FA Wireless SS Terminals
WT30
Construct a Wireless System for ON/OFF
Data Collection That Is Ideal for Monitoring
Production Site Equipment
• Wireless Slave Station equipped with I/O.
• Height of 90 mm and DIN Rail mounting enables installation in
control panels.
• Easily check wireless communications status from indicator
display.
• I/O Slave Stations can also be used as Slave Stations in WD30
systems.
• Conforms to radio wave standards for Japan, China (pending),
USA, and Europe.
Ordering Information
■ List of Models
Wireless Unit model
Type
Specifications/No. of I/O points
WT30-M01-FLK
Serial master
RS-232C
WT30-SID16
I/O slaves
16 DC inputs (NPN/PNP)
WT30-SMD16
8 DC inputs (NPN/PNP) + 8 transistor outputs (NPN)
WT30-SMD16-1
8 DC inputs (NPN/PNP) + 8 transistor outputs (PNP)
Note: An Antenna and Mounting Brackets are not included with the Wireless SS Terminal.
■ Accessories
Antennas
Applicable Standards
Model
Type
WT30-AT001
Magnet-base Antenna (2 antennas per set)
WT30-AT002
Flat Diversity Antenna (1 antenna)
WT30-AT003
Pencil Antenna (2 antennas per set)
Communications Cables
Model
Length
XW2Z-0100U-3
1m
XW2Z-0200U-3
2m
XW2Z-0500U-3
5m
XW2Z-0200U-5
2m
XW2Z-0500U-5
5m
Conformity to Safety Standards
Application
For personal computer
Always use a Class 2 power supply to conform to UL standards.
Main Class 2 Power Supplies
OMRON Switching Power Supplies
Cross cable for PLC
• S8VS (15 W, 30 W, 60 W type)
• S82K (15 W, 30 W, 50 W, 90 W type)
Conformity to EN Standards
Other
Model
• FCC part 15.247 (USA)
• EN 300 440-2 (Europe)
• ARIB STD-T66 (Japan)
•
(China) (approval pending)
Type
WT30-FT001
DIN Rail Mounting Bracket (for TH35-7.5)
WT30-FT002
DIN Rail Mounting Bracket (for TH35-15)
WT30-FT003
Surface Mounting Bracket (screw-mounting)
(2 brackets per set)
WT30-FT011
Flat Diversity Antenna Mounting Brackets
(with magnets)
WT30-CA2M
Antenna Extension Cable (1 cable, 2 m)
Use a DC power line less than 3 m to conform to EN standards. If a
power line of 3 m or longer is required, extend the length at the
Switching Power Supply’s primary side (i.e., the AC power line).
Applicable Countries
Wireless standards have been met for the following countries. The
product cannot be used in any other countries.
Austria, Belgium, Cyprus, Czech Republic, Denmark, Estonia,
Finland, France, Germany, Greece, Hungry, Iceland, Ireland, Italy,
Japan, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway,
Poland, Portugal, Slovakia, Slovenia, Spain, Sweden, Switzerland,
UK, USA
FA Wireless SS Terminals
WT30
1
Specifications
■ Ratings
Item
WT30-M01-FLK Serial Master
WT30-SID16/SMD16/SMD16-1 I/O Slaves
Power supply
(wireless
communications
power supply)
Rated voltage
24 V DC
Allowable voltage
range
20.4 to 26.4 V DC
Power consumption
3 W max. (See note 1.)
Error output/output
power supply
(for output circuits)
Rated voltage
---
24 V DC
Allowable voltage
range
---
20.4 to 26.4 V DC
Insulation resistance
20 MΩ min. (at 100 V DC) between the power 20 MΩ min. (at 100 V DC) between the power
supply and chassis
supply and all I/O and I/O power supply and
between the power supply and chassis
Dielectric strength
1,500 V AC for 1 min between power supply
and chassis
Noise immunity
IEC61000-4-4. 1 kV (power supply line)
Vibration resistance (See note 2.)
