New Product
Three-phase Voltage, Asymmetry, and Phase-sequence Phase-loss Relay
K8DS-PZ
Ideal for Monitoring 3-phase Power Supplies
for Industrial Facilities and Equipment.
• Greater resistance to inverter noise.
• Monitor undervoltages, overvoltages, voltage asymmetry, phase
sequence, and phase loss in three-phase three-wire circuits with one
unit.
• One SPDT output relay, 5 A at 250 VAC (resistive load).
• World-wide power specifications supported by one unit. (Set with a
rotary switch.)
• Relay status can be monitored using LED indicator.
Refer to Safety Precautions on page 9.
Refer to page 7 for commonly asked questions.
For the most recent information on models that have been
certified for safety standards, refer to your OMRON website.
Ordering Information
List of Models
Rated input voltage*
3-phase 3-wire mode
200, 220, 230, or 240 VAC
Model
K8DS-PZ1
380, 400, 415, or 480 VAC
K8DS-PZ2
Note: The input range is set with a rotary switch.
* The power supply voltage is the same as the rated input voltage.
1
K8DS-PZ
Ratings and Specifications
Ratings
Rated input
voltage
K8DS-PZ1
Three-phase, three-wire Mode: 200, 220, 230, or 240 VAC
K8DS-PZ2
Three-phase, three-wire Mode: 380, 400, 415, or 480 VAC
Input load
K8DS-PZ1: Approx. 1.7 VA
K8DS-PZ2: Approx. 2.8 VA
Operating value setting range (OVER/UNDER) (ASY)
Overvoltage/Undervoltage
2% to 30% of rated input voltage
Asymmetry
5% to 22% of rated input voltage
Operating value (OVER/UNDER)
Operates at 100% of set value.
Operating value (ASY.)
Asymmetry operating value = Rated input voltage × Asymmetry set value (%)
The asymmetry operation will function when the potential difference between the highest and lowest voltage phases equals or exceeds the asymmetry operating value.
Reset value
5% of operating value (fixed)
Reset method
Automatic reset
Overvoltage/Undervoltage
Operating time
setting range Asymmetry
(T)
Phase sequence
Phase loss
0.1 to 30 s
0.1 to 30 s
0.1 s±0.05 s
0.1 s max.
Power ON lock time (LOCK)
1 s±0.5 s
Indicators
Power (PWR): Green, Relay output (RY): Yellow, Alarm outputs (ALM): Red
Output relays
One SPDT relay output
Output relay ratings
Rated load
Resistive load
5 A at 250 VAC
5 A at 30 VDC
Maximum switching capacity: 1,250 VA, 150 W
Minimum load: 5 VDC, 10 mA (reference values)
Mechanical life: 10 million operations min.
Electrical life: 5 A at 250 VAC: 50,000 operations
3 A at 250 VAC: 100,000 operations
Ambient operating temperature
−20 to 60°C (with no condensation or icing)
Storage temperature
−25 to 65°C (with no condensation or icing)
Ambient operating humidity
25% to 85% (with no condensation)
Storage humidity
25% to 85% (with no condensation)
Altitude
2,000 m max.
Terminal screw tightening torque
0.49 to 0.59 N·m
Recommended wire
Solid wire: 2.5 mm2
Twisted wires: AWG16, AWG18
Terminal wiring method
Note: 1. Ferrules with insulating sleeves must be used with twisted wires.
2. Two wires can be twisted together.
Recommended ferrules
Al 1,5-8BK (for AWG16) manufactured by Phoenix Contact
Al 1-8RD (for AWG18) manufactured by Phoenix Contact
Al 0,75-8GY (for AWG18) manufactured by Phoenix Contact
2
Case color
N1.5
Case material
PC and ABS, UL 94 V-0
Weight
Approx. 65 g
Mounting
Mounts to DIN Track.
