QUINT4-CAP/24DC/20/16KJ/USB
Capacity module
Data sheet
108979_en_01
1
© PHOENIX CONTACT 2021-09-06
Description
The QUINT capacity module combines an electronic switchover unit and energy storage in the same housing. The
capacity module stores the energy required to bridge mains
failures in maintenance-free double-layer capacitors. Long
mains buffering is possible depending on the required load
current.
– Maximum energy efficiency
– High level of system availability due to high capacitor
service life
– Large temperature range
– Electronic switchover unit and energy storage device in
one housing
– Communication interface for connection to
superordinate controllers
– Static boost for starting difficult loads
– Integrated “soft start” for limiting the inrush current and
prevent power supply unit overload
– Decoupled input enables improved control of the CAP
module, plus needs-based energy storage connection
and disconnection
– Comprehensive signaling with visual LEDs
– PC shutdown with USB interface
– Buffer time increase through parallel connectivity
– Reliability and safety with integrated safety functions
Technical data (short form)
Nominal input voltage
24 V DC ( SELV )
Current consumption (INo-Load /
ICharge / IMax)
0.1 A / 10 A / 30 A
Input voltage range
22.5 V DC ... 30 V DC
Activation threshold
Undervoltage
Overvoltage
< 22 V DC
> 30 V DC
Charging time ( for completely discharged capacitors )
approx. 6.3 min. (2.5 A) /
approx. 2.1 min. (10 A)
Buffer time
Recharging time
Nominal output voltage (UN)
4 min. (2.5 A) / 30 s (20 A)
approx. 5.4 min. (2.5 A) /
approx. 1.4 min. (10 A)
24 V DC
Nominal output current IN / IStat. Boost 20 A / 25 A
Efficiency ( with charged energy
storage device )
> 98 %
Dimensions W/H/D
244 mm / 130 mm / 125 mm
Ambient temperature (operation)
Weight
Order designation
QUINT4-CAP/24DC/20/16KJ/USB
QUINT4-CAP/24DC/20/16KJ/PN
QUINT4-CAP/24DC/20/16KJ/EIP
QUINT4-CAP/24DC/20/16KJ/EC
-25 °C ... 60 °C ( > 40 °C Derating:
1 %/K )
2.86 kg
USB (Modbus/RTU)
PROFINET
EtherNet/IP (Modbus/TCP)
EtherCAT
All technical specifications are nominal and refer to a room temperature of 25 °C and 70% relative humidity at
2000 m above sea level.
QUINT4-CAP/24DC/20/16KJ/USB
2
Table of contents
1
Description ..................................................................................................................................1
3
Ordering data ..............................................................................................................................4
2
4
5
Table of contents......................................................................................................................... 2
Technical data............................................................................................................................. 5
Safety regulations and installation notes ................................................................................... 14
5.1
5.2
Symbols used ...............................................................................................................................................14
Safety and warning notes .............................................................................................................................14
6.1
6.2
6.3
6.4
Rating plate ..................................................................................................................................................16
Function elements ........................................................................................................................................16
Device dimensions and keep-out areas........................................................................................................17
Block diagram...............................................................................................................................................17
7.1
7.2
7.3
7.4
7.5
Convection ...................................................................................................................................................18
Normal mounting position .............................................................................................................................18
Mounting the capacity module ......................................................................................................................18
Removing the capacity module.....................................................................................................................19
Wall mounting...............................................................................................................................................19
8.1
8.2
Electrical installation design..........................................................................................................................20
Connection parameters ................................................................................................................................20
9.1
9.2
9.3
9.4
DC input connection terminal blocks.............................................................................................................21
DC output connection terminal blocks ..........................................................................................................21
Connection terminal block signaling .............................................................................................................21
Securing the connection wiring.....................................................................................................................21
10.1
10.2
Communication via the USB interface ..........................................................................................................23
Communication via the RJ45 interface .........................................................................................................25
11.1
11.2
11.3
11.4
11.5
11.6
Functions in buffer mode ..............................................................................................................................27
Setting the buffer time...................................................................................................................................27
Remote.........................................................................................................................................................29
Switch-on delay ............................................................................................................................................30
Setting charging mode..................................................................................................................................31
