2021-06-02
Product version 01
Data sheet
Document revision 01
Order No.: 1110629
Type: LPC 2,5/ 3-STF-5,08
PCB connector, Lever Push-in connection
The figure shows an 10-position version
Main features
2,5 mm 2
320V
IEC
IEC
5,08 mm
No. of pos.
Conductor cross section
Color
Pitch
Connection method
3
2.5 mm²
green (6021)
5.08 mm
Lever Push-in connection
0°
Nominal current
Nominal voltage
Connection direction
Type of packaging
16 A
320 V
0°
packed in cardboard
16A
1
Your advantages
Tool-free lever principle enables time-saving connection and release of conductors with/without ferrules
Clear lever positions provide reliable feedback on opened or closed clamping spaces
Time-saving push-in connection when lever is closed
Screwable flange for superior mechanical stability
Quick and convenient testing using integrated test option
Make sure you always use the latest documentation.
It can be downloaded at: phoenixcontact.net/product/1110629
© PHOENIX CONTACT 2021
2
2021-06-02
Product version 01
1110629 LPC 2,5/ 3-STF-5,08
Document revision 01
Table of contents
1
Main features........................................................................................................................... 1
2
Your advantages ..................................................................................................................... 1
3
Table of contents ..................................................................................................................... 2
4
3D model in PDF can be activated (Acrobat Reader only)....................................................... 3
5
General Technical Data ........................................................................................................... 4
6
Mounting.................................................................................................................................. 5
7
Conductor connection ............................................................................................................. 6
8
Material properties................................................................................................................... 7
9
Dimensions.............................................................................................................................. 8
10
Series drawing......................................................................................................................... 9
11
Product notes ........................................................................................................................ 10
12
Packaging information ........................................................................................................... 10
13
Application............................................................................................................................. 10
14
General tests ......................................................................................................................... 11
15
Mechanical tests.................................................................................................................... 11
16
Insertion and withdrawal forces ............................................................................................. 13
17
Electrical tests ....................................................................................................................... 14
18
Current carrying capacity/derating curves ............................................................................. 15
19
Environmental and durability tests ......................................................................................... 16
20
Classification for connectors.................................................................................................. 16
21
Commercial Data................................................................................................................... 17
22
Accessories ........................................................................................................................... 17
23
Combination tests.................................................................................................................. 18
© PHOENIX CONTACT 2021
3
REF 1110628
PHOENIX CONTACT 2 / 18
2021-06-02