Dimensions
17.5 × 80 × 74 mm (W×D×H)
K8DS-PZ
Specifications
Input frequency
50/60 Hz
Overload capacity
Continuous 500 V
±0.5% full scale (at 25°C and 65% humidity, rated power supply voltage, 50/60 Hz sine wave
input)
Repeat accura- Operating value
cy
Operating time
Applicable
standards
±50 ms (at 25°C and 65% humidity, rated power supply voltage)
Conforming standards
EN 60947-5-1
Installation environment (pollution level 2, installation category III)
EMC
EN 60947-5-1
Safety standards
UL 508 (Recognition), Korean Radio Waves Act (Act 10564),
CSA: C22.2 No.14
Insulation resistance
20 MΩ min.
Between external terminals and case
Between input terminals and output terminals
Dielectric strength
2,000 VAC for one minute
Between external terminals and case
Between input terminals and output terminals
Noise immunity
1,500 V power supply terminal common/normal mode
Square-wave noise of ±1 µs/100 ns pulse width with 1-ns rise time
Vibration resistance
Frequency: 10 to 55 Hz, acceleration 50 m/s2
10 sweeps of 5 min each in X,Y, and Z directions
Shock resistance
100 m/s2, 3 times each in 6 directions along 3 axes
Degree of protection
Terminals: IP20
●Relationship of Mounting Distance between K8DS-PZ Relays
and Ambient Temperature (Reference Values)
The following diagram shows the relationship between the mounting distances and the
ambient temperature.
If the relay is used with an ambient temperature that exceeds these values, the
temperature of the K8DS may rise and shorten the life of the internal components.
70
Ambient temperature [°C]
60
50
40
30
20
10
0
5
10
15
20
25
30
35
40
45
50
Distance between products d [mm]
Test method
Sample: K8DS-PZ
Distance between products: 0, 5, 10, and 50 mm
K8DS
No.1
DIN Track
K8DS
No.2
K8DS
No.3
K8DS
No.4
K8DS
No.5
Distance between products: d
3
K8DS-PZ
Connections
Terminal Diagram
Control Output
L2
L1
Relay output
250 VAC, 5 A (resistive load)
30 VDC, 5 A (resistive load)
Input Voltages
L3
L1
L2
L3
3-phase,
3-wire
power
supply
Phase-to-phase voltage:
200 to 480 VAC
Relay Output
14
12
11
12
14
11
Note: Use the recommended ferrules if you use twisted wires.
Wiring Example
L1
3-phase
voltage
L2
Motor
L3
L1
L2
L3
Power supply
AC/DC
14
12
11
Timing Charts
●Overvoltage, Undervoltage, Phase Sequence, and Phase Loss Operation Diagram
Overvoltage set value
Hysteresis: Fixed at 5% Asymmetry operating value
L1
Input L2
L3
Undervoltage set value
Hysteresis: Fixed at 5%
Flashing
Alarm indicator
Flashing
Lit
Lit
t
Flashing
Lit
t: Operating time (0.1 to 30 s)
Contacts
t
t: Operating time (0.1 to 30 s)
t1: Power ON lock (1 s)
t1
Phase Loss Operation
Phase sequence Operation
L2
L1
L3
L1
Operation Table
L1
L1
L3
L2
L2
L3
L2
L1
L3
Input L2
Item
L3
Lit
Flashing Flashing
Flashing
Alarm indicator
Relay 11-14
Note: 1. The K8DS-PZ output contacts are normally operative.
2. The power ON lock prevents unnecessary alarms from being
generated during the unstable period when the power is first turned
ON. There is no contact output during timer operation.
3. Phase loss is detected by a drop in the L1, L2, or L3 voltage. A
phase loss is detected when any of the phase-to-phase voltages
goes below 60% of the rated input.
4. L2 and L3 are also used for the power supply. If the voltage
becomes very low, the Relay will not operate.
5. Phase loss (on power supply side and load side) is not detected in
the motor load during operation.
4
Indicators
RY_LED
ALM_LED
Contact
operation
Overvoltage
OFF
ON
OFF
Undervoltage
OFF
ON
OFF
Asymmetry
OFF
ON
OFF
Phase loss
OFF
ON*1
OFF
OFF
Flashing*2
OFF
ON
OFF
ON
Incorrect
phase
Phase
sequence Correct
phase
*1
*2
L2 and L3 are also used for the power supply. If the voltage becomes
very low, the indicator will turn OFF.
The indicator will flash once per second after an incorrect phase is
detected and once per 0.5 second during the detection time.
K8DS-PZ
Nomenclature
Front
●Indicators
Terminal block
(See notes 1 and 2.)
Item
L1 L2 L3
Input voltage range
rotary switch
Power indicator
Asymmetry rate knob
(ASY.)
Meaning
Power indicator
(PWR: Green)
Lit when power is being supplied.*
Relay status indicator
(RY: Yellow)
Lit when relay is operating (normally lit).
Alarm indicator
(ALM: Red)
Lit for asymmetry voltage error.
