NX-series Analog I/O Unit
NX-AD/DA
CSM_NX-AD_DA_DS_E_3_3
Analog inputs and outputs to meet
all machine control needs, from
general purpose to high-speed
synchronous control
• Connect to other NX I/O Units and EtherCAT Coupler
Units using the high-speed NX-bus
• Separate modules for voltage and current
Features
• Up to eight analog inputs per unit (NX-AD)
• Up to four analog outputs per unit (NX-DA)
• Free-run refreshing or synchronous I/O refreshing with the NX1P2 CPU Unit or EtherCAT Coupler Unit
• Sampling times down to 10 μs per channel and high resolution of 1/30,000
• Single-ended input type with built-in power supply terminals for low power equipments or noize-resistant differential
input type (NX-AD)
• Selecting channel to use, moving average, input disconnection detection, over range/under range detection, and
user calibration
• Detachable front connector with screwless Push-In Plus terminals for easy installation and maintenance
• Compact with a width of 12 mm per unit
• Connect to the CJ PLC using the EtherNet/IPTM bus coupler
Sysmac is a trademark or registered trademark of OMRON Corporation in Japan and other countries for OMRON factory automation products.
EtherCAT is a registered trademark and patented technology, licensed by Beckhoff Automation GmbH, Germany.
EtherNet/IPTM is a trademark of ODVA.
Other company names and product names in this document are the trademarks or registered trademarks of their respective companies.
1
NX-AD/DA
System Configurations
Connected to a CPU Unit or Communication Control Unit
The following figure shows a system configuration when NX Units are connected to an NX-series CPU Unit.
Support software
(Sysmac Studio)
● CPU Rack
NX-series CPU Unit
NX1P2-@@@@@@@
Connection to built-in
EtherNet/IP port
Built-in EtherCAT port
End Cover
NX Units
EtherCAT Slave Terminal
EtherCAT
NX Units
EtherCAT Coupler Unit
Note: For whether an NX Unit can be connected to the CPU Unit, refer to the version information.
Connected to an EtherCAT Coupler Unit
The following figure shows an example of the system configuration when an EtherCAT Coupler Unit is used as a Communications Coupler Unit.
Support software
(Sysmac Studio)
Connection to peripheral USB port
or built-in EtherNet/IPTM port on
CPU Unit or Industrial PC *1
EtherCAT master *2
NJ/NX-series CPU Unit, NY-series Industrial PC, or
master from another manufacturer
.xml
ESI files
Built-in EtherCAT port
Support software
(Sysmac Studio)
●EtherCAT Slave Terminal
Communications cable
Ethernet cables
Peripheral USB port.
NX Series
EtherCAT Coupler Unit
NX-ECC20@
Connection to peripheral USB
port on EtherCAT Coupler Unit
.xml
ESI files
NX Units
End Cover
*1. The connection method for the Sysmac Studio depends on the model of the CPU Unit or Industrial PC.
*2. An EtherCAT Slave Terminal cannot be connected to any of the OMRON CJ1W-NC@81/@82 Position Control Units even though they can
operate as EtherCAT masters.
Note: For whether an NX Unit can be connected to the Communications Coupler Unit, refer to the version information.
2
NX-AD/DA
System Configuration in the Case of a Communication Control Unit
The following figure shows a system configuration when a group of NX Units is connected to an NX-series Communication Control Unit. To
configure a Safety Network Controller, mount the Safety CPU Unit, which is one of the NX Units, to the CPU Rack of the Communication Control
Unit.
EtherNet/IP Unit
EtherNet/IP port
Support Software
Communications cable
Ethernet cables
CPU Rack
NX-series Communication Control Unit
NX-CSG320
Network Configurator
End Cover
Ethernet switch
NX Units
• Safety CPU Unit
• Safety I/O Unit
• Other NX Units
EDS files
CIP Safety on EtherNet/IP device
Note: For whether an NX Unit can be connected to the Communication Control Unit, refer to the version information.
3
NX-AD/DA
Model Number Structure
NX-@@@@@@
(1)
(2) (3)
(4)
(3) I/O range
(2) Number of points
(1) Unit type
No.
Specification
No.
Specification
No.
AD
Analog input
2
2 points
1
Specification
---
DA
Analog output
3
4 points
2
4 to 20 mA
4
8 points
6
-10 to +10 V
(4) Other specifications
Analog Input Units
I/O refreshing method
Free-Run refreshing *1 only
Switching synchronous
I/O refreshing *2
and Free-Run refreshing
Single-ended
Yes
---
Differential
Yes
---
Differential
---
Yes
No.
Resolution
Conversion time
Input method
03
1/8000
250 μs/point
04
1/8000
250 μs/point
08
1/30000
10 μs/point
*1 Free-Run refreshing
*2 Synchronous I/O refreshing
Analog Output Units
I/O refreshing method
No.
Switching synchronous
I/O refreshing *2
and Free-Run refreshing
Resolution
Conversion time
03
1/8000
250 μs/point
Yes
---
05
1/30000
10 μs/point
---
Yes
Free-Run refreshing *1 only
*1 Free-Run refreshing
*2 Synchronous I/O refreshing
4
NX-AD/DA
Ordering Information
Applicable standards
Refer to the OMRON website (www.ia.omron.com) or ask your OMRON representative for the most recent applicable standards for each model.
Analog Input Units
Specification
Product name
Number
of points
Input
range
Resolution
1/8000
Conversion
value, decimal
number
(0 to 100%)
-4000 to 4000
Over all
accuracy
(25°C)
±0.2%
(full scale)
Input
method
Single-ended
input
Differential
input
Conversion
time
Input
impedance
250 μs/
point
Free-Run
refreshing
10 μs/
point
Selectable
Synchronous
I/O refreshing
or Free-Run
refreshing
250 μs/
point
Free-Run
refreshing
2 points
Voltage Input type
4 points
1/30000
±0.1%
-15000 to 15000
(full scale)
1/8000
-4000 to 4000
±0.2%
(full scale)
-10 to
+10 V
Differential
input
Single-ended
input
Differential
input
1 MΩ min.
1/30000
1/8000
±0.1%
-15000 to 15000
(full scale)
-4000 to 4000
±0.2%
(full scale)
Differential
input
Single-ended
input
Differential
input
10 μs/
point
Selectable
Synchronous
I/O refreshing
or Free-Run
refreshing
250 μs/
point
Free-Run
refreshing
10 μs/
point
Selectable
Synchronous
I/O refreshing
or Free-Run
refreshing
250 μs/
point
Free-Run
refreshing
10 μs/
point
Selectable
Synchronous
I/O refreshing
or Free-Run
refreshing
8 points
1/30000
1/8000
±0.1%
-15000 to 15000
(full scale)
0 to 8000
±0.2%
(full scale)
Differential
input
Single-ended
input
Differential
input
2 points
1/30000
0 to 30000
Current Input type
1/8000
4 points
0 to 8000
±0.1%
(full scale)
±0.2%
(full scale)
4 to
20 mA
1/30000
1/8000
0 to 30000
±0.1%
(full scale)
0 to 8000
±0.2%
(full scale)
Differential
input
Single-ended
input
Differential
input
Differential
input
Single-ended
input
Differential
input
250 Ω
250 μs/
point
Free-Run
refreshing
10 μs/
point
Selectable
Synchronous
I/O refreshing
or Free-Run
refreshing
250 μs/
point
Free-Run
refreshing
85 Ω
8 points
1/30000
0 to 30000
±0.1%
(full scale)
Differential
input
I/O
refreshing
method
10 μs/
point
Selectable
Synchronous
I/O refreshing
or Free-Run
refreshing
Model
NX-AD2603
NX-AD2604
NX-AD2608
NX-AD3603
NX-AD3604
NX-AD3608
NX-AD4603
NX-AD4604
NX-AD4608
NX-AD2203
NX-AD2204
NX-AD2208
NX-AD3203
NX-AD3204
NX-AD3208
NX-AD4203
NX-AD4204
NX-AD4208
5
NX-AD/DA
Analog Output Units
Specification
Product name
Voltage Output type
Number of
points
Output
range
Resolution
Output setting value,
decimal number
(0 to 100%)
Model
±0.3%
(full scale)
250 μs/point
Free-Run refreshing
NX-DA2603
1/30000
-15000 to 15000
±0.1%
(full scale)
10 μs/point
Selectable Synchronous
I/O refreshing or FreeRun refreshing
NX-DA2605
1/8000
-4000 to 4000
±0.3%
(full scale)
250 μs/point
Free-Run refreshing
NX-DA3603
1/30000
-15000 to 15000
±0.1%
(full scale)
10 μs/point
Selectable Synchronous
I/O refreshing or FreeRun refreshing
NX-DA3605
1/8000
0 to 8000
±0.3%
(full scale)
250 μs/point
Free-Run refreshing
NX-DA2203
1/30000
0 to 30000
±0.1%
(full scale)
10 μs/point
Selectable Synchronous
I/O refreshing or FreeRun refreshing
NX-DA2205
1/8000
0 to 8000
±0.3%
(full scale)
250 μs/point
Free-Run refreshing
NX-DA3203
10 μs/point
Selectable Synchronous
I/O refreshing or FreeRun refreshing
NX-DA3205
2 points
4 to
20 mA
I/O refreshing method
-4000 to 4000
4 points
Current Output type
Conversion
time
1/8000
2 points
-10 to
+10 V
Over all
accuracy
(25°C)
4 points
1/30000
±0.1%
(full scale)
0 to 30000
Optional Products
Product name
Unit/Terminal Block Coding Pins
Specification
Model
For 10 Units
(Terminal Block: 30 pins, Unit: 30 pins)
NX-AUX02
Specification
Product name
No. of terminals
Terminal number
indications
Ground terminal mark
Terminal current
capacity
8
Terminal Block
12
16
Model
NX-TBA082
A/B
None
10 A
NX-TBA122
NX-TBA162
Accessories
Not included.
