAY
Example 2: 0.8-second
G9SX-NS
LED Indicators
G9SX-NS202
G9SXNSA222
G9SX-EX
G9SX-EX-T
Power supply
indicator
❍
❍
❍
❍
Lights while power is supplied.
Orange
Safety input #1
indicator
---
❍
---
---
Lights while a high signal is input to T12.
Flashes when an error relating to safety
input #1 occurs.
T2
Orange
Safety input #2
indicator
---
❍
---
---
Lights while a high signal is input to T22.
Flashes when an error relating to safety
input #2 occurs.
NS
Orange
Non-contact Door
Switch input
indicator
❍
❍
---
---
Lights when the Non-contact Door Switch
input turns ON. Flashes when an error
relating to the Non-contact Door Switch
input occurs.
---
Lights in the following cases:
With automatic reset while a high signal is
input to T33.
With manual reset while a high signal is
input to T32.
Flashes when an error relating to feedback/
reset input occurs.
Marking
Color
PWR
Green
T1
FB
Name
Orange
Feedback/reset
input indicator
❍
❍
---
Function
AND
Orange
Logical AND input
indicator
❍
❍
---
---
Lights while a high signal is input to T41.
Flashes when an error relating to logical
AND connection input occurs.
EI
Orange
Instantaneous
safety output
indicator
❍
❍
❍
---
Lights while the Instantaneous safety
outputs (S14, S24, S34) are in the ON state.
Flashes when an error relating to the
instantaneous safety output occurs.
ED
Orange
OFF-delayed
safety output
indicator
---
❍
---
❍
Lights while OFF-delayed safety outputs
(S44, S54) are in the ON-state.
Flashes when an error relating to
OFF-delayed safety output occurs.
ERR
Red
Error indicator
❍
❍
❍
❍
Lights or flashes when an error occurs.
Reference
---
*
* Refer to “Fault Detection” on the next page for details.
Settings Indication (at Power ON)
Settings for the G9SX can be checked by the orange indicators for approx. 3 seconds after the power is turned ON. During this settings indication
period, the ERR indicator will light, however the auxiliary error output will remain OFF.
Indicator
Item
Setting
position
T1
Cross fault
detection
mode
Y1 terminal
FB
Reset mode
T32 or T33
terminal
AND
Logical AND
connection
input mode
Logical AND
connection
preset switch
Indicator
status
Lit
Not lit
Lit
Not lit
Setting mode
Detection mode
Non-detection mode
Setting status
Y1 = open
Y1 = 24 VDC
Manual reset mode
T33 = 24 VDC
Auto reset mode
T32 = 24 VDC
Lit
Enable logical AND input
AND
Not lit
Disable logical AND input
OFF
25
G9SX-NS
Fault Detection
When the Non-contact Door Switch Controller detects a fault, the ERR indicator and/or other indicators light up or flash to inform the user about
the fault.
Check and take necessary measures referring to the following table, and then re-supply power to the Non-contact Door Switch Controller.
(G9SX-NS202-@/NSA222-T03-@)
ERR
indicator
Other
indicator
---
Flashes
T1 flashes
T2 flashes
NS
flashes
Fault
Lights
1. Excessive electromagnetic
disturbance
2. Failure of the internal circuit
Fault involved with safety
input 1
1. Error in the wiring of safety input 1
1. Check the wiring to T11 and T12.
2. Incorrect setting of cross fault
2. Check the wiring to Y1.
detection input
3. Failure of the circuit of safety input 1 3. Replace with a new product.
Fault involved with safety
input 2
1. Error in the wiring of safety input 2
1. Check the wiring to T21 and T22.
2. Incorrect setting of cross fault
2. Check the wiring to Y1.
detection input
3. Failure of the circuit of safety input 2 3. Replace with a new product.
1. Check the wiring to D1 and D2.
Fault involved with
Non-contact Door Switch
input
1. Error in the wiring of Non-contact
Door Switch input
2. Error in the wiring of Non-contact
Door Switch inputs in series
connections.
3. Failure of the internal circuits of
Non-contact Door Switch inputs
4. Failure of the Non-contact Door
Switch
1. Error in the wiring of feedback/reset
input.
2. Failure of the circuit of feedback/
reset input
1. Check the wiring to T31, T32 and T33.
1. Improper feedback signals from
Expansion Unit
2. Abnormal supply voltage to
Expansion Unit
1. Check the connecting cable of Expansion Unit
and the connection of the termination socket.
2. Check the supply voltage to Expansion Unit.
Fault in Expansion Unit
3. Failure of the circuit of safety relay
contact outputs
Fault involved with
instantaneous safety
outputs, logical AND
EI flashes connection outputs, or
auxiliary monitor output
ED
flashes
26
Check points and measures to take
Fault due to
electromagnetic
disturbance or of internal
circuits.