Bypass function ............................................................................................................................................31
6
Design ....................................................................................................................................... 16
7
Mounting and removing............................................................................................................. 18
8
Device connection..................................................................................................................... 20
9
Device connection terminal blocks ............................................................................................ 20
10 Communication interface........................................................................................................... 22
11 Device operation ..................................................................................................................................................27
108979_en_01
PHOENIX CONTACT
2/40
QUINT4-CAP/24DC/20/16KJ/USB
12 Signaling ................................................................................................................................... 31
12.1
12.2
12.3
12.4
12.5
12.6
Connection terminal block signaling .............................................................................................................31
LED indicators ..............................................................................................................................................32
Signaling in operation ...................................................................................................................................33
Signaling the bypass function .......................................................................................................................34
Signal outputs ...............................................................................................................................................34
Signal inputs .................................................................................................................................................34
13.1
13.2
Switch-on behavior .......................................................................................................................................35
Switching behavior .......................................................................................................................................35
14.1
14.2
14.3
Ambient temperature ....................................................................................................................................36
Installation height..........................................................................................................................................36
Service life ....................................................................................................................................................36
13 Switch-on and switching behavior ............................................................................................. 35
14 Derating..................................................................................................................................... 36
15 Parallel operation ...................................................................................................................... 36
16 Safety functions......................................................................................................................... 37
16.1
16.2
16.3
16.4
16.5
16.6
Reverse polarity protection ...........................................................................................................................37
Line protection ..............................................................................................................................................37
Short-circuit protection..................................................................................................................................37
Overload protection ......................................................................................................................................37
Undervoltage and surge protection...............................................................................................................37
Protection against overtemperature..............................................................................................................37
17.1
17.2
Software installation......................................................................................................................................38
Software settings for signaling ......................................................................................................................38
18.1
18.2
Connecting an IPC (industrial PC) ................................................................................................................39
Connecting a controller.................................................................................................................................40
17 Software .................................................................................................................................... 38
18 Application examples ................................................................................................................ 39
108979_en_01
PHOENIX CONTACT
3/40
QUINT4-CAP/24DC/20/16KJ/USB
3
Ordering data
Description
Type
QUINT capacity module, with maintenance-free energy
storage based on double-layer capacitor, DIN rail
mounting, input: 24 V DC, output: 24 V DC / 20 A / 16 kJ
incl. mounted UTA 107 universal DIN rail adapter
QUINT4-CAP/24DC/20/16KJ/ 1076860
PN
1
QUINT4-CAP/24DC/20/16KJ/ 1076861
EIP
1
QUINT capacity module, with maintenance-free energy
storage based on double-layer capacitor, DIN rail
mounting, input: 24 V DC, output: 24 V DC / 20 A / 16 kJ
incl. mounted UTA 107 universal DIN rail adapter
QUINT4-CAP/24DC/20/16KJ/ 1076858
EC
1
Accessories
Type
Order No.
Pcs./Pkt.
2938235
1
2908217
1
1252232
1
QUINT capacity module, with maintenance-free energy
storage based on double-layer capacitor, DIN rail
mounting, input: 24 V DC, output: 24 V DC / 20 A / 16 kJ
incl. mounted UTA 107 universal DIN rail adapter
QUINT capacity module, with maintenance-free energy
storage based on double-layer capacitor, DIN rail
mounting, input: 24 V DC, output: 24 V DC / 20 A / 16 kJ
incl. mounted UTA 107 universal DIN rail adapter
2-piece universal wall adapter for securely mounting the
device in the event of strong vibrations. The profiles that
are screwed onto the side of the device are screwed
directly onto the mounting surface. The universal wall
adapter is attached on the left/right.
