Founded in 1933, JAPAN
Multi-range, Multi-mode Timer
Order Code
H3DT-N2
24 to 240 VAC/DC
Dimensions (Unit: mm)
Terminal Arrangement
17.5
100
90
86
90
Front
5
Side view
Technical criteria
Rated supply voltage
Operating mode
Input method
Minimum input signal width
Power Reset (Minimum power-OFF time)
Control Output
Accuracy of operating time
Setting error
Operating Temperature
Operating Humidity
IP
24 to 240 VAC/DC, 50/60 Hz
A2, B3, B4, D, E2, E3, F2, F3
Voltage input
50 ms (start input)
0.1 s
5 A at 250 VAC with resistive load (cosφ = 1),
5 A at 30 VDC with resistive load,
0.15 A max. at 125 VDC with resistive load,
0.1A max. at 125 VDC with L/R of 7 ms.
Minimum applicable load:10 mA at 5 VDC.
±1% of FS max. (±1% ±10 ms max. at 1.2-s range)
±10% of FS ±0.05 s max.
−20 to 60°C
25% to 85%
IP30 (Terminal block: IP20)
For the most recent information on models that have been certified for safety standards, refer to your OMRON website.
Nomenclature
1
2
3
1
2
3
4
5
6
5
6
4
INIT/TIME switch for relay R2
Operation/power indicator
Output indicator
Operating mode switch
Time range switch
Main dial
Time range
Time range setting
Set time range
Scale numbers
0.1 s
0.1 to 1.2 s
1s
1 to 12 s
10 s
10 to 120 s
1 min
1 to 12 min
10 min
10 to 120 min
1h
1 to 12 h
10 h
10 to 120 h
100 h
100 to 1,200 h
12
Timing Chart
A2: ON Delay
E2: Interval
B3: Flicker OFF Start
E3: Signal OFF Interval
B4: Flicker ON Start
F2: Cumulative (ON Delay)
D: Signal OFF Delay
F3:Cumulative (Interval)
Note: Refer to the official Datasheet, how to use Gate input.
Accessories
Front Cover
Y92A-D1A
Contact: www.ia.omron.com
© OMRON Corporation 2019 All Rights Reserved.
In the interest of product improvement,
specifications are subject to change without notice.
Cat. No. L191-E1-01
1019
很抱歉,暂时无法提供与“H3DT-N2AC/DC24-240”相匹配的价格&库存,您可以联系我们找货
免费人工找货