Fault involved with
feedback/reset inputs
FB
flashes
Expected causes of the fault
Fault involved with
OFF-delayed safety
outputs
1. Check the disturbance level around the G9SX
and the related system.
2. Replace with a new product.
2. Check the wiring to the D40A.
3. Replace with a new product.
4. Replace with a new D40A.
2. Replace with a new product.
Note: Make sure that all Expansion Units' PWR
indicators are lit.
3. Replace with a new product.
1. Error in the wiring of instantaneous
safety outputs
2. Failure of the circuit of instantaneous
safety outputs
3. Error in the wiring of the logical AND
connection output
4. Failure of the circuit of the logical
AND connection output
5. Error in the wiring of the auxiliary
monitor output
6. Impermissible high ambient
temperature
1. Check the wiring to S14 and S24.
1. Error in the wiring of OFF-delayed
safety relay contact outputs
2. Incorrect set values for OFF-delay
time
3. Failure of the circuit of OFF-delayed
safety relay contact outputs
4. Impermissible high ambient
temperature
1. Check the wiring to S44 and S54.
2. Replace with a new product.
3. Check the wiring to L1.
4. Replace with a new product.
5. Check the wiring to X1.
6. Check the ambient temperature and spacing
around the G9SX.
2. Check the settings of the OFF-delay time setting
switch.
3. Replace with a new product.
4. Check the ambient temperature and spacing
around the G9SX.
G9SX-NS
ERR
indicator
Other
indicator
Fault
Expected causes of the fault
1. Error in the wiring of the logical AND
connection input
AND
flashes
Fault involved with logical
AND connection input
2. Incorrect setting for the logical AND
connection input
3. Failure of the circuit of the logical
AND connection input
Lights
Supply voltage outside the 1. Supply voltage outside the rated
All
indicators rated value
value
except
PWR flash
Check points and measures to take
1. Check the wiring to T41 and T42.
Note: 1. Make sure that the wiring length for the
T41, T42 terminal is 100 meters or less.
2. Make sure that the logical AND
connection signal is branched for 4 units
or fewer.
2. Confirm the set value of the logical AND
connection preset switch.
3. Replace with a new product.
1. Check the supply voltage to the Units.
When indicators other than the ERR indicator flash, check and take necessary actions referring to the following table.
ERR
Other
indicator indicators
T1
Off
T2
Fault
Expected cause of the fault
The input status between input 1 and
Mismatch between input 1 input 2 is different, due to contact failure
and input 2.
or a short circuit of safety input
flash
device(s) or a wiring fault.
Check points and measures to take
Check the wiring from safety input devices to the
G9SX. Or check the input sequence of safety input
devices. After removing the fault, turn both safety
inputs 1 and 2 to the OFF state.
(Expansion Unit)
ERR
Other
indicator indicators
--Lights
Fault
Fault involved with safety
relay outputs of
Expansion Units
Expected cause of the fault
1. Welding of relay contacts
2. Failure of the internal circuit
Check points and measures to take
Replace with a new product.
27
G9SX-NS
Application Examples
Example 1: Connection with D40A
Highest achievable
PL/safety category
PLd/3 equivalent
Model
Stop category
Reset
0
Manual
Emergency Stop Switch A165E/A22E
Non-contact Door Switch D40A
Non-contact Door Switch Controller G9SX-NSA222-T03-@
Note: The PL evaluation result on this connection example applies to safety functions related to the D40A Non-Contact Door Switch. The above
PL is only the evaluation result of the example. The PL must be evaluated in an actual application by the customer after confirming the usage
conditions.
● Application Overview
• The power supply to the motor M is turned OFF immediately when the emergency stop switch S1 is pressed.
• The power supply to the motor M is turned OFF immediately when the S2 detects that the guard is opened.
• The power supply to the motor M is kept OFF until the reset switch S3 is pressed while the guard is closed and the emergency stop switch S1
is released.
Feedback Loop
KM1
Guard
S2
Actuator
+24 V
Emergency
Stop Switch
Non-contact
Door Switch
KM2
S3
S1
KM1
+24 V
Y1
D1
D2
D3
blue
Black
NC
T11 T12 T21 T22 T31 T32 T33
Brown
NC
A1
White
KM2
D4
NC
NC
AND
T41 T42
OFF
M
G9SX-NSA222-T03-@
+24 V
Control circuit
A2
S14 S24
S44 S54
L1
X1
X2
Timing chart
KM1 KM2
PLC etc.
