EC-E...
Electronic miniature circuit-breaker
CLIPLINE
Data sheet
103906_en_01
1
© PHOENIX CONTACT - 09/2009
Description
The EC-E... electronic miniature circuit-breaker selectively
protects all 24 V DC load circuits on power supply units. A
combination of active electronic current limitation for short
circuits and an overload shutdown function from 1.1 x IN
upwards ensures that the miniature circuit-breaker can
react to overloads faster than the power supply unit. In this
case, the residual current is constantly restricted to 1.3 1.8 times the nominal current.
This enables capacitive loads of up to 20, 000 µF to be
switched on; loads are shut down only in the event of an
overload or short circuit.
Once an overload or short circuit has been detected in the
load circuit, the load output of the EC-E... is blocked. The
current flow in the faulty circuit is interrupted. The EC-E...
and, therefore, the current circuit can be activated again
using the electronic reset input or manually on the device
using the slide switch.
Wiring and signaling tasks can be implemented easily using
power rails and plug-in bridges.
A multi-color LED and the integrated status output display
the operating and fault state.
The miniature circuit-breaker has a design width of 12.5 mm
and can be snapped onto NS 35 DIN rails using a modular
approach. It is equipped with screw connections.
1.1
–
–
–
–
–
–
–
–
–
Properties
Selective load protection, electronic shutdown
characteristic curve
Active current limitation when switching on capacitive
loads of up to 20, 000 µF and in the event of an
overload/short circuit
Nominal current can be selected in fixed current
strengths from 0.5 A ... 12 A
Safe overload shutdown from 1.1 x IN upwards, even
with long load lines or small cable cross-sections
Manual on/off switch (S1)
Clear signaling by means of LED, SF status output, or F
alarm output (signal contact), (can be combined)
RE electronic reset input (option)
Integrated fail-safe element, adapted to nominal current
Straightforward wiring using LINE+ power rail and 0 V,
as well as signal rails and signal bridges
NOTE: Make sure that you adapt the cable cross-section of the relevant load circuit to the nominal current of the
EC-E... being used.
Take special precautions in the system or machine to eliminate the possibility of system parts restarting (in
accordance with the Machinery Directive 2006/42/EC and EN 60204-1). In the event of a fault (short circuit/
overload), the EC-E... shuts down the load circuit electronically.
Make sure you always use the latest documentation.
It can be downloaded at www.phoenixcontact.net/download.
This data sheet is valid for all products listed on the following page:
EC-E...
2
Ordering data
Electronic miniature circuit-breakers
Description
Type
Order No.
Pcs./Pkt.
Electronic miniature circuit-breaker with signal contact: 1 N/O contact 0.5 A
EC-E1 0.5 A
0903022
6
Electronic miniature circuit-breaker with signal contact: 1 N/O contact 1 A
EC-E1 1.0 A
0903023
6
Electronic miniature circuit-breaker with signal contact: 1 N/O contact 2 A
EC-E1 2.0 A
0903024
6
Electronic miniature circuit-breaker with signal contact: 1 N/O contact 3 A
EC-E1 3.0 A
0903025
6
Electronic miniature circuit-breaker with signal contact: 1 N/O contact 4 A
EC-E1 4.0 A
0903026
6