JIS C0040
Frequency: 10 to 55 Hz; Amplitude of 0.35 mm or acceleration of 50 m/s2, whichever is smaller
(DIN Rail mounting: single amplitude of 0.1 mm or acceleration of 15 m/s2)
10 sweeps of 8 min each (i.e., 80 min in total) in X, Y, Z directions
Shock resistance
Conforms to JIS C0041: 300 m/s2 3 times each in X, Y, and Z directions
Ambient operating temperature
−10 to 55°C (with no condensation or icing)
Number of simultaneously ON I/O points
(with the Terminal mounted with the dust-proof 10 max.: −10 to 55°C (with no condensation or
label facing up)
icing)
16 max.: −10 to 50°C (with no condensation or
icing)
(with the Terminal mounted with the dust-proof
label facing up)
Ambient operating humidity
25% to 85% (with no condensation or icing)
Ambient environment
No corrosive gases
Storage temperature
−25 to 65°C (with no condensation or icing)
Protective structure
1,500 V AC for 1 min between the power supply
and all I/O and I/O power supply and between
the power supply and chassis
IP20
Terminal construction
Power supply and I/O Screwless terminal block (Phoenix Contact FFKDS/V1-5.08 or equivalent)
--D-sub, 9-pin (female) Inch screws (OMRON
XM2F-0910-132 or equivalent), Master station
only
Serial
Safety standards
UL: UL508 (Listing)
Weight
330 g max.
Note: 1. Provide a power supply of at least 15 W, considering the inrush current generated at startup.
2. Use the WT30-FT003 Surface Mounting Bracket when installing the WT30 in environments subject to vibration.
■ Wireless Interface Specifications
Item
Specifications
Wave type
Spread Spectrum (direct sequence; DS-SS)
Communication method
Simplex
Frequency band
2,401 to 2,480.2 MHz
Number of channels
67 channels (based on switching)
Transmitter output power
10 mW/MHz
Baud rate between wireless stations
100 kbps
Communications distance (See note.)
Indoors: 60 m min. (approx. 50 m min. with Magnet-base Antennas and Flat Diversity Antennas)
Outdoors: Approx. 300 m min. (anticipated distances)
(without using relay stations)
Error detection method
CRC-CCITT (16 bits)
Relay functions
One stage using I/O slave for the serial master configuration.
Number of stations per area (See note.)
10 sets max. (recommended)
Number of I/O Slaves connected
64 max.
Note: Varies according to the installation environment.
■ Package Contents
• WT30 FA Wireless SS Terminal
• Terminal labels (I/O Slaves only)
• Instruction Sheet
• Adhesive non-slip feet (Serial Master only)
2
FA Wireless SS Terminals WT30
Nomenclature
■ Serial Master Station
■ Unit No. Switch
Set the unit number of the Serial Master Station
Unit No. switch
Set the unit number of the Serial Master Station.
Node setting switch (WNODE)
Set the number of connected I/O Slave Stations.
Channel setting switch (WCH)
Set the communications frequency
channel.
Antenna terminal (ANT1)
Antenna terminal (ANT2)
Default: 00
■ Node Setting Switch (WNODE)
Set the number of connected I/O Slave Stations.
Set the node number of the Slave Stations being used as I/O Slave
Stations. The Slave Station functions as a relay station when the
node number is set to 99.
Default: 01
Status
indicators
Received
signal
strength
indicator
Special
function
switch
■ Channel Setting Switch (WCH)
Set the communications frequency.
Default: 02
■ Function Setting Switch
Serial Master Station
No.
Mode selection switch
Switch between RUN,
TEST, and SET mode.
Function setting switch
Make the detailed settings
for RUN/TEST/SET mode.
Power supply terminal
Supply power to the WT30.
1
RS-232C Terminal
Connect the PLC, personal computer, etc.
Serial communications
setting switch
Set the baud rate.
I/O terminal status indicators (0 to 7 or 8 to 15)
The contact status is displayed.
Channel setting switch (WCH)
Set the communications frequency.
Antenna terminal (ANT1)
Antenna terminal (ANT2)
OFF functions
Clears I/O status data
when a
communications error
occurs.
