QUINT4-PS/12-24DC/24DC/1.3/PT - DC/DC converter
1066716
https://www.phoenixcontact.com/us/products/1066716
Please be informed that the data shown in this PDF document is generated from our online catalog. Please find the complete data in the user
documentation. Our general terms of use for downloads are valid.
Primary-switched DC/DC converter, QUINT POWER, DIN rail mounting, input: 12 V DC - 24 V DC, output: 24 V DC / 1.3 A
Product description
In the power range of up to 100 W, QUINT POWER provides superior system availability in the smallest size. Preventative function monitoring and
exceptional power reserves are available for applications in the low-power range.
Your advantages
• Most powerful output side: easy system expansion, reliable heavy load startup and miniature circuit breaker tripping
• Most comprehensive signaling: preventive function monitoring reports critical operating states before errors occur
• Free selection between Push-in and screw connection
Commercial data
Item number
1066716
Packing unit
1 pc
Minimum order quantity
1 pc
Sales key
CM01
Product key
CMDI43
GTIN
4055626734262
Weight per piece (including packing)
221.866 g
Weight per piece (excluding packing)
169 g
Customs tariff number
85044095
Country of origin
CN
Jan 8, 2024, 9:27 AM
Page 1 (19)
QUINT4-PS/12-24DC/24DC/1.3/PT - DC/DC converter
1066716
https://www.phoenixcontact.com/us/products/1066716
Technical data
Input data
Nominal input voltage range
12 V DC ... 24 V DC
Input voltage range
12 V DC ... 24 V DC -25 % ... +33 % (SELV)
Wide-range input
yes
Electric strength, max.
35 V DC (60 s)
Inrush current
typ. 1.6 A
2
Inrush current integral (I t)
typ. 0.1 A2s
Inrush current limitation
typ. 1.6 A
Mains buffering time
typ. 19 ms (24 V DC)
Current consumption
typ. 3.75 A (12 V DC)
typ. 1.85 A (24 V DC)
Typical response time
700 ms (from SLEEP MODE)
Switch-on time
24 V DC, constant capacity)
Nominal output current (IN)
1.3 A
Static Boost (IStat.Boost)
1.625 A (≤ 40 °C)
Dynamic Boost (IDyn.Boost)
2.6 A (≤ 60 °C (4.9 s))
Short-circuit-proof
yes
No-load proof
yes
Derating
> 60 °C (2.5%/K of POut nom.)
Output power (PN)
30 W
Output power (PStat. Boost)
38 W
Output power (PDyn. Boost)
60 W
Feedback voltage resistance
≤ 35 V DC
Protection against overvoltage at the output (OVP)
< 32 V DC
Residual ripple
< 20 mVPP
Control deviation
< 1 % (change in load, static 10 % ... 90 %)
Control deviation
< 1 % (change in load, static 10 % ... 90 %)
Control deviation
< 1 % (change in load, static 10 % ... 90 %)
Rise time
< 1 s (UOUT (10 % ... 90 %))
Connection in series
yes
Maximum no-load power dissipation
< 1.3 W
Jan 8, 2024, 9:27 AM
Page 2 (19)
QUINT4-PS/12-24DC/24DC/1.3/PT - DC/DC converter
1066716
https://www.phoenixcontact.com/us/products/1066716
Power loss nominal load max.
