New Product
Switch Mode Power Supply
S8VK-C (60/120/240/480-W Models)
Cost-effective Single Phase Power Supply
Universal input and Safety standards
for worldwide applications
Space-saving Compact Design
• Universal input for worldwide applications:
100 to 240 VAC (85 to 264 VAC)
• DC input can be available: 90 to 350 VDC
• Operation temperature range: –25 to 60 °C
• Compact Dimension for small space
• Flexible installation by special mounting brackets
• Safety standards:
UL508/60950-1, CSA C22.2 No.107.1/60950-1
EN50178 (=VDE0160), EN60950-1 (=VDE0805)
• EMS: Conform to EN61204-3
EMI: EN55011 Class A
!
Refer to Safety Precautions for All Power Supplies and Safety
Precautions on page 11.
Model Number Structure
Model Number Legend
Note: Not all combinations are possible. Refer to List of Models in Ordering Information, below.
S8VK-C @@@ 24
1
2
1. Power Ratings
060: 60 W
120: 120 W
240: 240 W
480: 480 W
2. Output voltage
24: 24 V
Ordering Information
Note: For details on normal stock models, contact your nearest OMRON representative.
Power ratings
Input voltage
60 W
120 W
240 W
480 W
Output Voltage
24 V
Single phase
100 to 240 VAC
90 to 350 VDC
Output current
2.5 A
Model number
S8VK-C06024
24 V
5A
S8VK-C12024
24 V
10 A
S8VK-C24024
24 V
20 A
S8VK-C48024
1
S8VK-C
Specifications
Ratings, Characteristics, and Functions
Item
Efficiency (Typical)
Power ratings
60 W
120 W
240 W
Output voltage
24 V
24 V
24 V
230 VAC input
Voltage *1
Input
Power factor
(Typical)
89%
24 V
92%
50/60 Hz (47 to 450 Hz)
115 VAC input
1.0 A
2.0 A
2.5 A
4.8 A
230 VAC input
0.7 A
1.4 A
1.3 A
2.4 A
230 VAC input
0.44
0.45
0.92
0.97
Harmonic current emissions
Output
89%
100 to 240 VAC, 90 to 350 VDC (allowable range: 85 to 264 VAC) *6
Frequency *1
Current (Typical)
88%
480 W
---
Conforms to EN61000-3-2
Leakage current
(Typical)
115 VAC input
0.19 mA
0.19 mA
0.24 mA
0.26 mA
230 VAC input
0.34 mA
0.36 mA
0.54 mA
0.65 mA
Inrush current
(Typical) *2
115 VAC input
16 A
230 VAC input
32 A
70 mV
130 mV
Voltage adjustment range *3
–10% to 15% (with V.ADJ) (guaranteed)
Ripple at 20 MHz
(Typical) *4
70 mV
230 VAC input
120 mV
Input variation influence
0.5% max. (at 85 to 264 VAC input, 100% load)
Load variation Influence
(Rated Input voltage)
1.5% max., at 0% to 100% load
Temperature variation influence
0.05%/°C max.
Start up time
(Typical) *2
115 VAC input
530 ms
720 ms
790 ms
770 ms
230 VAC input
410 ms
510 ms
750 ms
670 ms
Hold time
(Typical) *2
115 VAC input
24 ms
27 ms
34 ms
21 ms
230 VAC input
117 ms
128 ms
36 ms
22 ms
Overload protection *2
Additional Overvoltage protection *2
functions Parallel operation
105% to 160% of rated load current
Yes *5
No
Series operation
Possible for up to two Power Supplies (with external diode)
Ambient operating temperature
–25 to 60°C (Refer to Engineering Data)
Storage temperature
–25 to 65°C
Ambient operating humidity
20% to 90% (Storage humidity: 10% to 95%)
Dielectric strength
(detection current: 20 mA)
3.0 kVAC for 1 min. (between all inputs and outputs)
2.0 kVAC for 1 min. (between all inputs and PE terminal)
1.0 kVAC for 1 min. (between all outputs and PE terminal)
Insulation resistance
100 MΩ min. (between all outputs and all inputs/ PE terminals) at 500 VDC
10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions
Vibration resistance
10 to 150 Hz, 0.35-mm single amplitude (5 G max for 60W, 120W, 240 W, 3 G max for 480 W) for 80 min.
