AXC F IL ADAPT
PLCnext Technology,
Inline adapter terminal (INTERBUS master),
right-alignable
Data sheet
108629_en_00
1
© PHOENIX CONTACT 2018-10-05
Description
The Inline adapter terminal (INTERBUS master) is designed
to be aligned to the right of an AXC F ... PLCnext controller.
The Inline adapter terminal can be used to set up a PLCnext
Inline station and integrate INTERBUS devices.
Features
–
–
–
Automatic detection of the transmission speed in
INTERBUS (500 kbps or 2 Mbps)
Up to 63 INTERBUS devices can be connected
Diagnostic and status indicators
NOTE: Device defect due to
impermissible firmware version
The Inline adapter terminal is designed to be
aligned to the right of PLCnext controllers with
specific firmware versions. If you align the
Inline adapter terminal next to a PLCnext
controller with a firmware version that is not
permitted, this can cause a device defect to
the PLCnext controller.
Make sure that the Inline adapter terminal is
only aligned next to a PLCnext controller with
a firmware version that is permitted.
AXC F ... PLCnext controllers with the
following firmware versions are permitted:
– AXC F 2152 with firmware Version 1.2
Please note:
Align the Inline adapter terminal directly on the
controller. Axioline F modules may not be
aligned on the controller.
This data sheet is only valid in association with the Axioline F system manual and the user manual for the
Axioline F controller being used.
Make sure you always use the latest documentation.
It can be downloaded at: phoenixcontact.net/product/1020304
AXC F IL ADAPT
2
Table of contents
1
Description .............................................................................................................................. 1
2
Table of contents ..................................................................................................................... 2
3
Ordering data .......................................................................................................................... 3
4
Technical data ......................................................................................................................... 4
5
Module components ................................................................................................................ 7
6
Internal circuit diagram ............................................................................................................ 8
7
Design of a PLCnext Inline station ........................................................................................... 9
8
Mounting................................................................................................................................ 10
8.1
Removing the controller ...................................................................................................... 10
8.2
Mount bus base module ...................................................................................................... 10
8.3
Snapping on the controller ................................................................................................... 11
8.4
Snapping on electronics modules .......................................................................................... 11
8.5
Mount Inline connector ........................................................................................................ 11
9
Connecting the supply voltage............................................................................................... 12
10
Connection example.............................................................................................................. 13
11
Diagnostics and status indicators .......................................................................................... 14
12
Supported INTERBUS master services ................................................................................. 15
13
PCP communication .............................................................................................................. 18
108629_en_00
PHOENIX CONTACT
2 / 18
AXC F IL ADAPT
3
Ordering data
Description
Order No.
Pcs./Pkt.
Right-alignable Inline adapter terminal (INTERBUS
AXC F IL ADAPT
master) for a PLCnext controller for setting up a PLCnext
Inline station
1020304
1
Documentation
Order No.
Pcs./Pkt.
User manual, English, Axioline F: System and installation UM EN AXL F SYS INST
-
-
User manual, English, Axioline F: Diagnostic registers,
and error messages
UM EN AXL F SYS DIAG
-
-
User Manual, English, for diagnosis in Generation 4
controller boards
IBS SYS DIAG DSC UM E
2747293
1
User manual, English, for the Peripherals Communication IBS PCP UM E
Protocol (PCP), only available as a download.
2753931
1
User manual, English, for the Peripherals Communication IBS SYS PCP G4 UM E
Protocol (PCP), only available as a download.
2745169
1
108629_en_00
Type
Type
PHOENIX CONTACT
3 / 18
AXC F IL ADAPT
4
Technical data
Dimensions (nominal sizes in mm)
71,5
119,8
Width
12.2 mm
Height
119.8 mm
Depth
71.5 mm
General data
Weight
66 g
Ambient temperature (operation)
-25 °C ... 55 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Permissible humidity (operation)
10 % ... 95 % (non-condensing)
Permissible humidity (storage/transport)
10 % ... 95 % (non-condensing)
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
10 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection
IP20
Mounting type
DIN rail mounting
Connection data: Inline connector
Connection method
Spring-cage connection
Conductor cross section solid / stranded
0.08 mm² ... 1.5 mm² / 0.08 mm² ... 1.5 mm²
Conductor cross section [AWG]
28 ... 16
Stripping length
8 mm
System limits
Amount of process data
max. 4096 Bit (INTERBUS)
Number of local bus devices that can be connected
max. 63 (observe current consumption)
Number of devices with parameter channel
max. 62
24 V supply UILC
Supply voltage
24 V DC -15 % / +20 % (acc. to EN 61131-2)
Current draw
20 mA
108629_en_00
PHOENIX CONTACT
4 / 18
AXC F IL ADAPT
7.5 V communications power UL (potential jumper)
Supply voltage
7.5 V DC ±5 %
Power supply unit
max. 0.8 A DC (observe derating)
24 V analog supply UANA (potential jumper)
Supply voltage
24 V DC -15 % / +20 %
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Power supply unit
0.5 A DC (observe derating)
24 V main supply UM
Supply voltage
24 V DC -15 % / +20 % (acc. to EN 61131-2)
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Power supply unit
max. 8 A DC (sum of UM + US)
24 V segment supply US
Supply voltage
24 V DC -15 % / +20 % (in accordance with EN 61131)
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Power supply unit
max. 8 A (sum of UM + US)
Protective circuit
Polarity reversal protection of the supply voltage
Polarity protection diode
Transient protection
Suppressor diode
Protection
NOTE: Damage to the electronics
Provide external protection for the module to protect it against polarity reversal. The power supply unit and the
external fuse must be coordinated so that safe tripping is ensured in the event of an error.
