Switch Mode Power Supply
Power
supplies
S8VS
15/30-W Models
Compact, Thin Power Supplies That Mount
Just About Anywhere to Contribute to
Control Panel Downsizing
• Compact, thin size: 22.5 × 85 × 96.5 mm (W × H × D).
• Three mounting directions
(standard, horizontal, facing horizontal).
• Mounting directly onto the panel is possible.
• Safety standards:
UL508/60950-1/1604, CSA C22.2 No. 14/60950-1/213,
EN50178 (= VDE0160), EN60950-1 (= VDE0805).
60/90/120/180/240-W Models
New Models with Total Run Time Monitor in
Addition to Models with Maintenance
Forecast Monitor
• Compact size: 40 × 95 mm (W × H) (60-W Models).
• Status displayed on 3-digit, 7-segment display.
• Safety standards:
UL508/60950, CSA C22.2 No. 14/60950,
EN50178 (= VDE0160), EN60950 (= VDE0805).
Features Common to All Models
• Mount to DIN-rail.
• Lead-free solder.
Switch Mode Power Supply
S8VS
B-5
Model Number Structure
■ Model Number Legend
S8VS- @@@@@@@
1
2
3
3. Configuration
15-W, 30-W Models
None: Standard
1. Power Ratings
015: 15 W
030: 30 W
060: 60 W
090: 90 W
120: 120 W
180: 180 W
240: 240 W
60-W Models
None: Standard
A:
With maintenance forecast monitor
B:
With total run time monitor
2. Output voltage
05: 5 V
12: 12 V
24: 24 V
90-W, 120-W, 180-W, 240-W Models
None: Standard
A:
With maintenance forecast monitor
and undervoltage alarm
(transistor (sinking))
B:
With total run time monitor and undervoltage alarm
(transistor (sinking))
AP: With maintenance forecast monitor
and undervoltage alarm
(transistor (sourcing))
BP: With total run time monitor and undervoltage alarm
(transistor (sourcing))
Ordering Information
Power ratings
15 W
30 W
60 W
Input Voltage
100 to 240 VAC
Output voltage
Output current
5V
2.0 A
12 V
1.2 A
24 V
0.65 A
5V
4.0 A
12 V
2.5 A
24 V
1.3 A
24 V
2.5 A
Alarm output
---
Model number
S8VS-01505 (See note 1.)
S8VS-01512
S8VS-01524
---
S8VS-03005 (See note 2.)
S8VS-03012
S8VS-03024
---
S8VS-06024
S8VS-06024A
S8VS-06024B
90 W
3.75 A
120 W
5A
180 W
7.5 A
240 W
10 A
Note: 1. The output capacity of the S8VS-01505 is 10 W.
2. The output capacity of the S8VS-03005 is 20 W.
B-6
Switch Mode Power Supply S8VS
---
S8VS-09024
Sinking
S8VS-09024A
Sourcing
S8VS-09024AP
Sinking
S8VS-09024B
Sourcing
S8VS-09024BP
---
S8VS-12024
Sinking
S8VS-12024A
Sourcing
S8VS-12024AP
Sinking
S8VS-12024B
Sourcing
S8VS-12024BP
---
S8VS-18024
Sinking
S8VS-18024A
Sourcing
S8VS-18024AP
Sinking
S8VS-18024B
Sourcing
S8VS-18024BP
---
S8VS-24024
Sinking
S8VS-24024A
Sourcing
S8VS-24024AP
Sinking
S8VS-24024B
Sourcing
S8VS-24024BP
Specifications
Power ratings
Type
Item
Efficiency (typical)
Input
Voltage
Frequency
Current
5-V models
12-V models
24-V models
100 V input
200 V input
230 V input
Power factor
Harmonic current emissions
Leakage current
100 V input
200 V input
230 V input
Inrush current
100 V input
(See note 1.)
200 V input
230 V input
Voltage adjustment range
(See note 2.)