each in X, Y, and Z directions
Shock resistance
150 m/s2, 3 times each in ±X, ±Y, and ±Z directions
Output indicatior
Others
EMI
Yes (color: green), lighting from 80% to 90% or more of rated voltage
Conducted Emission
Conforms to EN61204-3 EN55011 Class A and based on FCC Class A
Radiated Emission
Conforms to EN61204-3 EN55011 Class A
EMS
Conforms to EN61204-3 high severity levels
Approved Standards
UL Listed: UL508 (Listing)
UL UR: UL60950-1 (Recognition)
cUL: CSA C22.2 No.107.1
cUR: CSA C22.2 No.60950-1
EN/VDE: EN50178 (=VDE0160), EN60950-1 (=VDE0805)
Fulfilled Standards
SELV (EN60950-1/EN50178/UL60950-1)
EN50274 for Terminal parts
Degree of protection
IP20 by EN / IEC60529
SEMI
F47-0706 (200 to 240 VAC)
Weight
260 g
580 g
940 g
1,550 g
*1. Do not use an inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal
temperature of the Power Supply may result in ignition or burning.
*2. For a cold start at 25°C. Refer to Engineering Data on page 5 for details.
*3. If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than +15% of the voltage adjustment range. When adjusting
the output voltage, confirm the actual output voltage from the Power Supply and be sure that the load is not damaged.
*4. A characteristic when the ambient operating temperature is between –25 to 60°C.
*5. To reset the protection, turn OFF the input power for three minutes or longer and then turn it back ON.
*6. 90 to 350 VDC’s UL standards are scheduled to obtain certification in June, 2013.
2
S8VK-C
Connections
Block Diagrams
S8VK-C06024 (60W)
AC (L)
INPUT
+V
Fuse:
250 VAC 6.3 A HBC
+V
−V DC OUTPUT
Noise filter
AC (N)
Rectifier
Inrush
Smoothing
current
protection circuit
Rectifier/
smoothing circuit
−V
−V
Drive control
circuit
Voltage
detection circuit
Overcurrent
detection circuit
Overvoltage
detection circuit
Photocoupler
S8VK-C12024 (120W)
+V
Fuse:
250 VAC 8.0 A HBC
AC (L)
INPUT
+V
−V DC OUTPUT
Noise filter
AC (N)
Rectifier
Rectifier/
smoothing circuit
Inrush current Smoothing
protection
circuit
circuit
−V
−V
Drive control
circuit
Voltage
detection circuit
Overcurrent
detection circuit
Overvoltage
detection circuit
Photocoupler
S8VK-C24024 (240W)
+V
Fuse:
250 VAC 8.0 A HBC
AC (L)
INPUT
+V
−V DC OUTPUT
Noise filter
AC (N)
Inrush current Rectifier
protection
Harmonic current
suppression circuit
(Power factor
improvement)
Smoothing
circuit
Rectifier/
smoothing circuit
−V
−V
Drive circuit
Overcurrent
detection circuit
Drive control
circuit
Voltage
detection circuit
Overvoltage
detection circuit
Photocoupler
S8VK-C48024 (480W)
+V
Fuse:
250 VAC 12.0 A HBC
AC (L)
INPUT
+V
−V DC OUTPUT
Noise filter
AC (N)
Inrush
current
protection
Rectifier
Harmonic current Smoothing
suppression circuit circuit
(Power factor
improvement)
Rectifier/
smoothing circuit
−V
−V
Drive circuit
Drive control
circuit
Overcurrent
detection circuit
Voltage
detection circuit
Overvoltage
detection circuit
Photocoupler
3
S8VK-C
Construction and Nomenclature
Nomenclature
60-W Models
120-W Models
240-W Models
480-W Models
S8VK-C06024
S8VK-C12024
S8VK-C24024
S8VK-C48024
3
3
3
4
4
4
4
5
5
5
5
1
2
1
No.