Error messages to the higher level control or computer system
Bus error in INTERBUS
Yes
Peripheral fault in INTERBUS
Yes
Mechanical tests
Shock in acc. with EN 60068-2-27/IEC 60068-2-27
30g, 11 ms period, half-sine shock pulse
Continuous shock according to EN 60068-2-27/
IEC 60068-2-27
10g
Vibration resistance in acc. with EN 60068-2-6/
IEC 60068-2-6
2g
Conformance with EMC Directive 2014/30/EU
Noise immunity test in accordance with EN 61000-6-2
EN 61000-4-2 (ESD)
Electrostatic discharge (ESD) EN 61000-4-2/
IEC 61000-4-2
Criterion B, 4 kV contact discharge, 8 kV air discharge
EN 61000-4-3 (electromagnetic fields)
Electromagnetic fields EN 61000-4-3/IEC 61000-4-3
Criterion A, Field intensity: 10 V/m
EN 61000-4-4
Fast transients (burst) EN 61000-4-4/IEC 61000-4-4
Criterion B, 2 kV
108629_en_00
PHOENIX CONTACT
5 / 18
AXC F IL ADAPT
Conformance with EMC Directive 2014/30/EU
EN 61000-4-5 (surge)
Transient overvoltage (surge) EN 61000-4-5/
IEC 61000-4-5
Criterion B, DC supply lines: ±0.5 kV/±0.5 kV (symmetrical/
asymmetrical)
EN 61000-4-6 (line noise immunity)
Conducted interference EN 61000-4-6/IEC 61000-4-6
Criterion A; Test voltage 10 V
Noise emission test as per EN 61000-6-4
Class A
Approvals
For the latest approvals, please visit phoenixcontact.net/products.
108629_en_00
PHOENIX CONTACT
6 / 18
AXC F IL ADAPT
5
Module components
U
IL
FA
PF
B
S
A
R
D
Y
5
4
3
2
1
Figure 1
1
2
3
4
5
Module components
Bus base module
Electronics module
Inline connector
Terminal points
Diagnostic and status indicators
108629_en_00
PHOENIX CONTACT
7 / 18
AXC F IL ADAPT
6
Internal circuit diagram
3,3V
5V
IB
RDY
UL+
UANA
FAIL
ULBSA
&
PF
7,5V
24V
24V
P
Local bus
U
24V
US
UM
S
UL
US
UM
PWR
Figure 2
Basic circuit diagram
Key:
Power supply unit
Protocol chip
IB
LED
AND gates
&
P
Parallel-to-serial converters
S
108629_en_00
PHOENIX CONTACT
8 / 18
AXC F IL ADAPT
7
Design of a PLCnext Inline station
3
4
5
SD-CARD
MAC Addr.: XX.XX.XX.XX.XX.XX
1
Ord. No. 2404267 AXC
F 2152
2
R
X4
1
RDY
FAIL
BSA
PF
U
X2
X1
Figure 3
1
2
3
4
5
Design of a PLCnext Inline station
End clamp (e.g., CLIPFIX 35-5, Order No. 3022276)
PLCnext controller for Axioline F (in the example: AXC F 2152)
Inline adapter terminal
Inline terminals corresponding to the application
End plate (snap onto the DIN rail as station end)
108629_en_00
PHOENIX CONTACT
9 / 18
AXC F IL ADAPT
8
Mounting
Please note:
8.1
Removing the controller
The controller must be removed in order to mount the bus
base module of the Inline adapter terminal.
On a controller for Axioline F, only one Inline
adapter terminal may be aligned to the right.