When the input exceeds the set value, the indicator flashes for the operating time to indicate
the error status.
Relay status indicator
Overvoltage/undervoltage
knob (OV/UV)
Alarm indicator
* This indicator uses the input across L2 and L3 as the internal power
supply. It will not light unless there is an input across L2 and L3.
●Setting Knobs
Operating time knob (T)
Item
Terminal block
(See notes 1 and 2.)
14 12 11
Description
Input voltage range
rotary switch
Used to change the input voltage range.
K8DS-PZ1: 200, 220, 230, or 240 V
K8DS-PZ2: 380, 400, 415, or 480 V
Overvoltage/undervoltage knob
(OV/UN)
Used to set from 2% to 30% of the rated input.
Asymmetry rate knob
(ASY.)
Used to set from 5% to 22%.
Operating time knob
(T)
Used to set the operating time to 0.1 to 30 s.
Note: 1. Use either a solid wire of 2.5 mm2 maximum or a ferrule with
insulating sleeve for the terminal connection.
The length of the exposed current-carrying part inserted into
the terminal must be 8 mm or less to maintain dielectric
strength after connection.
For 2.5 mm2 or
smaller solid wires
For ferrules with
an insulation sleeve.
8 mm max.
8 mm max.
Recommended ferrules
Phoenix Contact
• Al 1,5-8BK (for AWG16)
• Al 1-8RD (for AWG18)
• Al 0,75-8GY (for AWG18)
2. Tightening torque: 0.49 to 0.59 N·m
Operation Methods
Connections
●Input
L1 L2 L3
Wire the input to the L1, L2, and L3 terminals (3-phase, 3-wire).
Make sure the phase sequence is wired correctly. The Unit will not
operate normally if the phase sequence is incorrect.
Voltage input
●Outputs
L1
L2
L3
Terminals 11, 12, and 14 are the output terminals.
* Use the recommended ferrules if you use twisted wires.
14
Signal output
12
11
Relay signal
output
Load
5
K8DS-PZ
Setting Methods
●Asymmetry
The asymmetry rate is set using the asymmetry rate knob (ASY).
The setting range is 5% to 22% of the rated input.
To correctly detect asymmetry, set the asymmetry rate knob to a value that is equal to or less than the overvoltage/undervoltage set value. If
you set it to a value that is greater than the overvoltage/undervoltage set value, overvoltage/undervoltage detection will operate first, and
asymmetry alarms will not be output.
If the knob is turned with an input applied to the input terminals, the alarm indicator will flash when the set value equals the input value.
Use this as a guide to make the setting.
The rated input depends on the model and the rotary switch setting.
Example: K8DS-PZ1 with Rotary Switch Set to 200 V
The rated input is 200 VAC, so the setting range is 4 to 44 V.
If you set the setting knob (ASY.) to 10%, the asymmetry operating voltage would be 20 V and an alarm would be output when the
difference between the highest and lowest phase-to-phase voltages exceeds 20 V.
●Overvoltage/Undervoltage
Overvoltage/Undervoltage is set using the overvoltage/undervoltage knob (OV/UV).
The setting range is 2% to 30% of the rated input for overvoltage detection and −2% to −30% of the rated input for an undervoltage detection.
Use this as a guide to make the setting.
The rated input depends on the model and the rotary switch setting.
Example: K8DS-PZ1 with Rotary Switch Set to 200 V
The rated input is 200 VAC, so the setting range is 204 to 260 V for overvoltage detection and 140 to 196 V for undervoltage
detection.
●Operating Time
The operating time is set using the operating time knob (T).
The operating time can be set to between 0.1 and 30 s.
Turn the knob while there is an input to the input terminals until the alarm indicator flashes (when the set value and the input have reached the
same level.)
Use this as a guide to set the operating time.
If the input exceeds (or drops lower than) the voltage set value, the alarm indicator will start flashing for the set period and then stay lit.
Dimensions
(Unit: mm)
Three-phase Voltage, Asymmetry, and Phase-sequence Phase-loss Relays
K8DS-PZ1
K8DS-PZ2
74
17.5
80
44
69
Optional Parts for DIN Track Mounting
●DIN Tracks
PFP-100N
PFP-50N
7.3±0.15
4.5
35±0.3
15
25
10
25
25
1,000 (500)*
10
25
15 (5)*
27±0.15
1
*Dimensions in parentheses are for the PFP-50N.