Enable scan list
Disable scan list
3
Relays used
Relays not used
TEST mode Signal strength monitor Signal strength monitor
disabled
enabled
All channels
Specified channels
automatically switched
6
7
SET mode
---
---
Scan list recognition
Nothing done
8
Registers specified I/O Registers all I/O slaves
slave
automatically
9
Recognizes serial
numbers
Ignores serial numbers
---
---
10
Not used
I/O Slave Station
Status
indicators
Received
signal
strength
indicator
No.
1
I/O terminals
Connect the contact
signals.
Power supply terminal
Supply power to the WT30
and output circuits.
Applicable
mode
RUN mode Holds I/O status data
when a
communications error
occurs.
OFF functions
Clears I/O status data
when a
communications error
occurs.
Input hold
Normal mode
3
Input filter: 100 ms
Input filter: 10 ms
TEST mode Signal strength monitor Signal strength monitor
disabled
enabled
5
All channels
Specified channels
automatically switched
6
Installation test
function
Nothing done
---
---
Special function switch
Function setting switch
Make the detailed settings
for RUN/TEST mode.
ON functions
2
4
Mode selection switch
Switch between RUN,
TEST, and SET mode.
RUN mode Holds I/O status data
when a
communications error
occurs.
5
Node setting switch (WNODE)
Set the unit number of the I/O Slave Station.
ON functions
2
4
■ I/O Slave Station
Applicable
mode
7 to
10
Not used
FA Wireless SS Terminals
WT30
3
■ Serial Communications Setting
Switch
No.
1
2
3
4
Function
ON
Communications setting Detailed
selection
settings
(settings for
No. 2 to 8
used)
1
Baud rate (bps)
(See note.)
2
Total value = 0: 1,200
4
= 1: 2,400
= 2: 4,800
= 3: 9,600
= 4: 19,200
= 5: 38,400
= 6: 57,600
= 7: 115,200
OFF
Default settings
(baud rate: 9,600 bps;
data length: 7 bits;
parity: even; stop bits:
2)
Settings for No. 2 to 8
are ignored.
0
Data length
8 bits
7 bits
6
Parity
None
Yes
Odd
Even
1 bit
2 bits
8
Stop bits
Indicator
Color
Status
PWR
Green Lit
ERR
(Slave Station)
Red
Meaning (primary error)
Power is being supplied.
Not lit
Power is not being supplied.
Lit
Error output is ON:
Wireless device error or
wireless communications
error. (See note)
Not lit
No wireless device error or
wireless communications
error.
0
0
5
7
■ Display
COMM
Yellow Lit
(Master Station)
Not lit
Serial communications in
progress.
No serial communications.
0 to 15
(Slave Station)
Yellow Lit/Not lit ON/OFF status for input or
output signals
RSSI
Lit/
Receiving Signal Strength
Red/
Yellow/ All not lit Indicator monitor: Number of
indicators lit (receiving signal
Green
strength 1 to 9)
Receiving signal strength less
than 0 to 1.
MS
Green Lit
Communications are normal.
(Module Status)
Flashing TEST mode or SET mode has
been activated.
Red
Lit
Note: For example, if pins number 2, 3, and 4 are all ON, the total is
7, which corresponds to a baud rate of 115,200 bps.
A fatal error has occurred that
cannot be recovered from.
Replace the Unit
Flashing A non-fatal error has occurred
that can be recovered from by
resetting the system.
--WS
(Wireless
Status)
Not lit
Green Lit
Power is not being supplied or
the system is resetting.
The station has joined the
wireless network.
Flashing Permission to join wireless
network received from Serial
Master Station (Slave Station)
Red
Lit
A fatal error has occurred that
cannot be recovered from.
Flashing Error from which recovery is
possible
---
Not lit
Wireless communications are
not in progress.
Note: When using the WD30 as the Serial Master Station, the ERR
indicator will light if normal I/O communications are not
possible due to an error in the host network.
4
FA Wireless SS Terminals WT30
Wiring
■ Serial Master Station (WT30-M01-FLK)
D-sub, 9-pin, Female End at WT30
RS-232C Connector
54321
Power supply terminal
Supply power to the Unit
WT30
9876
Pin No.