Electronic miniature circuit-breaker with signal contact: 1 N/O contact 6 A
EC-E1 6.0 A
0903028
6
Electronic miniature circuit-breaker with signal contact: 1 N/O contact 8 A
EC-E1 8.0 A
0903029
6
Electronic miniature circuit-breaker with signal contact: 1 N/O contact 10 A
EC-E1 10 A
0903030
6
Electronic miniature circuit-breaker with signal contact: 1 N/O contact 12 A
EC-E1 12 A
0903031
6
Electronic miniature circuit-breaker with signal contact: 1 N/C contact 0.5 A
EC-E4 0.5 A
0903040
6
Electronic miniature circuit-breaker with signal contact: 1 N/C contact 1 A
EC-E4 1.0 A
0903032
6
Electronic miniature circuit-breaker with signal contact: 1 N/C contact 2 A
EC-E4 2.0 A
0903033
6
Electronic miniature circuit-breaker with signal contact: 1 N/C contact 3 A
EC-E4 3.0 A
0903034
6
Electronic miniature circuit-breaker with signal contact: 1 N/C contact 4 A
EC-E4 4.0 A
0903035
6
Electronic miniature circuit-breaker with signal contact: 1 N/C contact 6 A
EC-E4 6.0 A
0903036
6
Electronic miniature circuit-breaker with signal contact: 1 N/C contact 8 A
EC-E4 8.0 A
0903037
6
Electronic miniature circuit-breaker with signal contact: 1 N/C contact 10 A
EC-E4 10 A
0903038
6
Electronic miniature circuit-breaker with signal contact: 1 N/C contact 12 A
EC-E4 12 A
0903039
6
Electronic miniature circuit-breaker with reset input and status output 0.5 A
EC-E 0.5 A 24 V DC
0903041
6
Electronic miniature circuit-breaker with reset input and status output 1 A
EC-E 1.0 A 24 V DC
0903042
6
Electronic miniature circuit-breaker with reset input and status output 2 A
EC-E 2.0 A 24 V DC
0903043
6
Electronic miniature circuit-breaker with reset input and status output 3 A
EC-E 3.0 A 24 V DC
0903044
6
Electronic miniature circuit-breaker with reset input and status output 4 A
EC-E 4.0 A 24 V DC
0903045
6
Electronic miniature circuit-breaker with reset input and status output 6 A
EC-E 6.0 A 24 V DC
0903046
6
Electronic miniature circuit-breaker with reset input and status output 8 A
EC-E 8.0 A 24 V DC
0903047
6
Electronic miniature circuit-breaker with reset input and status output 10 A
EC-E 10 A 24 V DC
0903048
6
Electronic miniature circuit-breaker with reset input and status output 12 A
EC-E 12 A 24 V DC
0903049
6
Nominal
current
Version
Signal input
Signal output
F alarm output (signal contact)
RE +24 V reset input
SF status output
Individual-signal N/O contact
(normally open)
Individual-signal N/C contact
(normally closed)
SF +24 V status output = OK
–
EC-E1
–
x
–
EC-E4
–
–
x
–
EC-E
x
–
–
x
Accessories
Description
Continuous plug-in bridge for LINE+ and 0 V, insulated with gray
material, 500 mm long, can be cut to length
Order No.
Pcs./Pkt.
Gray FBST 500 TMC-NGY
Type
0901028
10
Blue
FBST 500-PLC-BU
2966692
20
Red
FBST 500-PLC-RD
2966789
20
Current carrying capacity with one supply: Imax = 50 A,
(recommendation: central input)
Current carrying capacity with two supplies: Imax = 63 A
Continuous plug-in bridge for signal contacts and reset inputs,
insulated with gray material, 500 mm long, can be cut to length
Current carrying capacity with one supply: max = 1 A
With signal contacts connected in series: Imax = 0.5 A
Zack marker strip, flat, 10-section
UC-TMF12
0819233
10
Screwdriver
SZS 0.6X3.5
1205053
10
103906_en_01
PHOENIX CONTACT
2
EC-E...
3
Technical data
NOTE: Data apply where TA = 25°C and UB = 24 V DC.