6
K8DS-PZ
Questions and Answers
Q
Q
Checking Operation
How to Measure the Operating Time
Overvoltage
Change the input value quickly from 70% to 120% of the set
value and measure the time required for the Relay to operate.
Undervoltage
Change the input value quickly from 120% to 70% of the set
value and measure the time required for the Relay to operate.
Operating Time
Adjust the slide resistor so that the voltage applied to the
K8DS terminals is 120% of the set value for overvoltage
detection, 80% of the set value for undervoltage detection, or
equal to or greater than the asymmetry operating value when
the auxiliary relay in connection diagram 2 operates.
Close the switch and use a cycle counter to measure the
operating time.
Overvoltage
Gradually increase the input from 80% of the set value. The
input will equal the operating value when the input exceeds
the set value and the alarm indicator starts flashing.
Operation can be checked because the Relay will operate
after the operating time has passed.
Undervoltage
Gradually decrease the input from 120% of the set value and
check the operation using the same method as for an
overvoltage.
Example: Monitoring Mode for Rated Voltage of 200 V and an Operating
Time Setting of 5 s
Connection Diagram 2
Operating set value
Input voltage
L1
Flashing
Lit
Alarm indicator
L2
L1
5s
R1
Relay output
Asymmetry
With the rated input voltage applied, gradually change one of
the phase-to-phase voltages. The Relay will operate when
the difference between the highest and lowest voltage
phases reaches or exceeds the asymmetry operating value.
Asymmetry operating value = Rated input voltage ×
Asymmetry set value (%)
X
X/a
X/b
V2
V3
L3
R2
L2
R1: Sliding resistor, 200 Ω, 200 W
R2: 100 Ω, 400 W
L3
Example: Monitoring Mode for Rated Voltage of 200 V and an Operating
Time Setting of 5 s
±
C 200 V
Cycle counter
L1
Asymmetry operating voltage (set value)
Input L2
L3
Q
Flashing
Lit
Alarm indicator
Relay output
T: Operating time (0.1 to 30 s)
T
T1: Power ON lock (1 or 5 s)
Connection Diagram 1
L1
V1
3-phase,
200 VAC
V1
3-phase, 200 VAC
L2
V2
Checking the Phase Sequence and Phase Loss
Operation
Phase Sequence
Switch the wiring, as shown by the dotted lines in connection
diagram 1, to reverse the phase sequence and check that the
K8DS operates.
Phase loss
Create a phase loss for any input phase and check that the
K8DS operates.
V3
L1
L3
0 to 150 V
L2
L3
3-phase variable autotransformer
7
K8DS-PZ
Questions and Answers
Q
Q
Load-side Phase Loss
In principle, phase loss cannot be detected on the load side
because the K8DS-PZ measures three-phase voltage to
determine phase loss.
Q
Motor Load Phase Loss during Operation
Motor load phase loss cannot be detected during operation. It
can be used to detect phase loss at startup.
Normally, three-phase motors will continue to rotate even if
one phase is open. The three-phase voltage will be induced
at the motor terminals. The diagram shows voltage induction
at the motor terminals when phase R has been lost with a
load applied to a three-phase motor. The horizontal axis
shows the motor load as a percentage of the rated load, and
the vertical axis shows voltage as a percentage of the rated
voltage. The lines in the graph show the voltage induced at
the motor terminals for each load phase loss occurs during
operation. As the graph shows, phase loss cannot be
detected because the motor terminal voltage does not drop
very much even if a phase is lost when the load on the motor
is light. To detect motor load phase loss during operation, use
the undervoltage detection function to detect the motor
terminal voltages at phase loss.
Set the operating time carefully because it will affect the time
from when the phase loss occurs until tripping when this
function is used.
Characteristic Curve Diagram
Voltage (as a percentage of rated voltage)
Note: This characteristic curve shows the approximate
values only.
100
95
90
VST
85
80
VTR
75
70
65
60
55
50
45
0
VRS
10 20 30 40 50 60 70 80 90 100 110
Motor load (as a percentage of rated load)
Note: For phase loss of phase R. VST, VTR, and VRS indicate the motor
terminal voltage at phase loss.
8
Is an overvoltage detected if only one of the three-phase
phase-to-phase voltages exceeds the overvoltage set
value?
The K8DS monitors all three phase voltages. Therefore, an
overvoltage is detected if only one of the phase-to-phase
voltages exceeds the set value. The same is true for
undervoltages.
K8DS-PZ
Safety Precautions
Be sure to read the precautions for all models in the website at the following URL: http://www.ia.omron.com/.