1
2
3
4
5
Name
Input terminals (L), (N)
Protective Earth terminal (PE)
DC Output terminals (−V), (+V)
Output indicator (DC ON: Green)
Output voltage adjuster (V.ADJ)
2
1
2
1
2
Function
Connect the input lines to these terminals. *1
Connect the ground line to this terminal. *2
Connect the load lines to these terminals.
Lights while a direct current (DC) output is ON.
Use to adjust the voltage.
*1. The fuse is located on the (L) side. It is not user-replaceable. For a DC input, connect the positive voltage to the L terminal.
*2. This is the protective earth terminal specified in the safety standards. Always ground this terminal.
Engineering Data
Derating Curve
Load ratio (%)
60, 120, 240, 480 W
120
100
A
80
B
60
40
20
0
−40
−25
−10 0 10 20 30 40 50 60 70 80
Ambient temperature (°C)
Note: 1. At less than 90 VAC, the derating is 2.5%/V
2. For a DC power input, reduce the load given in the above
derating curve by multiplying the following coefficients.
S8VK-C06024/S8VK-C12024: 0.8
S8VK-C24024/S8VK-C48024: 0.7
A. Standard mounting
40°C and over: the derating is 2.0%/°C
B. Face-up mounting
30°C and over: the derating is 1.67%/°C
4
3
S8VK-C
Overvoltage Protection
(A) Standard (Vertical) mounting
(B) Face-up mounting
Overload Protection
The load and the power supply are automatically protected from
overcurrent damage by this function.
Overload protection is activated if the output current rises above
105% of the rated current.
When the output current returns within the rated range overload
protection is automatically cleared.
Consider the possibility of an overvoltage and design the system so
that the load will not be subjected to an excessive voltage even if the
feedback circuit in the Power Supply fails. If an excessive voltage that
is approximately 130% of the rated voltage or more is output, the
output voltage is shut OFF. Reset the input power by turning it OFF
for at least three minutes and then turning it back ON again.
Output voltage (V)
Mounting
+30%
(approx.)
Overvoltage protection
operating
+15%
Rated output
voltage
Variable range
−10%
Output voltage (V)
0V
The values shown in the above diagram is for reference only.
Note: Do not turn ON the power again until the cause of the
overvoltage has been removed.
Inrush Current, Startup Time, Output Hold Time
Intermittent operation
Input ON
0
50
100
Output current (%)
Input OFF
AC input
voltage
The values shown in the above diagrams are for reference only.
Note: 1. Internal parts may occasionally deteriorate or be damaged
if a short-circuited or overcurrent state continues during
operation.
2. Internal parts may possibly deteriorate or be damaged if the
Power Supply is used for applications with frequent inrush
current or overloading at the load end. Do not use the Power
Supply for such applications.
Inrush current on input application
AC input
current
96.5%
90%
Output
voltage
Startup time (1,000 ms max.)
Hold time
(20 ms min.)
Note: Twice the input current or above will flow during the parallel
operation or redundant system.
Therefore, check the fusing characteristics of fuses and
operating characteristics of breakers making sure that the
external fuses will not burn out and the circuit breakers will not
be activated by the inrush current.
5
S8VK-C
Two phases application for Single phase models
For All Single phase Models, S8VK-C
Basically OMRON single phase power supply can be used on twophases of a 3–phase-system when some of conditions satisfy like
below.
1. The supplying voltage is below the maximum rated input.
OMRON Power supply allows the input voltage equivalent or less
than 240 VAC+10%.
Please confirm the input voltage between two lines if the input
voltage satisfies this condition before connecting.
2. The external protector is needed on N input line to secure a safety.
N line has no protection of a fuse internally.
An appropriate fuse or circuit breaker should be connected on N
input line like the following.
