Power supply unit - UNO2-PS/1AC/48DC/240W
1110155
https://www.phoenixcontact.com/in/products/1110155
Please be informed that the data shown in this PDF document is generated from our Online Catalog. Please find the complete data in the user
documentation. Our General Terms of Use for Downloads are valid.
Primary-switched power supply unit, UNO POWER, Screw connection, DIN rail mounting,
input: 1-phase, output: 48 V DC / 5 A
Your advantages
• Save space in the control cabinet with an extremely narrow overall width of just 45 mm
• Save energy, thanks to a high degree of efficiency
• Outdoor installation possible, with a wide temperature range of -25°C … +70°C
• Simple output voltage monitoring, thanks to the floating DC OK relay contact
May 19, 2022, 10:06 AM
Page 1 (16)
Power supply unit - UNO2-PS/1AC/48DC/240W
1110155
https://www.phoenixcontact.com/in/products/1110155
Commercial Data
Item number
1110155
Packing unit
1 pc
Minimum order quantity
1 pc
Product Key
CMPV14
GTIN
4063151024840
Weight per Piece (including packing)
857 g
Weight per Piece (excluding packing)
855 g
Customs tariff number
85044030
Country of origin
TH
May 19, 2022, 10:06 AM
Page 2 (16)
Power supply unit - UNO2-PS/1AC/48DC/240W
1110155
https://www.phoenixcontact.com/in/products/1110155
Technical Data
Input data
Supply system configuration
Star network (TN, TT, IT (PE))
Nominal input voltage range
100 V AC ... 240 V AC
Input voltage range
100 V AC ... 240 V AC -15 % ... +10 %
Derating
< 90 V AC (1 %/V)
Typical national grid voltage
120 V AC
230 V AC
Voltage type of supply voltage
AC
Inrush current
10 A
Inrush current integral (I2t)
< 0.05 A2s
Inrush current limitation
< 20 A (at 25 °C)
Frequency range (fN)
50 Hz ... 60 Hz ±10 %
Mains buffering time
typ. 20 ms (120 V AC)
typ. 20 ms (230 V AC)
Current consumption
2.6 A (100 V AC)
2.2 A (120 V AC)
1.16 A (230 V AC)
1.2 A (240 V AC)
Protective circuit
Transient surge protection; Varistor, gas-filled surge arrester
Switch-on time
typ. 530 ms
Device mains fuse
5 A internal (device protection), fast-blow
Recommended breaker for input protection
10 A ... 16 A (Characteristic B, C, D, K or comparable)
Discharge current to PE
< 3.5 mA
Output data
Efficiency
typ. 91.5 % (120 V AC)
typ. 93 % (230 V AC)
Nominal output voltage
48 V DC
Setting range of the output voltage (USet)
42 V DC ... 56 V DC (≥48 V DC, constant capacity
restricted 550000 h (40 °C)
> 280000 h (55 °C)
Environmental protection directive
RoHS Directive 2011/65/EU
WEEE
Reach
Insulation characteristics
Protection class
I
Degree of pollution
2
May 19, 2022, 10:06 AM
Page 5 (16)
Power supply unit - UNO2-PS/1AC/48DC/240W
1110155
https://www.phoenixcontact.com/in/products/1110155
Dimensions
Dimensional drawing
Width
45 mm
Height
130 mm
Depth
125 mm (Device depth (DIN rail mounting))
Depth
129 mm
Installation dimensions
Installation distance right/left (active, passive)
0 mm / 0 mm (POut ≥50% )
Installation distance top/bottom (active, passive)
30 mm / 30 mm (POut ≥50% )
Mounting
Mounting type
DIN rail mounting
Assembly instructions
alignable: 0 mm horizontally, 30 mm vertically
Mounting position
horizontal DIN rail NS 35, EN 60715
With protective coating
No
Material specifications
Flammability rating according to UL 94
V0 (Housing, terminal blocks)
Housing material
Metal
Hood version
Stainless steel
Side element version
Aluminum
Foot latch material
Sheet steel, zinc-plated
Housing material
Aluminum (AlMg3) / sheet steel, zinc-plated
Environmental and real-life conditions
Ambient conditions
Degree of protection
IP20
Ambient temperature (operation)
-25 °C ... 70 °C (> 55 °C Derating: 2.5 %/K)
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Ambient temperature (start-up type tested)
-40 °C
Maximum altitude
≤ 3000 m (> 2000 m, Derating: 10 %/1000 m)
Climatic class
3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation)
≤ 95 % (at 25 °C, non-condensing)
Shock (operation)
18 ms, 30g, per spatial direction (IEC 60068-2-27)
Vibration (operation)
10 Hz ... 50 Hz, amplitude ±0.2 mm
May 19, 2022, 10:06 AM
Page 6 (16)
