https://www.phoenixcontact.com/us/products/0900139
Electronic device circuit breaker - ECP-E2-1A - 0900139
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Electronic device circuit breaker, Number of positions: 1, Connection method: Screw connection, Width: 12.5 mm,
Fuse type: Electronic, Fuse type: Automatic device, Mounting type: On base element, Color: black
Why buy this product
■
■
■
■
■
■
Includes the advantages of current limitation
Sufficient supply of all error-free load circuits
Output voltage of switched-mode power supply unit remains stable
Responds faster than switched-mode power supply unit to overload and short circuit
In addition, the ECP-E2 can be controlled remotely by the control input (12), e.g., by means of a PLC
Application - all aspects of the switched-mode power supply unit
Key Commercial Data
Packing unit
1 STK
Weight per Piece (excluding packing)
44.0 g
Custom tariff number
85363030
Country of origin
Germany
Technical data
General
Installation instructions
When mounted in rows without convection cooling, the nominal device
current should only be led to a maximum of 80% due to the thermal effect
during continuous operation (100% operating factor).
Special precautionary measures must be taken in systems or machines, to
prevent components from restarting (e.g., use of a safety PLC).
Parallel connection of multiple circuit breakers is not permitted.
Mounting type
On base element
Color
black
08/01/2016 Page 1 / 5
https://www.phoenixcontact.com/us/products/0900139
Electronic device circuit breaker - ECP-E2-1A - 0900139
Technical data
General
Number of positions
1
Overvoltage category
II
Insulating material
PA66/6
Flammability rating according to UL 94
V0
Electrical data
Fuse
Electronic
Fuse type
Automatic device
Rated surge voltage
0.5 kV
Operating voltage
24 V DC
24 V DC ()
18 V DC ... 32 V DC
Nominal current IN
1A
Required backup fuse
not required, integrated failsafe element
Dielectric strength
max. 32 V DC (Load circuit)
Degree of pollution
2
Overvoltage category
II
Insulating material group
I
Switching capacity ICN
Active current limitation
Closed-circuit current range I0
typ. 25 mA ±5 mA (When switched on)
Dimensions
Height
60 mm
Width
12.5 mm
Depth
70 mm
Height NS 35/7,5
144 mm
Height NS 35/15
151.5 mm
Complete module height
115 mm
Complete module width
38 mm
Complete module depth
112.5 mm
Ambient conditions
Degree of protection
IP30 (Actuation area)
Ambient temperature (operation)
0 °C ... 50 °C (non-condensing)
Connection data
Connection method
Screw connection
Standards and Regulations
Standards/specifications
UL 2367
08/01/2016 Page 2 / 5
https://www.phoenixcontact.com/us/products/0900139
Electronic device circuit breaker - ECP-E2-1A - 0900139
Technical data
Standards and Regulations
UL 508
CSA 22.2 No. 14
Drawings
Block diagram
Diagram
Stop point
typ. 1,1 x l N
On/Off
14 12 2
Switching time [s]
GND (-)
SC
SO
很抱歉,暂时无法提供与“0900139”相匹配的价格&库存,您可以联系我们找货