6
NX-AD/DA
General Specifications
Item
Enclosure
Specification
Mounted in a panel
Grounding method
Ground to 100 Ω or less
Ambient operating temperature
0 to 55°C
Ambient operating humidity
10% to 95% (with no condensation or icing)
Atmosphere
Must be free from corrosive gases.
Ambient storage temperature
−25 to 70°C (with no condensation or icing)
Altitude
2,000 m max.
Pollution degree
Operating
Noise immunity
environment
Overvoltage category
2 or less: Meets IEC 61010-2-201.
2 kV on power supply line (Conforms to IEC61000-4-4.)
Category II: Meets IEC 61010-2-201.
EMC immunity level
Zone B
Vibration resistance
Conforms to IEC 60068-2-6.
5 to 8.4 Hz with 3.5-mm amplitude, 8.4 to 150 Hz, acceleration of 9.8 m/s2, 100 min each
in X, Y, and Z directions
(10 sweeps of 10 min each = 100 min total)
Shock resistance
IConforms to IEC 60068-2-27. 147 m/s2, 3 times each in X, Y, and Z directions
cULus: Listed (UL508), ANSI/ISA 12.12.01, EU: EN 61131-2, C-Tick or RCM,
KC Registration, NK, LR
* Refer to the OMRON website (www.ia.omron.com) or ask your OMRON representative for the most recent applicable standards for each model.
Applicable standards *
7
NX-AD/DA
Analog Input Unit Specifications
Analog Input Unit (voltage input type) 2 points NX-AD2603
Unit name
Analog Input Unit (voltage input type)
Model
NX-AD2603
Number of points
2 points
External connection
terminals
Screwless clamping terminal block (8
terminals)
I/O refreshing method
Free-Run refreshing
Input method
Single-ended input
Input range
-10 to +10 V
Input conversion range
-5 to 105% (full scale)
Absolute maximum
rating
±15 V
Input impedance
1 MΩ min.
TS indicator
Indicator
Resolution
1/8000 (full scale)
25°C
Overall
accuracy 0 to 55°C
±0.2% (full scale)
Conversion time
250 μs/point
±0.4% (full scale)
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
Supply from the NX bus
Current capacity of I/O
power supply terminal
IOV: 0.1 A/terminal max.,
IOG: 0.1 A/terminal max.
NX Unit power
consumption
Weight
• Connected to a CPU Unit or
Communication Control Unit
1.35 W max.
• Connected to a Communications
Coupler Unit
1.05 W max.
I/O current consumption No consumption
70 g max.
IOV
Terminal block
Input1+ to 2+
AMP
1 MΩ
Circuit layout
IOG
AG
NX bus
connector
(left)
Installation orientation
and restrictions
AG: Analog circuit internal GND
I/O power supply +
I/O power supply +
I/O power supply −
I/O power supply −
NX bus
connector
(right)
Installation orientation:
• Connected to a CPU Unit or Communication Control Unit: Possible in upright installation.
• Connected to a Communications Coupler Unit: Possible in 6 orientations.
Restrictions: No restrictions
Additional I/O
Power Supply Unit
A1
B1
IOV
IOV
IOG
IOG
Voltage Input Unit
NX-AD2603
A1
B1
Input1+ Input2+
Input +
24 V (Sensor power supply +)
Terminal connection
diagram
0 V (Sensor power supply − / Input −)
IOV
24 VDC
Three-wire sensor
A8
Input disconnection
detection
IOV
IOV
IOV
IOG
IOG
IOG
IOG
NC
NC
B8
A8
B8
The NC terminal is not connected to the internal circuit.
Not supported.
8
NX-AD/DA
Analog Input Unit (voltage input type) 2 points NX-AD2604
Unit name
Analog Input Unit (voltage input type)
Model
NX-AD2604
Number of points
2 points
External connection
terminals
Screwless clamping terminal block (8
terminals)
I/O refreshing method
Free-Run refreshing
Input method
Differential Input
Input range
-10 to +10 V
Input conversion range
-5 to 105% (full scale)
Absolute maximum
rating
±15 V
Input impedance
1 MΩ min.
TS indicator
Indicator
Resolution
1/8000 (full scale)
25°C
Overall
accuracy 0 to 55°C
±0.2% (full scale)
Conversion time
250 μs/point
±0.4% (full scale)
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
No supply
Current capacity of I/O
power supply terminal
Without I/O power supply terminals
NX Unit power
consumption
Weight
• Connected to a CPU Unit or
Communication Control Unit
1.35 W max.
• Connected to a Communications
Coupler Unit
1.05 W max.
I/O current consumption No consumption
70 g max.
Input1+ to 2+
AMP
Terminal block
Input1− to 2−
510 KΩ
Circuit layout
510 KΩ
AG
AG
NX bus
connector
(left)
Installation orientation
and restrictions
AG: Analog circuit internal GND
I/O power supply +
I/O power supply +
I/O power supply −
I/O power supply −
NX bus
connector
(right)
Installation orientation:
• Connected to a CPU Unit or Communication Control Unit: Possible in upright installation.
• Connected to a Communications Coupler Unit: Possible in 6 orientations.
Restrictions: No restrictions
Voltage Input Unit
NX-AD2604
A1
B1
Input1+ Input2+
Input +
Input −
Terminal connection
diagram
Input1− Input2−
AG
AG
NC
NC
A8
Input disconnection
detection
AG terminal is connected to 0 V of analog circuit inside the Unit.
B8 It is not necessary to wire AG terminal normally.
Not supported.
9
NX-AD/DA
Analog Input Unit (voltage input type) 2 points NX-AD2608
Unit name
Analog Input Unit (voltage input type)
Model
NX-AD2608
Number of points
2 points
External connection
terminals
Screwless clamping terminal block (8
terminals)
I/O refreshing method
Selectable Synchronous I/O refreshing or Free-Run refreshing
TS indicator
Indicator
Input method
Differential Input
Input range
-10 to +10 V
Input conversion range
-5 to 105% (full scale)
Absolute maximum
rating
±15 V
Input impedance
1 MΩ min.
Resolution
1/30000 (full scale)
25°C
Overall
accuracy 0 to 55°C
±0.1% (full scale)
Conversion time
10 μs/point
±0.2% (full scale)
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
No supply
Current capacity of I/O
power supply terminal
Without I/O power supply terminals
NX Unit power
consumption
Weight
• Connected to a CPU Unit or
Communication Control Unit
1.35 W max.
• Connected to a Communications
Coupler Unit
1.05 W max.
I/O current consumption No consumption
70 g max.
Input1+ to 2+
AMP
Terminal block
Input1− to 2−
510 KΩ
Circuit layout
510 KΩ
AG
AG
NX bus
connector
(left)
Installation orientation
and restrictions
AG: Analog circuit internal GND
I/O power supply +
I/O power supply +
I/O power supply −
I/O power supply −
NX bus
connector
(right)
Installation orientation:
• Connected to a CPU Unit or Communication Control Unit: Possible in upright installation.
• Connected to a Communications Coupler Unit: Possible in 6 orientations.
Restrictions: No restrictions
Voltage Input Unit
NX-AD2608
A1
B1
Input +
Input1+ Input2+
Input −
Input1− Input2−
Terminal connection
diagram
AG
AG
NC
NC
A8
Input disconnection
detection
B8
AG terminal is connected to 0 V of analog circuit inside the Unit.
It is not necessary to wire AG terminal normally.
Not supported.
10
NX-AD/DA
Analog Input Unit (voltage input type) 4 points NX-AD3603
Unit name
Analog Input Unit (voltage input type)
Model
NX-AD3603
Number of points
4 points
External connection
terminals
Screwless clamping terminal block (12
terminals)
I/O refreshing method
Free-Run refreshing
Input method
Single-ended input
Input range
-10 to +10 V
Input conversion range
-5 to 105% (full scale)
Absolute maximum
rating
±15 V
Input impedance
1 MΩ min.
TS indicator
Indicator
Resolution
1/8000 (full scale)
25°C
Overall
accuracy 0 to 55°C
±0.2% (full scale)
Conversion time
250 μs/point
±0.4% (full scale)
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
Supply from the NX bus
Current capacity of I/O
power supply terminal
IOV: 0.1 A/terminal max.,
IOG: 0.1 A/terminal max.
NX Unit power
consumption
Weight
• Connected to a CPU Unit or
Communication Control Unit
1.35 W max.
• Connected to a Communications
Coupler Unit
1.10 W max.
I/O current consumption No consumption
70 g max.