Power supply unit - UNO2-PS/1AC/48DC/240W
1110155
https://www.phoenixcontact.com/in/products/1110155
50 Hz to 150 Hz, 2.3 g, 90 min.
Standards and regulations
Overvoltage category
EN 61010-1
II (≤ 3000 m)
Overvoltage category
EN 62477-1
III (≤3000 m)
Safety of power supply units up to 1100 V (insulation distances)
Standards/specifications
DIN EN 61558-2-16
Electrical safety
Standards/specifications
IEC 61010-2-201 (SELV)
Electronic equipment for use in power installations
Standards/specifications
EN 50178/VDE 0160 (PELV)
Safety for measurement, control, and laboratory equipment
Standards/specifications
IEC 61010-1
Protective extra-low voltage
Standards/specifications
IEC 61010-1 (SELV)
IEC 61010-2-201 (PELV)
Safe isolation
Standards/specifications
IEC 61558-2-16
IEC 61010-2-201
Limitation of harmonic line currents
Standards/specifications
EN 61000-3-2
Mains voltage dips
Standards/specifications
SEMI F47 - 0706 (185 V AC)
Approval data
UL
Identification
UL/C-UL Listed UL 61010-1
UL
Identification
UL/C-UL Listed UL 61010-2-201
UL
Identification
UL/C-UL Listed ANSI/UL 121201 Class I, Division 2, Groups A,
B, C, D (Hazardous Location)
SIQ
Identification
CB scheme (IEC 61010-1, IEC 61010-2-201)
May 19, 2022, 10:06 AM
Page 7 (16)
Power supply unit - UNO2-PS/1AC/48DC/240W
1110155
https://www.phoenixcontact.com/in/products/1110155
EMC data
Low Voltage Directive
Conformance with Low Voltage Directive 2014/35/EC
Electromagnetic compatibility
Conformance with EMC Directive 2014/30/EU
EMC requirements for noise immunity
EN 61000-6-2
Conducted noise emission
EN 55016
EN 61000-6-3 (Class B)
Interference emission
Noise emission according to EN 61000-6-3 (residential and
commercial) and EN 61000-6-4 (industrial)
Noise emission
EN 55016
EN 61000-6-3 (Class B)
Noise immunity
EN 61000-6-2:2005
Harmonic currents
Standards/regulations
EN 61000-3-2
EN 61000-3-2 (Class A)
Frequency range
0 kHz ... 2 kHz
Electrostatic discharge
Standards/regulations
EN 61000-4-2
Electrostatic discharge
Contact discharge
6 kV (Test Level 3)
Discharge in air
8 kV (Test Level 3)
Comments
Criterion A
Electromagnetic HF field
Standards/regulations
EN 61000-4-3
Electromagnetic HF field
Frequency range
80 MHz ... 1 GHz
Test field strength
10 V/m (Test Level 3)
Frequency range
1 GHz ... 2 GHz
Test field strength
10 V/m (Test Level 3)
Frequency range
2 GHz ... 3 GHz
Test field strength
10 V/m (Test Level 3)
Comments
Criterion A
Fast transients (burst)
Standards/regulations
EN 61000-4-4
Fast transients (burst)
Input
4 kV (Test Level 4 - asymmetrical)
Output
2 kV (Test Level 3 - asymmetrical)
Comments
Criterion A
Surge voltage load (surge)
Standards/regulations
EN 61000-4-5
May 19, 2022, 10:06 AM
Page 8 (16)
Power supply unit - UNO2-PS/1AC/48DC/240W
1110155
https://www.phoenixcontact.com/in/products/1110155
Input
2 kV (Test Level 3 - symmetrical)
4 kV (Test Level 4 - asymmetrical)
Output
1 kV (Test Level 2 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Comments
Criterion A
Conducted interference
Standards/regulations
EN 61000-4-6
Conducted interference
Input/Output
asymmetrical
Frequency range
0.15 MHz ... 80 MHz
Comments
Criterion A
Voltage
10 V (Test Level 3)
Voltage dips
Standards/regulations
EN 61000-4-11
Voltage
230 V AC
Frequency
50 Hz
Voltage dip
70 %
Number of periods
25 / 30 periods
Comments
Criterion A
Voltage dip
40 %
Number of periods
12 periods
Additional text
Test Level 2
Comments
Criterion A
Voltage dip
0%
Number of periods
1 period
Additional text
Test Level 2
Comments
Criterion B
Criterion A
Normal operating behavior within the specified limits.