Emergency stop
switch operation
Emergency stop switch S1
Guard opens
S1: Emergency Stop Switch
S2: Non-contact Door Switch (D40A)
S3: Reset Switch
KM1, KM2: Magnetic contactor
M: Motor
Non-contact Door Switch S2
Reset switch S3
G9SX-NSA S14, S24
KM1, KM2 N.O. contact
Rotation of motor M
Note: For details on Non-contact Door Switch wiring, refer to page 19 or to the Instruction Sheet.
28
Guard closes
G9SX-NS
Example 2: Connection with D40A
Highest achievable
PL/safety category
Model
Stop category
Emergency Stop Switch A165E/A22E
Non-contact Door Switch D40A
Flexible Safety Unit G9SX-BC202-@
Non-contact Door Switch Controller G9SX-NS202-@
PLd/3 equivalent
Reset
Emergency Stop Switch: Manual
Non-contact Door Switch: Auto
0
Note: The PL evaluation result on this connection example applies to safety functions related to the D40A Non-Contact Door Switch. The above
PL is only the evaluation result of the example. The PL must be evaluated in an actual application by the customer after confirming the usage
conditions.
● Application Overview
•
•
•
•
The power supply to the motor M1 and M2 is turned OFF immediately when the emergency stop switch S1 is pressed.
The power supply to the Motor M1 is kept OFF until the reset switch S2 is pressed while the emergency stop switch S1 is released.
The power supply to the motor M2 is turned OFF immediately when the S3 detects that the guard is opened.
The power supply to the motor M2 is kept OFF until the reset switch S1 is pressed while the guard is closed and the emergency stop switch S1
is released.
Feedback Loop
Emergency
Stop Switch
KM1
S1
KM2
+24V
S2
KM1
KM2
A1
T11 T12 T21 T22 T31 T32 T33 Y1
M1
G9SX-BC202-@ (Unit 1)
+24 V
Control circuit
A2
L1
S14 S24
L2
X1
KM1 KM2
S1: Emergency Stop Switch
S2: Reset Switch
KM1, KM2: Magnetic contactor
M1: Motor
X2
PLC etc.
Actuator
Non-contact
Door Switch
S3
Guard
Timing chart
Feedback Loop
Emergency stop
switch operation
G9SX-BC202-@ (Unit 1)
KM3
Emergency stop switch S1
KM4
A1
D1 D2 D3
Unit 1 S14, S24
+24 V
Blue
Brown
Black
+24 V
White
Reset switch S2
AND
D4 T31 T32 T33
T41
T42
KM1, KM2 N.O. contact
OFF
Logical AND output L1
G9SX-NS202-@ (Unit 2)
KM3
Control circuit
Rotation of motor M1
KM4
G9SX-NS202-@ (Unit 2)
M2
A2
S14 S24
KM3 KM4
L1
X1
Logical AND input T41
Guard opens
X2
Guard closes
Non-contact Door Switch S3
PLC etc.
Unit 2 S14, S24
S3: Non-contact Door Switch (D40A)
KM3, KM4: Magnetic contactor
M2: Motor
KM3, KM4 N.O. contact
Rotation of motor M2
Note: For details on Non-contact Door Switch wiring, refer to page 19 or to the Instruction Sheet.
29
G9SX-NS
Example 1: Connection with D40Z
Highest achievable
PL/safety category
PLe/4 equivalent
Model
Stop category
Reset
0
Manual
Emergency Stop Switch A165E/A22E
Non-contact Door Switch D40Z
Non-contact Door Switch Controller G9SX-NSA222-T03-@
Note: The above PL is only the evaluation result of the example. The PL must be evaluated in an actual application by the customer after confirming
the usage conditions.
● Application Overview
• The power supply to the motor M1 is turned OFF immediately when the emergency stop switch S1 is pressed.
• The power supply to the motor M1 is turned OFF immediately when the S2 detects that the guard is opened.
• The power supply to the motor M1 is kept OFF until the reset switch S3 is pressed while the guard is closed and the emergency stop switch S1
is released.
Feedback Loop
Guard
KM1
Actuator
S1
Non-contact
Door Switch
S2
KM2
Emergency
Stop Switch
A1
T11 T12 T21 T22
Y1
T31 T32 T33
D1
D2
D3
Blue
Brown
Black
+24 V
NC
White
S3
D4
G9SX-NSA222-T03-@
24 VDC
S14 S24
S44 S54
NC
T41 T42
AND
Control circuit
A2
NC
L1
X1
OFF
X2
PLC etc.
KM1 KM2
Timing chart
KM1
Emergency stop
switch operation
KM2
Emergency stop switch S1
Guard opens
Non-contact Door Switch S2
M1
S1: Emergency Stop Switch
S2: Non-contact Door Switch (D40Z)
S3: Reset Switch
KM1, KM2: Magnetic contactor
M1: Motor
Reset switch S3
G9SX-NSA S14, S24
KM1, KM2 N.O. contact
Rotation of motor M
Note: For details on Non-contact Door Switch wiring, refer to page 19 or to the Instruction Sheet.