Signal
I/O direction
1
---
---
2
RD
Output
3
SD
Input
4
---
---
5
SG
---
6
---
---
7
---
---
8
---
---
9
---
---
I/O Characteristics
■ I/O Slave Station
WT30-SID16
Error output
(PNP)
Inputs
IN
V
G
24 V DC 0 V
0
8
Power supply
1
9
2
10
3
11
COM
COM
4
12
IN
Inputs
5
13
6
14
7
15
COM ERRP
COM ERRN
Error output
(NPN)
Inputs
WT30-SMD16
WT30-SMD-16-1
Error output/output
power supply
Inputs
Error output
(PNP)
Inputs
IN
V
G
24 V DC 0 V
0
0
Power supply
1
1
2
2
Outputs
3
3
COM
4
COM 4
OUT
5
5
6
6
Outputs
Input Characteristics
Inputs
7
7
COM ERRP
Output/Error Output
Characteristics
Error output
power supply
Item
Specifications
Input voltage
24 V DC
Allowable
voltage range
20.4 to 26.4 V DC
Input
impedance
4.7 kΩ (typical)
Input current
5 mA (typical)
ON voltage/
17.4 V DC, 3.0 mA min.
current
characteristics
OFF voltage/
5.0 V DC, 1.0 mA max.
current
characteristics
Input filter
10 ms/100 ms (Selected using switch.)
Input voltage
24 V DC
Allowable
voltage
20.4 to 26.4 V DC
Max.
switching
current
100 mA max. per output (at 20.4 to 26.4 V DC)
Simultaneous usage of error output NPN/PNP
is not possible.
Leakage
current
0.1 mA max.
Residual
voltage
1.0 V max.
Fuse
One for every two outputs except for error
output circuits, which have one for every NPN/
PNP output. (No fuses can be replaced by the
user.)
COM ERRN
Error output
(NPN)
FA Wireless SS Terminals
WT30
5
Input Circuit Diagram
Output Circuit Diagram (NPN)
V
OUT 0
Secondary internal circuit
Secondary internal circuit
IN 0
IN 1
IN 2
OUT 1
Fuse
OUT 2
Fuse
IN 15
OUT 7
COM (IN)
Fuse
Error Output Circuit Diagram
Output Circuit Diagram (PNP)
Fuse
Fuse
V
OUT 0
Secondary internal circuit
Secondary internal circuit
V
Fuse
G
ERRP
ERRN
OUT 1
Fuse
OUT 2
OUT 3
G
OUT 7
G
Dimensions
Note: All units are in millimeters unless otherwise indicated.
Serial Master Station
I/O Slave Station
WT30-M01-FLK
WT30-SID16
WT30-SMD16
WT30-SMD16-1
13.3
105
105
13.3
120
ia.
(15)
ur,
5d
Fo
90
60 40
(15)
Surface mounting bracket
WT30-FT003
6
FA Wireless SS Terminals WT30
DIN rail mounting bracket
WT30-FT001 or WT30-FT002
7.3
With Magnet-base
Antenna
With Flat Diversity
Antenna
WT30-AT001
WT30-AT002
With Pencil Antenna
WT30-AT003
40
150
(46)
(23)
(34)
(46)
R50
R38
20
R40
(32)
4.6
(38)
Serial Master Station
Surface Mounting Bracket
WT30-FT003
I/O Slave Station
I/O Slave Station
DIN Rail mounting bracket
WT30-FT001 or
WT30-FT002
DIN Rail mounting bracket
WT30-FT001 or
WT30-FT002
Magnet-base Antenna
Flat Diversity Antenna
Pencil Antenna
WT30-AT001
WT30-AT002
WT30-AT003
57.5
26
Three, 3 dia.
57.5 52
75
115
10.5 dia.
10.5 dia.
2010
2010
35.8 dia.
39
DIN Rail Mounting
Bracket
Surface Mounting
Bracket
Flat Diversity Antenna Mounting
Brackets (with magnets)
WT30-FT001
WT30-FT002
WT30-FT003
WT30-FT011
FA Wireless SS Terminals
WT30
7
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Cat. No. N139-E1-01
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company
Industrial Devices and Components Division H.Q.
Wireless Components Department
Shiokoji Horikawa, Shimogyo-ku,
Kyoto, 600-8530 Japan
Tel: (81)75-344-7116/Fax: (81)75-344-7189
Printed in Japan
0105