Ripple
Output
15 W
Standard
72% min. (76% typ.)
74% min. (79% typ.)
77% min. (81% typ.)
100 to 240 VAC (85 to 264 VAC)
50/60 Hz (47 to 450 Hz)
0.45 A max.
0.25 A max.
5 V: (0.14 A typ.), 12 V/24 V (0.19 A typ.)
--Conforms to EN61000-3-2
0.5 mA max.
1.0 mA max.
5 V/12 V/24 V: (0.30 mA typ.)
25 A max. (20 A typ.) (for a cold start at 25°C)
50 A max. (40 A typ.) (for a cold start at 25°C)
5 V/12 V/24 V: (29 A typ.) (See note 6.)
−10% to 15% (with V.ADJ) (guaranteed)
Power
supplies
■ Ratings/Characteristics
30 W
Standard
70% min. (76% typ.)
76% min. (83% typ.)
80% min. (85% typ.)
0.9 A max.
0.6 A max.
5 V: (0.27 A typ.), 12 V/24 V (0.37 A typ.)
5 V/12 V/24 V:(0.32 mA typ.)
5 V/12 V/24 V: (40 A typ.) (See note 6.)
2.0% (p-p) max. (at rated input/output voltage)
5 V: (0.70%(p-p) typ.), 12 V:(0.48%(p-p) typ.), 24 V:(0.25%(p-p) 5 V: (0.70%(p-p) typ.), 12 V:(0.52%(p-p) typ.), 24 V:(0.19%(p-p)
typ.)
typ.)
f=100MHz measuring 5 V: (0.86%(p-p) typ.), 12 V:(0.56%(p-p) typ.), 24 V:(0.32%(p-p) 5 V: (0.80%(p-p) typ.), 12 V:(0.58%(p-p) typ.), 24 V:(0.21%(p-p)
typ.)
typ.)
Input variation influence
0.5% max. (at 85 to 264 VAC input, 100% load)
Load variation influence (rated input voltage)
2.0% max. (5 V), 1.5% max. (12 V, 24 V), (with rated input, 0 to 100% load)
Temperature variation influence
0.05%/°C max.
Start up time (See note 1 and 7.)
100 ms max. (at rated input/output voltage)
1,000 ms max. (at rated input/output voltage)
5 V: (6 ms typ.), 12 V: (12 ms typ.), 24 V: (18 ms typ.)
5 V/12 V/24 V: (240 ms typ.)
Hold time (See note 1.)
20 ms min. (at rated input/output voltage)
at 100% load
5 V: (328 ms typ.), 12V: (251 ms typ.), 24 V: (243 ms typ.)
5 V: (299 ms typ.), 12 V: (217 ms typ.), 24 V: (210 ms typ.)
Overload protection (See note 1.)
105% to 160% of rated load current, voltage drop, automatic re- 105% to 160% of rated load current, voltage drop, intermittent
set
operation, automatic reset
Overvoltage protection (See note 1.)
Yes (a zener diode clamp) (See note 3.)
Yes (See note 4.)
Output voltage indication
No
Output current indication
No
Peak-hold current indication
No
Maintenance forecast monitor indication
No
Maintenance forecast monitor output
No
Total run time monitor indication
No
Total run time monitor output
No
Undervoltage alarm indication
Yes (color: red)
Undervoltage alarm output
No
Parallel operation
No
Series operation
Models with 24-V output: Possible for up to 2 Power Supplies (with external diode)
Models with 5- or 12-V output: Not possible
Operating ambient temperature
Refer to the derating curve in Engineering Data. (with no icing or condensation)
Storage temperature
−25 to 65°C
Operating ambient humidity
25% to 85% (Storage humidity: 25% to 90%)
Dielectric strength
3.0 kVAC for 1 min. (between all inputs and outputs; detection current: 20 mA)
2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA)
1.0 kVAC for 1 min. (between all outputs and PE terminals; detection current: 20 mA)
Insulation resistance
100 MΩ min. (between all outputs and all inputs/ PE terminals) at 500 VDC
Vibration resistance
10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions
10 to 150 Hz, 0.35-mm single amplitude (5 G max.) for 80 min. each in X, Y, and Z directions
Shock resistance
150 m/s2, 3 times each in ±X, ±Y, and ±Z directions
f=20MHz measuring
Additional
functions
Other
Output indicator
EMI
Conducted
Emissions
Radiated
Emissions
Yes (color: green)
Conforms to EN61204-3 EN55011 Class B and based on FCC Class A
Conforms to EN61204-3 EN55011 Class B
EMS
Approved standards
Note:
1.