Operating data
Nominal voltage UB
24 V DC (18 V DC ... 32 V DC)
Nominal current IN
Depending on product version selected:
Fixed current strengths: 0.5 A, 1 A, 2 A, 3 A, 4 A, 6 A, 8 A, 10 A, 12 A
Closed-circuit current I0
When ON: Typically 20 mA ... 30 mA, depending on signal output
Shutdown
Shutdown times
Refer to the time/current characteristic curve (see page 8)
Typical behavior
3 s where Iload > 1.1 x IN
100 ms ... 3 s where Iload > 1.8 x IN (or 1.5 x IN/1.3 x IN)
EC-E4: Pin 11/12
Individual signaling (N/C contact)
EC-E1: Pin 13/14
Individual signaling (N/O contact)
EC-E: SF 23, RE 22
RE reset input, SF status output
Status indicators
Operating state signaling
–
–
–
–
Multi-color LED
SF status output (option)
Floating signal contact (F alarm output) (option)
On/off setting for switch S1
Multi-color LED
Green = Device switched on (S1 = ON) or load circuit/Power MOSFET forced
to trip
Orange = Overload or short circuit leading to electronic shutdown
Red = Device shut down electronically, load circuit/Power MOSFET switched
off, undervoltage (UB < 8 V) or after switch-on up to end of switch-on delay
time
OFF: Manually switched off (S1 = OFF) or device voltage is disconnected
Load circuit
Load output
Power MOSFET switching output (positive switching)
Overload shutdown (OL)
Typically 1.1 x IN (1.05 ... 1.35 x IN)
Short-circuit current IK
Active current limitation (see page 5)
Temperature shutdown
Internal temperature monitoring with electronic shutdown
Undervoltage monitoring for load output after each switch-on procedure
With hysteresis, no reset required: Load "OFF" at UB < 8 V
Switch-on delay tStart
Typically 0.5 s after reset and after UB applied
Load circuit shutdown
Electronic shutdown after overload/short circuit
Free running circuit
External free-wheeling diode recommended for inductive load
Parallel connection of multiple load outputs
Not permitted
F alarm output, signal contact (for EC-E1 and EC-E4 only)
Electrical data
Floating signal contact
30 V DC/0.5 A maximum, 10 V/10 mA minimum
Normal state, LED lights up green
UB is present, switch S1 is set to ON, and no overloads or short circuits occur
OFF state, LED off
–
–
103906_en_01
Device switched off (switch S1 set to OFF)
Operating voltage UB is not present
PHOENIX CONTACT
3
EC-E...
F alarm output, signal contact (for EC-E1 and EC-E4 only) (continued)
Fault state, LED lights up orange
Overload condition > 1.1 x IN leading to electronic shutdown
Fault state, LED lights up red
–
–
–
–
Fault description
F alarm output (signal contact) is in a fault state if
–
Operating voltage UB is not present
–
ON/OFF switch S1 is set to OFF
–
The LED lights up red (electronic shutdown)
Electronic shutdown after overload or short circuit
Device switched off with control signal (switch S1 set to ON)
EC-E1: Individual signal, N/O contact open, pins 13 and 14
EC-E4: Individual signal, N/C contact closed, pins 11 and 12
Status output (for EC-E only)
Electrical data
Positive-switching signal output,
switches UB to pin 23,
nominal data: 24 V DC/0.2 A maximum (short-circuit-proof)
The status output is terminated internally to 0 V with a 10-kohm resistance.
OUT status
EC-E... (OUT signal status), where UB = +24 V
+24 V = S1 is ON, load output forced to trip
0 V = S1 is ON, load output blocked, and/or switch S1 is OFF.
LED lights up red
OFF state
0 V level at status output in all cases where:
–
Switch S1 is set to ON, but the device is still subject to a switch-on delay
–
Switch S1 is set to OFF or control signal OFF, device is switched off
–
Operating voltage UB is not present
Reset input (for EC-E only)
Electrical data
Maximum voltage: +32 V DC
High > 8 V DC ≤ 32 V DC
Low ≤ 3 V DC > 0 V DC
Current consumption: Typ. 2.6 mA (+24 V DC)
Minimum pulse duration: 10 ms
RE reset signal, pin 22
When the EC-E is electronically blocked, it can be switched on again remotely
on the falling edge of a +24 V DC pulse, using an external button. A common
reset signal can also be applied to several devices at the same time. Devices
that are switched on remain unaffected by this.