0.9 x USet
Connection data
Input
Position
1.x
Conductor connection
Connection method
Push-in connection
rigid
0.5 mm² ... 2.5 mm²
flexible
0.5 mm² ... 2.5 mm²
flexible with ferrule without plastic sleeve
0.5 mm² ... 2.5 mm²
flexible with ferrule with plastic sleeve
0.25 mm² ... 2.5 mm²
rigid (AWG)
22 ... 14
Stripping length
10 mm
Output
Position
2.x
Conductor connection
Connection method
Push-in connection
rigid
0.2 mm² ... 2.5 mm²
flexible
0.25 mm² ... 2.5 mm²
flexible with ferrule without plastic sleeve
0.25 mm² ... 2.5 mm²
flexible with ferrule with plastic sleeve
0.25 mm² ... 2.5 mm²
rigid (AWG)
24 ... 14
Stripping length
10 mm
Signal
Position
3.x
Conductor connection
Connection method
Push-in connection
rigid
0.2 mm² ... 2.5 mm²
flexible
0.2 mm² ... 2.5 mm²
flexible with ferrule without plastic sleeve
0.25 mm² ... 2.5 mm²
flexible with ferrule with plastic sleeve
0.25 mm² ... 2.5 mm²
rigid (AWG)
24 ... 14
Jan 8, 2024, 9:27 AM
Page 3 (19)
QUINT4-PS/12-24DC/24DC/1.3/PT - DC/DC converter
1066716
https://www.phoenixcontact.com/us/products/1066716
Stripping length
10 mm
Signaling
LED signaling
Signal threshold
> PThr (LED lights up yellow, output power > PThr, depending on
the rotary selector switch setting)
> 0.9 x USet (LED lights up green)
< 0.9 x USet (LED flashes green)
Electrical properties
Number of phases
1.00
Insulation voltage input/output
2.6 kV DC (type test)
1.2 kV DC (routine test)
Switching frequency
130 kHz ... 130 kHz (Auxiliary converter stage)
70 kHz ... 250 kHz (Main converter stage)
Product properties
Product type
DC/DC converters
Product family
QUINT POWER
MTBF (IEC 61709, SN 29500)
> 1999348 h (25 °C)
> 1120490 h (40 °C)
> 471066 h (60 °C)
Insulation characteristics
Protection class
II
Degree of pollution
2
Life expectancy (electrolytic capacitors)
Current
0.65 A
Temperature
40 °C
Time
242000 h
Additional text
24 V DC
Life expectancy (electrolytic capacitors)
Current
1.3 A
Temperature
40 °C
Time
160000 h
Additional text
24 V DC
Life expectancy (electrolytic capacitors)
Current
1.3 A
Temperature
30 °C
Time
320000 h
Additional text
24 V DC
Dimensions
Jan 8, 2024, 9:27 AM
Page 4 (19)
QUINT4-PS/12-24DC/24DC/1.3/PT - DC/DC converter
1066716
https://www.phoenixcontact.com/us/products/1066716
Item dimensions
Width
22.5 mm
Height
106 mm
Depth
90 mm
Installation dimensions
Installation distance right/left (active)
15 mm / 15 mm (POut ≥50% )
Installation distance right/left (passive)
5 mm / 5 mm (POut ≥50% )
Installation distance right/left (active, passive)
0 mm / 0 mm (POut ≤50 %)
Installation distance top/bottom (active)
30 mm / 30 mm (POut ≥50% )
Installation distance top/bottom (passive)
30 mm / 30 mm (POut ≥50% )
Installation distance top/bottom (active, passive)
30 mm / 30 mm (POut ≤50 %)
Mounting
Mounting type
DIN rail mounting
Assembly instructions
alignable: PN ≥50%, 5 mm horizontally, 15 mm next to active
components, 50 mm vertically
alignable: PN 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Ambient temperature (start-up type tested)
-40 °C
Maximum altitude
≤ 5000 m (> 2000 m, observe derating)
Climatic class
3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation)
≤ 95 % (at 25 °C, non-condensing)
Shock
18 ms, 30g, in each space direction (according to IEC 60068-227)
Vibration (operation)
< 15 Hz, ±2.5 mm amplitude; 15 Hz ... 100 Hz: 2.3 g 90 Min. (in
accordance with IEC 60068-2-6)
Standards and regulations