52
21
F
X
X
C
.X
A
X
.X
X
.X
X
.X
X
r.:
X
X
D
.X
R
X
R
A
-C
O
rd
.N
o.
24
04
26
7
D
M
A
C
A
dd
4
•
8.2
1
The Inline adapter terminal is designed to be
aligned to the right of PLCnext controllers with
specific firmware versions. If you align the
Inline adapter terminal next to a PLCnext
controller with a firmware version that is not
permitted, this can cause a device defect to
the PLCnext controller.
X
NOTE: Device defect due to
impermissible firmware version
2
•
X
Figure 4
2
X
A
1
X
Mount all the necessary modules before
supplying power to the PLCnext Inline station.
Modules to which power is only supplied
following the controller boot process are not
detected or may result in a malfunction.
To ensure that the Inline adapter terminal is
detected correctly, proceed as follows:
- Switch on the power to the Inline adapter
terminal before switching on the power to the
controller
or
- Switch on the power to the Inline adapter
terminal and the controller simultaneously.
A
S
B
Please note:
Removing the controller
Insert a suitable tool (e.g., bladed screwdriver) into the
upper and lower snap-on mechanisms (base latches) of
the controller one after the other and release it (A).
The base latches are latched in place in the open
position.
Remove the controller perpendicular to the DIN rail (B).
Mount bus base module
A
Make sure that the Inline adapter terminal is
only aligned next to a PLCnext controller with
a firmware version that is permitted.
B
AXC F ... PLCnext controllers with the
following firmware versions are permitted:
– AXC F 2152 with firmware Version 1.2
Figure 5
•
•
Mounting the bus base module
Place the bus base module of the Inline adapter
terminal on the DIN rail (A).
Push the bus base module of the Inline adapter terminal
into the connection of the bus base module on the
controller (B).
Please note:
Align the Inline adapter terminal directly on the
controller. Axioline F modules may not be
aligned on the controller.
108629_en_00
PHOENIX CONTACT
10 / 18
AXC F IL ADAPT
Snapping on the controller
8.5
Mount Inline connector
X
.X
.X
X
.X
X
.X
X
D
D
X
M
A
C
4
r.:
X
X
R
.X
X
R
A
-C
A
dd
S
O
rd
.N
o.
24
04
26
7
A
X
C
F
21
52
8.3
B
1
X
2
X
X
2
X
1
A
Figure 8
•
Figure 6
•
•
8.4
•
•
Insert the Inline connectors in the specified order (A, B).
Snapping on the controller
Place the controller vertically on the first bus base
module and the DIN rail until it snaps into place with a
click.
Make sure that the device connector for the bus base
connection is situated above the corresponding socket
on the bus base module.
Snapping on electronics modules
Figure 7
•
Insert Inline connector
Snapping on the electronics module of the
Inline adapter terminal
Place the electronics module of the Inline adapter
terminal vertically on the corresponding bus base
module and on the DIN rail until it snaps into place with
a click.
Make sure that the device connector for the bus base
connection is situated above the corresponding socket
on the bus base module.
Mount the electronics modules of all necessary Inline
terminals. Note the assembly instructions in the devicespecific packing slip.
108629_en_00
PHOENIX CONTACT
11 / 18
AXC F IL ADAPT
9
Connecting the supply voltage
Terminal point assignment
NOTE: Device defect due to
impermissible firmware version
The Inline adapter terminal is designed to be
aligned to the right of PLCnext controllers with
specific firmware versions. If you align the
Inline adapter terminal next to a PLCnext
controller with a firmware version that is not
permitted, this can cause a device defect to
the PLCnext controller.
Make sure that the Inline adapter terminal is
only aligned next to a PLCnext controller with
a firmware version that is permitted.
AXC F ... PLCnext controllers with the
following firmware versions are permitted:
– AXC F 2152 with firmware Version 1.2
A
8
B
C
Figure 9
•
•
•
•
Connecting cables
Strip 8 mm off the cables.
Release the spring by pressing with the screwdriver.
Insert the cable into the terminal point.
Secure the cable by removing the screwdriver.