IOV
Terminal block
Input1+ to 4+
AMP
1MΩ
Circuit layout
IOG
AG
NX bus
connector
(left)
Installation orientation
and restrictions
I/O power supply +
I/O power supply −
I/O power supply −
A1
B1
IOV
IOG
Voltage Input Unit
NX-AD3603
A1
IOV
B1
Input1+ Input2+
IOG
24 VDC
Input +
IOV
IOV
24 V (Sensor power supply +)
IOG
IOG
0 V (Sensor power supply − / Input −)
Input3+ Input4+
A8
Input disconnection
detection
NX bus
connector
(right)
Installation orientation:
• Connected to a CPU Unit or Communication Control Unit: Possible in upright installation.
• Connected to a Communications Coupler Unit: Possible in 6 orientations.
Restrictions: No restrictions
Additional I/O
Power Supply Unit
Terminal connection
diagram
AG: Analog circuit internal GND
I/O power supply +
IOV
IOV
IOG
IOG
B8
A8
IOV
IOV
IOG
IOG
Three-wire sensor
B8
Not supported.
11
NX-AD/DA
Analog Input Unit (voltage input type) 4 points NX-AD3604
Unit name
Analog Input Unit (voltage input type)
Model
NX-AD3604
Number of points
4 points
External connection
terminals
Screwless clamping terminal block (12
terminals)
I/O refreshing method
Free-Run refreshing
Input method
Differential Input
Input range
-10 to +10 V
Input conversion range
-5 to 105% (full scale)
Absolute maximum
rating
±15 V
Input impedance
1 MΩ min.
TS indicator
Indicator
Resolution
1/8000 (full scale)
25°C
Overall
accuracy 0 to 55°C
±0.2% (full scale)
Conversion time
250 μs/point
±0.4% (full scale)
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
No supply
Current capacity of I/O
power supply terminal
Without I/O power supply terminals
NX Unit power
consumption
Weight
• Connected to a CPU Unit or
Communication Control Unit
1.35 W max.
• Connected to a Communications
Coupler Unit
1.10 W max.
I/O current consumption No consumption
70 g max.
Input1+ to 4+
AMP
Terminal block
Input1− to 4−
510 KΩ
Circuit layout
510 KΩ
AG
AG
NX bus
connector
(left)
Installation orientation
and restrictions
AG: Analog circuit internal GND
I/O power supply +
I/O power supply +
I/O power supply −
I/O power supply −
NX bus
connector
(right)
Installation orientation:
• Connected to a CPU Unit or Communication Control Unit: Possible in upright installation.
• Connected to a Communications Coupler Unit: Possible in 6 orientations.
Restrictions: No restrictions
Voltage Input Unit
NX-AD3604
A1
Terminal connection
diagram
B1
Input1+ Input2+
Input +
Input1− Input2−
Input −
Input3+ Input4+
Input3− Input4−
AG
AG
AG
AG
A8
Input disconnection
detection
AG terminal is connected to 0 V of analog circuit inside the Unit.
B8 It is not necessary to wire AG terminal normally.
Not supported.
12
NX-AD/DA
Analog Input Unit (voltage input type) 4 points NX-AD3608
Unit name
Analog Input Unit (voltage input type)
Model
NX-AD3608
Number of points
4 points
External connection
terminals
Screwless clamping terminal block (12
terminals)
I/O refreshing method
Selectable Synchronous I/O refreshing or Free-Run refreshing
TS indicator
Indicator
Input method
Differential Input
Input range
-10 to +10 V
Input conversion range
-5 to 105% (full scale)
Absolute maximum
rating
±15 V
Input impedance
1 MΩ min.
Resolution
1/30000 (full scale)
25°C
Overall
accuracy 0 to 55°C
±0.1% (full scale)
Conversion time
10 μs/point
±0.2% (full scale)
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
No supply
Current capacity of I/O
power supply terminal
Without I/O power supply terminals
NX Unit power
consumption
Weight
• Connected to a CPU Unit or
Communication Control Unit
1.45 W max.
• Connected to a Communications
Coupler Unit
1.10 W max.
I/O current consumption No consumption
70 g max.
Input1+ to 4+
AMP
Terminal block
Input1− to 4−
510 KΩ
Circuit layout
510 KΩ
AG
AG
NX bus
connector
(left)
Installation orientation
and restrictions
AG: Analog circuit internal GND
I/O power supply +
I/O power supply +
I/O power supply −
I/O power supply −
NX bus
connector
(right)
Installation orientation:
• Connected to a CPU Unit or Communication Control Unit: Possible in upright installation.
• Connected to a Communications Coupler Unit: Possible in 6 orientations.
Restrictions: No restrictions
Voltage Input Unit
NX-AD3608
A1
Terminal connection
diagram
B1
Input1+ Input2+
Input +
Input1− Input2−
Input −
Input3+ Input4+
Input3− Input4−
AG
AG
AG
AG
A8
Input disconnection
detection
AG terminal is connected to 0 V of analog circuit inside the Unit.
B8 It is not necessary to wire AG terminal normally.
Not supported.
13
NX-AD/DA
Analog Input Unit (voltage input type) 8 points NX-AD4603
Unit name
Analog Input Unit (voltage input type)
Model
NX-AD4603
Number of points
8 points
External connection
terminals
Screwless clamping terminal block (16
terminals)
I/O refreshing method
Free-Run refreshing
Input method
Single-ended input
Input range
-10 to +10 V
Input conversion range
-5 to 105% (full scale)
Absolute maximum
rating
±15 V
Input impedance
1 MΩ min.
TS indicator
Indicator
Resolution
1/8000 (full scale)
25°C
Overall
accuracy 0 to 55°C
±0.2% (full scale)
Conversion time
250 μs/point
±0.4% (full scale)
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
Supply from the NX bus
Current capacity of I/O
power supply terminal
IOG: 0.1 A/terminal max.
NX Unit power
consumption
Weight
• Connected to a CPU Unit or
Communication Control Unit
1.45 W max.
• Connected to a Communications
Coupler Unit
1.15 W max.
I/O current consumption No consumption
70 g max.
Input1+ to 8+
AMP
1 MΩ
Terminal block
IOG
Circuit layout
AG
NX bus
connector
(left)
Installation orientation
and restrictions
I/O power supply +
I/O power supply −
I/O power supply −
A1
B1
IOV
I/O Power Supply
Connection Unit
A1
IOV
IOG
IOG
IOV
IOV
IOG
IOG
24 VDC
A8
Input disconnection
detection
NX bus
connector
(right)
Installation orientation:
• Connected to a CPU Unit or Communication Control Unit: Possible in upright installation.
• Connected to a Communications Coupler Unit: Possible in 6 orientations.
Restrictions: No restrictions
Additional I/O
Power Supply Unit
Terminal connection
diagram
AG: Analog circuit internal GND
I/O power supply +
B8
A8
B1
IOV
IOV
IOV
IOV
IOV
IOV
IOV
IOV
IOV
IOV
IOV
IOV
IOV
IOV
IOV
IOV
Voltage Input Unit
NX-AD4603
A1
B1
Input1+ Input2+
IOG
Input +
IOG
24 V (Sensor power supply +)
0 V (Sensor power supply − / I
Input3+ Input4+
IOG
IOG
Three-wire sensor
Input5+ Input6+
IOG
IOG
Input7+ Input8+
IOG
B8
A8
IOG
B8
Not supported.
14
NX-AD/DA
Analog Input Unit (voltage input type) 8 points NX-AD4604
Unit name
Analog Input Unit (voltage input type)
Model
NX-AD4604
Number of points
8 points
External connection
terminals
Screwless clamping terminal block (16
terminals)
I/O refreshing method
Free-Run refreshing
Input method
Differential Input
Input range
-10 to +10 V
Input conversion range
-5 to 105% (full scale)
Absolute maximum
rating
±15 V
Input impedance
1 MΩ min.
TS indicator
Indicator
Resolution
1/8000 (full scale)
25°C
Overall
accuracy 0 to 55°C
±0.2% (full scale)
Conversion time
250 μs/point
±0.4% (full scale)
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
No supply
Current capacity of I/O
power supply terminal
Without I/O power supply terminals
NX Unit power
consumption
Weight
• Connected to a CPU Unit or
Communication Control Unit
1.45 W max.
• Connected to a Communications
Coupler Unit
1.15 W max.
I/O current consumption No consumption
70 g max.
Input1+ to 8+
Terminal block
AMP
Input1− to 8−
510 KΩ
510 KΩ
Circuit layout
AG
NX bus
connector
(left)
Installation orientation
and restrictions
AG
AG: Analog circuit internal GND
I/O power supply +
I/O power supply +
I/O power supply −
I/O power supply −
NX bus
connector
(right)
Installation orientation:
• Connected to a CPU Unit or Communication Control Unit: Possible in upright installation.
• Connected to a Communications Coupler Unit: Possible in 6 orientations.
Restrictions: No restrictions
Voltage Input Unit
NX-AD4604
A1
Terminal connection
diagram
B1
Input1+ Input2+
Input +
Input1− Input2−
Input −
Input3+ Input4+
Input3− Input4−
Input5+ Input6+
Input5− Input6−
Input7+ Input8+
Input7− Input8−
A8
Input disconnection
detection
B8
Not supported.