Overvoltage category
EN 61010-1
II (≤ 5000 m)
Safety for measurement, control, and laboratory equipment
Jan 8, 2024, 9:27 AM
Page 5 (19)
QUINT4-PS/12-24DC/24DC/1.3/PT - DC/DC converter
1066716
https://www.phoenixcontact.com/us/products/1066716
Standard designation
Electrical safety (of control and regulation devices)
Standards/specifications
IEC 61010-1
Protective extra-low voltage
Standard designation
Protective extra-low voltage
Standards/specifications
IEC 61010-1 (SELV)
Mains voltage dips
Standard designation
Mains variation/undervoltage
Standards/specifications
EN 61000-4-29
Approvals
SIQ
CB-Scheme (IEC 61010-1, IEC 61010-2-201)
UL approvals
UL Listed UL 61010-1
UL Listed UL 61010-2-201
ANSI/UL 121201 Class I, Division 2, Groups A, B, C, D
(Hazardous Location)
UL
Identification
UL Listed UL 61010-1
UL
Identification
CAN/CSA C22.2 No. 61010-1-12
UL
Identification
UL Listed UL 61010-2-201
UL
Identification
CAN/CSA C22.2 No. 61010-2-201:18
UL
Identification
UL 121201 & CSA C22.2 No. 213-17 Class I, Division 2, Groups
A, B, C, D T4 (Hazardous Location)
CB scheme
Identification
IEC 61010-1
CB scheme
Identification
IEC 61010-2-201
Shipbuilding
Identification
DNV GL
EMC data
EMC requirements for noise emission
EN 61000-6-3
EN 61000-6-4
EMC requirements for noise immunity
EN 61000-6-1
EN 61000-6-2
Electromagnetic compatibility
Conformance with EMC Directive 2014/30/EU
Jan 8, 2024, 9:27 AM
Page 6 (19)
QUINT4-PS/12-24DC/24DC/1.3/PT - DC/DC converter
1066716
https://www.phoenixcontact.com/us/products/1066716
EMC requirements, power plant
EN 61850-3
EN 61000-6-5
Conducted noise emission
EN 55016
EN 61000-6-3 (Class B)
Noise emission
Additional basic standard EN 61000-6-5 (immunity in power
station), IEC/EN 61850-3 (energy supply)
Noise emission
EN 55016
EN 61000-6-3 (Class B)
DNV GL conducted interference
Class B
Additional text
Bridge and deck area
DNV GL noise radiation
Class B
Additional text
Bridge and deck area
Electrostatic discharge
Standards/regulations
EN 61000-4-2
Electrostatic discharge
Contact discharge
6 kV (Test Level 4)
Discharge in air
8 kV (Test Level 3)
Comments
Criterion A
Electromagnetic HF field
Standards/regulations
EN 61000-4-3
Electromagnetic HF field
Frequency range
80 MHz ... 1 GHz
Test field strength
20 V/m (Test Level 3)
Frequency range
1 GHz ... 6 GHz
Test field strength
10 V/m (Test Level 3)
Comments
Criterion A
Fast transients (burst)
Standards/regulations
EN 61000-4-4
Fast transients (burst)
Input
2 kV (Test Level 4 - asymmetrical)
Output
2 kV (Test Level 4 - asymmetrical)
Signal
2 kV (Test Level 4 - asymmetrical)
Comments
Criterion B
Surge voltage load (surge)
Standards/regulations
EN 61000-4-5
Input
1 kV (Test Level 4 - symmetrical)
2 kV (Test Level 4 - asymmetrical)
Output
1 kV (Test Level 3 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Signal
1 kV (Test Level 4 - symmetrical)
Jan 8, 2024, 9:27 AM
Page 7 (19)
QUINT4-PS/12-24DC/24DC/1.3/PT - DC/DC converter
1066716
https://www.phoenixcontact.com/us/products/1066716
2 kV (Test Level 4 - asymmetrical)
Comments
Criterion A
Conducted interference
Standards/regulations
EN 61000-4-6
Conducted interference
I/O/S
asymmetrical
Frequency range
0.15 MHz ... 80 MHz
Comments
Criterion A
Voltage
10 V (Test Level 3)
Power frequency magnetic field
Standards/regulations
EN 61000-4-8
Frequency
16.67 Hz
50 Hz
60 Hz
Test field strength
100 A/m
Additional text
60 s
Comments
Criterion A