Connection terminal blocks
LINE+/LOAD+/0 V connection terminal blocks
Screw connections
M4
Connection capacity
Solid
Stranded
With ferrule
1 conductor
0.5 mm2 ... 10 mm2
0.5 mm2 ... 10 mm2
0.5 mm2 ... 10 mm2
2 conductors (two conductors with the same cross-section)
0.5 mm2 ... 4 mm2
0.5 mm2 ... 4 mm2
0.5 mm2 ... 2.5 mm2
0.5 mm2 ... 6 mm2
2 stranded conductors with a TWIN ferrule
Stripping length
10 mm
Torque (EN 60934)
1.5 Nm ... 1.8 Nm
Signal connections for connection terminal blocks
Screw connections
M3
Stranded connection capacity with ferrule
0.25 mm2 ... 2.5 mm2
Stripping length
8 mm
Torque (EN 60934)
0.5 Nm
103906_en_01
PHOENIX CONTACT
4
EC-E...
General data
Fail-safe element
No backup fuse required for EC-E... as a redundant fail-safe element is
integrated (fuse element)
Mounting the housing
DIN rail in acc. with EN 50022, NS 35 x 7.5
Ambient temperature (operation)
0°C ... +50°C (without condensation, see EN 60204-1)
Ambient temperature (storage)
-20°C ... +70°C
Humid heat
96 h, 95% relative humidity, 40°C
in acc. with IEC 60068-2-78, Test Cab. Climatic class 3K3 according to
EN 60721
Degree of protection (housing, terminals)
IP20, DIN 40050
Installation dimensions (W x H x D)
12.5 mm x 80 mm x 83 mm
Weight
Approx. 65 g
Tests/approvals
Conformance with EMC Directive 2004/108/EC
Noise emission: EN 61000-6-3
Insulation coordination (IEC 60934)
0.5 kV/pollution degree 2, increased insulation in actuation area
Noise immunity: EN 61000-6-2
Dielectric strength
32 V DC maximum (load circuit)
Insulation resistance ("off" state)
None, electronic shutdown only
Vibration resistance
3g, tested in acc. with IEC 60068-2-6, test Fc
Approvals
UL 2367, File E317172
Solid State Overcurrent Protectors
UL 1604, File E324415 (class I, division 2, groups A, B, C, D)
c
Voltage drop, current limitation, maximum load current
Nominal current IN
Typical voltage drop UON at
IN
Active current limitation
(typical)
Max. load current at 100% OT,
TA = 40°C
Max. load current at 100% OT,
TA = 50°C
0.5 A
70 mV
1.8 x IN
0.5 A
0.5 A
1A
80 mV
1.8 x IN
1A
1A
2A
130 mV
1.8 x IN
2A
2A
3A
80 mV
1.8 x IN
3A
3A
4A
100 mV
1.8 x IN
4A
4A
6A
130 mV
1.8 x IN
6A
5A
8A
120 mV
1.5 x IN
8A
7A
10 A
150 mV
1.5 x IN
10 A
9A
12 A
180 mV
1.3 x IN
12 A
10.8 A
In cases where a row-mounting configuration is being used without convection cooling, the effect of the heat during continuous operation
(100% OT) means that the nominal device current may only be run at a maximum of 80% of its strength.
103906_en_01
PHOENIX CONTACT
5
EC-E...
3.1
Connection diagrams
The signal contacts are shown in an off state or
fault state.
EC-E1
LINE+
EC-E4
1
LINE+
1
EC-E
LINE+
14
12
SF 23
13
11
RE 22
2
LOAD+
0V
2
LOAD+
0V
3
2
3
1
LOAD+
0V
3
Without signal input, with F alarm output
(individual signal, N/O contact)
Without signal input, with F alarm output
(individual signal, N/C contact)
With RE reset input (+24 V DC0), with SF status
output (+24 V = load output ON)
Normal state: 13 - 14 closed
Fault state: 13 - 14 open
Normal state: 11 - 12 open
Fault state: 11 - 12 closed
Normal state: SF +24 V = OK
Fault state: SF 0 V
Figure 1
3.2
Signal inputs/outputs
Block diagram (using example of EC-E)
LOAD (+)
load output
Figure 2
103906_en_01
S1
Control electronics
Rsense
Fail-safe
LINE (+)
24 V DC
on/off
Operating state,
green/orange/red
RE
Reset input
SF
Status output
0V
Block diagram (using example of EC-E)
PHOENIX CONTACT
6
EC-E...