30
Guard closes
G9SX-NS
Example 2: Connection with D40Z
Highest achievable
PL/safety category
Model
Stop category
Emergency Stop Switch A165E/A22E
Non-contact Door Switch D40Z
Flexible Safety Unit G9SX-BC202-@
Non-contact Door Switch Controller G9SX-NS202-@
PLe/4 equivalent
Reset
Emergency Stop Switch: Manual
Non-contact Door Switch: Auto
0
Note: The above PL is only the evaluation result of the example. The PL must be evaluated in an actual application by the customer after confirming
the usage conditions.
● Application Overview
•
•
•
•
The power supply to the motor M1 and M2 is turned OFF immediately when the emergency stop switch S1 is pressed.
The power supply to the Motor M1 is kept OFF until the reset switch S2 is pressed while the emergency stop switch S1 is released.
The power supply to the motor M2 is turned OFF immediately when the S3 detects that the guard is opened.
The power supply to the motor M2 is kept OFF until the reset switch S1 is pressed while the guard is closed and the emergency stop switch S1
is released.
Emergency
Stop Switch
Feedback Loop
KM1
S1
KM2
S2
+24 V
NC
A1 T11 T12 T21 T22 T31 T32 T33 Y1
KM1
G9SX-BC202-@ (Unit 1)
KM2
+24 V
Control circuit
M1
A2
S14 S24
L1 L2
X1 X2
S1: Emergency Stop Switch
S2: Reset Switch
KM1, KM2: Magnetic contactor
M1: Motor
PLC etc.
KM1 KM2
Feedback Loop
Timing chart
S3
KM3
Non-contact
Door Switch
Actuator
Guard
Emergency stop
switch operation
KM4
G9SX-BC202-@ (Unit 1)
Emergency stop switch S1
Reset switch S2
A1
D1
D2
D3
Blue
Brown
Black
White
Unit 1 S14, S24
+24 V
D4
T31 T32 T33
KM1, KM2 N.O. contact
T41 T42
G9SX-NS202-@ (Unit 2)
AND
Control circuit
Logical AND output L1
Rotation of motor M1
OFF
G9SX-NS202-@ (Unit 2)
A2
S14 S24
L1
X1
X2
Logical AND input T41
Guard opens
24 VDC
PLC etc.
KM3 KM4
Guard closes
KM3
Non-contact Door Switch S3
KM4
Unit 2 S14, S24
M2
S3: Non-contact Door Switch (D40Z)
KM3, KM4: Magnetic contactor
M2: Motor
KM3, KM4 N.O. contact
Rotation of motor M2
Note: For details on Non-contact Door Switch wiring, refer to page 19 or to the Instruction Sheet.
31
D40A/G9SX-NS
Safety Precautions
Be sure to read the Common Precautions for Safety Warning at the following URL: http://www.ia.omron.com/.
Indication and Meaning for Safe Use
WARNING
Indicates a potentially hazardous situation
which, if not avoided, will result in minor
or moderate injury, or may result in
serious injury or death. Additionally there
may be significant property damage.
Precautions
for Safe Use
Supplementary comments on what to do
or avoid doing, to use the product safely.
Precautions
for Correct
Use
Supplementary comments on what to do
or avoid doing, to prevent failure to
operate, or undesirable effect on product
performance.
!WARNING
Serious injury may possibly occur due to breakdown of
safety outputs.
Do not connect loads beyond the rated value to the
safety outputs.
Serious injury may possibly occur due to loss of required
safety functions.
Wire the D40A and G9SX-NS properly so that supply
voltages or voltages for loads do NOT touch the safety
outputs accidentally.
Serious injury may possibly occur due to damage to
safety outputs.
Provide protective circuits against counter-electromotive
force if inductive loads are connected to safety outputs.
Serious injury may possibly occur due to loss of safety
functions.
Use appropriate devices referring to the information
provided below.
The machine may start operating and may result in
serious injury or death.
Do not put the actuator close to the switch when the door
is open.
Control device
Requirements
Emergency stop
switch
Use approved device with direct opening
mechanism complying with IEC/EN 60947-5-1.
Use approved device with direct opening
Safety door switch, mechanism complying with IEC/EN 60947-5-1
Safety limit switch and capable of switching micro loads of 24 VDC,
5 mA.
32
Non-contact
Door Switch
The G9SX-NS must be used with D40A
Non-contact Door Switches.
Relay with
forcibly guided
contacts
Use approved devices with forcibly guided
contacts complying with IEC 61810-3 (EN
50205).