Product version 01
1110629 LPC 2,5/ 3-STF-5,08
3D model in PDF can be activated (Acrobat Reader only)
© PHOENIX CONTACT 2021
4
Document revision 01
REF 1110628
PHOENIX CONTACT 3 / 18
2021-06-02
Product version 01
1110629 LPC 2,5/ 3-STF-5,08
5
General Technical Data
5.1
item properties
Document revision 01
Order No.
1110629
Type
LPC 2,5/ 3-STF-5,08
Connector system
CLASSIC COMBICON
Product type
PCB connector
Type of contact
Female connector
Range of articles
LPC 2,5/..-ST-LR
Pitch
5.08 mm
Number of positions
3
1
Connection method
Lever Push-in connection
Connection direction of the conductor to plug-in direction
0°
© PHOENIX CONTACT 2021
Number of levels
REF 1110628
PHOENIX CONTACT 4 / 18
2021-06-02
Product version 01
1110629 LPC 2,5/ 3-STF-5,08
6
Mounting
6.1
Flange mounting
Document revision 01
Screw locking
Mounting flange
Screw flange
Torque
0.3 Nm
© PHOENIX CONTACT 2021
Type of locking
REF 1110628
PHOENIX CONTACT 5 / 18
2021-06-02
Product version 01
1110629 LPC 2,5/ 3-STF-5,08
7
Conductor connection
7.1
Connection capacity
Document revision 01
Nominal cross section
2.5 mm²
Conductor cross section, rigid
0.2 mm² ... 2.5 mm²
Conductor cross section, flexible
0.2 mm² ... 2.5 mm²
Conductor cross section flexible, with ferrule without plastic sleeve
0.25 mm² ... 2.5 mm² (Stripping length: 7 mm ... 12 mm)
Conductor cross section flexible, with ferrule with plastic sleeve
0.25 mm² ... 2.5 mm² (Stripping length: 7 mm ... 12 mm)
2 conductors with the same cross section flexible with TWIN ferrule and
plastic sleeve
0.5 mm² ... 1 mm² (Stripping length: 7 mm ... 12 mm)
Cylindrical gauge a x b / diameter
2.8 mm x 2.0 mm / 2.4 mm
Stripping length
10 mm
7.2
Connection capacity AWG
26 ... 12
© PHOENIX CONTACT 2021
Conductor cross section AWG
REF 1110628
PHOENIX CONTACT 6 / 18
2021-06-02
Product version 01
1110629 LPC 2,5/ 3-STF-5,08
8
Material properties
8.1
Material of metal parts
Document revision 01
Note
WEEE/RoHS-compliant, whisker-free acc. to IEC 60068-2-82/JEDEC JESD 201
Contact material
Cu alloy
Terminal point surface
Tin (4 - 8 µm Sn)
Surface contact area
Tin (4 - 8 µm Sn)
Surface characteristics
hot-dip tin-plated
8.2
Material of plastic parts
Housing
Actuation element
green (6021)
orange (2003)
Insulating material
PA
PA GF
Insulating material group
I
I
CTI according to IEC 60112
600
600
Flammability rating according to UL 94
V0
V0
Glow wire flammability index GWFI according to EN 60695-2-12
850
Glow wire ignition temperature GWIT according to EN 60695-2-13
775
Temperature for the ball pressure test according to EN 60695-10-2
125 °C
© PHOENIX CONTACT 2021
Color
REF 1110628
PHOENIX CONTACT 7 / 18
2021-06-02
Product version 01
1110629 LPC 2,5/ 3-STF-5,08
9
Dimensions
9.1
Dimensions for the product
Length
Document revision 01
27.37 mm
25.42 mm
Total height
15.39 mm
© PHOENIX CONTACT 2021
Width
REF 1110628
PHOENIX CONTACT 8 / 18
2021-06-02
Product version 01
1110629 LPC 2,5/ 3-STF-5,08
Series drawing
© PHOENIX CONTACT 2021
10
Document revision 01
REF 1110628
PHOENIX CONTACT 9 / 18
2021-06-02
Product version 01
1110629 LPC 2,5/ 3-STF-5,08
11
Product notes
11.1
General information
Notes on operation
12
Document revision 01
In accordance with IEC 61984, COMBICON connectors have no switching power
(COC). During designated use, they must not be plugged in or disconnected
when carrying voltage or under load.
Packaging information
Type of packaging
packed in cardboard
Pieces per package
100
13
Application
Ferrules without insulating collar, according to DIN 46228-1
Recommended crimping pliers
1212034 CRIMPFOX 6
Ferrules without insulating collar, according to DIN 46228-1
Cross section: 0.25 mm²; Length: 7 mm
Cross section: 0.34 mm²; Length: 7 mm
Cross section: 0.5 mm²; Length: 8 mm ... 10 mm
Cross section: 0.75 mm²; Length: 8 mm ... 10 mm
Cross section: 1 mm²; Length: 8 mm ... 12 mm
Cross section: 1.5 mm²; Length: 10 mm ... 12 mm
Cross section: 2.5 mm²; Length: 10 mm ... 12 mm
1212034 CRIMPFOX 6
Ferrules with insulating collar, according to DIN 46228-4
Cross section: 0.25 mm²; Length: 8 mm ... 10 mm
Cross section: 0.34 mm²; Length: 8 mm ... 10 mm
Cross section: 0.5 mm²; Length: 8 mm ... 10 mm
Cross section: 0.75 mm²; Length: 10 mm ... 12 mm
Cross section: 1 mm²; Length: 10 mm ... 12 mm
Cross section: 1.5 mm²; Length: 10 mm ... 12 mm