QUINT4-CAP/24DC/20/16KJ/ 1065635
USB
UWA 130
Universal wall adapter for securely mounting the device in UWA 182/52
the event of strong vibrations. The device is screwed
directly onto the mounting surface. The universal wall
adapter is attached on the top/bottom.
Used for communication between an industrial PC and
Phoenix Contact devices with USB-Mini-B connection.
Configuration and management software
Order No.
MINI-SCREW-USBDATACABLE
POWER MANAGEMENT
SUITE
2901664
Pcs./Pkt.
1
1
Our range of accessories is being continually extended, our current range can be found in the download area.
108979_en_01
PHOENIX CONTACT
4/40
QUINT4-CAP/24DC/20/16KJ/USB
4
Technical data
Unless otherwise specified, the technical data applies to all QUINT4-CAP/20/16KJ capacity modules with
-/USB, -/PN, -/EIP, and -/EC communication interfaces.
Input data
Nominal input voltage
24 V DC (SELV)
Dielectric strength
max. 35 V DC (Reverse polarity protection)
Input voltage range
Activation threshold
Undervoltage
Overvoltage
Voltage drop, input/output
Buffer time
Charging time ( for completely discharged capacitors )
Recharging time
Current consumption
IN (UN, IOut = IN, ICharge = 0)
INo-Load (UN, IOut = 0, ICharge = 0)
ICharge (UN, IOut = 0, ICharge = max)
IMax (UN, IOut = IStat.Boost, ICharge = max)
22.5 V DC ... 30 V DC
< 22 V DC
> 30 V DC
0.5 V DC
4 min. (2.5 A) / 30 s (20 A)
approx. 6.3 min. (2.5 A) / approx. 2.1 min. (10 A)
approx. 5.4 min. (2.5 A) / approx. 1.4 min. (10 A)
20 A
0.1 A
10 A
30 A
Power consumption
PN (UN, IOut = IN, ICharge = 0)
PNo-Load (UN, IOut = 0, ICharge = 0)
PCharge (UN, IOut = 0, ICharge = max)
PMax (UN, IOut = Istat.Boost, ICharge = max)
488 W
4W
244 W
599 W
Internal input fuse
no
Inrush current
Switch-on time in buffer mode
Input connection data
≤ 7 A (≤ 4 ms)
1 ms
Connection method
Screw connection
Conductor cross section, flexible
0.2 mm² ... 4 mm²
Conductor cross section, rigid
Conductor cross section flexible, with ferrule with plastic
sleeve
0.2 mm² ... 6 mm²
0.25 mm² ... 4 mm²
Conductor cross section flexible, with ferrule without
plastic sleeve
0.25 mm² ... 4 mm²
2 conductors with same cross section, stranded
0.2 mm² ... 1.5 mm²
2 conductors with same cross section, solid
0.2 mm² ... 1.5 mm²
Two conductors with the same cross section, flexible, with 0.5 mm² ... 2.5 mm²
TWIN ferrule with plastic sleeve
Conductor cross section AWG
24 ... 10
Torque
0.5 Nm ... 0.6 Nm
Stripping length
108979_en_01
8 mm
PHOENIX CONTACT
5/40
QUINT4-CAP/24DC/20/16KJ/USB
Output data (mains operation)
Nominal output voltage UN
24 V DC
Output power
PN (UN, IOut = IN, ICharge = 0)
PStat.Boost (UN, IOut = IStat.Boost, ICharge = 0)
480 W
600 W
Nominal output current IN / IStat. Boost
Short-circuit-proof
No-load proof
Power dissipation (mains mode)
QUINT4-CAP/24DC/20/16KJ/USB
20 A / 25 A
yes (with input fuse)
yes
No load
(UN, IOut = 0, ICharge = 0)
3W