Warning Indications
WARNING
Indicates a potentially hazardous situation
which, if not avoided, will result in minor or
moderate injury, or may result in serious
injury or death. Additionally there may be
significant property damage.
CAUTION
Indicates a potentially hazardous situation
which, if not avoided, may result in minor or
moderate injury or in property damage.
Precautions for Safe
Use
Supplementary comments on what to do or
avoid doing, to use the product safely.
Precautions for
Correct Use
Supplementary comments on what to do or
avoid doing, to prevent failure to operate,
malfunction, or undesirable effects on
product performance.
Meaning of Product Safety Symbols
Used to warn of the risk of electric shock under
specific conditions.
WARNING
Electrical shock may occasionally cause serious injury.
Confirm that the input voltage is OFF before starting any
wiring work and wire all connections correctly.
CAUTION
Electrical shock may cause minor injury.
Do not touch terminals while electricity is being supplied.
There is a risk of minor electrical shock, fire, or device failure.
Do not allow any pieces of metal, conductors, or cutting chips
that occur during the installation process to enter the product.
Explosions may cause minor injuries. Do not use the product
in locations with inflammable or explosive gases.
Used for general prohibitions for which there is no
specific symbol.
There is a risk of minor electrical shock, fire, or device failure.
Do not disassemble, modify, repair, or touch the inside of the
product.
Used to indicate prohibition when there is a risk of
minor injury from electrical shock or other source if
the product is disassembled.
Loose screws may cause fires. Tighten terminal screws to the
specified torque of 0.49 to 0.59 N·m.
Used for general mandatory action precautions for
which there is no specified symbol.
Use of excessive torque may damage the terminal screws.
Tighten terminal screws to the specified torque of 0.49 to
0.59 N·m.
Use of the product beyond its life may result in contact welding
or burning. Make sure to consider the actual operating
conditions and use the product within its rated load and
electrical life count. The life of the output relay varies
significantly with the switching capacity and switching
conditions.
9
K8DS-PZ
Precautions for Safe Use
1. Do not use or store the product in the following locations.
• Locations subject to water or oil
• Outdoor locations or under direct sunlight
• Locations subject to dust or corrosive gases (particularly
sulfurizing gases, ammonia, etc.)
• Locations subject to rapid temperature changes
5. To reduce the error in the setting knob, always turn the setting
knob from the minimum setting toward the maximum setting.
6. Phase loss is detected only when the power supply to the motor is
turned ON. Phase loss during motor operation is not detected.
7. Phase loss can be detected only from the input contacts to the
power supply side. Phase loss cannot be detected from the input
contacts to the load side.
8. When cleaning the product, do not use thinners or solvents. Use
commercial alcohol.
• Locations prone to icing and dew condensation
• Locations subject to excessive vibration or shock
• Locations subject to wind and rain
• Locations subject to static electricity and noise
• Habitats of insects or small animals
2. Use and store the product in a location where the ambient
temperature and humidity are within the specified ranges. If
applicable, provide forced cooling.
3. Mount the product in the correct direction.
4. Do not wire the input and output terminals incorrectly.
5. Make sure the input voltage and loads are within the
specifications and ratings for the product.
6. Make sure the crimp terminals for wiring are of the specified size.
7. Do not connect anything to terminals that are not being used.
8. Use a power supply that will reach the rated voltage within 1
second after the power is turned ON.
9. Keep wiring separate from high voltages and power lines that
draw large currents.
Do not place product wiring in parallel with or in the same path as
high-voltage or high-current lines.
10.Do not install the product near equipment that generates high
frequencies or surges.
11.The product may cause incoming radio wave interference. Do not
use the product near radio wave receivers.
12.Install an external switch or circuit breaker and label it clearly so
that the operator can quickly turn OFF the power supply.
13.Make sure the indicators operate correctly. Depending on the
application environment, the indicators may deteriorate
prematurely and become difficult to see.
14.Do not use the product if it is accidentally dropped. The internal
components may be damaged.
15.Be sure you understand the contents of this catalog and handle
the product according to the instructions provided.
16.Do not install the product in any way that would place a load on it.
17.When discarding the product, properly dispose of it as industrial
waste.
18.The product must be handled only by trained electrician.
19.Prior to operation, check the wiring before you supply power to
the product.
20.Do not install the product immediately next to heat sources.
21.Perform periodic maintenance.