Frequency
50 Hz
60 Hz
Frequency range
50 Hz ... 60 Hz
Test field strength
1 kA/m
Additional text
3s
Frequency
0 Hz
Test field strength
300 A/m
Additional text
DC, 60 s
Voltage dips
Standards/regulations
EN 61000-4-29
Voltage
24 V DC
Voltage dip
70 %
Number of periods
0.5 / 1 / 25 periods
Time
100 ms
Additional text
Test Level 2
Comments
Criterion A
Voltage dip
40 %
Number of periods
5 / 10 / 50 periods
Time
100 ms
Additional text
Test Level 2
Comments
Criterion A
Voltage dip
0%
Number of periods
0.5 / 1 / 5 / 50 periods
Time
50 ms
Additional text
Test Level 2
Jan 8, 2024, 9:27 AM
Page 8 (19)
QUINT4-PS/12-24DC/24DC/1.3/PT - DC/DC converter
1066716
https://www.phoenixcontact.com/us/products/1066716
Comments
Criterion B
Pulse-shape magnetic field
Standards/regulations
EN 61000-4-9
Test field strength
1000 A/m
Comments
Criterion A
Asymmetrical conducted disturbance variables
Standards/regulations
EN 61000-4-16
Test level 1
15 Hz 150 Hz (Test Level 3)
Voltage
10 V 1 V (Permanent)
Test level 2
150 Hz 1.5 kHz (Test Level 3)
Voltage
1V
Test level 3
1.5 kHz 15 kHz (Test Level 3)
Voltage
1 V 10 V
Test level 4
15 kHz 150 kHz (Test Level 3)
Voltage
10 V
Test level 5
16.7 Hz 50 Hz 60 Hz 150 Hz 180 Hz (Test Level 3)
Voltage
10 V (Permanent)
Test level 6
0 Hz 16.7 Hz 50 Hz 60 Hz (Test Level 3)
Voltage
100 V (1 s)
Comments
Criterion A
Alternating component of direct voltage
Standards/regulations
EN 61000-4-17
Alternating component
10 % (UN)
Frequency
50 Hz
100 Hz
150 Hz
300 Hz
Comments
Criterion A
Attenuated oscillating wave
Standards/regulations
EN 61000-4-18
Input, output (test level 1)
1 MHz (Test Level 2 - symmetrical)
Voltage
0.5 kV
Input, output (test level 2)
1 MHz (Test Level 2 - asymmetrical)
Voltage
1 kV
Signals (test level 1)
1 MHz (Test Level 2 - symmetrical)
Voltage
0.5 kV
Signals (test level 2)
1 MHz (Test Level 2 - asymmetrical)
Voltage
1 kV
Comments
Criterion A
Attenuated oscillating magnetic field
Standards/regulations
EN 61000-4-10
Jan 8, 2024, 9:27 AM
Page 9 (19)
QUINT4-PS/12-24DC/24DC/1.3/PT - DC/DC converter
1066716
https://www.phoenixcontact.com/us/products/1066716
Test field strength
100 A/m
Test level 1
100 kHz
Test field strength
100 A/m
Test level 2
1 MHz
Comments
Criterion A
Criteria
Criterion A
Normal operating behavior within the specified limits.
Criterion B
Temporary impairment to operational behavior that is corrected
by the device itself.
Criterion C
Temporary adverse effects on the operating behavior, which the
device corrects automatically or which can be restored by
actuating the operating elements.
Jan 8, 2024, 9:27 AM
Page 10 (19)
QUINT4-PS/12-24DC/24DC/1.3/PT - DC/DC converter
1066716
https://www.phoenixcontact.com/us/products/1066716
Drawings
IIn [A]
Diagram
4,0
3,5
3,0
2,5
2,0
1,5
1,0
0,5
0,0
0,00 0,25
2
1
1 = U : 12 V DC/U : 24 V DC
In
Out
2 = UIn: 24 V DC/UOut: 24 V DC
0,50 0,75
1,00 1,25
1,50 1,75 2,00
IOut [A]
Eta [%]
Diagram
100
90
80
70
2
60
50
40
30
20
10
0
0,00 0,25 0,50
1
1 = UIn: 12 V DC/UOut: 24 V DC
2 = UIn: 24 V DC/UOut: 24 V DC
0,75 1,00
1,25 1,50 1,75 2,00
IOut [A]
Jan 8, 2024, 9:27 AM
Page 11 (19)
QUINT4-PS/12-24DC/24DC/1.3/PT - DC/DC converter
1066716
https://www.phoenixcontact.com/us/products/1066716
Dimensional drawing
3.1 2.1 2.2
SIG
Output DC
+ −
UOut
Signal (SIG)
POut > PThr
Boost > 100%
> 75%
> 50%
106
QUINT POWER Ord.No.xxxxxxx
53
22,5
DC OK
Input DC
+ −
1.1 1.2
Jan 8, 2024, 9:27 AM
Page 12 (19)