15
NX-AD/DA
Analog Input Unit (voltage input type) 8 points NX-AD4608
Unit name
Analog Input Unit (voltage input type)
Model
NX-AD4608
Number of points
8 points
External connection
terminals
Screwless clamping terminal block (16
terminals)
I/O refreshing method
Selectable Synchronous I/O refreshing or Free-Run refreshing
TS indicator
Indicator
Input method
Differential Input
Input range
-10 to +10 V
Input conversion range
-5 to 105% (full scale)
Absolute maximum
rating
±15 V
Input impedance
1 MΩ min.
Resolution
1/30000 (full scale)
25°C
Overall
accuracy 0 to 55°C
±0.1% (full scale)
Conversion time
10 μs/point
±0.2% (full scale)
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
No supply
Current capacity of I/O
power supply terminal
Without I/O power supply terminals
NX Unit power
consumption
Weight
• Connected to a CPU Unit or
Communication Control Unit
1.45 W max.
• Connected to a Communications
Coupler Unit
1.15 W max.
I/O current consumption No consumption
70 g max.
Input1+ to 8+
Terminal block
AMP
Input1− to 8−
510 KΩ
510 KΩ
Circuit layout
AG
NX bus
connector
(left)
Installation orientation
and restrictions
AG
AG: Analog circuit internal GND
I/O power supply +
I/O power supply +
I/O power supply −
I/O power supply −
NX bus
connector
(right)
Installation orientation:
• Connected to a CPU Unit or Communication Control Unit: Possible in upright installation.
• Connected to a Communications Coupler Unit: Possible in 6 orientations.
Restrictions: No restrictions
Voltage Input Unit
NX-AD4608
A1
Terminal connection
diagram
B1
Input1+ Input2+
Input +
Input1− Input2−
Input −
Input3+ Input4+
Input3− Input4−
Input5+ Input6+
Input5− Input6−
Input7+ Input8+
Input7− Input8−
A8
Input disconnection
detection
B8
Not supported.
16
NX-AD/DA
Analog Input Unit (current input type) 2 points NX-AD2203
Unit name
Analog Input Unit (current input type)
Model
NX-AD2203
Number of points
2 points
External connection
terminals
Screwless clamping terminal block (8
terminals)
I/O refreshing method
Free-Run refreshing
Input method
Single-ended input
Input range
4 to 20 mA
Input conversion range
-5 to 105% (full scale)
Absolute maximum
rating
±30 mA
Input impedance
250 Ω
TS indicator
Indicator
Resolution
1/8000 (full scale)
25°C
Overall
accuracy 0 to 55°C
±0.2% (full scale)
Conversion time
250 μs/point
±0.4% (full scale)
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
Supply from the NX bus
Current capacity of I/O
power supply terminal
IOV: 0.1 A/terminal max.,
IOG: 0.1 A/terminal max.
NX Unit power
consumption
Weight
• Connected to a CPU Unit or
Communication Control Unit
1.25 W max.
• Connected to a Communications
Coupler Unit
0.90 W max.
I/O current consumption No consumption
70 g max.
IOV
Terminal block
Input1+ to 2+
AMP
250 Ω
Circuit layout
IOG
AG
NX bus
connector
(left)
Installation orientation
and restrictions
AG: Analog circuit internal GND
I/O power supply +
I/O power supply +
I/O power supply −
I/O power supply −
NX bus
connector
(right)
Installation orientation:
• Connected to a CPU Unit or Communication Control Unit: Possible in upright installation.
• Connected to a Communications Coupler Unit: Possible in 6 orientations.
Restrictions: No restrictions
Additional I/O
Power Supply Unit
A1
B1
IOV
IOV
IOG
IOG
Current Input Unit
NX-AD2203
A1
B1
Input1+ Input2+
Input +
24 V (Sensor power supply +)
Terminal connection
diagram
0 V (Sensor power supply − / Input −)
IOV
24 VDC
Three-wire sensor
A8
Input disconnection
detection
IOV
IOV
IOV
IOG
IOG
IOG
IOG
NC
NC
B8
A8
B8
The NC terminal is not connected to the internal circuit.
Supported.
17
NX-AD/DA
Analog Input Unit (current input type) 2 points NX-AD2204
Unit name
Analog Input Unit (current input type)
Model
NX-AD2204
Number of points
2 points
External connection
terminals
Screwless clamping terminal block (8
terminals)
I/O refreshing method
Free-Run refreshing
Input method
Differential Input
Input range
4 to 20 mA
Input conversion range
-5 to 105% (full scale)
Absolute maximum
rating
±30 mA
Input impedance
250 Ω
TS indicator
Indicator
Resolution
1/8000 (full scale)
25°C
Overall
accuracy 0 to 55°C
±0.2% (full scale)
Conversion time
250 μs/point
±0.4% (full scale)
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
No supply
Current capacity of I/O
power supply terminal
Without I/O power supply terminals
NX Unit power
consumption
Weight
• Connected to a CPU Unit or
Communication Control Unit
1.25 W max.
• Connected to a Communications
Coupler Unit
0.90 W max.
I/O current consumption No consumption
70 g max.
Input1+ to 2+
250 Ω
Terminal block
AMP
Input1− to 2−
510 KΩ
Circuit layout
510 KΩ
AG: Analog circuit
internal GND
AG
AG
NX bus
connector
(left)
Installation orientation
and restrictions
I/O power supply +
I/O power supply +
I/O power supply −
I/O power supply −
NX bus
connector
(right)
Installation orientation:
• Connected to a CPU Unit or Communication Control Unit: Possible in upright installation.
• Connected to a Communications Coupler Unit: Possible in 6 orientations.
Restrictions: No restrictions
Current Input Unit
NX-AD2204
A1
B1
Input1+ Input2+
Input +
Input −
Input1− Input2−
Terminal connection
diagram
AG
AG
NC
NC
A8
Input disconnection
detection
AG terminal is connected to 0 V of analog circuit inside the Unit.
B8 It is not necessary to wire AG terminal normally.
Supported.
18
NX-AD/DA
Analog Input Unit (current input type) 2 points NX-AD2208
Unit name
Analog Input Unit (current input type)
Model
NX-AD2208
Number of points
2 points
External connection
terminals
Screwless clamping terminal block (8
terminals)
I/O refreshing method
Selectable Synchronous I/O refreshing or Free-Run refreshing
TS indicator
Indicator
Input method
Differential Input
Input range
4 to 20 mA
Input conversion range
-5 to 105% (full scale)
Absolute maximum
rating
±30 mA
Input impedance
250 Ω
Resolution
1/30000 (full scale)
25°C
Overall
accuracy 0 to 55°C
±0.1% (full scale)
Conversion time
10 μs/point
±0.2% (full scale)
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
No supply
Current capacity of I/O
power supply terminal
Without I/O power supply terminals
NX Unit power
consumption
Weight
• Connected to a CPU Unit or
Communication Control Unit
1.25 W max.
• Connected to a Communications
Coupler Unit
0.90 W max.
I/O current consumption No consumption
70 g max.
Input1+ to 2+
250 Ω
Terminal block
AMP
Input1− to 2−
510 KΩ
Circuit layout
510 KΩ
AG: Analog circuit
internal GND
AG
AG
NX bus
connector
(left)
Installation orientation
and restrictions
I/O power supply +
I/O power supply +
I/O power supply −
I/O power supply −
NX bus
connector
(right)
Installation orientation:
• Connected to a CPU Unit or Communication Control Unit: Possible in upright installation.
• Connected to a Communications Coupler Unit: Possible in 6 orientations.
Restrictions: No restrictions
Current Input Unit
NX-AD2208
A1
B1
Input1+ Input2+
Input +
Input −
Input1− Input2−
Terminal connection
diagram
AG
AG
NC
NC
A8
Input disconnection
detection
AG terminal is connected to 0 V of analog circuit inside the Unit.
B8 It is not necessary to wire AG terminal normally.
Supported.
19
NX-AD/DA
Analog Input Unit (current input type) 4 points NX-AD3203
Unit name
Analog Input Unit (current input type)
Model
NX-AD3203
Number of points
4 points
External connection
terminals
Screwless clamping terminal block (12
terminals)
I/O refreshing method
Free-Run refreshing
Input method
Single-ended input
Input range
4 to 20 mA
Input conversion range
-5 to 105% (full scale)
Absolute maximum
rating
±30 mA
Input impedance
250 Ω
TS indicator
Indicator
Resolution
1/8000 (full scale)
25°C
Overall
accuracy 0 to 55°C
±0.2% (full scale)
Conversion time
250 μs/point
±0.4% (full scale)
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
Supply from the NX bus
Current capacity of I/O
power supply terminal
IOV: 0.1 A/terminal max.,
IOG: 0.1 A/terminal max.
NX Unit power
consumption
Weight
• Connected to a CPU Unit or
Communication Control Unit
1.25 W max.
• Connected to a Communications
Coupler Unit
0.90 W max.
I/O current consumption No consumption
70 g max.
IOV
Terminal block
Input1+ to 4+
AMP
250 Ω
Circuit layout
IOG
AG
NX bus
connector
(left)
Installation orientation
and restrictions
I/O power supply +
I/O power supply −
I/O power supply −
A1
B1
IOV
IOG
Current Input Unit
NX-AD3203
A1
IOV
B1
Input1+ Input2+
IOG
24 VDC
IOV
IOV
IOG
IOG
Input +
24 V (Sensor power supply +)
0 V (Sensor power supply − / Input −)
Input3+ Input4+
IOV
IOG
A8
Input disconnection
detection
NX bus
connector
(right)
Installation orientation:
• Connected to a CPU Unit or Communication Control Unit: Possible in upright installation.