3.3
Information on UL approval
3.4
Dimensions
a UL1604
12.5
83
File E324415
WARNING:
– Exposure to some chemicals may degrade the sealing
properties of materials used in the following device:
Relay
Sealant material:
– Generic name: Modified diglycidyl ether of
bisphenol A
– Supplier: Fine Polymers Corporation
– Type: Epi Fine 4616L-160PK
Casing material:
– Generic name: Liquid crystal polymer
– Supplier: Sumitomo Chemical
– Type: E4008, E4009, or E6008
RECOMMENDATION:
– Periodically inspect the device named above for any
degradation of properties and replace if degradation is
found
1
80
Operating Temperature Code T5
– This equipment is suitable for use in Class I, Division 2,
Groups A, B, C and D or non-hazardous locations only
2
80
Figure 4
1
2
Dimensions in mm
UC-TMF 12 marking label
Snap-on socket for DIN rail in acc. with EN 50022,
NS 35 x 7.5
3.5
Structure
WARNING – EXPLOSION HAZARD:
– Do not disconnect equipment unless power has been
removed or the area is known to be non-hazardous
– Substitution of any components may impair suitability
for Class I, Division 2
a UL2367
Non-hazardous use - UL File E317172
Class 2
Meets requirement for Class 2 current limitation
(EC-E...-0.5 A/1 A/2 A/3 A)
Figure 5
Figure 3
103906_en_01
UL approval package slip
1
2
3
4
Structure (using example of EC-E1)
Line+ power rail
0-V power rail
Signal rail or signal bridge
Shock protection slides (molded below the housing and
can be easily removed)
PHOENIX CONTACT
7
EC-E...
3.6
Time/current characteristic curve (TA = 25°C)
Stop point
typ. 1.1 x l N
1.8 x l N
10000
Switching time in seconds
1000
100
10
5
1
0.1
0.01
0
Figure 6
–
–
–
*
IK
1
2
3
min. 1.05 x l N max. 1.25 x lN
Multiples of the nominal current
Time/current characteristic curve
In the 1.1 ... 1.8 x IN* range, the shutdown time is
typically 3 s.
The electronic current limitation function is typically
used from 1.8 x IN* upwards.
This means that, typically, 1.8 times the nominal
current* is flowing in the case of all overload conditions
that lead to a shutdown (regardless of the power supply
and load circuit resistance). The shutdown time ranges
from 100 ms to 3 s depending on the multiple of the
nominal current, or in the event of a short circuit (IK).
Without the current limitation function used at, typically,
1.8 x IN*, a considerably higher overcurrent would flow
in the event of an overload or a short circuit.
Current limitation typically 1.8 x IN where IN =
0.5 A ... 6 A
Current limitation typically 1.5 x IN where IN = 8 A or 10 A
Current limitation typically 1.3 x IN where IN = 12 A
103906_en_01
PHOENIX CONTACT
8
EC-E...
3.7
Safe shutdown
Safe shutdown of the EC-E... with different supply line lengths and cable cross-sections
Specific electrical resistance for electrolytic copper: ρ0 = 0.0178 (Ω x mm²)/m
UB = 19.2 V DC (80% of 24 V DC)
The voltage drop on the EC-E... and the tolerance of the shutdown point
(typically 1.1 x IN = 1.05 ... 1.35 x IN) have already been taken into account.