2.
3.
4.
5.
6.
7.
Conforms to EN61204-3 high severity levels
UL: UL508 (Listing, Class 2: Per UL1310), UL60950-1, UL1604 (Class I/Division2)
cUL: CSA C22.2 No.14 (Class 2), No.60950-1, No.213 (Class I/Division2)
EN/VDE: EN50178 (=VDE0160), EN60950-1 (=VDE0805)
SELV (EN60950/EN50178/UL60950-1)
According to VDE0106/P100, IP20
Weight
160 g max.
180 g max.
Refer to the Engineering Data section on page B-21 for details.
If the V.ADJ adjuster is turned, the voltage will increase by more than +15% of the voltage adjustment range. When adjusting the output voltage, confirm the actual output voltage from
the Power Supply and be sure that the load is not damaged.
The overvoltage protection of the S8VS-015@@ uses a zener diode clamp. If the internal feedback circuit is destroyed by any chance, the load may be destroyed by the clamped output
voltage (approx. 140% to 190% of the rated output voltage).
To reset the protection, turn OFF the power supply for three minutes or longer and then turn the power supply back ON.
The typical values indicate the values for an input condition of 230 VAC. All items are measured at a frequency of 50 Hz.
The inrush current circuits do not differ for voltage specifications. Therefore, the typical values are the data values for 24-V models.
The circuit forms are different, so the start up time is shorter only when using a 15-W power rating.
Switch Mode Power Supply
S8VS
B-7
Specifications
■ Ratings/Characteristics
Power ratings
Type
Standard
Item
Efficiency (typical)
Input
Voltage
Frequency
Current
Output
Additional
functions
60 W
Maintenance
forecast monitor
Total run time
monitor
Standard
90 W
Maintenance
forecast monitor
Total run time
monitor
78% min. (86% typ.)
80% min. (87% typ.)
100 to 240 VAC (85 to 264 VAC)
50/60 Hz (47 to 450 Hz)
100 V input
1.7 A max.
2.3 A max.
200 V input
1.0 A max.
1.4 A max.
230 V input
(0.7 A typ.)
(0.9 A typ.)
Power factor
--Harmonic current emissions
Conforms to EN61000-3-2
Leakage current
100 V input
0.5 mA max.
200 V input
1.0 mA max.
230 V input
(0.40 mA typ.)
(0.35 mA typ.)
Inrush current
100 V input
25 A max. (for a cold start at 25°C)
(See note 1.)
200 V input
50 A max. (for a cold start at 25°C)
230 V input
(47 A typ.)
(38 A typ.)
Voltage adjustment range (See note 2.)
−10% to 15% (with V.ADJ) (guaranteed)
Ripple
2.0% (p-p) max. (at rated input/output voltage)
f=20MHz measuring (0.29% (p-p) typ.)
(0.38% (p-p) typ.)
f=100MHz measuring (0.32% (p-p) typ.)
(0.42% (p-p) typ.)
Input variation influence
0.5% max. (at 85 to 264 VAC input, 100% load)
Load variation influence (rated input voltage)
1.5% max. (with rated input, 0 to 100% load)
Temperature variation influence
0.05%/°C max.
Start up time (See note 1.)
1,000 ms max. (at rated input/output voltage)
(270 ms typ.)
(260 ms typ.)
