NE0A-SCPU01

NE0A-SCPU01

  • 厂商:

    OMRON(欧姆龙)

  • 封装:

  • 描述:

    NE0A-SCPU01 - Safety Network Controller - Omron Electronics LLC

  • 详情介绍
  • 数据手册
  • 价格&库存
NE0A-SCPU01 数据手册
Safety Network Controller NE0A-SCPU01 CSM_NE0A-SCPU01_DS_E_4_1 New Lineup for Safety Applications with Up to 12 Inputs • Circuits for the required safety category are easy to build. • The safety circuits you create can be registered as templates and reused, for easy standardization. • A wide range of TÜV-certified templates is also available. • The NE0A operating conditions can be monitored from a standard DeviceNet Master. • Network distribution is possible by combining with an NE1A Safety Controller. • EN954-1 (Cat.4), ISO13849-1 (PLe), and IEC 61508 SIL3 certification. Ordering Information Name No. of I/O points Safety inputs Test outputs Safety outputs Model Unit version Safety Network Controllers 12 * 2 6 NE0A-SCPU01 Ver. 1.0 Note: 1. The standard NE0A Safety Network Controller is equipped with spring-cage terminal blocks, but screw terminal blocks are available if desired, e.g., to replace previous terminals. 2. Network Configurator version 2.1@ or higher must be used when using a NE0A-SCPU01 Safety Network Controller. * When using the NE0A-SCPU01 as a standalone Controller, one input each is required for the feedback input and manual restart. Specifications Certified Standards Certification body Standard NFPA 79-2007 ISO13849-1:1999 IEC61508 part1-7/12.98-05.00 IEC61131-2:2007 EN ISO13849-2:2003 EN ISO 13850:2006 EN954-1:1996 EN61000-6-4:2007 EN61000-6-2:2005 EN60204-1:2006 ANSI RIA15.06-1999 ANSI B11.19-2003 UL508 UL1604 UL1998 NFPA79 IEC61508 CSA22.2 No.142 CSA22.2 No.213 Specifications Communications 11 to 25 VDC supplied via communicapower supply voltage tions connector Internal circuit power supply voltage (V0) *1 I/O power supply voltage (V1, V2) *1 Communications power supply 20.4 to 26.4 VDC (24 VDC −15%/+10%) TÜV Rheinland 24 VDC, 15 mA Current Internal circoncuit power sumpsupply tion I/O power supply *2 Noise immunity 24 VDC, 110 mA 24 VDC, 80 mA (Input) 80 mA (Output) Conforms to IEC61131-2. 10 to 57 Hz: 0.35 mm, 57 to 150 Hz: 50 m/s2 150 m/s2 : 11 ms DIN Track (IEC 60715 TH35-7.5/TH35-15) −10 to 55°C 10% to 95% (with no condensation) Overvoltage category II UL Vibration resistance Shock resistance Mounting method Ambient operating temperature Ambient operating humidity Ambient storage tem−40 to 70°C perature Degree of protection Serial I/F Weight IP20 USB version 1.1 440 g max. *1. V0-G0: Internal control circuit V1-G1: For external input device, test output V2-G2: For external output device *2. Not including power consumption for external devices. 1 NE0A-SCPU01 Safety Input Specifications Input type ON voltage OFF voltage OFF current Input current Sinking inputs (PNP) 11 VDC min. between each terminal and ground 5 VDC max. between each terminal and ground 1 mA max. 4.5 mA Test Output Specifications Output type Rated output current ON residual voltage Sourcing outputs (PNP) 60 mA 1.2 V max. between each output terminal and V1 Leakage current 0.1 mA max. Safety Output Specifications Output type Rated output current ON residual voltage Sourcing outputs (PNP) 0.5 A max./output 1.2 V max. between each output terminal and V2 Leakage current 0.1 mA max. DeviceNet Communications Specifications Communications protocol Connection form Communications speed Communications media DeviceNet compliant Multi-drop system and T-branch system can be combined (for trunk line and branch lines) 500/250/125 kbps Special cable, 5 conductors (2 for communications, 2 for power supply, 1 for shielding) Communications speed Communications distance 500 kbps 250 kbps 125 kbps Communications power 11 to 25 VDC supply No. of connectable nodes Safety I/O communications 63 Safety Slave function • Max. no. of connections: 2 (one each for inputs and outputs) Multi-cast inputs can be used to enable communications with up to 15 Safety Masters. • Connection type: Single-cast, multi-cast Standard Slave function • Max. no. of connections: 2 • Connection type: Poll, bit-strobe, COS, cyclic Max. message length: 502 bytes Max. network length 100 m max. (100 m max.) 250 m max. (100 m max.) 500 m max. (100 m max.) 6 m max. Branch length Total branch length 39 m max. 78 m max. 156 m max. Note: Figures in parentheses ( ) indicate values when a thin cable is used. Standard I/O communications Message communications 2 NE0A-SCPU01 Functions The following function blocks are available for designing safety circuits with the NE0A-SCPU01. These function blocks can be selected and assembled using the interactive wizard format to efficiently design safety applications. Classification of function block for safety circuit designs Application The following six parts can be selected for use as safety input devices. For Category 3 or 4 compliance, the filter monitoring time between signals can also be adjusted with redundant wiring for the necessary safety devices. Function blocks for safety input devices and setting input filter times Emergency Stop Switches Safety Door Switches Limit