QUINT4-PS/12-24DC/24DC/1.3/PT - DC/DC converter
1066716
https://www.phoenixcontact.com/us/products/1066716
Schematic diagram
Housing
(+)
L
N
(-)
Input
Signaling
A
A
Output
+
Jan 8, 2024, 9:27 AM
Page 13 (19)
QUINT4-PS/12-24DC/24DC/1.3/PT - DC/DC converter
1066716
https://www.phoenixcontact.com/us/products/1066716
Block diagram
+
-
1.1
2.1
1.2
2.2
3.1
OVP
+
SIG
SIG
C
Jan 8, 2024, 9:27 AM
Page 14 (19)
QUINT4-PS/12-24DC/24DC/1.3/PT - DC/DC converter
1066716
https://www.phoenixcontact.com/us/products/1066716
Approvals
To download certificates, visit the product detail page: https://www.phoenixcontact.com/us/products/1066716
IECEE CB Scheme
IECEE CB Scheme
Approval ID: DK-97404-UL
Approval ID: DE/PTZ/0122
cULus Listed
Approval ID: FILE E 123528
DNV
Approval ID: TAA00000BV
cULus Listed
Approval ID: FILE E 199827
Jan 8, 2024, 9:27 AM
Page 15 (19)
QUINT4-PS/12-24DC/24DC/1.3/PT - DC/DC converter
1066716
https://www.phoenixcontact.com/us/products/1066716
Classifications
ECLASS
ECLASS-11.0
27040701
ECLASS-12.0
27040701
ECLASS-13.0
27040701
ETIM
ETIM 9.0
EC002540
UNSPSC
UNSPSC 21.0
39121000
Jan 8, 2024, 9:27 AM
Page 16 (19)
QUINT4-PS/12-24DC/24DC/1.3/PT - DC/DC converter
1066716
https://www.phoenixcontact.com/us/products/1066716
Environmental product compliance
REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 25;
For information on hazardous substances, refer to the
manufacturer’s declaration available under “Downloads”
Jan 8, 2024, 9:27 AM
Page 17 (19)
QUINT4-PS/12-24DC/24DC/1.3/PT - DC/DC converter
1066716
https://www.phoenixcontact.com/us/products/1066716
Accessories
SF-SL 0,4X2,0-60 - Screwdriver
1212546
https://www.phoenixcontact.com/us/products/1212546
Screwdriver, flat bladed, size: 0.4 x 2.0 x 60 mm, 2-component grip, with non-slip
grip
CBMC E4 24DC/1-10A NO - Electronic circuit breaker
2906032
https://www.phoenixcontact.com/us/products/2906032
Multi-channel electronic circuit
breaker for protecting four loads at 24
V DC in the event of overload and
short circuit. With electronic locking of
the set nominal currents. For
installation on DIN rails.
CBMC E4 24DC/1-4A NO - Electronic circuit breaker
2906031
https://www.phoenixcontact.com/us/products/2906031
Multi-channel electronic circuit
breaker for protecting four loads at 24
V DC in the event of overload and
short circuit. With electronic locking of
the set nominal currents. For
installation on DIN rails.
Jan 8, 2024, 9:27 AM
Page 18 (19)
QUINT4-PS/12-24DC/24DC/1.3/PT - DC/DC converter
1066716
https://www.phoenixcontact.com/us/products/1066716
CBMC E4 24DC/1-4A NO-C - Electronic circuit breaker
2908713
https://www.phoenixcontact.com/us/products/2908713
Multi-channel electronic circuit
breaker that can be preconfigured, for
protecting four loads at 24 V DC in the
event of overload and short circuit.
With electronic locking of the set
nominal currents. For installation on
DIN rails.
PLT-SEC-T3-24-FM-UT - Type 3 surge protection device
2907916
https://www.phoenixcontact.com/us/products/2907916
Type 3 surge protection, consisting of
protective plug and base element,
with integrated status indicator and
remote signaling for single-phase
power supply networks. Nominal
voltage: 24 V AC/DC
Phoenix Contact 2024 © - all rights reserved
https://www.phoenixcontact.com
Phoenix Contact USA
586 Fulling Mill Road
Middletown, PA 17057, United States
(+717) 944-1300
info@phoenixcon.com
Jan 8, 2024, 9:27 AM
Page 19 (19)