• Connected to a Communications Coupler Unit: Possible in 6 orientations.
Restrictions: No restrictions
Additional I/O
Power Supply Unit
Terminal connection
diagram
AG: Analog circuit internal GND
I/O power supply +
IOV
IOV
IOV
IOG
IOG
Three-wire sensor
IOG
B8
A8
B8
Supported.
20
NX-AD/DA
Analog Input Unit (current input type) 4 points NX-AD3204
Unit name
Analog Input Unit (current input type)
Model
NX-AD3204
Number of points
4 points
External connection
terminals
Screwless clamping terminal block (12
terminals)
I/O refreshing method
Free-Run refreshing
Input method
Differential Input
Input range
4 to 20 mA
Input conversion range
-5 to 105% (full scale)
Absolute maximum
rating
±30 mA
Input impedance
250 Ω
TS indicator
Indicator
Resolution
1/8000 (full scale)
25°C
Overall
accuracy 0 to 55°C
±0.2% (full scale)
Conversion time
250 μs/point
±0.4% (full scale)
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
No supply
Current capacity of I/O
power supply terminal
Without I/O power supply terminals
NX Unit power
consumption
Weight
• Connected to a CPU Unit or
Communication Control Unit
1.25 W max.
• Connected to a Communications
Coupler Unit
0.90 W max.
I/O current consumption No consumption
70 g max.
Input1+ to 4+
250 Ω
Terminal block
AMP
Input1− to 4−
510 KΩ
Circuit layout
510 KΩ
AG: Analog circuit
internal GND
AG
AG
NX bus
connector
(left)
Installation orientation
and restrictions
I/O power supply +
I/O power supply +
I/O power supply −
I/O power supply −
NX bus
connector
(right)
Installation orientation:
• Connected to a CPU Unit or Communication Control Unit: Possible in upright installation.
• Connected to a Communications Coupler Unit: Possible in 6 orientations.
Restrictions: No restrictions
Current Input Unit
NX-AD3204
A1
Terminal connection
diagram
B1
Input1+ Input2+
Input +
Input1− Input2−
Input −
Input3+ Input4+
Input3− Input4−
AG
AG
AG
AG
A8
Input disconnection
detection
AG terminal is connected to 0 V of analog circuit inside the Unit.
B8 It is not necessary to wire AG terminal normally.
Supported.
21
NX-AD/DA
Analog Input Unit (current input type) 4 points NX-AD3208
Unit name
Analog Input Unit (current input type)
Model
NX-AD3208
Number of points
4 points
External connection
terminals
Screwless clamping terminal block (12
terminals)
I/O refreshing method
Selectable Synchronous I/O refreshing or Free-Run refreshing
TS indicator
Indicator
Input method
Differential Input
Input range
4 to 20 mA
Input conversion range
-5 to 105% (full scale)
Absolute maximum
rating
±30 mA
Input impedance
250 Ω
Resolution
1/30000 (full scale)
25°C
Overall
accuracy 0 to 55°C
±0.1% (full scale)
Conversion time
10 μs/point
±0.2% (full scale)
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
No supply
Current capacity of I/O
power supply terminal
Without I/O power supply terminals
NX Unit power
consumption
Weight
• Connected to a CPU Unit or
Communication Control Unit
1.30 W max.
• Connected to a Communications
Coupler Unit
0.95 W max.
I/O current consumption No consumption
70 g max.
Input1+ to 4+
250 Ω
Terminal block
AMP
Input1− to 4−
510 KΩ
Circuit layout
510 KΩ
AG
AG: Analog circuit
internal GND
AG
NX bus
connector
(left)
Installation orientation
and restrictions
I/O power supply +
I/O power supply +
I/O power supply −
I/O power supply −
NX bus
connector
(right)
Installation orientation:
• Connected to a CPU Unit or Communication Control Unit: Possible in upright installation.
• Connected to a Communications Coupler Unit: Possible in 6 orientations.
Restrictions: No restrictions
Current Input Unit
NX-AD3208
A1
B1
Input1+ Input2+
Input +
Input1− Input2−
Input −
Input3+ Input4+
Terminal connection
diagram
Input3− Input4−
AG
AG
AG
AG
A8
Input disconnection
detection
B8
AG terminal is connected to 0 V of analog circuit inside the Unit.
It is not necessary to wire AG terminal normally.
Supported.
22
NX-AD/DA
Analog Input Unit (current input type) 8 points NX-AD4203
Unit name
Analog Input Unit (current input type)
Model
NX-AD4203
Number of points
8 points
External connection
terminals
Screwless clamping terminal block (16
terminals)
I/O refreshing method
Free-Run refreshing
Input method
Single-ended input
Input range
4 to 20 mA
Input conversion range
-5 to 105% (full scale)
Absolute maximum
rating
±30 mA
Input impedance
85 Ω
TS indicator
Indicator
Resolution
1/8000 (full scale)
25°C
Overall
accuracy 0 to 55°C
±0.2% (full scale)
Conversion time
250 μs/point
±0.4% (full scale)
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
Supply from the NX bus
Current capacity of I/O
power supply terminal
IOV: 0.1 A/terminal max.
NX Unit power
consumption
Weight
• Connected to a CPU Unit or
Communication Control Unit
1.40 W max.
• Connected to a Communications
Coupler Unit
1.05 W max.
I/O current consumption No consumption
70 g max.
IOV
Terminal block
Input1+ to 8+
AMP
Circuit layout
AG: Analog circuit internal GND
85 Ω
AG
NX bus
connector
(left)
Installation orientation
and restrictions
I/O power supply +
I/O power supply −
I/O power supply −
A1
B1
IOV
I/O Power Supply
Connection Unit
A1
IOV
IOG
IOG
IOV
IOV
IOG
IOG
24 VDC
A8
Input disconnection
detection
NX bus
connector
(right)
Installation orientation:
• Connected to a CPU Unit or Communication Control Unit: Possible in upright installation.
• Connected to a Communications Coupler Unit: Possible in 6 orientations.
Restrictions: No restrictions
Additional I/O
Power Supply Unit
Terminal connection
diagram
AG
I/O power supply +
B8
A8
B1
IOG
IOG
IOG
IOG
IOG
IOG
IOG
IOG
IOG
IOG
IOG
IOG
IOG
IOG
IOG
IOG
Voltage Input Unit
NX-AD4203
A1
B1
Input1+ Input2+
IOV
Input +
IOV
24 V (Sensor power supply +)
0 V (Sensor power supply − / Input −)
Input3+ Input4+
IOV
IOV
Three-wire Sensor
Input5+ Input6+
IOV
IOV
Input7+ Input8+
IOV
B8
A8
IOV
B8
Supported.
23
NX-AD/DA
Analog Input Unit (current input type) 8 points NX-AD4204
Unit name
Analog Input Unit (current input type)
Model
NX-AD4204
Number of points
8 points
External connection
terminals
Screwless clamping terminal block (16
terminals)
I/O refreshing method
Free-Run refreshing
Input method
Differential Input
Input range
4 to 20 mA
Input conversion range
-5 to 105% (full scale)
Absolute maximum
rating
±30 mA
Input impedance
85 Ω
TS indicator
Indicator
Resolution
1/8000 (full scale)
25°C
Overall
accuracy 0 to 55°C
±0.2% (full scale)
Conversion time
250 μs/point
±0.4% (full scale)
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
No supply
Current capacity of I/O
power supply terminal
Without I/O power supply terminals
NX Unit power
consumption
Weight
• Connected to a CPU Unit or
Communication Control Unit
1.40 W max.
• Connected to a Communications
Coupler Unit
1.05 W max.
I/O current consumption No consumption
70 g max.
Input1+ to 8+
Terminal block
85 Ω
AMP
Input1− to 8−
510 KΩ
510 KΩ
Circuit layout
AG
NX bus
connector
(left)
Installation orientation
and restrictions
AG
AG: Analog circuit
internal GND
I/O power supply +
I/O power supply +
I/O power supply −
I/O power supply −
NX bus
connector
(right)
Installation orientation:
• Connected to a CPU Unit or Communication Control Unit: Possible in upright installation.
• Connected to a Communications Coupler Unit: Possible in 6 orientations.
Restrictions: No restrictions
Current Input Unit
NX-AD4204
A1
B1
Input1+ Input2+
Input1− Input2−
Terminal connection
diagram
Input +
Input −
Input3+ Input4+
Input3− Input4−
Input5+ Input6+
Input5− Input6−
Input7+ Input8+
Input7− Input8−
A8
Input disconnection
detection
B8
Supported.
24
NX-AD/DA
Analog Input Unit (current input type) 8 points NX-AD4208
Unit name
Number of points
I/O refreshing method
Indicator
Analog Input Unit (current input type)
Model
External connection
8 points
terminals
Selectable Synchronous I/O refreshing or Free-Run refreshing
TS indicator
Input method
Input range
Input conversion range
Absolute maximum
rating
Input impedance
Resolution
25°C
Overall
accuracy 0 to 55°C
Conversion time
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
Dielectric strength
I/O power supply
method
No supply
Current capacity of I/O
power supply terminal
NX Unit power
consumption
Weight
• Connected to a CPU Unit or
Communication Control Unit
1.45 W max.
• Connected to a Communications
Coupler Unit
1.10 W max.
70 g max.