Switches Safety Light Curtains Enabling Switches Mode Selectors Select a Safety Light Curtain as the safety input device, and select a muting function when required. No setting Logic function blocks for input conditions OR operation AND/OR operations AND operation OR/AND operations Function blocks for resets Logic function blocks for output conditions Selects manual or auto reset. For applications such as stopping all outputs for multiple safety devices. No setting AND operation OR/AND operations Function blocks for setting the welded contact check No setting EDM Uses the ON/OFF status of the safety signal exactly as it is. Selects the interlock conditions for the safety signal. For switching maintenance areas with a Mode Selector. For applications such as a Safety Light Curtain muting function. Uses the ON/OFF status from the safety input device exactly as it is. Used to check the safety condition of an output device. No checking of the output device (used for Category 2 or lower). Used to check for contact welding in a Relay or Contactor. Also used to change the setting for monitoring time. Function blocks for safety Logic output devices and setting For setting an auxiliary output (to output an error condition) and for setting the output delay. output delay times Note: There is a possibility that safety cannot be maintained when an OR part or an AND/OR part is selected for input logic, or an OR/AND part is selected for output logic. Sufficiently confirm safety prior to use. 3 NE0A-SCPU01 Internal Circuit Diagrams NE0A-SCPU01 DC-DC Converter (Non-insulated) V0 24 VDC G0 V+ CAN H Shield CAN L V− DeviceNet Physical Layer V1 G1 T0 T1 IN0 Safety Input Circuit Test Output Circuit 24 VDC IN8 DC-DC Converter (Non-insulated) Internal Circuit T0 T1 IN9 IN10 IN11 V2 Safety Output Circuit G2 24 VDC D+ USB D− OUT0 L L OUT5 Terminal No. ----1 11 24 34 2 to 10 21 to 23 12 to 20 31 to 33 25 to 30 35 to 40 Terminal name V0 G0 V1 G1 V2 G2 IN0 to IN8 IN9 to IN11 T0 to T1 OUT0 to OUT5 G2 Description Power supply terminal for internal circuit (24 VDC) Power supply terminal for external input device and test output (24 VDC) Power supply terminal for external output device (24 VDC) Safety input terminal Terminals IN10 and IN11 are used only for connecting a reset switch or EDM feedback. Test output terminal Connected to IN0 to IN11 safety inputs. T0 and T1 output test pulses with different patterns. The T0 terminals are internally connected and the T1 terminals are internally connected. Safety output terminals Common terminal Terminals 34 to 40 are internally connected. 4 NE0A-SCPU01 Dimensions NE0A-SCPU01 (Unit: mm) (90) 80 71.4 190 Safety Precautions Be sure to read the following operation manual for precautions and other details required for correct use of the Safety Network Controller. DeviceNet Safety Safety Network Controller NE0A Series operation Manual (Cat. No. Z916) 5 Read and Understand This Catal og Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. Warranty and Limitations of Li abilit y WARRANTY OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified) from date of sale by OMRON. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED. LIMITATIONS OF LIABILITY OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY. In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted. IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR. Application Considerations SUITABILITY FOR USE OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's application or use of the products. At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product, machine, system, or other application or use. The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible uses of the products, nor is it intended to imply that the uses listed may be suitable for the products: • Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog. • Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles, safety equipment, and installations subject to separate industry or government regulations. • Systems, machines, and equipment that could present a risk to life or property. Please know and observe all prohibitions of use applicable to the products. NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM. PROGRAMMABLE PRODUCTS OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof. Disclaimers CHANGE IN SPECIFICATIONS Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made. However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual specifications of purchased products. DIMENSIONS AND WEIGHTS Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown. PERFORMANCE DATA Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON Warranty and Limitations of Liability. ERRORS AND OMISSIONS The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical, typographical, or proofreading errors, or omissions. 2010.3 In the i nter est of product improvement, specifications are subject t o change without notice. Indust rial Automat ion Company http://www.i a.omron.com/ OMRON Corporation (c)Copyright OMRON Corporation 2010 All Right Reserved.
NE0A-SCPU01
1. 物料型号: - 型号:NE0A-SCPU01 - 版本:Ver. 1.0