For feedback, use devices with contacts
capable of switching micro loads of 24 VDC,
5 mA.
Contactor
Use approved devices complying with IEC/EN
60947-4-1 for auxiliary contact linked with power
contact (mirror contact).
For feedback, use devices with contacts
capable of switching micro loads of 24 VDC,
5 mA.
Other devices
Evaluate whether devices used are appropriate
to satisfy the requirements of the safety
category level.
Precautions for Safe Use
1. Disconnect the G9SX-NS from the power supply when wiring the
D40A.
1. Turn OFF the load power supply before wiring. Failure to do so
may cause electric shock.
2. Devices connected to the product may operate unexpectedly.
2. Do not operate the product in atmospheres containing flammable
or explosive gas. Arcs or heating of relays during switching may
cause fire or explosion.
3. Wire conductors correctly and verify the operation of the product
before using the system in which the product is incorporated.
Incorrect wiring may lead to loss of safety functions.
4. Do not dismantle, repair, or modify the product. Doing so may lead
to loss of safety functions.
5. Auxiliary monitoring outputs are NOT safety outputs. Do not use
auxiliary monitoring outputs as safety outputs. Such incorrect use
will cause loss of safety function of D40A and peripheral devices.
6. After installing the D40A, qualified personnel must confirm the
installation, and must conduct test operations and maintenance.
The qualified personnel must be qualified and authorized to
secure safety at each phases of design, installation, running,
maintenance, and disposal of the system.
7. A qualified person in charge, who is familiar with the machine in
which the D40A is to be installed, must conduct and verify the
installation.
8. Be sure to inspect the D40A daily and every 6 months. Otherwise,
serious injury may possibly occur due to system malfunctions.
9. Connect the D40A to only appropriate components or devices
complying with relevant safety standards corresponding to the
required level of safety category. Conformity to requirements of
the safety category must be determined for the entire system. It is
recommended to consult an authorized certification body
regarding assessment of conformity to the required safety level.
10. Use the G9SX within an enclosure with a IP54 degree of
protection or higher according to IEC/EN 60529.
11. Do not apply DC voltages exceeding the rated voltages, nor any
AC voltages to G9SX-NS@. Do not connect to DC distribution
network.
12. Use a DC supply satisfying the requirements given below to
prevent electric shock.
• A DC power supply with double or reinforced insulation, for
example, according to IEC/EN 60950 or EN 50178, or a
transformer according to IEC/EN 61558.
• A DC supply satisfying the requirements for class 2 circuits or
limited voltage/current circuits stated in UL 508.
13. Properly apply the specified voltages to the inputs. Applying
inappropriate voltages may cause the product to fail to perform its
specified function, which could lead to the loss of safety functions
or damages to the product.
14. Auxiliary error outputs and auxiliary monitoring outputs are NOT
safety outputs. Do not use these outputs as safety outputs.
Such incorrect use will cause loss of safety functions of the G9SX
and its relevant system. Also logical AND connection outputs can
only be used for logical AND connections with the G9SX-@.
15. After installing the G9SX-NS@, qualified personnel must confirm
the installation, and must conduct test operations and
maintenance. The qualified personnel must be qualified and
authorized to secure safety at each phases of design, installation,
running, maintenance, and disposal of system.
16. A qualified person in charge, who is familiar with the machine in
which G9SX-NS@ is to be installed, must conduct and verify the
installation.
17. Perform daily and 6-month inspections for the G9SX-NS@.
Otherwise, the system may fail to work properly, resulting in
serious injury.
D40A/G9SX-NS
18. Connect to the G9SX-NS@ only appropriate components or
devices complying with relevant safety standards corresponding
to the required level of safety category.
Conformity to requirements of safety category must be
determined as an entire system. It is recommended to consult an
authorized certification body regarding assessment of conformity
to the required safety level.
19. OMRON is not responsible for conformity with any safety
standards covering the customer's entire system.
20. Be careful not to have your fingers caught when mounting terminal
blocks.
21. The service life will depend on the switching conditions. Be sure
to check the actual operating conditions using the actual devices,
and make sure that the number of switching operations will not
cause performance problems.
Precautions for Correct Use
1. Handle with Care.
Do not drop the product or expose it to excessive vibration or
mechanical shock. The product may be damaged and may not
function properly.
2. Storage and Operating Conditions
Do not store or use the products under the following conditions.
1. In direct sunlight
2. At ambient temperatures not between −10 and 55°C
3. At relative humidity not between 25% and 85% or under
temperature changes that could causes condensation
4. In corrosive or combustible gases
5 Where subject to vibration or mechanical shock beyond the
rated values
6. Where subject to contact with water, oil, or chemicals
7. In an atmosphere containing excessive dust, saline, or metal
powder
8. Where iron filings or powder may fall on the product
3. D40A is a class A product.In residential areas D40A may cause
radio interference, in which case the user may be required to take
adequate measures to reduce interference.