NX-AD4208
Screwless clamping terminal block (16
terminals)
Differential Input
4 to 20 mA
-5 to 105% (full scale)
±30 mA
85 Ω
1/30000 (full scale)
±0.1% (full scale)
±0.2% (full scale)
10 μs/point
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
Without I/O power supply terminals
I/O current consumption No consumption
Input1+ to 8+
Terminal block
85 Ω
AMP
Input1− to 8−
510 KΩ
510 KΩ
Circuit layout
AG
NX bus
connector
(left)
Installation orientation
and restrictions
AG
AG: Analog circuit
internal GND
I/O power supply +
I/O power supply +
I/O power supply −
I/O power supply −
NX bus
connector
(right)
Installation orientation:
• Connected to a CPU Unit or Communication Control Unit: Possible in upright installation.
• Connected to a Communications Coupler Unit: Possible in 6 orientations.
Restrictions: No restrictions
Current Input Unit
NX-AD4208
A1
B1
Input1+ Input2+
Input1− Input2−
Terminal connection
diagram
Input +
Input −
Input3+ Input4+
Input3− Input4−
Input5+ Input6+
Input5− Input6−
Input7+ Input8+
Input7− Input8−
A8
Input disconnection
detection
B8
Supported.
25
NX-AD/DA
Analog Output Unit Specifications
Analog Output Unit (voltage output type) 2 points NX-DA2603
Unit name
Analog Output Unit (voltage output type)
Model
NX-DA2603
Number of points
2 points
External connection
terminals
Screwless clamping terminal block (8
terminals)
I/O refreshing method
Free-Run refreshing
Output range
-10 to +10 V
Output conversion
range
-5 to 105% (full scale)
Allowable load
resistance
5 kΩ min.
Output impedance
0.5 Ω max.
TS indicator
Indicator
Resolution
1/8000 (full scale)
25°C
Overall
accuracy 0 to 55°C
±0.3% (full scale)
Conversion time
250 μs/point
±0.5% (full scale)
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
Supply from the NX bus
Current capacity of I/O
power supply terminal
IOV: 0.1 A/terminal max.,
IOG: 0.1 A/terminal max.
NX Unit power
consumption
Weight
• Connected to a CPU Unit or
Communication Control Unit
1.40 W max.
• Connected to a Communications
Coupler Unit
1.10 W max.
I/O current consumption No consumption
70 g max.
IOV
AMP
Output V1+ to V2+
Circuit layout
IOG
AG: Analog circuit internal GND
NX bus
connector
(left)
Installation orientation
and restrictions
AG
I/O power supply +
I/O power supply +
I/O power supply −
I/O power supply −
NX bus
connector
(right)
Installation orientation:
• Connected to a CPU Unit or Communication Control Unit: Possible in upright installation.
• Connected to a Communications Coupler Unit: Possible in 6 orientations.
Restrictions: No restrictions
Additional I/O
Power Supply Unit
A1
Terminal connection
diagram
Terminal block
B1
Voltage Output Unit
NX-DA2603
A1
B1
IOV
IOV
V1+
V2+
Voltage output +
IOG
IOG
IOV
IOV
Voltage output −
IOV
IOV
IOG
IOG
IOG
IOG
NC
NC
24 VDC
A8
B8
A8
B8
26
NX-AD/DA
Analog Output Unit (voltage output type) 2 points NX-DA2605
Unit name
Analog Output Unit (voltage output type)
Model
NX-DA2605
Number of points
2 points
External connection
terminals
Screwless clamping terminal block (8
terminals)
I/O refreshing method
Selectable Synchronous I/O refreshing or Free-Run refreshing
TS indicator
Indicator
Output range
-10 to +10 V
Output conversion
range
-5 to 105% (full scale)
Allowable load
resistance
5 kΩ min.
Output impedance
0.5 Ω max.
Resolution
1/30000 (full scale)
25°C
Overall
accuracy 0 to 55°C
±0.1% (full scale)
Conversion time
10 μs/point
±0.3% (full scale)
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
Supply from the NX bus
Current capacity of I/O
power supply terminal
IOV: 0.1 A/terminal max.,
IOG: 0.1 A/terminal max.
NX Unit power
consumption
Weight
• Connected to a CPU Unit or
Communication Control Unit
1.40 W max.
• Connected to a Communications
Coupler Unit
1.10 W max.
I/O current consumption No consumption
70 g max.
IOV
AMP
Output V1+ to V2+
Circuit layout
IOG
AG: Analog circuit internal GND
NX bus
connector
(left)
Installation orientation
and restrictions
AG
I/O power supply +
I/O power supply +
I/O power supply −
I/O power supply −
NX bus
connector
(right)
Installation orientation:
• Connected to a CPU Unit or Communication Control Unit: Possible in upright installation.
• Connected to a Communications Coupler Unit: Possible in 6 orientations.
Restrictions: No restrictions
Additional I/O
Power Supply Unit
A1
Terminal connection
diagram
Terminal block
B1
Voltage Output Unit
NX-DA2605
A1
B1
IOV
IOV
V1+
V2+
Voltage output +
IOG
IOG
IOV
IOV
Voltage output −
IOV
IOV
IOG
IOG
IOG
IOG
NC
NC
24 VDC
A8
B8
A8
B8
27
NX-AD/DA
Analog Output Unit (voltage output type) 4 points NX-DA3603
Unit name
Analog Output Unit (voltage output type)
Model
NX-DA3603
Number of points
4 points
External connection
terminals
Screwless clamping terminal block (12
terminals)
I/O refreshing method
Free-Run refreshing
Output range
-10 to +10 V
Output conversion
range
-5 to 105% (full scale)
Allowable load
resistance
5 kΩ min.
Output impedance
0.5 Ω max.
TS indicator
Indicator
Resolution
1/8000 (full scale)
25°C
Overall
accuracy 0 to 55°C
±0.3% (full scale)
Conversion time
250 μs/point
±0.5% (full scale)
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
Supply from the NX bus
Current capacity of I/O
power supply terminal
IOV: 0.1 A/terminal max.,
IOG: 0.1 A/terminal max.
NX Unit power
consumption
Weight
• Connected to a CPU Unit or
Communication Control Unit
1.35 W max.
• Connected to a Communications
Coupler Unit
1.25 W max.
I/O current consumption No consumption
70 g max.
IOV
AMP
Output V1+ to V4+
Circuit layout
IOG
AG: Analog circuit internal GND
NX bus
connector
(left)
Installation orientation
and restrictions
AG
I/O power supply +
I/O power supply +
I/O power supply −
I/O power supply −
NX bus
connector
(right)
Installation orientation:
• Connected to a CPU Unit or Communication Control Unit: Possible in upright installation.
• Connected to a Communications Coupler Unit: Possible in 6 orientations.
Restrictions: No restrictions
Additional I/O
Power Supply Unit
A1
B1
IOV
Terminal connection
diagram
Terminal block
IOG
Voltage Output Unit
NX-DA3603
A1
IOV
IOG
24 VDC
IOV
IOG
A8
IOV
B1
V1+
V2+
IOV
IOV
IOG
IOG
V3+
V4+
IOV
IOV
IOG
IOG
Voltage output +
Voltage output −
IOG
B8
A8
B8
28
NX-AD/DA
Analog Output Unit (voltage output type) 4 points NX-DA3605
Unit name
Analog Output Unit (voltage output type)
Model
NX-DA3605
Number of points
4 points
External connection
terminals
Screwless clamping terminal block (12
terminals)
I/O refreshing method
Selectable Synchronous I/O refreshing or Free-Run refreshing
TS indicator
Indicator
Output range
-10 to +10 V
Output conversion
range
-5 to 105% (full scale)
Allowable load
resistance
5 kΩ min.
Output impedance
0.5 Ω max.
Resolution
1/30000 (full scale)
25°C
Overall
accuracy 0 to 55°C
±0.1% (full scale)
Conversion time
10 μs/point
±0.3% (full scale)
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
Supply from the NX bus
Current capacity of I/O
power supply terminal
IOV: 0.1 A/terminal max.,
IOG: 0.1 A/terminal max.
NX Unit power
consumption
Weight
• Connected to a CPU Unit or
Communication Control Unit
1.60 W max.
• Connected to a Communications
Coupler Unit
1.25 W max.
I/O current consumption No consumption
70 g max.
IOV
AMP
Output V1+ to V4+
Circuit layout
IOG
AG: Analog circuit internal GND
NX bus
connector
(left)
Installation orientation
and restrictions
AG
I/O power supply +
I/O power supply +
I/O power supply −
I/O power supply −
NX bus
connector
(right)
Installation orientation:
• Connected to a CPU Unit or Communication Control Unit: Possible in upright installation.
• Connected to a Communications Coupler Unit: Possible in 6 orientations.
Restrictions: No restrictions
Additional I/O
Power Supply Unit
A1
B1
IOV
Terminal connection
diagram
Terminal block
IOG
Voltage Output Unit
NX-DA3605
A1
IOV
IOG
24 VDC
IOV
IOG
A8
IOV
B1
V1+
V2+
IOV
IOV
IOG
IOG
V3+
V4+
IOV
IOV
IOG
IOG
Voltage output +
Voltage output −
IOG
B8
A8
B8
29
NX-AD/DA
Analog Output Unit (current output type) 2 points NX-DA2203
Unit name
Analog Output Unit (current output type)
Model
NX-DA2203
Number of points
2 points
External connection
terminals
Screwless clamping terminal block (8
terminals)
I/O refreshing method
Free-Run refreshing
Output range
4 to 20 mA
Output conversion
range
-5 to 105% (full scale)
Allowable load
resistance
600 Ω max.