Figure 10
1.1
1.1 2.1
2.1
1.2
1.2 2.2
2.2
1.3
1.3 2.3
2.3
1.4
1.4 2.4
2.4
Terminal point assignment
Terminal point
1.1
1.2
1.3
1.4
2.1
2.2
2.3
2.4
Assignment
US (24 V DC)
UILC (24 V DC)
GND UILC
FE
UM (24 V DC)
UM (24 V DC)
GND UM/US
FE
Key:
US (24 V DC)
UM (24 V DC)
UILC (24 V DC)
GND
FE
24 V supply for segment circuit
24 V supply for main circuit
24 V main voltage / 7.5 V logic supply /
24 V analog supply
Ground
Functional earth ground
Recommended: flat-bladed screwdriver with blade
dimensions of 0.6 mm x 3.5 mm x 100 mm (e. g.,
SZF 1-0,6X3,5, Order No. 1204517)
108629_en_00
PHOENIX CONTACT
12 / 18
AXC F IL ADAPT
Figure 11
I/O
I/O
I/O
AXC F IL ADAPT
Connection example
AXC F...
10
Connection example
Key:
AXC F ...
AXC F IL ADAPT
I/O
INTERBUS
108629_en_00
AXC F ... PLCnext controller
Inline adapter terminal
Inline terminals corresponding to your application
INTERBUS devices according to your application
PHOENIX CONTACT
13 / 18
AXC F IL ADAPT
11
Diagnostics and status indicators
RDY
FAIL
BSA
PF
U
Figure 12
Diagnostic and status indicators
Designation
RDY
Color
Meaning
State
Description
Green
INTERBUS master
FAIL
Red
Error
BSA
Yellow
Bus segment
PF
Yellow
Peripheral fault
U
Green
Supply voltages US,
UM, UL
On
Flashing
OFF
On
OFF
On
OFF
On
OFF
On
INTERBUS master in the RUN state
INTERBUS master in the READY or ACTIVE state
INTERBUS master is not ready to operate
Bus, controller or user error
No error
At least one bus segment aborted
No bus segment aborted
Peripheral fault on at least one device in INTERBUS
No peripheral fault
Supply voltages US, UM, UL present
OFF
At least one of the supply voltages US, UM or UL is not
present
108629_en_00
PHOENIX CONTACT
14 / 18
AXC F IL ADAPT
12
Supported INTERBUS master services
For more detailed information on the
INTERBUS G4 services, please refer to the
IBS SYS FW G4 UM E user manual. The user
manual can be downloaded at
phoenixcontact.net/products.
The following restrictions apply for the
INTERBUS master:
- Support for INTERBUS devices with slave
protocol chip SUPI3 or higher
- No FO diagnostics
- No single-channel diagnostics
- No support for LPC1 or LPC2
- No isolated disconnection possible
Firmware services are used to carry out the configuration, parameterization, and diagnostics of INTERBUS.
The Inline adapter terminal (INTERBUS master) supports the following INTERBUS G4 services (some of which have a limited
scope of functions):
Code (hex)
0306
Service
Initiate_Load_Configuration
0307
Load_Configuration
0308
Terminate_Load_Configuration
0309
Read_Configuration
108629_en_00
Description
Create configuration frame for data transmission
- Max. 127 characters
- Can only be set when New_Config = 1
Transmit the device data for a configuration
Used_Attributes:
Bit 0: device number
Bit 1: device code
Bit 2: reserved
Bit 3: device level
Bit 4: logical group number (always FFFFhex)
Bits 5 ... 13: reserved
Bit 14: extended device information
Bit 15: reserved
Terminate the transmission of configuration data (only for automatic parameterization)
Default_Parameter:
The PCP channel is always parameterized automatically.
The process data channel is only parameterized automatically if bit 0 is set.