4. Always use the D40A/G9SX-NS together with the special actuator
and a G9X-NS@ Controller. If you use any other OMRON Safety
Controller, confirm applicability in the manual for the Safety
Controller.
5. Use cables with a length of less than 100 m total to connect D40A
Switches. The supply voltage to D40A may decrease by the
voltage drop depending on the cable or the wiring configuration.
Check the power-supply voltage is in the rated range.
Total wiring length 100 m max.
D1 D2 D3 D4
G9SX-NS202-@
G9SX-NSA222-T03-@
6. Disconnect the G9SX-NS@ from the power supply when replacing
the D40A. Devices connected to the G9SX-NS@ may operate
unexpectedly.
7. Adhesion of solvent such as alcohol, thinner, trichlorobenzene or
gasoline on the product should be avoided.
Such solvents make the marking on D40A illegible and cause
deterioration of parts.
8. Do not use the D40A in a magnetic field of 1.5 mT or higher. The
D40A may not function properly.
9. Do not use the D40A in the water or in an environment
continuously exposed to water. Water may penetrate into the
D40A. (The IP67 degree of protection for this switch means that it
has been checked for penetration of water after having been left
in water for a fixed period of time.)
10. Do not use the switch or actuator as a stopper. Protect the switch
and the actuator by installing a stopper. Separate the switch and
the actuator to a distance of 1 mm or more.
11. Install the actuator and switch at an appropriate distance so that
they do not create a gap that provides access to the hazard.
Correct
Incorrect
33
D40A/G9SX-NS
12. When two or more Switches are mounted side-by-side, they must
be no closer than 25 mm in the X, Y, and Z directions.
25 mm min.
25 mm min.
25 mm min.
13. Check that the machine is stopped whenever the interlocked
guard door is open.
19. Mounting
Mount the G9SX-NS to a DIN rail using End Plates (PFP-M, not
included with the product) so that the G9SX-NS does not fall off of
the rails due to vibration or other causes, especially when the
length of DIN railing is short compared to the width of the
G9SX-NS@.
20. The following space must be provided around the G9SX-NS@ to
enable applying the rated current to the outputs of the G9SXNS@, to ensure sufficient ventilation, and to enable wiring:
1. At least 25 mm between side surfaces of the G9SX-NS@
2. At least 50 mm above the top surface of the G9SX-NS@ and
below the bottom surface of the G9SX-NS@.
14. Do not mount the switch and actuator on magnetic materials,
otherwise it may affect the operating distance.
Distance from surface of
magnetic body
Operating distance
0 to 5 mm
Reduce to approx. 90% of
original value.
5 mm or longer
No influence.
15. Tighten all screws to the specified torque by using non-magnetic
M4 screws with a maximum diameter of 7 mm and washer for the
installation of the switch and actuator. After installation and using,
the actuator and switch fixing screws must be coated with tamper
proof varnish or similar
compound. Using anaerobic locking compounds can have a
detrimental effect on the plastic switch case if the compounds
come into contact with the switch case.
Actuator
1.0 N·m
Switch
16. Wiring
1. Use the following to wire to the product.
Stranded wire (flexible wire): 0.2 to 2.5 mm2 (AWG24 to
AWG12)
Solid wire (steel wire): 0.2 to 2.5 mm2 (AWG24 to AWG12)
2. When an auxiliary output is not used, cut off the wiring and
cover it with tape so that it does not contact other terminals.
3. When you use an additional cable of 20m or longer, use a
multiconductor cable to group the white, black, brown, and blue
lines together.
17. Handle cables with care
1. For bending cables, it is recommended to bend them with a
radius of bend no less than six times the cable outer diameter.
2. Do not apply a tensile strength of 50N or greater to the cables.
3. For the handling of the XS2F/XS2W connector with cable, refer
to Precautions for Correct Use of the XS2 series.
18. If there is any machine that has a large surge current (e.g.,
amotor) near D40A, connect a surge absorber to D40A between
the blue and the other cables (white, black, brown, and yellow),
respectively.
Suggested surge absorber's specification is as follows:
• Peak pulse power: 600W (10/1000 ms) or more (Per
IEC61000-4-5(surge immunity))
• Breakdown voltage: 27-33V
34
50 mm min.
25 mm min.
25 mm min.
50 mm min.
21. Wiring
1. G9SX-NS@-RT (with Screw Terminals)
• Use the following to wire the G9SX-NS@-RT.