EC-E... nominal current setting IN (in A) →
3A
6A
E.g., shutdown current Ishut = 1.25 A x IN (in A) → 3.75 A
7.5 A
→ EC-E... typically shuts down after 3 s
*
Rmax in ohms = (UB/Ishut) - 0.050 Ω → 5.07 Ω
2.51Ω
EC-E... trips safely from 0 Ω up to max. circuit resistance Rmax
Cable cross-section A in mm² → 0.14 mm² 0.25 mm² 0.34 mm² 0.5 mm² 0.75 mm² 1 mm²
1.5 mm²
Length L in meters
Total cable resistance in ohms = (R0 x 2 x L)/A
(= single length)
0
0
0
0
0
0
0
0
5 m 1.27 Ω
0.71 Ω
0.52 Ω
0.36 Ω
0.24 Ω
0.18 Ω
0.12 Ω
10 m 2.54 Ω
1.42 Ω
1.05 Ω
0.71 Ω
0.47 Ω
0.36 Ω
0.24 Ω
15 m 3.81 Ω
2.14 Ω
1.57 Ω
1.07 Ω
0.71 Ω
0.53 Ω
0.36 Ω
20 m 5.09 Ω
2.85 Ω
2.09 Ω
1.42 Ω
0.95 Ω
0.71 Ω
0.47 Ω
25 m 6.36 Ω
3.56 Ω
2.62 Ω
1.78 Ω
1.19 Ω
0.89 Ω
0.59 Ω
30 m 7.63 Ω
4.27 Ω
3.14 Ω
2.14 Ω
1.42 Ω
1.07 Ω
0.71 Ω
35 m 8.90 Ω
4.98 Ω
3.66 Ω
2.49 Ω
1.66 Ω
1.25 Ω
0.83 Ω
40 m 10.17 Ω
5.70 Ω
4.19 Ω
2.85 Ω
1.90 Ω
1.42 Ω
0.95 Ω
45 m 11.44 Ω
6.41 Ω
4.71 Ω
3.20Ω
2.14 Ω
1.60 Ω
1.07 Ω
50 m 12.71 Ω
7.12 Ω
5.24 Ω
3.56 Ω
2.37 Ω
1.78 Ω
1.19 Ω
75 m 19.07 Ω 10.68 Ω
7.85 Ω
5.34 Ω
3.56 Ω
2.67 Ω
1.78 Ω
100 m 25.34 Ω 14.24 Ω 10.47 Ω
7.12 Ω
4.75 Ω
3.56 Ω
2.37 Ω
125 m 31.79 Ω 17.80 Ω 13.09 Ω
8.90 Ω
5.93 Ω
4.45 Ω
2.97 Ω
150 m 38.14 Ω 21.36 Ω 15.71 Ω 10.68 Ω
7.12 Ω
5.34 Ω
3.56 Ω
175 m 44.50 Ω 24.92 Ω 18.32 Ω 12.46 Ω
8.31 Ω
6.23 Ω
4.15 Ω
200 m 50.86 Ω 28.48 Ω 20.94 Ω 14.24 Ω
9.49 Ω
7.12 Ω
4.75 Ω
225 m 57.21 Ω 32.04 Ω 23.56 Ω 16.02 Ω 10.68 Ω
8.01 Ω
5.34 Ω
250 m 63.57 Ω 35.60 Ω 26.18 Ω 17.80 Ω 11.87 Ω
8.90 Ω
5.93 Ω
†
Example 1: Max. permissible length at 1.5 mm² and 3 A →
Approx. 200 m
Example 2: Max. permissible length at 1.5 mm² and 6 A →
Approx. 100 m
Example 3: Mixed wiring:
R1 = 40 m in 1.5 mm² and R2 = 5 m in 0.25 mm²
(control cabinet--- sensor/actuator level)
R1 = 0.95 ohms, R2 = 0.71 ohms
Total (R1 + R2) = 1.66 ohms
*
Internal resistance of miniature circuit-breakers
†
Shutdown current Ishut = 3 A x 1.25 A = 3.75 A
Max. current resistance Rmax = UB/Ishut - 0.050 Ω (internal resistance of miniature circuit-breakers)
Rmax = (19.2 V/3.75 A) - 0.050 Ω = 5.07 Ω
The value calculated, 5.07 Ω, falls between 200 m and 225 m in the table (4.75 Ω and 5.34 Ω).
This means that you can bridge 200 m comfortably.
103906_en_01
PHOENIX CONTACT
9
EC-E...