Cross section: 2.5 mm²; Length: 12 mm
Temperature limit values
-40 °C ... 70 °C
Ambient temperature (assembly)
-5 °C ... 100 °C
Ambient temperature (operation)
-40 °C ... 105 °C (dependent on the derating curve)
© PHOENIX CONTACT 2021
Ambient temperature (storage/transport)
13.1
Ferrules with insulating collar, according to DIN 46228-4
Recommended crimping pliers
REF 1110628
PHOENIX CONTACT 10 / 18
2021-06-02
Product version 01
1110629 LPC 2,5/ 3-STF-5,08
14
General tests
14.1
Specification
Document revision 01
Specification
IEC 61984
Specification
IEC 60999-1
Brief description
Printed-circuit board connector
15
Mechanical tests
15.1
Check for damage to conductor or loosening
Result
Test passed
Specification
IEC 60999-1:1999-11
15.2
Pull-out test
Specification
IEC 60999-1:1999-11
Result
Test passed
Conductor cross section/conductor type/tractive force actual value
0.2 mm² / solid / > 10 N
Conductor cross section/conductor type/tractive force actual value
0.2 mm² / flexible / > 10 N
Conductor cross section/conductor type/tractive force actual value
2.5 mm² / solid / > 50 N
Conductor cross section/conductor type/tractive force actual value
2.5 mm² / flexible / > 50 N
Repeated connection and disconnection
15.3
Specification
IEC 60999-1:1999-11
Result
Test passed
Conductor connection
15.4
IEC 60999-1:1999-11
Result
Test passed
Specification
Visual examination
Specification
IEC 61984:2008-10
Visual examination
Test passed
Specification
IEC 60512-1-1:2002-02
15.6
Dimensional test
Dimensional test
Test passed
Specification
IEC 60512-1-2:2002-02
15.7
© PHOENIX CONTACT 2021
15.5
Resistance of marking
REF 1110628
PHOENIX CONTACT 11 / 18
2021-06-02
Product version 01
1110629 LPC 2,5/ 3-STF-5,08
Document revision 01
Resistance of marking
Test passed
Specification
IEC 60068-2-70:1995-12
15.8
Polarization and coding
Test passed
Specification
IEC 60512-13-5:2006-02
© PHOENIX CONTACT 2021
Polarization when inserted
Requirement >20 N
REF 1110628
PHOENIX CONTACT 12 / 18
2021-06-02
Product version 01
1110629 LPC 2,5/ 3-STF-5,08
16
Document revision 01
Insertion and withdrawal forces
Insertion and withdrawal force
Test passed
Specification
IEC 60512-13-2:2006-02
25
Insertion strength per pos. approx.
8N
Withdraw strength per pos. approx.
6N
© PHOENIX CONTACT 2021
No. of cycles
REF 1110628
PHOENIX CONTACT 13 / 18
2021-06-02
Product version 01
1110629 LPC 2,5/ 3-STF-5,08
17
Document revision 01
Electrical tests
Rated current / conductor cross section
16 A / 2.5 mm²
Rated insulation voltage (III/2)
320 V
Rated surge voltage (III/2)
4 kV
Contact resistance
2 mΩ
Degree of pollution
2
17.1
Air and creepage distances
Component
PCB connector
Specification
IEC 60664-1:2007-04
Mains type
unearthed mains
Insulating material group
I
Comparative tracking index (IEC 60112:2003-01)
CTI 600
Rated insulation voltage
250 V
320 V
630 V
Rated surge voltage
4 kV
4 kV
4 kV
Degree of pollution
3
2
2
Overvoltage category
III
III
II
Minimum clearance case A (inhomogeneous field)
3 mm
3 mm
3 mm
Minimum value of the creepage path requirement in acc. with table
3.2 mm
3 mm
3.2 mm
Electrical function
Specification
IEC 60999-1:1999-11
Result
Test passed
Voltage drop (U) after the load ≤ 15 mV
Test current (minimum cross section)
3 A AC
Test current (maximum cross section)
16 A AC
Voltage drop
17.2
Conductor cross section, flexible
0.2 mm² ... 2.5 mm²
Conductor cross section, rigid
0.2 mm² ... 2.5 mm²
Temperature cycles
17.3
IEC 60999-1:1999-11
Result
Test passed
Voltage drop
Voltage drop (U) after the load ≤ 22.5 mV or 1.5 x U after 24 h
The small value is to be used.
Test current (minimum cross section)
3 A AC
Test current (maximum cross section)
16 A AC
Temperature cycles
192
Conductor cross section, flexible
0.2 mm² ... 2.5 mm²
Conductor cross section, rigid
0.2 mm² ... 2.5 mm²
REF 1110628
© PHOENIX CONTACT 2021
Specification
PHOENIX CONTACT 14 / 18
2021-06-02
Product version 01
1110629 LPC 2,5/ 3-STF-5,08
18
Document revision 01
Current carrying capacity/derating curves
Specification
IEC 61984:2008-10
Note
Representation based on IEC 60512-5-2:2002-02
Note
For number of positions, see diagram
Reduction factor
0.8
Conductor cross section
2.5 mm²
I [A]
Type: LPC 2,5/...-STF-5,08 with MSTBV 2,5/...-GF-5,08
24
22
20
18
16
14
12
10
8
6
4
2
0
1
1
2
3
4
0
= 2-pos.