L1
L2
L3
PE
Power Supply
Internal
Fuse
A external
fuse or a
circuit breaker
L
N
max. 240 VAC+10%
Reference Value
Value
Reliability
(MTBF)
6
Single phase model
60 W: 630,000 hrs
120 W: 490,000 hrs
240 W: 270,000 hrs
480 W: 190,000 hrs
Definition
MTBF stands for Mean Time Between
Failures, which is calculated according to the
probability of accidental device failures, and
indicates reliability of devices.
Therefore, it does not necessarily represent a
life of the product.
Life expectancy
10 yrs. Min.
Definition
The life expectancy indicates average
operating hours under the ambient
temperature of 40°C and a load rate of 50%.
Normally this is determined by the life
expectancy of the built-in aluminum electrolytic
capacitor.
S8VK-C
Dimensions
(Unit: mm)
S8VK-C06024 (60 W)
5
(1)
110
3.6 dia. (Bit #1)
106
34.9
90
75.4
3.6 dia. (Bit #1)
Rail Stopper
3.5
4.7
(Sliding: 10 max.)
7.62
32
S8VK-C12024 (120 W)
122.2
117.8
112.2
(1)
5.0 dia. (Bit #2)
6.35
104.6
(4)
34.7
125
5.0 dia. (Bit #2)
Rail Stopper
4.7
(Sliding: 7.5 max.)
6.35
40
(10)
S8VK-C24024 (240 W)
150
145.6
6.35
5.0 dia. (Bit #2)
(1)
(4)
140
125
104.6
34.7
5.0 dia. (Bit #2)
Rail Stopper
(10)
6.35
4.7
(Sliding: 7.5 max.)
60
S8VK-C48024 (480 W)
(1)
150
145.6
140
(4)
125
34.7
52.3
5.0 dia. (Bit #2)
6.35
6.35
95
Rail Stopper
5.0 dia. (Bit #2)
4.7
(Sliding: 7.5 max.)
(10)
7
S8VK-C
DIN Rail (Order Separately)
Note: All units are in millimeters unless otherwise indicated.
Mounting Rail (Material: Aluminum)
PFP-100N
PFP-50N
7.3±0.15
4.5
35±0.3
15
25
10
25
25
10
1,000 (500) *
25
27±0.15
15(5) *
1
* Values in parentheses are for the PFP-50N.
Mounting Rail (Material: Aluminum)
PFP-100N2
16
4.5
35±0.3 27
15
25
10
25
25
10
1,000
25
15
24
29.2
1
1.5
End Plate
PFP-M
10
6.2
M4×8 panhead screw
1.8
1
50
1.8
35.5 35.5
11.5
10
M4 spring washer
1.3
4.8
Note: If there is a possibility that the Unit will be subject to vibration or shock, use a steel DIN Rail. Otherwise, metallic filings may result from
aluminum abrasion.
8
S8VK-C
Mounting Brackets
Name
Front-mounting bracket (for 60 W models)
Model
S82Y-VS10F
Front-mounting bracket (for 120, 240 and 480 W models) S82Y-VK10F
Side-mounting bracket (for 60 W models)
S82Y-VS10S
Side-mounting bracket (for 120 W models)
S82Y-VK10S
Side-mounting bracket (for 240 W models)
S82Y-VK20S
Type
Model
Dimensions
Appearance
41
4.5 dia.±0.1
35
25
Front-mounting
bracket
S82Y-VS10F
(For 60 W models)
35±0.1
7.3
10
40
50
t = 1.0
(For 120 W types)
Front-mounting
bracket
(for 120, 240 and
480 W models)
(For 240 W types)
140±0.1
150
S82Y-VK10F
25±0.1
4.5 dia.±0.1
5.4
38
t = 2.0
9
S8VK-C
Type
Model
Dimensions
Appearance
4.5 dia.±0.1
55±0.1
35
Right-side mounting
Left-side mounting
Right-side mounting
Left-side mounting
Right-side mounting
60±0.1
80
Side-mounting
bracket
S82Y-VS10S
(For 60 W models)
Left-side mounting
13
64
t = 2.0
73
40
49
50±0.1
15.5±0.1
4.5 dia.±0.1
Side-mounting
bracket
(For 120 W
models)
S82Y-VK10S
140±0.1
125
150
t = 2.0
73
40
59
50±0.1
15.5±0.1
4.5 dia.±0.1
Side-mounting
bracket
(For 240 W
models)
140±0.1
S82Y-VK20S
125
t = 2.0
10
150
S8VK-C
Safety Precautions
Warning Indications
CAUTION
Indicates a potentially hazardous
situation which, if not avoided, may
result in minor or moderate injury or in
property damage.