Mounting and Removing
• The product may be mounted in any direction, but it must be
mounted securely and as level as possible.
• To mount the product to the DIN Track, hook it on the DIN Track at
(A) and then press in on the Unit in direction (B).
(A)
(B)
• To remove the product, insert a flat-blade screwdriver at (C) and
pull down the hook to release the Unit.
(C)
Hook
• Leave at least 30 mm of space between the product and other
devices to allow easy installation and removal.
Operating the Setting Knobs and
Rotary Switch
• Use a screwdriver to adjust the setting knobs and rotary switch.
The knobs have a stopper that prevents them from turning beyond
the full right or left position. Do not force a knob beyond these
points.
Precautions for Correct Use
Observe the following operating
methods to prevent failure and
malfunction.
1. Use the input power and other power supplies and converters
with suitable capacities and rated outputs.
2. Use a precision screwdriver or similar tool to adjust the setting
knobs and rotary switches.
3. The distortion in the input waveform must be 30% max. If the
input waveform is distorted beyond this level, it may cause
unnecessary operation.
4. The product cannot be used for thyristor control or on the
secondary side of an inverter. To use the product on the
secondary side of an inverter, install a noise filter on the primary
side of the inverter.
10
30 mm min.
Setting knob
Terms and Conditions of Sale
1. Offer; Acceptance. These terms and conditions (these "Terms") are deemed
part of all quotes, agreements, purchase orders, acknowledgments, price lists,
catalogs, manuals, brochures and other documents, whether electronic or in
writing, relating to the sale of products or services (collectively, the "Products")
by Omron Electronics LLC and its subsidiary companies (“Omron”). Omron
objects to any terms or conditions proposed in Buyer’s purchase order or other
documents which are inconsistent with, or in addition to, these Terms.
2. Prices; Payment Terms. All prices stated are current, subject to change without notice by Omron. Omron reserves the right to increase or decrease prices
on any unshipped portions of outstanding orders. Payments for Products are
due net 30 days unless otherwise stated in the invoice.
3. Discounts. Cash discounts, if any, will apply only on the net amount of invoices
sent to Buyer after deducting transportation charges, taxes and duties, and will
be allowed only if (i) the invoice is paid according to Omron’s payment terms
and (ii) Buyer has no past due amounts.
4. Interest. Omron, at its option, may charge Buyer 1-1/2% interest per month or
the maximum legal rate, whichever is less, on any balance not paid within the
stated terms.
5. Orders. Omron will accept no order less than $200 net billing.
6. Governmental Approvals. Buyer shall be responsible for, and shall bear all
costs involved in, obtaining any government approvals required for the importation or sale of the Products.
7. Taxes. All taxes, duties and other governmental charges (other than general
real property and income taxes), including any interest or penalties thereon,
imposed directly or indirectly on Omron or required to be collected directly or
indirectly by Omron for the manufacture, production, sale, delivery, importation, consumption or use of the Products sold hereunder (including customs
duties and sales, excise, use, turnover and license taxes) shall be charged to
and remitted by Buyer to Omron.
8. Financial. If the financial position of Buyer at any time becomes unsatisfactory
to Omron, Omron reserves the right to stop shipments or require satisfactory
security or payment in advance. If Buyer fails to make payment or otherwise
comply with these Terms or any related agreement, Omron may (without liability and in addition to other remedies) cancel any unshipped portion of Products sold hereunder and stop any Products in transit until Buyer pays all
amounts, including amounts payable hereunder, whether or not then due,
which are owing to it by Buyer. Buyer shall in any event remain liable for all
unpaid accounts.
9. Cancellation; Etc. Orders are not subject to rescheduling or cancellation
unless Buyer indemnifies Omron against all related costs or expenses.
10. Force Majeure. Omron shall not be liable for any delay or failure in delivery
resulting from causes beyond its control, including earthquakes, fires, floods,
strikes or other labor disputes, shortage of labor or materials, accidents to
machinery, acts of sabotage, riots, delay in or lack of transportation or the
requirements of any government authority.
11. Shipping; Delivery. Unless otherwise expressly agreed in writing by Omron:
a. Shipments shall be by a carrier selected by Omron; Omron will not drop ship
except in “break down” situations.
b. Such carrier shall act as the agent of Buyer and delivery to such carrier shall
constitute delivery to Buyer;
c. All sales and shipments of Products shall be FOB shipping point (unless otherwise stated in writing by Omron), at which point title and risk of loss shall
pass from Omron to Buyer; provided that Omron shall retain a security interest in the Products until the full purchase price is paid;
d. Delivery and shipping dates are estimates only; and
e. Omron will package Products as it deems proper for protection against normal handling and extra charges apply to special conditions.