Hold time (See note 1.)
20 ms min. (at rated input/output voltage)
at 100% load
(220 ms typ.)
(190 ms typ.)
Overload protection (See note 1.)
105% to 160% of rated load current, voltage drop, intermittent, automatic reset
Overvoltage protection (See notes 1 and 3.) Yes
Output voltage indication (See note 4.)
No
Yes (selectable) (See note 5.)
No
Yes (selectable) (See note 5.)
Output current indication (See note 4.)
No
Yes (selectable) (See note 6.)
No
Yes (selectable) (See note 6.)
Peak-hold current indication (See note 4.)
No
Yes (selectable) (See note 7.)
No
Yes (selectable) (See note 7.)
Maintenance forecast monitor indication (See note 4.) No
Yes (selectable)
No
No
Yes (selectable)
No
Yes (open collector out- No
Maintenance forecast monitor output
No
put), 30 VDC max., 50
mA max. (See note 8.)
Total run time monitor indication (See note 4.)
Total run time monitor output
No
No
Undervoltage alarm indication (See note 4.) No
Undervoltage alarm output terminals
No
Other
Parallel operation
Series operation
Operating ambient temperature
Storage temperature
Operating ambient humidity
Dielectric strength
Insulation resistance
Vibration resistance
Yes (selectable)
Yes (open collector output), 30 VDC max., 50
mA max. (See note 8.)
Yes (selectable)
No
Yes (selectable)
Yes (open collector output)
30 VDC max., 50 mA max. (See note 8.)
150 m/s2, 3 times each in ±X, ±Y, and ±Z directions
Yes (color: green)
Conducted
Conforms to EN61204-3 EN55011 Class A and based on FCC Class A
Emissions
Conforms to EN61204-3 EN55011 Class B (See note 9.)
Radiated
Conforms to EN61204-3 EN55011 Class A
Emissions
Conforms to EN61204-3 EN55011 Class B (See note 9.)
EMS
Conforms to EN61204-3 high severity levels
Approved standards
UL: UL508 (Listing, Class 2: Per UL1310), UL60950
UL: UL508 (Listing), UL60950
cUL: CSA C22.2 No.14 (Class 2), No.60950
cUL: CSA C22.2 No.14, No.60950
EN/VDE: EN50178 (=VDE0160), EN60950 (=VDE0805)
EN/VDE: EN50178 (=VDE0160), EN60950 (=VDE0805)
SELV (EN60950/EN50178/UL60950-1)
SELV (EN60950/EN50178/UL60950-1)
According to VDE0106/P100, IP20
According to VDE0106/P100, IP20
Weight
330 g max.
490 g max.
1. Refer to the Engineering Data section on page B-21 for details.
2. If the V.ADJ adjuster is turned, the voltage will increase by more than +15% of the voltage adjustment range (by more than +10% for 240-W models). When adjusting the output voltage,
confirm the actual output voltage from the Power Supply and be sure that the load is not damaged.
3. To reset the protection, turn OFF the power supply for three minutes or longer and then turn the power supply back ON.
4. Displayed on 7-segment LED. (character height: 8 mm)
5. Resolution of output voltage indication: 0.1 V, Precision of output voltage indication: ±2% (percentage of output voltage value, ±1 digit)
6. Resolution of output current indication: 0.1 A; Precision of output current indication: ±5% F.S. ±1 digit max. (specified by rated output voltage)
7. Resolution of peak-hold current indication: 0.1 A; Precision of peak-hold current indication: ±5% F.S. ±1 digit max. (specified by rated output voltage);
Signal width required for peak-hold current: 20 ms
8. A Type and B Type: Sinking, AP Type and P Type: Sourcing
9. To ensure the emission rating, a ferrite ring core should be used in all cabling (TDK HF60T, HF70RH or equivalent model).
10. The typical values indicate the values for an input condition of 230 VAC. All items are measured at a frequency of 50 Hz.