Precautions for
Safe Use
Supplementary comments on what to
do or avoid doing, to use the product
safely.
Precautions for
Correct Use
Supplementary comments on what to
do or avoid doing, to prevent failure to
operate, malfunction or undesirable
effect on product performance.
Meaning of Product Safety Symbols
Used to warn of the risk of electric shock under
specific conditions.
Used to warn of the risk of minor injury caused by
high temperatures.
Used for general mandatory action precautions
for which there is no specified symbol.
Use to indicate prohibition when there is a risk of
minor injury from electrical shock or other source
if the product is disassembled.
!CAUTION
Minor electric shock, fire, or Product failure may
occasionally occur. Do not disassemble, modify, or
repair the Product or touch the interior of the
Product.
Minor burns may occasionally occur. Do not touch
the Product while power is being supplied or
immediately after power is turned OFF.
Fire may occasionally occur. Tighten terminal screws
to the specified torque (0.5 to 0.6 N·m).
Minor injury due to electric shock may occasionally
occur. Do not touch the terminals while power is
being supplied. Always close the terminal cover after
wiring.
Minor electric shock, fire, or Product failure may
occasionally occur. Do not allow any pieces of metal
or conductors or any clippings or cuttings resulting
from installation work to enter the Product.
11
S8VK-C
Precautions for Safe Use
Wiring
• Connect the ground completely. A protective earthing terminal
stipulated in safety standards is used. Electric shock or malfunction
may occur if the ground is not connected completely.
• Minor fire may possibly occur. Ensure that input and output
terminals are wired correctly.
• Do not apply more than 75-N force to the terminal block when
tightening it.
• Be sure to remove the sheet covering the Product for machining
before power-ON so that it does not interfere with heat dissipation.
• Use the following material for the wires to be connected to the
S8VK-C to prevent smoking or ignition caused by abnormal loads.
Terminals and Wiring
INPUT
OUTPUT
American
Wire Gauge
Solid Wire
/Stranded Wire
American
Wire Gauge
Solid Wire
/Stranded Wire
S8VK-C06024
AWG22 to 12
0.35 to 4 mm2
/0.35 to 2.5 mm2
AWG20 to 12
0.5 to 4 mm2
/0.5 to 2.5 mm2
S8VK-C12024
AWG22 to 10
0.35 to 6 mm2
/0.35 to 4 mm2
AWG18 to 10
0.75 to 6 mm2
/0.75 to 4 mm2
AWG20 to 10
0.5 to 6 mm2
/0.5 to 4 mm2
AWG14 to 10
2.5 to 6 mm2
/2.5 to 4 mm2
AWG12 to 10
4 to 6 mm2
/4 mm2
Model
S8VK-C24024
2
S8VK-C48024
AWG16 to 10
1.5 to 6 mm
/1.5 to 4 mm2
PE
American
Wire Gauge
Solid Wire
/Stranded Wire
AWG14 or thicker
2.5 mm2 or thicker
/2.5 mm2 or thicker
• Strip I/O wires for 8 mm when using a screwless terminal block.
Note: The rated current for output terminals is 10 A per terminal.
Be sure to use multiple terminals simultaneously for current that exceeds the terminal rating.
When applying a current of 10 A or more, use at least two terminals each for the positive and negative wires.