12. Claims. Any claim by Buyer against Omron for shortage or damage to the
Products occurring before delivery to the carrier must be presented in writing
to Omron within 30 days of receipt of shipment and include the original transportation bill signed by the carrier noting that the carrier received the Products
from Omron in the condition claimed.
13. Warranties. (a) Exclusive Warranty. Omron’s exclusive warranty is that the
Products will be free from defects in materials and workmanship for a period of
twelve months from the date of sale by Omron (or such other period expressed
in writing by Omron). Omron disclaims all other warranties, express or implied.
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION,
EXPRESS OR IMPLIED, ABOUT NON-INFRINGEMENT, MERCHANTABIL-
14.
15.
16.
17.
18.
ITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS.
BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE
PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR
INTENDED USE. Omron further disclaims all warranties and responsibility of
any type for claims or expenses based on infringement by the Products or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at Omron’s election, to (i) replace (in the form
originally shipped with Buyer responsible for labor charges for removal or
replacement thereof) the non-complying Product, (ii) repair the non-complying
Product, or (iii) repay or credit Buyer an amount equal to the purchase price of
the non-complying Product; provided that in no event shall Omron be responsible for warranty, repair, indemnity or any other claims or expenses regarding
the Products unless Omron’s analysis confirms that the Products were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate modification. Return of any Products by
Buyer must be approved in writing by Omron before shipment. Omron Companies shall not be liable for the suitability or unsuitability or the results from the
use of Products in combination with any electrical or electronic components,
circuits, system assemblies or any other materials or substances or environments. Any advice, recommendations or information given orally or in writing,
are not to be construed as an amendment or addition to the above warranty.
See http://www.omron247.com or contact your Omron representative for published information.
Limitation on Liability; Etc. OMRON COMPANIES SHALL NOT BE LIABLE
FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY
WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS
BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.
Further, in no event shall liability of Omron Companies exceed the individual
price of the Product on which liability is asserted.
Indemnities. Buyer shall indemnify and hold harmless Omron Companies and
their employees from and against all liabilities, losses, claims, costs and
expenses (including attorney's fees and expenses) related to any claim, investigation, litigation or proceeding (whether or not Omron is a party) which arises
or is alleged to arise from Buyer's acts or omissions under these Terms or in
any way with respect to the Products. Without limiting the foregoing, Buyer (at
its own expense) shall indemnify and hold harmless Omron and defend or settle any action brought against such Companies to the extent based on a claim
that any Product made to Buyer specifications infringed intellectual property
rights of another party.
Property; Confidentiality. Any intellectual property in the Products is the exclusive property of Omron Companies and Buyer shall not attempt to duplicate it
in any way without the written permission of Omron. Notwithstanding any
charges to Buyer for engineering or tooling, all engineering and tooling shall
remain the exclusive property of Omron. All information and materials supplied
by Omron to Buyer relating to the Products are confidential and proprietary,
and Buyer shall limit distribution thereof to its trusted employees and strictly
prevent disclosure to any third party.
Export Controls. Buyer shall comply with all applicable laws, regulations and
licenses regarding (i) export of products or information; (iii) sale of products to
“forbidden” or other proscribed persons; and (ii) disclosure to non-citizens of
regulated technology or information.
Miscellaneous. (a) Waiver. No failure or delay by Omron in exercising any right
and no course of dealing between Buyer and Omron shall operate as a waiver
of rights by Omron. (b) Assignment. Buyer may not assign its rights hereunder
without Omron's written consent. (c) Law. These Terms are governed by the
law of the jurisdiction of the home office of the Omron company from which
Buyer is purchasing the Products (without regard to conflict of law principles). (d) Amendment. These Terms constitute the entire agreement between
Buyer and Omron relating to the Products, and no provision may be changed
or waived unless in writing signed by the parties. (e) Severability. If any provision hereof is rendered ineffective or invalid, such provision shall not invalidate
any other provision. (f) Setoff. Buyer shall have no right to set off any amounts
against the amount owing in respect of this invoice. (g) Definitions. As used
herein, “including” means “including without limitation”; and “Omron Companies” (or similar words) mean Omron Corporation and any direct or indirect
subsidiary or affiliate thereof.
