Power supply unit - EM-CPS-PS/3AC/24DC/5
1064922
https://www.phoenixcontact.com/in/products/1064922
Please be informed that the data shown in this PDF document is generated from our Online Catalog. Please find the complete data in the user
documentation. Our General Terms of Use for Downloads are valid.
Primary-switched power supply unit, TRIO POWER, Snap-on connection, Cross Power System installation, input: 3-phase, output: 24 V DC / 5 A
Product Description
The TRIO CROSS POWER power supply for the CrossPowerSystem power distribution board is perfectly adapted for use in machine building. All
of the functions and space-saving design are tailored to the high requirements in this area. The push-in connection enables quick and easy
connection of a 24 V DC control voltage.
Your advantages
• Push-in connections for easy 24 V DC control voltage connection
• Fast startup: Tool-free mounting and automatic contacting in just one step (CrossPowerSystem)
• Reliable startup of high loads, thanks to the dynamic boost
• Electrically robust, thanks to high electric strength
• Maximum flexibility, thanks to the temperature range of -25°C … +70°C and device startup at -40°C
May 19, 2022, 10:05 AM
Page 1 (14)
Power supply unit - EM-CPS-PS/3AC/24DC/5
1064922
https://www.phoenixcontact.com/in/products/1064922
Commercial Data
Item number
1064922
Packing unit
1 pc
Minimum order quantity
1 pc
Sales Key
CMP
Product Key
CMPO33
Catalog Page
Page 262 (C-4-2019)
GTIN
4055626725222
Weight per Piece (including packing)
781.6 g
Weight per Piece (excluding packing)
707 g
Customs tariff number
85044030
Country of origin
CN
May 19, 2022, 10:05 AM
Page 2 (14)
Power supply unit - EM-CPS-PS/3AC/24DC/5
1064922
https://www.phoenixcontact.com/in/products/1064922
Technical Data
Input data
AC operation
Network type
Star network
Nominal input voltage range
3x 400 V AC ... 500 V AC
2x 400 V AC ... 500 V AC
Input voltage range
3x 400 V AC ... 500 V AC -20 % ... +15 %
2x 400 V AC ... 500 V AC -10 % ... +15 %
Input voltage range AC
3x 320 V AC ... 575 V AC
Typical national grid voltage
3x 400 V AC
3x 480 V AC
Voltage type of supply voltage
2
AC
Inrush current integral (I t)
≤ 0.25 A2s
Inrush current limitation
≤ 22 A
AC frequency range
50 Hz ... 60 Hz
Mains buffering time
typ. 20 ms (400 V AC)
typ. 20 ms (500 V AC)
Current consumption
3x 0.4 A (400 V AC)
3x 0.3 A (500 V AC)
2x 0.6 A (400 V AC)
2x 0.5 A (500 V AC)
Nominal power consumption
243.6 VA
Protective circuit
Transient surge protection; Varistor
Power factor (cos phi)
0.55
Typical response time
24 V DC, constant capacity restricted)
Nominal output current (IN)
5A
Dynamic Boost (IDyn.Boost)
7.5 A (5 s)
Derating
> 60 °C ... 70 °C (2.5%/K)
Protection against overvoltage at the output (OVP)
≤ 30 V DC
Control deviation
< 1 % (change in load, static 10 % ... 90 %)
< 3 % (Dynamic load change 10 % ... 90 %, 10 Hz)
< 0.1 % (change in input voltage ±10 %)
Residual ripple
≤ 20 mVPP
Short-circuit-proof
yes
May 19, 2022, 10:05 AM
Page 3 (14)
Power supply unit - EM-CPS-PS/3AC/24DC/5
1064922
https://www.phoenixcontact.com/in/products/1064922
No-load proof
yes
Output power
120 W
180 W
Maximum no-load power dissipation
< 1 W (400 V AC)
Power loss nominal load max.
< 12 W (480 V AC)
Rise time
≤ 120 ms (UOUT (10 % ... 90 %))
Connection in parallel
yes, for redundancy and increased capacity
Connection in series
yes
Signal: DC OK
Continuous load current
100 mA
Signal relay 13/14
Default
closed
Digital
30 V AC 30 V DC 100 mA
Connection data
Input
Connection method
Snap-on connection
Output
Connection method
Push-in connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
4 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Single conductor/terminal point, stranded, with ferrule, min.
0.2 mm²
Single conductor/terminal point, stranded, with ferrule, max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
12
Stripping length
10 mm
Signal
Connection method
Push-in connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
1.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
1.5 mm²
Single conductor/terminal point, stranded, with ferrule, min.