Output indicator
EMI
B-8
No
No
Yes for up to 2 Power Supplies (with external diode)
Refer to the derating curve in Engineering Data. (with no icing or condensation)
−25 to 65°C
25% to 85% (Storage humidity: 25% to 90%)
3.0 kVAC for 1 min. (between all inputs and outputs/ alarm outputs; detection current: 20 mA)
2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA)
1.0 kVAC for 1 min. (between all outputs/ alarm outputs and PE terminals; detection current: 20 mA)
500 VAC for 1 min. (between all outputs and alarm outputs; detection current: 20 mA)
100 MΩ min. (between all outputs/ alarm outputs and all inputs/ PE terminals) at 500 VDC
10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions
10 to 150Hz, 0.35-mm single amplitude (5 G max.) for 80 min each in-X, Y, and Z directions
Shock resistance
Note:
Yes (selectable)
Switch Mode Power Supply S8VS
120 W
180 W
240 W
Maintenanc
Total run
Standard
Maintenanc
Total run
Standard
Maintenanc
Total run
e forecast
time
e forecast
time
e forecast
time
Item
monitor
monitor
monitor
monitor
monitor
monitor
Efficiency (typical)
80% min. (87% typ.)
80% min. (88% typ.)
80% min. (86% typ.)
Input
Voltage
100 to 240 VAC (85 to 264 VAC)
Frequency
50/60 Hz (47 to 63 Hz)
Current
100 V input
1.9 A max.
2.9 A max.
3.8 A max.
200 V input
1.1 A max.
1.6 A max.
2.0 A max.
230 V input
(0.6 A typ.)
(0.9 A typ.)
(1.2 A typ.)
Power factor
0.95 min.
Harmonic current emissions
Conforms to EN61000-3-2
Leakage current
100 V input
0.5 mA max.
200 V input
1.0 mA max.
230 V input
(0.43 mA typ.)
(0.45 mA typ.)
(0.45 mA typ.)
Inrush current
100 V input
25 A max. (for a cold start at 25°C)
(See note 1.)
200 V input
50 A max. (for a cold start at 25°C)
230 V input
(41 mA typ.)
(34 mA typ.)
(39 mA typ.)
Output
Voltage adjustment range (See note 2.)
−10% to 15% (with V.ADJ) (guaranteed)
±10% (with V.ADJ) (guaranteed)
Ripple
2.0% (p-p) max. (at rated input/output voltage)
f=20MHz measuring (0.66%(p-p) typ.)
(0.45%(p-p) typ.)
(0.13%(p-p) typ.)
f=100MHz measuring (0.67%(p-p) typ.)
(0.52%(p-p) typ.)
(0.21%(p-p) typ.)
Input variation influence
0.5% max. (at 85 to 264 VAC input, 100% load)
Load variation influence (rated input voltage)
1.5% max. (with rated input, 0 to 100% load)
Temperature variation influence
0.05%/°C max.
Start up time (See note 1.)
1,000 ms max. (at rated input/output voltage)
(380 ms typ.)
(530 ms typ.)
(780 ms typ.)
Hold time (See note 1.)
20 ms min. (at rated input/output voltage)
at 100% load
(60 ms typ.)
(60 ms typ.)
(30 ms typ.)
Addition- Overload protection (See note 1.)
105% to 160% of rated load current, voltage drop, intermittent, automatic reset
105% to 160% of rated load
al funccurrent, voltage drop, autotions
matic reset
Overvoltage protection (See notes 1 and 3.) Yes
Output voltage indication (See note 4.)
No
Yes (selectable)
No
Yes (selectable)
No
Yes (selectable)
(See note 5.)
(See note 5.)
(See note 5.)
Output current indication (See note 4.)
No
Yes (selectable)
No
Yes (selectable)
No
Yes (selectable)
(See note 6.)
(See note 6.)
(See note 6.)
Peak-hold current indication (See note 4.)
No
Yes (selectable)
No
Yes (selectable) (See note No
Yes (selectable)
(See note 7.)
