Power supply unit - TRIO-PS-IP67/3AC/24DC/20
1039829
https://www.phoenixcontact.com/in/products/1039829
Please be informed that the data shown in this PDF document is generated from our Online Catalog. Please find the complete data in the user
documentation. Our General Terms of Use for Downloads are valid.
TRIO POWER primary-switched power supply in IP67 die-cast housing, input: 3-phase, output:
24 V DC / 20 A
Your advantages
• Direct installation at the load in the field reduces cable lengths and saves space in the control cabinet
• The robust design (die-cast aluminum housing) ensures high system availability, thanks to resistance to extreme environmental conditions
(temperature, dust, and water)
• Reliable startup of high loads, thanks to the dynamic boost
• High efficiency of > 93%, thanks to low power losses
May 19, 2022, 10:06 AM
Page 1 (14)
Power supply unit - TRIO-PS-IP67/3AC/24DC/20
1039829
https://www.phoenixcontact.com/in/products/1039829
Commercial Data
Item number
1039829
Packing unit
1 pc
Minimum order quantity
1 pc
Sales Key
CMP
Product Key
CMPF33
Catalog Page
Page 265 (C-4-2019)
GTIN
4055626595795
Weight per Piece (including packing)
4,550 g
Weight per Piece (excluding packing)
4,550 g
Customs tariff number
85044030
Country of origin
CN
May 19, 2022, 10:06 AM
Page 2 (14)
Power supply unit - TRIO-PS-IP67/3AC/24DC/20
1039829
https://www.phoenixcontact.com/in/products/1039829
Technical Data
Input data
AC operation
Network type
Star network
Nominal input voltage range
3x 400 V AC ... 500 V AC
2x 400 V AC ... 500 V AC
Input voltage range
3x 400 V AC ... 500 V AC -20 % ... +15 %
2x 400 V AC ... 500 V AC -10 % ... +15 %
Input voltage range AC
3x 320 V AC ... 575 V AC
Typical national grid voltage
3x 400 V AC
3x 480 V AC
Voltage type of supply voltage
AC
Inrush current
typ. 22 A (at 25 °C)
2
Inrush current integral (I t)
0.5 A2s
Inrush current limitation
≤ 22 A (at 25 °C)
AC frequency range
50 Hz ... 60 Hz
Mains buffering time
typ. 10 ms (400 V AC)
typ. 20 ms (500 V AC)
Current consumption
3x 1.2 A (400 V AC)
3x 1 A (500 V AC)
2x 2.3 A (400 V AC)
2x 1.9 A (500 V AC)
Nominal power consumption
39 W
Protective circuit
Transient surge protection; Varistor
Typical response time
15 ms (230 V AC)
Current consumption
4.9 A (110 V DC)
2.1 A (250 V DC)
Output data
Efficiency
93 % (400 V AC)
93 % (500 V AC)
Nominal output voltage
24 V DC ±1 %
Nominal output current (IN)
20 A
Dynamic Boost (IDyn.Boost)
30 A (5 s)
Derating
> 60 °C ... 70 °C (2.5%/K)
Protection against overvoltage at the output (OVP)
≤ 30 V DC
May 19, 2022, 10:06 AM
Page 3 (14)
Power supply unit - TRIO-PS-IP67/3AC/24DC/20
1039829
https://www.phoenixcontact.com/in/products/1039829
Control deviation
< 1 % (change in load, static 10 % ... 90 %)
< 3 % (Dynamic load change 10 % ... 90 %, 10 Hz)
< 0.1 % (change in input voltage ±10 %)
Residual ripple
≤ 20 mVPP
Short-circuit-proof
yes
Output power
480 W
720 W
Maximum no-load power dissipation
< 2 W (400 V AC)
< 2.5 W (480 V AC)
Power loss nominal load max.