TS indicator
Indicator
Resolution
1/8000 (full scale)
25°C
Overall
accuracy 0 to 55°C
±0.3% (full scale)
Conversion time
250 μs/point
±0.6% (full scale)
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
Supply from the NX bus
Current capacity of I/O
power supply terminal
IOV: 0.1 A/terminal max.,
IOG: 0.1 A/terminal max.
NX Unit power
consumption
Weight
• Connected to a CPU Unit or
Communication Control Unit
2.10 W max.
• Connected to a Communications
Coupler Unit
1.75 W max.
I/O current consumption No consumption
70 g max.
IOV
AMP
Output I1+ to I2+
Circuit layout
Terminal block
IOG
AG: Analog circuit internal GND
NX bus
connector
(left)
AG
I/O power supply +
I/O power supply +
I/O power supply −
I/O power supply −
NX bus
connector
(right)
Installation orientation:
• Connected to a CPU Unit or Communication Control Unit: Possible in upright installation.
• Connected to a Communications Coupler Unit: Possible in 6 orientations.
Restrictions:
For upright installation: No restrictions
For any installation other than upright: Restricted as shown in the graph below.
Installation orientation
and restrictions
Load resistance (per point)
(Ω)
600
350
Use it within this range.
0
40
55 (°C)
Ambient operating temperature
30
NX-AD/DA
Additional I/O
Power Supply Unit
A1
Terminal connection
diagram
B1
Current Output Unit
NX-DA2203
A1
B1
IOV
IOV
I1+
I2+
Current output +
IOG
IOG
IOV
IOV
Current output −
IOV
IOV
IOG
IOG
IOG
IOG
NC
NC
24 VDC
A8
B8
A8
B8
31
NX-AD/DA
Analog Output Unit (current output type) 2 points NX-DA2205
Unit name
Analog Output Unit (current output type)
Model
NX-DA2205
Number of points
2 points
External connection
terminals
Screwless clamping terminal block (8
terminals)
I/O refreshing method
Selectable Synchronous I/O refreshing or Free-Run refreshing
TS indicator
Indicator
Output range
4 to 20 mA
Output conversion
range
-5 to 105% (full scale)
Allowable load
resistance
600 Ω max.
Resolution
1/30000 (full scale)
25°C
Overall
accuracy 0 to 55°C
±0.1% (full scale)
Conversion time
10 μs/point
±0.3% (full scale)
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
Supply from the NX bus
Current capacity of I/O
power supply terminal
IOV: 0.1 A/terminal max.,
IOG: 0.1 A/terminal max.
NX Unit power
consumption
Weight
• Connected to a CPU Unit or
Communication Control Unit
2.10 W max.
• Connected to a Communications
Coupler Unit
1.75 W max.
I/O current consumption No consumption
70 g max.
IOV
AMP
Output I1+ to I2+
Circuit layout
Terminal block
IOG
AG: Analog circuit internal GND
NX bus
connector
(left)
AG
I/O power supply +
I/O power supply +
I/O power supply −
I/O power supply −
NX bus
connector
(right)
Installation orientation:
• Connected to a CPU Unit or Communication Control Unit: Possible in upright installation.
• Connected to a Communications Coupler Unit: Possible in 6 orientations.
Restrictions:
For upright installation: No restrictions
For any installation other than upright: Restricted as shown in the graph below.
Installation orientation
and restrictions
Load resistance (per point)
(Ω)
600
350
Use it within this range.
0
40
55 (°C)
Ambient operating temperature
32
NX-AD/DA
Additional I/O
Power Supply Unit
A1
Terminal connection
diagram
B1
Current Output Unit
NX-DA2205
A1
B1
IOV
IOV
I1+
I2+
Current output +
IOG
IOG
IOV
IOV
Current output −
IOV
IOV
IOG
IOG
IOG
IOG
NC
NC
24 VDC
A8
B8
A8
B8
33
NX-AD/DA
Analog Output Unit (current output type) 4 points NX-DA3203
Unit name
Analog Output Unit (current output type)
Model
NX-DA3203
Number of points
4 points
External connection
terminals
Screwless clamping terminal block (12
terminals)
I/O refreshing method
Free-Run refreshing
Output range
4 to 20 mA
Output conversion
range
-5 to 105% (full scale)
Allowable load
resistance
350 Ω max.
TS indicator
Indicator
Resolution
1/8000 (full scale)
25°C
Overall
accuracy 0 to 55°C
±0.3% (full scale)
Conversion time
250 μs/point
±0.6% (full scale)
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
Supply from the NX bus
Current capacity of I/O
power supply terminal
IOV: 0.1 A/terminal max.,
IOG: 0.1 A/terminal max.
NX Unit power
consumption
Weight
• Connected to a CPU Unit or
Communication Control Unit
2.10 W max.
• Connected to a Communications
Coupler Unit
1.80 W max.
I/O current consumption No consumption
70 g max.
IOV
AMP
Output I1+ to I4+
Circuit layout
Terminal block
IOG
AG: Analog circuit internal GND
NX bus
connector
(left)
AG
I/O power supply +
I/O power supply +
I/O power supply −
I/O power supply −
NX bus
connector
(right)
Installation orientation:
• Connected to a CPU Unit or Communication Control Unit: Possible in upright installation.
• Connected to a Communications Coupler Unit: Possible in 6 orientations.
Restrictions:
For upright installation: No restrictions
For any installation other than upright: Restricted as shown in the graph below.
Installation orientation
and restrictions
Load resistance (per point)
(Ω)
350
250
Use it within this range.
0
40
55 (°C)
Ambient operating temperature
34
NX-AD/DA
Additional I/O
Power Supply Unit
A1
B1
IOV
Terminal connection
diagram
IOG
Current Output Unit
NX-DA3203
A1
IOV
IOG
24 VDC
IOV
IOG
A8
IOV
B1
I1+
I2+
IOV
IOV
IOG
IOG
I3+
I4+
IOV
IOV
IOG
IOG
Current output +
Current output −
IOG
B8
A8
B8
35
NX-AD/DA
Analog Output Unit (current output type) 4 points NX-DA3205
Unit name
Analog Output Unit (current output type)
Model
NX-DA3205
Number of points
4 points
External connection
terminals
Screwless clamping terminal block (12
terminals)
I/O refreshing method
Selectable Synchronous I/O refreshing or Free-Run refreshing
TS indicator
Indicator
Output range
4 to 20 mA
Output conversion
range
-5 to 105% (full scale)
Allowable load
resistance
350 Ω max.
Resolution
1/30000 (full scale)
25°C
Overall
accuracy 0 to 55°C
±0.1% (full scale)
Conversion time
10 μs/point
±0.3% (full scale)
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
Supply from the NX bus
Current capacity of I/O
power supply terminal
IOV: 0.1 A/terminal max.,
IOG: 0.1 A/terminal max.
NX Unit power
consumption
Weight
• Connected to a CPU Unit or
Communication Control Unit
2.10 W max.
• Connected to a Communications
Coupler Unit
1.80 W max.
I/O current consumption No consumption
70 g max.
IOV
AMP
Output I1+ to I4+
Circuit layout
Terminal block
IOG
AG: Analog circuit internal GND
NX bus
connector
(left)
AG
I/O power supply +
I/O power supply +
I/O power supply −
I/O power supply −
NX bus
connector
(right)
Installation orientation:
• Connected to a CPU Unit or Communication Control Unit: Possible in upright installation.
• Connected to a Communications Coupler Unit: Possible in 6 orientations.
Restrictions:
For upright installation: No restrictions
For any installation other than upright: Restricted as shown in the graph below.
Installation orientation
and restrictions
Load resistance (per point)
(Ω)
350
250
Use it within this range.
0
40
55 (°C)
Ambient operating temperature
36
NX-AD/DA
Additional I/O
Power Supply Unit
A1
B1
IOV
Terminal connection
diagram
IOG
Current Output Unit
NX-DA3205
A1
IOV
IOG
24 VDC
IOV
IOG
A8
IOV
B1
I1+
I2+
IOV
IOV
IOG
IOG
I3+
I4+
IOV
IOV
IOG
IOG
Current output +
Current output −
IOG
B8
A8
B8
37
NX-AD/DA
Version Information
Connected to a CPU Unit
Refer to the user's manual for the CPU Unit details on the CPU Units to which NX Units can be connected.
NX Unit
Model
Corresponding unit versions/versions
Unit version
CPU Unit
Sysmac Studio
Ver.1.0
Ver.1.13
Ver.1.17
NX-AD@@@@
NX-DA@@@@
Note: Some Units do not have all of the versions given in the above table. If a Unit does not have the specified version, support is provided by the oldest
available version after the specified version. Refer to the user’s manuals for the specific Units for the relation between models and versions.