7.)
(See note 7.)
Maintenance forecast monitor indication
No
Yes
No
No
Yes
No
No
Yes
No
(See note 4.)
(selectable)
(selectable)
(selectable)
Maintenance forecast monitor output
No
Yes
No
No
Yes
No
No
Yes
No
(open collec(open collec(open collector
output),
tor
output),
tor output),
30 VDC
30 VDC
30 VDC
max., 50 mA
max., 50 mA
max., 50 mA
max.
max.
max.
(See
note
8.)
(See note 8.)
(See note 8.)
Total run time monitor indication
No
Yes
No
Yes
No
Yes
(See note 4.)
(selectable)
(selectable)
(selectable)
Total run time monitor output
No
Yes (open
No
Yes (open
No
Yes (open
collector outcollector outcollector output), 30 VDC
put), 30 VDC
put), 30 VDC
max., 50 mA
max., 50 mA
max., 50 mA
max.
max.
max.
(See note 8.)
(See note 8.)
(See note 8.)
Undervoltage alarm indication (See note 4.) No
Yes (selectable)
No
Yes (selectable)
No
Yes (selectable)
Undervoltage alarm output terminals
No
Yes (open collector output), No
Yes (open collector output), No
Yes (open collector output),
30 VDC max., 50 mA max.
30 VDC max., 50 mA max.
30 VDC max., 50 mA max.
(See note 8.)
(See note 8.)
(See note 8.)
Parallel operation
No
Series operation
Yes for up to 2 Power Supplies (with external diode)
Other
Operating ambient temperature
Refer to the derating curve in Engineering Data. (with no icing or condensation)
Storage temperature
−25 to 65°C
Operating ambient humidity
25% to 85% (Storage humidity: 25% to 90%)
Dielectric strength
3.0 kVAC for 1 min. (between all inputs and outputs/ alarm outputs; detection current: 20 mA)
2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA)
1.0 kVAC for 1 min. (between all outputs/ alarm outputs and PE terminals; detection current: 20 mA)
500 VAC for 1 min. (between all outputs and alarm outputs; detection current: 20 mA)
Insulation resistance
100 MΩ min. (between all outputs/ alarm outputs and all inputs/ PE terminals) at 500 VDC
Vibration resistance
10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions
10 to 150Hz, 0.35-mm single amplitude (5 G max.) for 80 min each in-X, Y, and Z directions
Shock resistance
150 m/s2, 3 times each in ±X, ±Y, and ±Z directions
Output indicator
EMI
EMS
Approved standards
Weight
Conducted
Emissions
Radiated
Emissions
Standard
Yes (color: green)
Conforms to EN61204-3 EN55011 Class A and based on FCC Class A
Conforms to EN61204-3 EN55011 Class B (See note 9.)
Conforms to EN61204-3 EN55011 Class A
Conforms to EN61204-3 EN55011 Class B (See note 9.)
Conforms to EN61204-3 high severity levels
UL: UL508 (Listing), UL60950
cUL: CSA C22.2 No.14, No.60950
EN/VDE: EN50178 (=VDE0160), EN60950 (=VDE0805)
SELV (EN60950/UL50178/UL60950-1)
According to VDE0106/P100, IP20
550 g max.
850 g max.
1,150 g max.
Switch Mode Power Supply
S8VS
B-9
Power
supplies
Power ratings
Type
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Omron:
S8VS-24024A S8VS-18024A S8VS-01505 S8VS-03005 S8VS-03012 S8VS-01524 S8VS-09024AP S8VS12024A S8VS-18024AP S8VS-48024B-F S8VS-18024BP S8VS-48024 S8VS-48024A S8VS-06024-F S8VS-09024
S8VS-12024B S8VS-09024B S8VS-06024A S8VS-09024A S8VS-18024 S8VS-03024 S8VS-06024 S8VS-01512
S8VS-18024B S8VS-48024B