https://www.phoenixcontact.com/us/products/1076188
Power supply unit - TRIO-PS-2G/3AC/72DC/14 - 1076188
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Primary-switched TRIO power supply for DIN rail mounting, input: 3-phase, output: 72 V DC/14 A, dynamic boost,
tool-free fast connection technology for rigid and flexible conductors with ferrule
Product Description
TRIO POWER power supplies with standard functionality
The TRIO POWER power supply range with push-in connection has been perfected for use in machine building. All functions and the space-saving
design of the single and three-phase modules are optimally tailored to the stringent requirements. Under challenging ambient conditions, the power
supply units, which feature an extremely robust electrical and mechanical design, ensure the reliable supply of all loads.
Key Commercial Data
Packing unit
1 pc
GTIN
GTIN
4055626783918
Weight per Piece (excluding packing)
3,060.000 g
Custom tariff number
85044030
Country of origin
China
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width
110 mm
Height
130 mm
Depth
160 mm
Installation distance right/left
0 mm / 0 mm
04/22/2021 Page 1 / 7
https://www.phoenixcontact.com/us/products/1076188
Power supply unit - TRIO-PS-2G/3AC/72DC/14 - 1076188
Technical data
Dimensions
Installation distance top/bottom
50 mm / 50 mm
Ambient conditions
Degree of protection
IP20
Inflammability class in acc. with UL 94 (housing / terminal blocks)
V0
Ambient temperature (operation)
-25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
Ambient temperature (start-up type tested)
-40 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Max. permissible relative humidity (operation)
≤ 95 % (at 25 °C, non-condensing)
Climatic class
3K3 (in acc. with EN 60721)
Degree of pollution
2
Installation height
≤ 4000 m (> 2000 m, Derating: 10 %/1000 m)
Input data
Nominal input voltage range
3x 400 V AC ... 500 V AC
Input voltage range
3x 400 V AC ... 500 V AC -20 % ....+15 %
AC frequency range
50 Hz ... 60 Hz
Frequency range (fN)
50 Hz ... 60 Hz ±5 Hz
Discharge current to PE
< 3.5 mA
Current consumption
3x 1.9 A (400 V AC)
3x 1.7 A (500 V AC)
Nominal power consumption
1335.1 VA
Inrush current
≤ 30 A (typical)
Mains buffering time
> 10 ms (400 V AC)
> 20 ms (480 V AC)
Input fuse
6.3 A (internal (device protection))
Recommended breaker for input protection
10 A ... 16 A (Characteristics B, C, D, K)
Power factor (cos phi)
0.77
Type of protection
Transient surge protection
Protective circuit/component
Varistor
Output data
Nominal output voltage
72 V DC ±1 %
Setting range of the output voltage (USet)
70 V DC ... 85 V DC (> 72 V DC, constant capacity restricted)
Nominal output current (IN)
14 A
Dynamic Boost (IDyn.Boost)
21 A (5 s)
Derating
> 60 °C ... 70 °C (2.5%/K)
Connection in parallel
yes
Connection in series
yes
04/22/2021 Page 2 / 7
https://www.phoenixcontact.com/us/products/1076188
Power supply unit - TRIO-PS-2G/3AC/72DC/14 - 1076188
Technical data
Output data
Feedback voltage resistance
< 105 V DC
Protection against overvoltage at the output (OVP)
≤ 105 V DC
Control deviation
< 1 % (change in load, static 10 % ... 90 %)
< 3 % (Dynamic load change 10 % ... 90 %, 10 Hz)
< 0.1 % (change in input voltage ±10 %)
Residual ripple
≤ 300 mVPP
Output power
1008 W
Typical response time
94.6 % (400 V AC)
> 94.3 % (480 V AC)
MTBF (IEC 61709, SN 29500)
> 1730000 h (25 °C)
> 1051000 h (40 °C)
> 510000 h (60 °C)
Insulation voltage input/output
3 kV AC (type test)
1.5 kV AC (routine test)
Degree of protection
IP20
Protection class
I (in closed control cabinet)
Inflammability class in acc. with UL 94 (housing / terminal blocks)
V0
Mounting position
horizontal DIN rail NS 35, EN 60715
Assembly instructions
alignable: horizontally 0 mm (≤ 40 °C) 10 mm (≤ 70 °C), vertically 50 mm
Connection data, input
Connection method
Push-in connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
4 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
4 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
12
Stripping length
10 mm
Connection data, output
Connection method
Push-in connection
04/22/2021 Page 3 / 7
https://www.phoenixcontact.com/us/products/1076188
Power supply unit - TRIO-PS-2G/3AC/72DC/14 - 1076188
Technical data
Connection data, output
Conductor cross section solid min.
0.75 mm²
Conductor cross section solid max.
16 mm²
Conductor cross section flexible min.