Connected to an EtherCAT Coupler Unit
NX Unit
Model
NX-AD@@@@
NX-DA@@@@
Corresponding unit versions/versions
Unit version
EtherCAT Coupler Unit
CPU Unit or
Industrial PC
Sysmac Studio
Ver.1.0
Ver.1.0
Ver.1.05
Ver.1.06
Note: Some Units do not have all of the versions given in the above table. If a Unit does not have the specified version, support is provided by the oldest
available version after the specified version. Refer to the user’s manuals for the specific Units for the relation between models and versions.
Connected to an EtherNet/IP Coupler Unit
NX Unit
Corresponding unit versions/versions
Application with an NJ/NX/NY-series Controller *1
Model
Unit version
EtherNet/IP
Coupler Unit
CPU Unit or
Industrial PC
Sysmac
Studio
Application with a CS/CJ/CP-series PLC *2
EtherNet/IP
Coupler Unit
Sysmac
Studio
NX-IO
Configurator *3
NX-AD@@@@
Ver. 1.0
Ver. 1.2
Ver. 1.14
Ver. 1.19
Ver. 1.0
Ver. 1.10
Ver. 1.00
NX-DA@@@@
Note: Some Units do not have all of the versions given in the above table. If a Unit does not have the specified version, support is provided by the oldest
available version after the specified version. Refer to the user’s manuals for the specific Units for the relation between models and versions.
*1 Refer to the user’s manual for the EtherNet/IP Coupler Units for information on the unit versions of EtherNet/IP Units that are compatible with
EtherNet/IP Coupler Units.
*2 Refer to the user’s manual for the EtherNet/IP Coupler Units for information on the unit versions of CPU Units and EtherNet/IP Units that are
compatible with EtherNet/IP Coupler Units.
*3 For connection to an EtherNet/IP Coupler Unit with unit version 1.0, connection is supported only for a connection to the peripheral USB port
on the EtherNet/IP Coupler Unit. You cannot connect by any other path. If you need to connect by another path, use an EtherNet/IP Coupler
Unit with unit version 1.2 or later.
Connected to Communication Control Units
NX Unit
Model
Corresponding unit versions/versions
Unit version
Communication Control Unit
Sysmac Studio
NX-AD@@@@
Ver.1.0
Ver.1.00
Ver.1.24
NX-DA@@@@
Note: Some Units do not have all of the versions given in the above table. If a Unit does not have the specified version, support is provided by the oldest
available version after the specified version. Refer to the user’s manuals for the specific Units for the relation between models and versions.
38
NX-AD/DA
External Interface
Screwless Clamping Terminal Block Type
12 mm Width
(B)
(C)
(A)
Letter
Item
Specification
(A)
NX bus connector
(B)
Indicators
The indicators show the current operating status of the Unit.
Terminal block
The terminal block is used to connect to external devices.
The number of terminals depends on the Unit.
(C)
This connector is used to connect to another Unit.
39
NX-AD/DA
Terminal Blocks
(A)
(B)
A1
B1
A1
B1
A1
B1
A2
B2
A2
B2
A2
B2
A3
B3
A3
B3
A3
B3
A4
B4
A4
B4
A4
B4
A5
B5
A5
B5
A5
B5
A6
B6
A6
B6
A6
B6
A7
B7
A7
B7
A7
B7
A8
B8
A8
B8
A8
B8
(C)
12 mm width
8 terminals
Letter
12 mm width
16 terminals
12 mm width
12 terminals
Item
Specification
Terminal number
indication
The terminal number is identified by a column (A through D) and a row (1 through 8).
Therefore, terminal numbers are written as a combination of columns and rows, A1 through A8 and B1
through B8.
The terminal number indication is the same regardless of the number of terminals on the terminal block.
(B)
Release hole
A flat-blade screwdriver is inserted here to attach and remove the wiring.
(C)
Terminal hole
The wires are inserted into these holes.
(A)
Applicable Terminal Blocks for Each Unit Model
Terminal Blocks
Unit model
Model
No. of terminals
Terminal number
indications
Ground terminal
mark
Terminal current
capacity
NX-AD2@@@
NX-TBA082
8
A/B
None
10 A
NX-AD3@@@
NX-TBA122
12
A/B
None
10 A
NX-AD4@@@
NX-TBA162
16
A/B
None
10 A
NX-DA2@@@
NX-TBA082
8
A/B
None
10 A
NX-DA3@@@
NX-TBA122
12
A/B
None
10 A
40
NX-AD/DA
Applicable Wires
Using Ferrules
If you use ferrules, attach the twisted wires to them.
Observe the application instructions for your ferrules for the wire stripping length when attaching ferrules.
Always use plated one-pin ferrules. Do not use unplated ferrules or two-pin ferrules.
The applicable ferrules, wires, and crimping tool are given in the following table.
Terminal type
Manufacturer
Terminals other
than ground
terminals
Phoenix Contact
Ferrule model
Applicable wire
(mm2 (AWG))
AI0,34-8
0.34 (#22)
AI0,5-8
0.5 (#20)
Crimping tool
Phoenix Contact (The figure in parentheses is the applicable wire size.)
CRIMPFOX 6 (0.25 to 6 mm2, AWG24 to 10)
AI0,5-10
AI0,75-8
0.75 (#18)
AI0,75-10
AI1,0-8
1.0 (#18)
AI1,0-10
AI1,5-8
1.5 (#16)
AI1,5-10
Ground terminals
Terminals other
than ground
terminals
Weidmuller
AI2,5-10
2.0 *
H0.14/12
0.14 (#26)
H0.25/12
0.25 (#24)
H0.34/12
0.34 (#22)
H0.5/14
0.5 (#20)
Weidmuller (The figure in parentheses is the applicable wire size.)
PZ6 Roto (0.14 to 6 mm2, AWG 26 to 10)
H0.5/16
H0.75/14
0.75 (#18)
H0.75/16
H1.0/14
1.0 (#18)
H1.0/16
H1.5/14
1.5 (#16)
H1.5/16
* Some AWG 14 wires exceed 2.0 mm2 and cannot be used in the screwless clamping terminal block.
When you use any ferrules other than those in the above table, crimp them to the twisted wires so that the following processed dimensions are
achieved.
Finished Dimensions of Ferrules
8 to 10 mm
1.6 mm max. (except ground terminals)
2.4 mm max. (except ground terminals)
2.0 mm max. (ground terminals)
2.7 mm max. (ground terminals)
Using Twisted Wires/Solid Wires
If you use the twisted wires or the solid wires, use the following table to determine the correct wire specifications.
Terminals
Classification
Current capacity
Wire type
Twisted wires
Plated
2 A or less
All terminals except
ground terminals
Ground terminals
Greater than
2 A and 4 A or less
Unplated
Possible
Possible
Greater than 4 A
Possible *1
---
Possible
Not
Possible
Possible
Solid wire
Plated
Possible
Possible *1
Not
Possible
Possible *2
Wire size
Unplated
Conductor length
(stripping length)
Possible
Not
Possible
Possible *2
0.08 to 1.5 mm2
AWG28 to 16
8 to 10 mm
2.0 mm2
9 to 10 mm
*1. Secure wires to the screwless clamping terminal block. Refer to the Securing Wires in the USER'S MANUAL for how to secure wires.
*2. With the NX-TB@@@1 Terminal Block, use twisted wires to connect the ground terminal. Do not use a solid wire.
Conductor length (stripping length)
If more than 2 A will flow on the wires, use plated wires or use ferrules.
41
NX-AD/DA
Dimensions
(Unit/mm)
Screwless Clamping Terminal Block Type
12 mm Width
14.1
12.0
0.55*
1.5
100
1.5
104.5
65.2
71
80
* The dimension is 1.35 mm for Units with lot numbers through December 2014.
Related Manual
Cat. No.
W522
Model number
NX-AD@@@@
NX-DA@@@@
Manual name
NX-series Analog I/O Units
User’s Manual for Analog
Input Units and Analog
Output Units
Application
Description
Learning how to use NX-series The hardware, setup methods, and functions of
Analog Input Units and Analog the NX-series Analog Input Units and Analog
Output Units
Output Units are described.
42
Terms and Conditions Agreement
Read and understand this catalog.
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you
have any questions or comments.
Warranties.
(a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship
for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron
disclaims all other warranties, express or implied.
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT
NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS. BUYER
ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE
PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.
Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the
Products or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at
Omron’s election, to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or
replacement thereof) the non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount
equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsible for warranty,
repair, indemnity or any other claims or expenses regarding the Products unless Omron’s analysis confirms that the Products
were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate
modification. Return of any Products by Buyer must be approved in writing by Omron before shipment. Omron Companies shall
not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or
electronic components, circuits, system assemblies or any other materials or substances or environments. Any advice,
recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above
warranty.
See http://www.omron.com/global/ or contact your Omron representative for published information.
Limitation on Liability; Etc.
OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,
WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.
Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted.
Suitability of Use.
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the
combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable
third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself
is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine,
system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product
with respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE
QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS,
AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
OVERALL EQUIPMENT OR SYSTEM.
Programmable Products.
Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence
thereof.
Performance Data.
Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining
suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate
it to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability.
Change in Specifications.
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our
practice to change part numbers when published ratings or features are changed, or when significant construction changes are
made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers
may be assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at
any time to confirm actual specifications of purchased Product.
Errors and Omissions.
Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is
assumed for clerical, typographical or proofreading errors or omissions.
2020.10
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2020 All Right Reserved.