= 5-pos.
= 10-pos.
= 20-pos.
10
20
2
3
4
30
40
50
60
70
80
90 100 110
© PHOENIX CONTACT 2021
ă[°C]
REF 1110628
PHOENIX CONTACT 15 / 18
2021-06-02
Product version 01
1110629 LPC 2,5/ 3-STF-5,08
19
Environmental and durability tests
19.1
Vibration test
Document revision 01
Specification
IEC 60068-2-6:2007-12
Result
Test passed
Frequency
10 - 150 - 10 Hz
Sweep speed
1 octave/min
Amplitude
0.35 mm (10 - 60.1 Hz)
Acceleration
50 m/s² (60.1 - 150 Hz)
Test duration per axis
2.5 h
Test directions
X-, Y- and Z-axis
Note
19.2
Railway application, vibration test
Specification
IEC 61373:2010-05
Result
Test passed
Testing
Vibration, broadband noise
Frequency
5 - 150 Hz
Test directions
X-, Y- and Z-axis (pos. and neg.)
Spectrum
Service life test category 1, class B, body mounted
19.3
Shock test
IEC 60068-2-27:2008-02
Result
Test passed
Pulse shape
Semi-sinusoidal
Peak acceleration
200 m/s²
Shock duration
11 ms
Number of shocks per direction
3
Test directions
X-, Y- and Z-axis (pos. and neg.)
Specification
IEC 61984:2008-10
Main features
Connectors without switching capacity (COC)
Construction form
Fixed connectors
Strain relief elements
without strain relief
Connection method
Can be reconnected
Protection against electric shock
Not encapsulated - touch-proof when inserted
Protective conductor
without PE
Lock
no
Connection method
Screwless terminal points
REF 1110628
Classification for connectors
© PHOENIX CONTACT 2021
20
Specification
PHOENIX CONTACT 16 / 18
2021-06-02
Product version 01
1110629 LPC 2,5/ 3-STF-5,08
21
Document revision 01
Commercial Data
Order No.
1110629
Type
LPC 2,5/ 3-STF-5,08
Pieces per package
100
Net weight
2.22 g
GTIN
4063151027667
Information that applies locally, see link on page 1
Information that applies locally, see link on page 1
22
Accessories
Description
Order No.
Type
Coding profile, is inserted into the slot on the plug or inverted header, red
insulating material
1734634
CP-MSTB
SZS 0,6X3,5
© PHOENIX CONTACT 2021
Actuation tool, for ST terminal blocks, insulated, also suitable for use as a 1205053
bladed screwdriver, size: 0.6 x 3.5 x 100 mm, 2-component grip, with nonslip grip
REF 1110628
PHOENIX CONTACT 17 / 18
2021-06-02
Product version 01
1110629 LPC 2,5/ 3-STF-5,08
23
Document revision 01
Combination tests
LPC 2,5/..-ST-LR
MSTBV 2,5/..-GF
IEC 61984
IEC 61984
Mechanical tests (A)
Insertion/withdrawal force per position
approx. 8 N / 6 N
Polarization when inserted
Requirement >20 N
Test passed
Contact holder in insert
Requirements >20 N
Test passed
Durability tests (B)
Contact resistance R1 1st level
2 mΩ
Contact resistance R1 2nd level
Insertion/withdrawal cycles
25
Contact resistance R2
2.2 mΩ
Rated impulse voltage at sea level
Voltage waveform ≥ (1.2/50 μs)
4.8 kV
Power-frequency withstand voltage
Voltage waveform ≥ (50/60 Hz)
2.21 kV
Tested number of positions
20
Tested conductor cross section
2.5 mm²
Test current
12 A
Upper limiting temperature
Requirements < 100°C
Test passed
Thermal tests (C)
Climatic tests (D)
-40 °C/2 h
Test sequence 2: heat storage
105 °C/168 h
Test sequence 3: noxious gas storage
(ISO 6988)
0.2 dm3 SO2 on 300 dm3/
40 °C/1 cycle
Rated impulse voltage at sea level
Voltage waveform ≥ (1.2/50 μs)
4.8 kV
Power-frequency withstand voltage
Voltage waveform ≥ (50/60 Hz)
2.21 kV
Test sequence 1: low temperature storage
Specification
IEC 61984:2008-10
Degree of protection
Finger safety with IP20
test finger
REF 1110628
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany
phoenixcontact.com
© PHOENIX CONTACT 2021
Environmental and endurance tests (E)
PHOENIX CONTACT 18 / 18