Certain Precautions on Specifications and Use
1. Suitability of Use. Omron Companies shall not be responsible for conformity
with any standards, codes or regulations which apply to the combination of the
Product in the Buyer’s application or use of the Product. At Buyer’s request,
Omron will provide applicable third party certification documents identifying
ratings and limitations of use which apply to the Product. This information by
itself is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine, system, or other application
or use. Buyer shall be solely responsible for determining appropriateness of
the particular Product with respect to Buyer’s application, product or system.
Buyer shall take application responsibility in all cases but the following is a
non-exhaustive list of applications for which particular attention must be given:
(i) Outdoor use, uses involving potential chemical contamination or electrical
interference, or conditions or uses not described in this document.
(ii) Use in consumer products or any use in significant quantities.
(iii) Energy control systems, combustion systems, railroad systems, aviation
systems, medical equipment, amusement machines, vehicles, safety equipment, and installations subject to separate industry or government regulations.
(iv) Systems, machines and equipment that could present a risk to life or property. Please know and observe all prohibitions of use applicable to this Product.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS
RISK TO LIFE OR PROPERTY OR IN LARGE QUANTITIES WITHOUT
ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO
2.
3.
4.
5.
ADDRESS THE RISKS, AND THAT THE OMRON’S PRODUCT IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
OVERALL EQUIPMENT OR SYSTEM.
Programmable Products. Omron Companies shall not be responsible for the
user’s programming of a programmable Product, or any consequence thereof.
Performance Data. Data presented in Omron Company websites, catalogs
and other materials is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of Omron’s
test conditions, and the user must correlate it to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations
of Liability.
Change in Specifications. Product specifications and accessories may be
changed at any time based on improvements and other reasons. It is our practice to change part numbers when published ratings or features are changed,
or when significant construction changes are made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers may be assigned to fix or establish key specifications for
your application. Please consult with your Omron’s representative at any time
to confirm actual specifications of purchased Product.
Errors and Omissions. Information presented by Omron Companies has been
checked and is believed to be accurate; however, no responsibility is assumed
for clerical, typographical or proofreading errors or omissions.
OMRON AUTOMATION AND SAFETY • THE AMERICAS HEADQUARTERS • Chicago, IL USA • 847.843.7900 • 800.556.6766 • www.omron247.com
OMRON CANADA, INC. • HEAD OFFICE
Toronto, ON, Canada • 416.286.6465 • 866.986.6766 • www.omron247.com
OMRON ARGENTINA • SALES OFFICE
Cono Sur • 54.11.4783.5300
OMRON ELECTRONICS DE MEXICO • HEAD OFFICE
México DF • 52.55.59.01.43.00 • 01-800-226-6766 • mela@omron.com
OMRON CHILE • SALES OFFICE
Santiago • 56.9.9917.3920
OMRON ELECTRONICS DE MEXICO • SALES OFFICE
Apodaca, N.L. • 52.81.11.56.99.20 • 01-800-226-6766 • mela@omron.com
OTHER OMRON LATIN AMERICA SALES
54.11.4783.5300
OMRON ELETRÔNICA DO BRASIL LTDA • HEAD OFFICE
São Paulo, SP, Brasil • 55.11.2101.6300 • www.omron.com.br
OMRON EUROPE B.V. • Wegalaan 67-69, NL-2132 JD, Hoofddorp, The Netherlands. • +31 (0) 23 568 13 00 • www.industrial.omron.eu
Authorized Distributor:
Automation Control Systems
• Machine Automation Controllers (MAC) • Programmable Controllers (PLC)
• Operator interfaces (HMI) • Distributed I/O • Software
Drives & Motion Controls
• Servo & AC Drives • Motion Controllers & Encoders
Temperature & Process Controllers
• Single and Multi-loop Controllers
Sensors & Vision
• Proximity Sensors • Photoelectric Sensors • Fiber-Optic Sensors
• Amplified Photomicrosensors • Measurement Sensors
• Ultrasonic Sensors • Vision Sensors
Industrial Components
• RFID/Code Readers • Relays • Pushbuttons & Indicators
• Limit and Basic Switches • Timers • Counters • Metering Devices
• Power Supplies
Safety
• Laser Scanners • Safety Mats • Edges and Bumpers • Programmable Safety
Controllers • Light Curtains • Safety Relays • Safety Interlock Switches
/&
Note: Specifications are subject to change.
Printed on recycled paper.
© 2014 Omron Electronics LLC