Installation Environment
• Do not use the Power Supply in locations subject to shocks or
vibrations. In particular, install the Power Supply as far away as
possible from contactors or other devices that are a vibration
source.
• Install the Power Supply well away from any sources of strong,
high-frequency noise and surge.
Operating Life
• The life of a Power Supply is determined by the life of the
electrolytic capacitors used inside. Here, Arrhenius Law applies,
i.e., the life will be cut in half for each rise of 10°C or the life will be
doubled for each drop of 10°C. The life of the Power Supply can
thus be increased by reducing its internal temperature.
12
Ambient Operating and Storage Environments
• Store the Power Supply at a temperature of −25 to 65°C and a
humidity of 10% to 95%.
• Do not use the Power Supply in areas outside the derating curve
otherwise, internal parts may occasionally deteriorate or be
damaged.
• Use the Power Supply at a humidity of 20% to 90%.
• Do not use the Power Supply in locations subject to direct sunlight.
• Do not use locations where liquids, foreign matter, or corrosive
gases may enter the interior of Products.
S8VK-C
Precautions for Correct Use
Mounting
DIN Rail Mounting
• Take adequate measures to ensure proper heat dissipation to
increase the long-term reliability of the Product. Be sure to allow
convection in the atmosphere around devices when mounting. Do
not use in locations where the ambient temperature exceeds the
range of the derating curve.
• When cutting out holes for mounting, make sure that cuttings do
not enter the interior of the Products.
To mount the Block on a DIN Rail, hook portion (A) of the Block onto
the rail and press the Block in direction (B).
(A)
(B)
*1
To dismount the Block, pull down portion (C) with a flat-blade
screwdriver and pull out the Block.
30 mm min.
*1. Convection of air
*2. 20 mm min.
• Improper mounting will interfere with heat dissipation and may
occasionally result in deterioration or damage of internal parts. Use
the Product within the derating curve for the mounting direction that
is used.
• Use a mounting bracket when the Product is mounted facing
horizontally.
• Heat dissipation will be adversely affected. When the Product is
mounted facing horizontally, always place the side with the label
facing upward.
• Operate the Power Supply within a range that is 5°C less than the
values in the derating curve in Engineering Data on page 4 if the
Power Supply is used with an installation spacing of 10 mm min.
(20 mm max.) on the left and right.
Overcurrent Protection
• Internal parts may possibly deteriorate or be damaged if a
short-circuited or overcurrent state continues during operation.
• Internal parts may possibly deteriorate or be damaged if the Power
Supply is used for applications with frequent inrush current or
overloading at the load end. Do not use the Power Supply for such
applications.
• The DC ON indicator (green) flashes if the overload protection
function operates.
Charging a Battery
If you connect a battery as the load, install overcurrent control and
overvoltage protection circuits.
Output Voltage Adjuster (V.ADJ)
• The output voltage adjuster (V.ADJ) may possibly be damaged if it
is turned with unnecessary force. Do not turn the adjuster with
excessive force.
• After completing output voltage adjustment, be sure that the output
capacity or output current does not exceed the rated output
capacity or rated output current.
(C)
Track stopper
Series Operation
Two power supplies can be connected in series.
Correct
AC (L)
+V
AC (N)
−V
AC (L)
+V
AC (N)
−V
Note: 1. The diode is connected as shown in the figure. If the load is
short-circuited, a reverse voltage will be generated inside
the Power Supply. If this occurs the Power Supply may
possibly deteriorate or be damaged. Always connect a
diode as shown in the figure.
Select a diode having the following ratings.
Type
Schottky Barrier diode
Dielectric strength (VRRM) Twice the rated output voltage or above
Twice the rated output current or above
Forward current (IF)
2. Although Products having different specifications can be
connected in series, the current flowing through the load
must not exceed the smaller rated output current.
Making Positive/Negative Outputs
• The outputs are floating outputs (i.e., the primary circuits and
secondary circuits are separated). You can therefore make
positive and negative outputs by using two Power Supplies.
You can make positive and negative outputs with any of the
models.