0.75 mm²
Conductor cross section flexible max.
16 mm²
Conductor cross section AWG min.
20
Conductor cross section AWG max.
4
Stripping length
18 mm
Connection data for signaling
Connection method
Push-in connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
0.75 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
1.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
18
Stripping length
8 mm
Standards
EMC requirements for noise immunity
EN 61000-6-1
EN 61000-6-2
Standard - Safety of transformers
EN 61558-2-16 (air clearances and creepage distances only)
Standard - Electrical safety
IEC 61010-2-201
Standard - Safe isolation
DIN VDE 0100-410
Standard – Limitation of mains harmonic currents
EN 61000-3-2
Conformance/approvals
UL approvals
UL/C-UL Listed UL 61010-1
EMC data
Electromagnetic compatibility
Conformance with EMC Directive 2014/30/EU
Low Voltage Directive
Conformance with Low Voltage Directive 2014/35/EC
Conducted noise emission
EN 55016-2-1
EN 61000-6-4 (Class A)
Noise emission
EN 55016-2-3
EN 61000-6-4 (Class A)
Harmonic currents
EN 55016-2-3
EN 61000-3-2 (Class A)
Flicker
EN 61000-3-3
04/22/2021 Page 4 / 7
https://www.phoenixcontact.com/us/products/1076188
Power supply unit - TRIO-PS-2G/3AC/72DC/14 - 1076188
Technical data
EMC data
EN 61000-3-3
Electrostatic discharge
EN 61000-4-2
Contact discharge
6 kV (Test Level 3)
Discharge in air
8 kV (Test Level 3)
Electromagnetic HF field
EN 61000-4-3
Frequency range
80 MHz ... 1 GHz
Test field strength
10 V/m (Test Level 3)
Frequency range
1 GHz ... 2 GHz
Test field strength
10 V/m (Test Level 3)
Frequency range
2 GHz ... 6 GHz
Test field strength
10 V/m (Test Level 3)
Comments
Criterion A
Fast transients (burst)
EN 61000-4-4
Input
4 kV (Test Level 3 - asymmetrical)
Output
2 kV (Test Level 3 - asymmetrical)
Signal
2 kV (Test Level 3 - asymmetrical)
Comments
Criterion A
Surge voltage load (surge)
EN 61000-4-5
Input
2 kV (Test Level 4 - symmetrical)
4 kV (Test Level 4 - asymmetrical)
Output
1 kV (Test Level 3 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Signal
1 kV (Test Level 2 - asymmetrical)
Comments
Criterion A
Conducted interference
EN 61000-4-6
Frequency range
0.15 MHz ... 80 MHz
Voltage
10 V (Test Level 3)
Comments
Criterion A
Voltage dips
EN 61000-4-11
Voltage
400 V AC
Frequency
50 Hz
Voltage dip
70 %
Number of periods
25 periods
Comments
Criterion A
Voltage dip
40 %
Number of periods
10 periods
Comments
Criterion A
04/22/2021 Page 5 / 7
https://www.phoenixcontact.com/us/products/1076188
Power supply unit - TRIO-PS-2G/3AC/72DC/14 - 1076188
Technical data
EMC data
Voltage dip
0%
Number of periods
1 period
Comments
Criterion A
Criterion A
Normal operating behavior within the specified limits.
Criterion B
Temporary impairment to operational behavior that is corrected by the
device itself.
Criterion C
Temporary adverse effects on the operating behavior, which the device
corrects automatically or which can be restored by actuating the operating
elements.
Environmental Product Compliance
REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 25;
For details about hazardous substances go to tab “Downloads”, Category
“Manufacturer's declaration”
Drawings
Block diagram
L1
L2
L3
Diagram
Output DC
1.1
2.1
1.2
2.2
1.3
2.3
2.4
1.4
2.5
3.1
3.2
+
POut [%]
Input 3AC
+
13
14
200
175
150
125
100
75
50
25
0
"
! = PN 100 % # 60 °C
" = PDyn. 150 % # 60 °C
0
1000
2000
!
3000
4000
5000
H [m]
Classifications
eCl@ss
eCl@ss 10.0.1
27040701
eCl@ss 11.0
27040701
eCl@ss 9.0
27040701
Approvals
Approvals
Approvals
UL Listed / cUL Listed / cULus Listed
04/22/2021 Page 6 / 7
https://www.phoenixcontact.com/us/products/1076188
Power supply unit - TRIO-PS-2G/3AC/72DC/14 - 1076188
Approvals
Ex Approvals
Approval details
UL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 123528
cUL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 123528
cULus Listed
Phoenix Contact 2021 © - all rights reserved
http://www.phoenixcontact.com
04/22/2021 Page 7 / 7
很抱歉,暂时无法提供与“1076188”相匹配的价格&库存,您可以联系我们找货
免费人工找货