0.2 mm²
Single conductor/terminal point, stranded, with ferrule, max.
1.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
16
Stripping length
8 mm
LED signaling
May 19, 2022, 10:05 AM
Page 4 (14)
Power supply unit - EM-CPS-PS/3AC/24DC/5
1064922
https://www.phoenixcontact.com/in/products/1064922
Types of signaling
LED
Floating signal contact
Signal output: LED status indicator
Signalization designation
DC OK
Status display
LED
Color
green
Electrical properties
Number of phases
3.00
Insulation voltage input/output
3 kV AC (type test)
1.5 kV AC (routine test)
Product properties
Product type
Power supply
MTBF (IEC 61709, SN 29500)
> 2300000 h (25 °C)
> 1300000 h (40 °C)
> 620000 h (60 °C)
Insulation characteristics
Protection class
II (in closed control cabinet)
Degree of pollution
2
Dimensions
Width
36 mm
Height
160 mm
Depth
159 mm
Installation dimensions
Installation distance right/left
0 mm / 0 mm
Installation distance right/left (active)
14 mm / 14 mm
Installation distance top/bottom
50 mm / 50 mm
Installation distance top/bottom (active)
50 mm / 50 mm
Mounting
Mounting type
Cross Power System - installation
Assembly instructions
Cross Power System
Material specifications
Inflammability class in acc. with UL 94 (housing / terminal blocks)
V0
Type of housing
Polycarbonate
Hood version
Polycarbonate
Environmental and real-life conditions
Ambient conditions
Degree of protection
IP20
May 19, 2022, 10:05 AM
Page 5 (14)
Power supply unit - EM-CPS-PS/3AC/24DC/5
1064922
https://www.phoenixcontact.com/in/products/1064922
Ambient temperature (operation)
-25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Maximum altitude
≤ 4000 m (> 2000 m, Derating: 10 %/1000 m)
Climatic class
3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation)
≤ 95 % (at 25 °C, non-condensing)
Shock
18 ms, 30g, in each space direction (according to IEC 60068-227)
Vibration (operation)
10 ... 150 Hz, amplitude ±0.35 mm, 5g, 90 min. (in accordance
with IEC 60068-2-6)
2 Hz ... 15 Hz, amplitude ±1 mm, > 15 Hz, 0.7g (in accordance
with DNV GL Class A)
Standards and regulations
Standard – Electronic equipment for use in electrical power
installations and their assembly into electrical power installations
EN 50178/VDE 0160 (PELV)
Standard – Limitation of mains harmonic currents
EN 61000-3-2
Standard - Electrical safety
IEC 61010-1 (SELV)
Standard – Safety extra-low voltage
IEC 61010 (SELV) / (PELV)
Standard - Safe isolation
DIN VDE 0100-410
Standard - Safety of transformers
EN 61558-2-16 (air clearances and creepage distances only)
Overvoltage category
EN 61010-1
II
Approval data
UL approvals
UL Listed UL 61010-2-201
Conformity/Approvals
SIL in accordance with IEC 61508
0
EMC data
Low Voltage Directive
Conformance with Low Voltage Directive 2014/35/EC
Electromagnetic compatibility
Conformance with EMC Directive 2014/30/EU
EMC requirements for noise immunity
EN 61000-6-2
Conducted noise emission
EN 55016
EN 61000-6-4 (Class A)
Interference emission
Noise emission according to EN 61000-6-2 (industrial)
Noise emission
EN 55011 (EN 55022)
Noise emission
EN 55016
EN 61000-6-4 (Class A)
Noise immunity
Immunity according to EN 61000-6-2 (industrial)
Harmonic currents
Frequency range
Class A, B
Flicker
Frequency range
0 kHz ... 2 kHz
May 19, 2022, 10:05 AM
Page 6 (14)
Power supply unit - EM-CPS-PS/3AC/24DC/5
1064922
https://www.phoenixcontact.com/in/products/1064922
Electrostatic discharge
Standards/regulations
EN 61000-4-2
Electrostatic discharge
Contact discharge
6 kV (Test Level 4)
Discharge in air
8 kV (Test Level 4)
Comments
Criterion A
Electromagnetic HF field
Standards/regulations
EN 61000-4-3
Electromagnetic HF field
Frequency range
80 MHz ... 6 GHz
Test field strength
10 V/m (Test Level 3)
Comments
Criterion A
Fast transients (burst)
Standards/regulations
EN 61000-4-4
Fast transients (burst)
Input
4 kV (Test Level 4 - asymmetrical)
Output
2 kV (Test Level 3 - asymmetrical)
Signal
1 kV (Test Level 2 - asymmetrical)
Comments
Criterion A
Surge voltage load (surge)
Input
3 kV (Test Level 3 - symmetrical)
6 kV (Test Level 4 - asymmetrical)
Output
1 kV (Test Level 2 - symmetrical)
2 kV (Test Level 1 - asymmetrical)
Signal
1 kV (Test Level 1 - symmetrical)
Comments
Criterion B
Conducted interference
Standards/regulations
EN 61000-6-2
Voltage dips
Standards/regulations
EN 61000-4-11
Voltage
230 V AC
Frequency
50 Hz
Voltage dip
70 %
Number of periods
25 periods
Additional text
Test Level 2
Comments
Criterion A
Voltage dip
40 %
Number of periods
10 periods
Additional text
Test Level 2
May 19, 2022, 10:05 AM
Page 7 (14)
Power supply unit - EM-CPS-PS/3AC/24DC/5
1064922
https://www.phoenixcontact.com/in/products/1064922
Comments
Criterion A
Voltage dip
0%
Number of periods
1 period
Additional text
Test Level 2
Comments
Criterion A
Criterion A
Normal operating behavior within the specified limits.