If positive and negative outputs are used, connect Power Supplies
of the same model as in the following figure. (Combinations with
different output capacities or output voltages can be made.
However, use the lower of the two maximum rated output currents
as the current to the loads.)
+V
+V
INPUT
−V
Load
*1
0V
+V
INPUT
−V
Load
*2
−V
13
S8VK-C
• Depending on the model, internal circuits may be damaged due to
startup failure when the power is turned ON if loads such as a
servomotor or operational amplifier may operate in series.
Therefore, connect bypass diodes (D1, D2) as shown in the
following figure.
If the list of models that support series connection of outputs says
that an external diode is not required, an external diode is also not
required for positive/negative outputs.
D1
+V
INPUT
D2
Load
Load
−V
Load
+V
INPUT
−V
• Use the following information as a guide to the diode type, dialectic
strength, and current.
• Type: Schottky barrier diode
• Dielectric strength (VRRM): Twice the rated Power Supply output
voltage or higher
• Forward current (IF): Twice the rated Power Supply output
current or higher
Backup Operation
Backup operation can be performed with S8VK-R.
Refer to the S8VK-R Datasheet for detail.
In Case There Is No Output Voltage
The possible cause for no output voltage may be that the overcurrent
or overvoltage protection has operated. The internal protection may
operate if a large amount of surge voltage such as a lightening surge
occurs while turning ON the power supply.
In case there is no output voltage, please check the following points
before contacting us:
• Checking overload protected status:
Check whether the load is in overload status or is short-circuited.
Remove wires to load when checking.
• Checking overvoltage or internal protection:
Turn the power supply OFF once, and leave it OFF for at least
3 minutes. Then turn it ON again to see if this clears the condition.
Audible Noise at Power ON
(240-W, and 480-W Models)
A harmonic current suppression circuit is built into the Power Supply.
This circuit can create noise when the input is turned ON, but it will
last only until the internal circuits stabilize and does not indicate any
problem in the Product.
14
Read and Understand this Catalog
Please read and understand this catalog before purchasing the product. Please consult your OMRON representative if you have
any questions or comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year
(or other period if specified) from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT,
MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER
ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET
THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR
IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS
OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON
CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE
PRODUCTS UNLESS OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED,
INSTALLED, AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE
MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of the
product in the customer's application or use of the product.
Take all necessary steps to determine the suitability of the product for the systems, machines, and equipment with which it will
be used.
Know and observe all prohibitions of use applicable to this product.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT
ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON
PRODUCT IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR
SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons. Consult with
your OMRON representative at any time to confirm actual specifications of purchased product.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a
warranty. It may represent the result of OMRON's test conditions, and the users must correlate it to actual application
requirements. Actual performance is subject to the OMRON Warranty and Limitations of Liability.
OMRON Corporation
Industrial Automation Company
Authorized Distributor:
Tokyo, JAPAN
Contact: www.ia.omron.com
Regional Headquarters
OMRON EUROPE B.V.
Wegalaan 67-69-2132 JD Hoofddorp
The Netherlands
Tel: (31)2356-81-300/Fax: (31)2356-81-388
OMRON ELECTRONICS LLC
One Commerce Drive Schaumburg,
IL 60173-5302 U.S.A.
Tel: (1) 847-843-7900/Fax: (1) 847-843-7787
OMRON ASIA PACIFIC PTE. LTD.
No. 438A Alexandra Road # 05-05/08 (Lobby 2),
Alexandra Technopark,
Singapore 119967
Tel: (65) 6835-3011/Fax: (65) 6835-2711
OMRON (CHINA) CO., LTD.
Room 2211, Bank of China Tower,
200 Yin Cheng Zhong Road,
PuDong New Area, Shanghai, 200120, China
Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200
© OMRON Corporation 2013 All Rights Reserved.
In the interest of product improvement,
specifications are subject to change without notice.
CSM_1_2_0513
Cat. No. T058-E1-01
0313
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Omron:
S82Y-VK10F