Criterion B
Temporary impairment to operational behavior that is corrected
by the device itself.
May 19, 2022, 10:06 AM
Page 9 (16)
Power supply unit - UNO2-PS/1AC/48DC/240W
1110155
https://www.phoenixcontact.com/in/products/1110155
Drawings
Power Factor
Diagram
1,1
1,0
0,9
0,8
0,7
0,6
0,5
0,4
0,3
0
= UIn: 120 V AC/UOut : 48 V DC
= UIn: 230 V AC/UOut : 48 V DC
1
2
3
4
5
IOut [A]
POut [%]
Diagram
120
110
100
90
80
70
60
50
PN 100% ≤ 50°C
0
1000
2000
3000
4000
5000
H [m]
May 19, 2022, 10:06 AM
Page 10 (16)
Power supply unit - UNO2-PS/1AC/48DC/240W
1110155
https://www.phoenixcontact.com/in/products/1110155
Dimensional drawing
UNO POWER
Ord.No.1110155
45
3.1 3.2 2.1 2.2 2.3 2.4
13
+
+
14
Output DC
48V 240W
42-56 V
130
DC OK
Input AC
100-240V
L N
1.1 1.2 1.3
May 19, 2022, 10:06 AM
Page 11 (16)
Power supply unit - UNO2-PS/1AC/48DC/240W
1110155
https://www.phoenixcontact.com/in/products/1110155
Dimensional drawing
130
48
80
130
125
Block diagram
Input AC
1.1
L
1.2
N
1.3
Output DC
Filter
aktive
PFC
Filter
2.2
+
2.3
2.4
Signal
Functions
UVP
2.1
OVP
3.1
3.2
13
14
User Interface
OTP
OCP
SCP
UOUT
DC OK
May 19, 2022, 10:06 AM
Page 12 (16)
Power supply unit - UNO2-PS/1AC/48DC/240W
1110155
https://www.phoenixcontact.com/in/products/1110155
Eta [%]
Diagram
96
95
94
93
92
91
90
89
88
87
86
1
= UIn: 120 V AC/UOut : 48 V DC
= UIn: 230 V AC/UOut : 48 V DC
2
3
4
5
IOut [A]
IIn [A]
Diagram
2,5
2
1,5
1
0,5
0
0
= UIn: 120 V AC/UOut : 48 V DC
= UIn: 230 V AC/UOut : 48 V DC
1
2
3
4
5
IOut [A]
May 19, 2022, 10:06 AM
Page 13 (16)
Power supply unit - UNO2-PS/1AC/48DC/240W
1110155
https://www.phoenixcontact.com/in/products/1110155
Approvals
EAC
Approval ID: RU S-DE.BL08.W.00764
May 19, 2022, 10:06 AM
Page 14 (16)
Power supply unit - UNO2-PS/1AC/48DC/240W
1110155
https://www.phoenixcontact.com/in/products/1110155
Classifications
ECLASS
ECLASS-11.0
27040701
ETIM
ETIM 8.0
EC002540
UNSPSC
UNSPSC 21.0
May 19, 2022, 10:06 AM
Page 15 (16)
Power supply unit - UNO2-PS/1AC/48DC/240W
1110155
https://www.phoenixcontact.com/in/products/1110155
Environmental Product Compliance
REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 25;
For information on hazardous substances, refer to the
manufacturer’s declaration available under “Downloads”
Phoenix Contact 2022 © - all rights reserved
https://www.phoenixcontact.com
PHOENIX CONTACT (I) Pvt. Ltd.
A-58/2, Okhla Industrial Area, Phase - II, New Delhi-110 020
+91.1275.71420
info@phoenixcontact.co.in
May 19, 2022, 10:06 AM
Page 16 (16)