Criterion B
Temporary impairment to operational behavior that is corrected
by the device itself.
May 19, 2022, 10:05 AM
Page 8 (14)
Power supply unit - EM-CPS-PS/3AC/24DC/5
1064922
https://www.phoenixcontact.com/in/products/1064922
Drawings
Block diagram
L1
L2
L3
1.1
TRIO CROSS POWER
2.1
1.2
2.2
1.3
2.3
2.4
2.5
3.1
3.2
+
+
-
13
14
May 19, 2022, 10:05 AM
Page 9 (14)
Power supply unit - EM-CPS-PS/3AC/24DC/5
1064922
https://www.phoenixcontact.com/in/products/1064922
Approvals
UL Listed
cUL Listed
EAC
Approval ID: FILE E 123528
Approval ID: FILE E 123528
Approval ID: RU S-DE.BL08.W.00764
cULus Listed
May 19, 2022, 10:05 AM
Page 10 (14)
Power supply unit - EM-CPS-PS/3AC/24DC/5
1064922
https://www.phoenixcontact.com/in/products/1064922
Classifications
ECLASS
ECLASS-9.0
27040701
ECLASS-10.0.1
27040701
ECLASS-11.0
27040701
ETIM
ETIM 8.0
EC002540
UNSPSC
UNSPSC 21.0
May 19, 2022, 10:05 AM
Page 11 (14)
Power supply unit - EM-CPS-PS/3AC/24DC/5
1064922
https://www.phoenixcontact.com/in/products/1064922
Environmental Product Compliance
REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 25;
For information on hazardous substances, refer to the
manufacturer’s declaration available under “Downloads”
May 19, 2022, 10:05 AM
Page 12 (14)
Power supply unit - EM-CPS-PS/3AC/24DC/5
1064922
https://www.phoenixcontact.com/in/products/1064922
Accessories
Connection module
Connection module - EM-CPS-TB3/63A - 1002633
https://www.phoenixcontact.com/in/products/1002633
Connection module with integrated spring-loaded terminals for cables from 1.5 to
16 mm2, 3-pos., maximum 63 A
Power distribution board
Power distribution board - EM-CPS-225 - 1002634
https://www.phoenixcontact.com/in/products/1002634
Modular power distribution board with CrossLink® interface, 125 A, 3-pos., touchproof and protection against polarity reversal, width: 225 mm
May 19, 2022, 10:05 AM
Page 13 (14)
Power supply unit - EM-CPS-PS/3AC/24DC/5
1064922
https://www.phoenixcontact.com/in/products/1064922
Power distribution board
Power distribution board - EM-CPS-405 - 1002635
https://www.phoenixcontact.com/in/products/1002635
Modular power distribution board with CrossLink® interface, 125 A, 3-pos., touchproof and protection against polarity reversal, width: 405 mm
Phoenix Contact 2022 © - all rights reserved
https://www.phoenixcontact.com
PHOENIX CONTACT (I) Pvt. Ltd.
A-58/2, Okhla Industrial Area, Phase - II, New Delhi-110 020
+91.1275.71420
info@phoenixcontact.co.in
May 19, 2022, 10:05 AM
Page 14 (14)