Read various entries of the configuration directory
Used_Attributes:
Bit 0: device number
Bit 1: device code
Bit 2: reserved
Bit 3: device level
Bit 4: logical group number
Bits 5 ... 7: reserved
Bit 8: global_bus_error
Bit 9: separate_bus_error (Reconf and Watchdog not supported)
Bit 10: device status
Bits 11 ... 13: reserved
Bit 14: extended device information
Bit 15: reserved
PHOENIX CONTACT
15 / 18
AXC F IL ADAPT
Code (hex)
030A
Service
Complete_Load_Configuration
030B
Complete_Read_Configuration
030C
Delete_Configuration
030E
030F
0314
Control_Parameterization
Control_Statistics
Control_Device_Function_Not_Exclusive
0315
Read_Device_State
0316
0328
Get_Error_Info
Compact_Load_Process_Data_Reference_List
0329
Compact_Read_Process_Data_Reference_List
032A
032B
0351
Get_Version_Info
Get_Diag_Info
Read_Value
0701
0702
Start_Data_Transfer
Stop_Data_Transfer
108629_en_00
Description
Transmit all the device data for a configuration
Used_Attributes:
Bit 0: device number
Bit 1: device code
Bit 2: reserved
Bit 3: device level
Bit 4: logical group number (always FFFFhex)
Bits 5 ... 13: reserved
Bit 14: extended device information
Bit 15: reserved
Read all the device data for a configuration
Used_Attributes:
Bit 0: device number
Bit 1: device code
Bit 2: reserved
Bit 3: device level
Bit 4: logical group number (always FFFFhex)
Bits 5 ... 13: reserved
Bit 14: extended device information
Bit 15: reserved
Delete inactive configuration frames from the configuration
directory
Start or end the parameterization phase
Control statistical diagnostics
Send control commands to local bus device
Device_Function:
0003hex: Conf_Dev_Err
0004hex: Conf_Dev_Err_All
Read status of local bus devices
Device_State_Mask:
Bits 0 ... 10: reserved
Bit 11: peripheral fault
Bits 12 ... 15: reserved
Request additional error information
Configure controller board without software support
- Permitted addresses: 0000hex ... 03FFhex
- No overlapping or duplication possible
- Modules up to max. 8 bits with Byte-Cons at every address,
modules > 8 bits only at even addresses
Read address lists of the control or computer system that
were configured using the “Compact_Load_Process_Data_Reference_List” service (3028hex)
Read version information
Read local bus counter
Read system parameter
Supported values for the Variable_ID parameter: see next
table
Start data transfer
Stop data transfer
PHOENIX CONTACT
16 / 18
AXC F IL ADAPT
Code (hex)
0710
0711
Service
Create_Configuration
Activate_Configuration
0712
0713
Deactivate_Configuration
Control_Active_Configuration
0714
Control_Device_Function
0750
Set_Value
0760
1303
Confirm_Diagnostics
Alarm_Stop
Description
Read the connected bus
Check the configuration frame matches the connected bus
and whether addresses overlap
Deactivate configuration frame
Switch INTERBUS device on or off.
Only Switch_Codes 0004hex (Device_Disable) and 0005hex
(Device_Enable) are supported.
Switching or bridging has no influence on the position of the
process data in the memory or the CR assignment of the
PCP devices.
Send control commands to local bus device
Device_Function:
0003hex: Conf_Dev_Err
0004hex: Conf_Dev_Err_All
Assign new values to system parameters
Supported values for the Variable_ID parameter: see next
table
Update diagnostic display and diagnostic register
Reset local bus
Supported values for the Variable_ID parameter
Variable_ID
(hex)
0101
0104
0105
010D
2200
2204
2210
2211
2212
2216
2218
A228
108629_en_00
System parameter
Value/note
State of the system management
Contents of the diagnostic status register
Contents of the diagnostic parameter register
Contents of the extended diagnostic parameter register
Operating mode
Read access only
Read access only
Read access only
Read access only
0000 0000hex: asynchronous
0600 0000hex: asynchronous with synchronization
pulse
Control the behavior of the input data in the event of a 0: input data in the MPM is frozen (default setting)
bus error
1: input data in the MPM is set to zero
Specified process data cycle time in s (32-bit value) Permissible value range:
0000 0000hex: off
0000 0100hex ... 0001 FB00hex
Bus timeout in s (32-bit value)
Permissible value:
Default setting: 200 ms
0000 0000hex: (default setting)
Bus warning time in s (32-bit value)
Permissible value range:
Default setting: 0 (not activated)
0000 00100hex ... 000F FF00hex
Actual process data cycle time in s (32-bit value)
Read access only
Data cycle time in s (32-bit value)
Read access only
Read baud rate
Read access only
0: 2 Mbaud
1: 500 kBaud
PHOENIX CONTACT
17 / 18
AXC F IL ADAPT
13
PCP communication
The Inline adapter terminal (INTERBUS master) supports
the Peripherals Communication Protocol (PCP) Version 2.0
with Peripherals Message Specification (PMS).
Peripherals Network Management 7 (PNM7) services are
not supported.
For information on PCP communication,
please refer to the PCP user manuals (see
Ordering data).
Code
(hex)
0081
4081
C081
8081
0082
4082
C082
8082
0885
4885
0086
8086
0087
8087
008B
408B
C08B
808B
088D
488D
488E
0264
8264
Service
Read_Request
Read_Indication
Read_Response
Read_Confirmation
Write_Request
Write_Indication
Write_Response
Write_Confirmation
Information_Report_Request
Information_Report_Indication
Status_Request
Status_Confirmation
Identify_Request
Identify_Confirmation
Initiate_Request
Initiate_Indication
Initiate_Response
Initiate_Confirmation
Abort_Request
Abort_Indication
Reject_Indication
Load_CRL_Attribute_Loc_Request
Load_CRL_Attribute_Loc_Confirmation
108629_en_00
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany
phoenixcontact.com
18 / 18