QUINT4-CAP/24DC/20/16KJ/PN
5W
QUINT4-CAP/24DC/20/16KJ/EIP
24 V DC
Output power
PN (UN, IOut = IN, ICharge = 0)
PStat.Boost (UN, IOut = IStat.Boost, ICharge = 0)
480 W
600 W
Nominal output current IN / IStat. Boost
5W
No-load proof
yes
Efficiency
with charged energy storage device
MTBF (IEC 61709, SN 29500)
QUINT4-CAP/24DC/20/16KJ/USB
yes
> 98 %
25 °C
60 °C
1191809 h
597144 h
1351036 h
903325 h
470143 h
1351036 h
QUINT4-CAP/24DC/20/16KJ/EC
1351036 h
108979_en_01
40 °C
1839057 h
QUINT4-CAP/24DC/20/16KJ/PN
QUINT4-CAP/24DC/20/16KJ/EIP
10 W
20 A / 25 A
Power dissipation
No load (UN, IOut = 0, ICharge = 0)
Short-circuit-proof
10 W
5W
Nominal output voltage UN
10 W
10 W
5W
QUINT4-CAP/24DC/20/16KJ/EC
Output data (buffer mode)
Nominal load
(UN, IOut = IN, ICharge = 0)
903325 h
903325 h
470143 h
470143 h
PHOENIX CONTACT
6/40
QUINT4-CAP/24DC/20/16KJ/USB
Output connection data
Connection method
Screw connection
Conductor cross section, flexible
0.2 mm² ... 4 mm²
Conductor cross section, rigid
Conductor cross section flexible, with ferrule with plastic
sleeve
0.2 mm² ... 6 mm²
0.25 mm² ... 4 mm²
Conductor cross section flexible, with ferrule without
plastic sleeve
0.25 mm² ... 4 mm²
2 conductors with same cross section, stranded
0.2 mm² ... 1.5 mm²
2 conductors with same cross section, solid
0.2 mm² ... 1.5 mm²
Two conductors with the same cross section, flexible, with 0.5 mm² ... 2.5 mm²
TWIN ferrule with plastic sleeve
Conductor cross section AWG
24 ... 10
Torque
0.5 Nm ... 0.6 Nm
Stripping length
Signal state UIn OK
Connection labeling
8 mm
3.1, 3.2
Channel
DO (digital output)
State (configurable)
UIn OK
Switch contact (floating 13/14)
Electronic relays (OptoMOS)
State condition (configurable)
UIn > 22,5 V DC, UIn 100% Boost
> 75%
POut
> 50%
DC OK
3.1
3.2
3.3
3.4
3.5
3.6
3.7
Alarm
Ready
UIn OK
Input AC 100-240V
DC 110-250V
N/- L/+
1.1 1.2 1.3
5
5.1
230 V AC
108979_en_01
PHOENIX CONTACT
39/40
QUINT4-CAP/24DC/20/16KJ/USB
18.2
Connecting a controller
The illustration shows a typical application of the capacity
module with a controller.
To monitor the capacity module, the signal outputs are
connected to the controller. The device status of the
capacity module is indicated at all times via the digital
signals by the UIn OK, Alarm, and Ready LED status
indicators.
Figure 42
Schematic diagram, communication via
controller
24 V DC
2.2
2.3
+
+
–
2.4
–
Ord.No.1065635
2.1
2.5
–
Output DC 24V 40A
UOut
Signal
29,5V
24V
13
14
Rem
SGnd
Out 1
Out 2
3.1
3.2
3.3
3.4
3.5
3.6
1.1 1.2
+
+
1.3 1.4
–
Input
DC 24V
QUINT CAP 16KJ
QUINT POWER Ord.No.2904603
24 V DC
–
2.1 2.2
+
–
DC 24V 20A
Signal
13
14
Alarm
Ready
Remote
Parallel Port
SGnd
UIn OK
> 100% Boost
> 75%
POut
> 50%
DC OK
3.1
3.2
3.3
3.4
3.5
3.6
3.7
Alarm
Ready
UIn OK
Input AC 100-240V
DC 110-250V
N/- L/+
1.1 1.2 1.3
5
5.1
230 V AC
108979_en_01
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany
phoenixcontact.com
40/40