2. 器件简介: - NE0A-SCPU01是一个安全网络控制器,具有多达12个输入,适用于安全应用。它支持从标准DeviceNet主机监控NE0A工作条件,并可通过与NE1A安全控制器组合进行网络分配。该设备具有EN954-1 (Cat.4)、ISO13849-1 (PLe) 和 IEC 61508 SIL3认证。

3. 引脚分配: - 内部电路电源端口:VO, GO - 外部输入设备和测试输出电源端口:V1, G1 - 外部输出设备电源端口:V2, G2 - 安全输入端子:INO至IN8(IN10和IN11仅用于连接复位开关或EDM反馈) - 测试输出端子:TO至T1(与INO至IN11安全输入相连,输出不同模式的测试脉冲) - 安全输出端子:OUT0至OUT5 - 公共端子:G2(34至40号端子内部连接)

4. 参数特性: - 通信电源电压:11至25VDC通过通信连接器供应 - 内部电路电源电压:20.4至26.4VDC - I/O电源电压:24VDC,输入80mA,输出80mA - 过电压类别、抗干扰性:符合IEC61131-2标准 - 抗震性能:150 m/s²:11 ms - 工作温度:-10至55°C - 工作湿度:10%至95%(无凝结) - 存储温度:40至70°C - 保护等级:IP20 - 串行接口:USB版本1.1 - 重量:最大440g

5. 功能详解: - 设计安全电路时可用的功能块包括安全输入设备和设置输入滤波时间、输入条件的逻辑功能块、复位逻辑功能块、输出条件的逻辑功能块、设置焊接触点检查的功能块以及安全输出设备和设置输出延迟时间的功能块。

6. 应用信息: - 该产品适用于需要安全控制的应用,如机器安全、过程安全等。它也可以用于户外使用、可能涉及化学污染或电气干扰的场合,或者未在目录中描述的条件或用途。

7. 封装信息: - 封装:DIN轨道安装(IEC 60715 TH35-7.5/TH35-15)。
NE0A-SCPU01 价格&库存

很抱歉,暂时无法提供与“NE0A-SCPU01”相匹配的价格&库存,您可以联系我们找货

免费人工找货