< 44 W (400 V AC)
< 44 W (480 V AC)
Rise time
≤ 120 ms (UOUT (10 % ... 90 %))
Signal: DC OK
Maximum switching voltage
30 V AC/DC
Continuous load current
100 mA
Signal relay 13/14
Default
closed
Digital
30 V AC 30 V DC 100 mA
Connection data
Input
Connection method
Circular connector
Coding
S-coded
Type of locking
M12 screw locking
Number of positions
4
Output
Connection method
Circular connector
Coding
N-coded
Type of locking
M17 standard and SPEEDCON locking
Number of positions
4
Signal
Connection method
Circular connector
Coding
A-coded
Type of locking
SPEEDCON M12
Number of positions
5
LED signaling
Types of signaling
LED
Floating signal contact
Signal output: LED status indicator
Signalization designation
DC OK
May 19, 2022, 10:06 AM
Page 4 (14)
Power supply unit - TRIO-PS-IP67/3AC/24DC/20
1039829
https://www.phoenixcontact.com/in/products/1039829
Status display
LED
Color
green
Electrical properties
Number of phases
3.00
Insulation voltage input/output
4 kV AC (type test)
1.5 kV AC (routine test)
Product properties
Product type
Power supply
MTBF (IEC 61709, SN 29500)
> 1500000 h (25 °C)
> 620000 h (40 °C)
> 230000 h (60 °C)
Insulation characteristics
Protection class
I
Degree of pollution
4
Dimensions
Width
151 mm
Height
304 mm
Depth
120 mm
Installation dimensions
Installation distance right/left
20 mm / 20 mm
Installation distance top/bottom
50 mm / 100 mm
Mounting
Mounting type
Wall mounting
Assembly instructions
Alignable: 20 mm horizontally, 50 mm vertically above, 100 mm
vertically below
With protective coating
No
Material specifications
Inflammability class in acc. with UL 94 (housing / terminal blocks)
V0
Housing material
Metal
Type of housing
Aluminum (AlMg3)
Environmental and real-life conditions
Ambient conditions
Degree of protection
IP67
Ambient temperature (operation)
-25 °C ... 85 °C (Derating > 60 °C (3 AC): 2,5 %/K / > 50 °C
(2 AC): 2,5 %/K)
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Ambient temperature (start-up type tested)
-40 °C
Maximum altitude
≤ 4000 m (> 2000 m, Derating: 10 %/1000 m)
May 19, 2022, 10:06 AM
Page 5 (14)
Power supply unit - TRIO-PS-IP67/3AC/24DC/20
1039829
https://www.phoenixcontact.com/in/products/1039829
Climatic class
3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation)
≤ 95 % (at 25 °C, non-condensing)
Shock
18 ms, 30g, in each space direction (according to IEC 60068-227)
Vibration (operation)
In each space direction (in acc. with EN 60068-2-6)
10 Hz - 19.9 Hz, ±2.5 mm amplitude,
19.9 Hz - 150 Hz, 4g acceleration
Standards and regulations
Standard – Limitation of mains harmonic currents
EN 61000-3-2
Standard - Electrical safety
IEC 61010-2-201 (SELV)
Standard – Safety extra-low voltage
EN 60204-1 (PELV)
Standard - Safe isolation
DIN VDE 0100-410
Overvoltage category
EN 61010-1
III (≤ 2000 m)
II (≤ 4000 m)
Approval data
Conformity/Approvals
SIL in accordance with IEC 61508
0
Performance level according to ISO 13849
without
EMC data
Low Voltage Directive
Conformance with Low Voltage Directive 2014/35/EC
Electromagnetic compatibility
Conformance with EMC Directive 2014/30/EU
Conducted noise emission
EN 55016
EN 61000-6-3 (Class B)
Interference emission
Noise emission according to EN 61000-6-3 (residential and
commercial) and EN 61000-6-4 (industrial)
Noise emission
EN 55011 (EN 55022)
Noise emission
EN 55016
EN 61000-6-3 (Class B)
Noise immunity
Immunity according to EN 61000-6-1 (residential), EN 61000-6-2
(industrial)
Harmonic currents
Frequency range
Class A
Flicker
Standards/regulations
EN 61000-3-3
Frequency range
0 kHz ... 2 kHz
Electrostatic discharge
Standards/regulations
EN 61000-4-2
Electrostatic discharge
Contact discharge
6 kV (Test Level 4)
May 19, 2022, 10:06 AM
Page 6 (14)
Power supply unit - TRIO-PS-IP67/3AC/24DC/20
1039829
https://www.phoenixcontact.com/in/products/1039829
Discharge in air
8 kV (Test Level 4)
Comments
Criterion A
Electromagnetic HF field
Standards/regulations
EN 61000-4-3
Electromagnetic HF field
Frequency range
80 MHz ... 1 GHz
Test field strength
10 V/m (Test Level 3)
Frequency range
1 GHz ... 2 GHz
Test field strength
10 V/m (Test Level 3)
Frequency range
2 GHz ... 3 GHz
Test field strength
10 V/m (Test Level 3)
Comments
Criterion A
Fast transients (burst)
Standards/regulations
EN 61000-4-4
Fast transients (burst)
Input
4 kV (Test Level 4 - asymmetrical)
Output
2 kV (Test Level 3 - asymmetrical)
Signal
1 kV (Test Level 2 - asymmetrical)
Comments
Criterion A
Surge voltage load (surge)
Standards/regulations
EN 61000-4-5
Input
2 kV (Test Level 3 - symmetrical)
4 kV (Test Level 4 - asymmetrical)
Output
1 kV (Test Level 2 - symmetrical)
2 kV (Test Level 1 - asymmetrical)
Signal
1 kV (Test Level 1 - asymmetrical)
Comments
Criterion B
Conducted interference
Standards/regulations
EN 61000-4-6
Conducted interference
Input/Output
asymmetrical
Frequency range
0.15 MHz ... 80 MHz
Comments
Criterion A
Voltage
10 V (Test Level 3)
Voltage dips
Standards/regulations
EN 61000-4-11
Voltage
400 V AC
Frequency
50 Hz
Voltage dip
70 %
Number of periods
25 periods
May 19, 2022, 10:06 AM
Page 7 (14)
Power supply unit - TRIO-PS-IP67/3AC/24DC/20
1039829
https://www.phoenixcontact.com/in/products/1039829
Additional text
Test Level 2
Comments
Criterion A
Voltage dip
40 %
Number of periods
10 periods
Additional text
Test Level 2
Comments
Criterion A
Voltage dip
0%
Number of periods
1 period
Additional text
Test Level 2
Comments
Criterion A
Emitted interference
Standards/regulations
EN 61000-6-3
Radio interference voltage in acc. with EN 55011
EN 55011 (EN 55022) Class B, area of application: Industry and
residential
Emitted radio interference in acc. with EN 55011
EN 55011 (EN 55022) Class B, area of application: Industry and
residential
Criterion A
Normal operating behavior within the specified limits.