Solid wire
(steel wire)
0.2 to 2.5 mm2 (AWG24 to
AWG12)
Stranded wire
(flexible wire)
0.2 to 2.5 mm2 (AWG24 to
AWG12)
• Tighten each screw to the specified torque of 0.5 to 0.6 N·m,
or the G9SX-NS@ may malfunction or generate heat.
• Strip the wire for no longer than 7 mm.
2. G9SX-NS@-RC (with Spring-cage Terminals)
• Use the following to wire the G9SX-NS@-RC.
Solid wire
(steel wire)
0.2 to 2.5 mm2 (AWG24 to
AWG12)
Stranded wire
(flexible wire)
0.2 to 2.5 mm2 (AWG24 to
AWG12)
• Strip the wire for no longer than 7 mm.
3. Logical AND Connections
• Use VCTF cables or shielded cables for logical AND connect
ions between Units.
22. Connecting G9SX-EX@-@ Expansion Units
1. Remove the terminating connector from the connector on the
G9SX-NSA222-T03@. Insert the connector on the connecting
cable of Expansion Unit into the connector on the G9SX-NSA222T03-@.
2. Connect the terminating connector to the connector on the
Expansion Unit at the end position.
When the G9SX-NSA222-T03-@ is used without Expansion
Units, leave the terminating connector on the G9SX-NSA222T03-@.
3. Do not remove the terminating connector or connecting cables
of Expansion Units while the system is operating.
4. Before applying the supply voltage, confirm that the connectors
are locked firmly.
5. All of the Expansion Units must be supplied with its specified
voltages within 10 s after the connected G9SX-NSA222-T03-@
is supplied with voltage.
Otherwise, the G9SX-NSA222-T03-@ will detect a power
supply error for the Expansion Units.
23. Use cables with a length of less than 100 m total to connect the
safety inputs, feedback/reset inputs, and logical AND connection
inputs and outputs.
D40A/G9SX-NS
24. Set the time duration of OFF-delay to an appropriate value that
does not cause the loss of safety functions of system.
25. Logical AND connections between Units (Refer to “Functions” on
page 23.)
1. To use logical AND connection inputs, enable the logical AND
connection input for the G9SX-NS@ that will receive the inputs.
2. Connect the logical AND connection inputs appropriately to the
logical AND connection outputs of the G9SX-@.
3. When configuring the safety system, be sure to consider that
the delay of response time caused by logical AND connection
does not degrade the safety functions of the system. (Refer to
“Response Time and Operating Time” on page 17.)
26. To determine safety distance to hazards, take into account the
delay of safety outputs caused by the following time:
1. Response time of safety inputs
2. Response time of D40A Non-contact Door Switch inputs
3. Response time of logical AND connection input
(Refer to “Response Time and Operating Time” on page 17.)
4. Preset OFF-delay time
5. Accuracy of OFF-delay time
27. Start the rest of the system after 5 s or longer has passed since
applying supply voltage to all G9SX-@ in the system.
28. Be sure to ground the A2 terminal of the power supply to help
prevent malfunctions caused by noise. Also, connect a surge
absorber to each end of the coil on inductive loads to reduce noise
generation. When sharing a power supply with a Light Curtain,
use a DC power supply that will not fail for a momentary power
interruption of 20 ms or less.
29. Devices connected to the G9SX-NS may operate unexpectedly.
When replacing the G9SX-NS, disconnect it from power supply.
30. Adhesion of solvent
Do not allow organic solvents, such as alcohol, thinner,
trichloroethane, or gasoline, to come into contact with the product.
Such solvents make the markings on G9SX-NS illegible and
cause deterioration of parts.
31. Do not mix AC and DC circuits for contact outputs in a single
G9SX-EX@-@. When using AC and DC circuits, connect at least
two G9SX-EX@-@ Units and use them respectively as dedicated
DC-circuit and AC-circuit contact outputs.
32. Safety Application Controller’s Relay durability depends greatly
on the switching condition. Confirm the actual conditions of
operation in which the Relay will be used in order to make sure the
permissible number of switching operations.
When the accumulated number of operation exceeds its
permissible range, it can cause failure of reset of safety control
circuit. In such case, please replace the Relay or the Safety
Application Controller immediately.
If the Relay or the Safety Application Controller is used
continuously without replacing, then it can lead to loss of safety
function.
33. Operate the reset input more than 0.4 seconds immediately after
the safety outputs are OFF.
G9SX does not accept the reset input from when the outputs are
turned ON and until 0.4 seconds passes after the outputs are
turned OFF.
Switch and Actuator Operation
Switch and Actuator Mounting Directions
Switch
Switch
Actuator
Actuator
Switch and Actuator Operating Directions
Correct
Correct
Correct
Incorrect
Safety Categories (EN ISO13849-1)
You can use the D40A with the G9SX-NS@ for applications in PLd
and Safety Category 3 environments defined in the EN ISO13849-1
European standard and the ISO 13849-1 international standard.