4
Mounting the potenial distribution system
LINE+power rail continuous
plug-in bridge, gray
FB ST 500 TMC-NGY
Continuous plug-in bridges
500 mm length, shorten
(12.5 mm x n) – 3 mm = length of rails +/- 0.5 mm
E.g. (12.5 mm x 5) – 3 = 59.5 mm +/- 0.5 mm
Signal rail or signal bridge
continuous plug-in bridge
FBST 500-PLC-BU
FBST 500-PLC-RD
BU = blue
RD = red
Simply remove shock
protection slides from
underside of device
0-V power rail
continuous plug-in bridge, gray
FB ST 500 TMC-NGY
Press in bridges and
shock protection slides
so that they are flush
with the sides of the housing
Attach shock protection
slides to sides of device
12.5 mm x n = width of device block
E.g. 12.5 mm x 5 = 62.5 mm
Press in bridges
so that they are flush
with the housing and
place in a central
position above
the contacts
Figure 7
Mounting
A potential distribution system is integrated into the EC-E...
Various continuous plug-in bridges can be used to create
the following wiring configurations:
– LINE +(24 V DC)
– 0V
– Signal contacts
– Reset inputs
103906_en_01
NOTE: The EC-E... electronic miniature circuitbreakers require a 0-V connection.
PHOENIX CONTACT
10
EC-E...
5
Application examples
The signal contacts are shown in an off state or
fault state.
5.1
EC-E1– group signaling (series connection)
+ Supply for the SI
+ Supply
LINE + Power Rail
Continuous Plug-in Bridges, Gray
1
LINE+
+24 V
13
14
1
LINE+
13
14
1
LINE+
13
14
Group Signaling Using
a Signal Lamp
Power Supply Unit
24 V DC
Signal Bridges Plugged in Offset
0V
In Relation to Each Other
EC-E1
EC-E1
EC-E1
2 LOAD+
2 LOAD+
2 LOAD+
30V
30V
30V
Continuous Plug-in Bridges, Blue or Red
0 V-Power Rail
Continuous Plug-in Bridges, Gray
- Supply
+
-
+
Load
Figure 8
5.2
+
-
Load
-
Load
EC-E1– group signaling (series connection)
EC-E4 – individual signaling with common supply
Individual Signaling for
Each channel using a
Signal Lamp
+ Supply for the SI
+ Supply
1
LINE+
1
LINE+
+24 V
12
11
1
LINE+
12
11
LINE+ Power Rail
Continuous Plug-in Bridges, Gray
12
11
Power Supply Unit
24 V DC
EC-E4
EC-E4
0V
Signal Rail for Common
Suppy
EC-E4
Continuous Plug-In Bridges, Blue or Red
2 LOAD+
2 LOAD+
2 LOAD+
30V
30V
30V
0 V-Power Rail
Continuous Plug-in Bridges, Gray
- Supply
+
Load
Figure 9
103906_en_01
-
+
-
Load
+
-
Load
EC-E4 – individual signaling with common supply
PHOENIX CONTACT
11
EC-E...
5.3
EC-E – individual signaling with common reset
Reset
button
Individual signaling for each
channel using a signal lamp
+ supply
LINE+ power rail
continuous plug-in bridge, gray
1
LINE+
1
LINE+
+24 V
22
RE
SF
23
22
RE
SF
1
LINE+
23
22
RE
SF
23
24 V DC
power supply unit
EC-E
EC-E
0V
Signal rail for common
supply
Continuous plug-in bridges, blue or red
EC-E
2 LOAD+
2 LOAD+
2 LOAD+
30V
30V
30V
0-V power rail
continuous plug-in bridge, gray
- supply
+
Load
Figure 10
103906_en_01
-
+
-
Load
+
-
Load
EC-E – individual signaling with common reset
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany • Phone: +49-(0) 5235-3-00
PHOENIX CONTACT • P.O.Box 4100 • Harrisburg • PA 17111-0100 • USA • Phone: +1 (0) 717-944-1300
www.phoenixcontact.com