Criterion B
Temporary impairment to operational behavior that is corrected
by the device itself.
Criterion C
Temporary adverse effects on the operating behavior, which the
device corrects automatically or which can be restored by
actuating the operating elements.
May 19, 2022, 10:06 AM
Page 8 (14)
Power supply unit - TRIO-PS-IP67/3AC/24DC/20
1039829
https://www.phoenixcontact.com/in/products/1039829
Drawings
Block diagram
Input AC
X1
L1
L2
L3
1
1
2
active
2
3
PFC
3
PE
PE
+
Output DC
–
X2
–
PE
Signal
1
13
2 14
X3
May 19, 2022, 10:06 AM
Page 9 (14)
Power supply unit - TRIO-PS-IP67/3AC/24DC/20
1039829
https://www.phoenixcontact.com/in/products/1039829
Approvals
CSA
CSAus
Approval ID: 70175690
Approval ID: 70175690
cCSAus
EAC
CSA
EAC
CSAus
Approval ID: RU S-DE.BL08.W.00764
Approval ID: 70175690
Approval ID: RU S-DE.BL08.W.00764
Approval ID: 70175690
cCSAus
May 19, 2022, 10:06 AM
Page 10 (14)
Power supply unit - TRIO-PS-IP67/3AC/24DC/20
1039829
https://www.phoenixcontact.com/in/products/1039829
Classifications
ECLASS
ECLASS-9.0
27040701
ECLASS-10.0.1
27040701
ECLASS-11.0
27040701
ETIM
ETIM 8.0
EC002540
UNSPSC
UNSPSC 21.0
May 19, 2022, 10:06 AM
Page 11 (14)
Power supply unit - TRIO-PS-IP67/3AC/24DC/20
1039829
https://www.phoenixcontact.com/in/products/1039829
Environmental Product Compliance
REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 25;
For information on hazardous substances, refer to the
manufacturer’s declaration available under “Downloads”
May 19, 2022, 10:06 AM
Page 12 (14)
Power supply unit - TRIO-PS-IP67/3AC/24DC/20
1039829
https://www.phoenixcontact.com/in/products/1039829
Accessories
Connector
Connector - SACC-FS-5SC M SCO - 1432583
https://www.phoenixcontact.com/in/products/1432583
Connector, 5-position, Socket straight M12 SPEEDCON, Coding: A, Spring-cage
connection, knurl material: Zinc die-cast, nickel-plated, external cable diameter 4
mm ... 8 mm
Cable connector
Cable connector - ST-3EP1N8A8005 - 1624534
https://www.phoenixcontact.com/in/products/1624534
Cable connector, straight, Screw locking, M17, number of positions: 3+PE, type
of contact: Pin, shielded: yes, degree of protection: IP67, cable diameter range:
10 mm ... 12.5 mm, number of positions: 4, connection method: Crimp
connection, series: ST
May 19, 2022, 10:06 AM
Page 13 (14)
Power supply unit - TRIO-PS-IP67/3AC/24DC/20
1039829
https://www.phoenixcontact.com/in/products/1039829
Power connector
Power connector - SACC-M12FSS-3PECON-PG11-M - 1404642
https://www.phoenixcontact.com/in/products/1404642
Power connector, Power, 4-position, Socket straight M12, Coding: S, Screw
connection, knurl material: Zinc die-cast, nickel-plated, cable gland Pg11,
external cable diameter 8 mm ... 10 mm, for AC current up to 12 A/630 V
Phoenix Contact 2022 © - all rights reserved
https://www.phoenixcontact.com
PHOENIX CONTACT (I) Pvt. Ltd.
A-58/2, Okhla Industrial Area, Phase - II, New Delhi-110 020
+91.1275.71420
info@phoenixcontact.co.in
May 19, 2022, 10:06 AM
Page 14 (14)