Compliance was determined using circuit examples specified by
OMRON and may not be applicable to all conditions.
Safety categories are determined for the overall safety control
system. Confirm compliance sufficiently with your application.
Requirements for Safety Category 3 (EN ISO 13849-1)
1. Connect external input D1-D2 and external output D3-D4 to D40A
Switches.
2. Input two channels for external inputs T11-T12 and T21-T22.
3. Input external inputs T11-T12 and T21-T22 from switches with
direct opening mechanisms. For limit switches, make sure at least
one of the switches has a direct opening mechanism.
4. Input the NC signal from the contactor to T31-T32 for a manual
reset and to T31-T33 for an auto reset. (Refer to “Application
Examples” on page 28)
5. Make sure to connect the A2 terminal to ground.
Standards Certification
Directives
• EMC Directive
• Machinery Directive
Standards/UL Certification
• EN ISO 13849-1 PLd/Safety Category 3 (Used with D40A and
G9SX-NS@)
• EN 61508 SIL 3 (Used with D40A and G9SX-NS@)
• EN 60947-5-3 (Used with D40A and G9SX-NS@)
• IEC/EN 61000-6-4
• EN ISO14119 (Used with D40A and G9SX-NS@)
• UL 508
• CAN/CSA C22.2 No.14
• KOSHA certification (excluding connector model)
• EN ISO 13849-1 PLd/Safety Category 3 (Used with D40A)
• EN ISO 13849-1 PLe/Safety Category 4 (Used with D40Z)
• IEC/EN 61508 SIL3
• IEC/EN 61000-6-2
• IEC/EN 61000-6-4
• UL508
• UL1998
• CAN/CSA C22.2 No.142
35
Terms and Conditions Agreement
Read and understand this catalog.
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have
any questions or comments.
Warranties.
(a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship
for a period of twelve months from the date of sale by Omron (or such other period expressed in writing
by Omron). Omron disclaims all other warranties, express or implied.
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT
NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE
PRODUCTS. BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE PRODUCTS WILL
SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.
Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the Products
or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at Omron’s election,
to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or replacement thereof) the
non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount equal to the purchase price
of the non-complying Product; provided that in no event shall Omron be responsible for warranty, repair, indemnity or any other
claims or expenses regarding the Products unless Omron’s analysis confirms that the Products were properly handled, stored,
installed and maintained and not subject to contamination, abuse, misuse or inappropriate modification. Return of any Products by
Buyer must be approved in writing by Omron before shipment. Omron Companies shall not be liable for the suitability or
unsuitability or the results from the use of Products in combination with any electrical or electronic components, circuits, system
assemblies or any other materials or substances or environments. Any advice, recommendations or information given orally or in
writing, are not to be construed as an amendment or addition to the above warranty.
See http://www.omron.com/global/ or contact your Omron representative for published information.
Limitation on Liability; Etc.
OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,
WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.
Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted.
Suitability of Use.
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the
combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable
third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself is
not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine, system,
or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product with
respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE
QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS,
AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
OVERALL EQUIPMENT OR SYSTEM.
Programmable Products.
Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence thereof.
Performance Data.
Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining
suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate it
to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability.
Change in Specifications.
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice
to change part numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers may be
assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at any time to
confirm actual specifications of purchased Product.
Errors and Omissions.
Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is
assumed for clerical, typographical or proofreading errors or omissions.
Note: Do not use this document to operate the Unit.
OMRON Corporation
Industrial Automation Company
Authorized Distributor:
Kyoto, JAPAN
Contact: www.ia.omron.com
Regional Headquarters
OMRON EUROPE B.V.
Wegalaan 67-69, 2132 JD Hoofddorp
The Netherlands
Tel: (31)2356-81-300/Fax: (31)2356-81-388
OMRON ELECTRONICS LLC
2895 Greenspoint Parkway, Suite 200
Hoffman Estates, IL 60169 U.S.A.
Tel: (1) 847-843-7900/Fax: (1) 847-843-7787
OMRON ASIA PACIFIC PTE. LTD.
No. 438A Alexandra Road # 05-05/08 (Lobby 2),
Alexandra Technopark,
Singapore 119967
Tel: (65) 6835-3011/Fax: (65) 6835-2711
OMRON (CHINA) CO., LTD.
Room 2211, Bank of China Tower,
200 Yin Cheng Zhong Road,
PuDong New Area, Shanghai, 200120, China
Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200
© OMRON Corporation 2006-2021 All Rights Reserved.
In the interest of product improvement,
specifications are subject to change without notice.
CSM_10_5
Cat. No. C140-E1-03
0621 (0906)