2021-02-23
Product version 00
Data sheet
Document revision 00
Order No.: 1119820
Type: LPT 16/ 4-15,0-ZB
Main features
No. of pos.
Conductor cross section
Color
Pitch
Connection method
4
16 mm²
green (6021)
15 mm
Lever Push-in connection
Nominal current
Nominal voltage
Connection direction
Type of packaging
76 A
1000 V
0°
packed in cardboard
1
PCB terminal block, Lever Push-in connection
Your advantages
Tool-free lever principle enables time-saving connection and release of conductors with/without ferrules
Clear lever positions provide reliable feedback on opened or closed clamping spaces
Defined contact force ensures that contact remains stable over the long term
Time-saving push-in connection when lever is closed
Intuitive operation, thanks to a color-coded actuation lever
Make sure you always use the latest documentation.
It can be downloaded at: phoenixcontact.net/product/1119820
© PHOENIX CONTACT 2021
2
2021-02-23
Product version 00
1119820 LPT 16/ 4-15,0-ZB
Document revision 00
Table of contents
1
Main features........................................................................................................................... 1
2
Your advantages ..................................................................................................................... 1
3
Table of contents ..................................................................................................................... 2
4
3D model in PDF can be activated (Acrobat Reader only)....................................................... 3
5
General Technical Data ........................................................................................................... 4
6
Conductor connection ............................................................................................................. 5
7
Material properties................................................................................................................... 5
8
Dimensions.............................................................................................................................. 6
9
Series drawing......................................................................................................................... 7
10
Application............................................................................................................................... 8
11
Packaging information ............................................................................................................. 8
12
Mechanical tests...................................................................................................................... 9
13
Electrical tests ....................................................................................................................... 10
14
Current carrying capacity/derating curves ............................................................................. 12
15
Environmental and durability tests ......................................................................................... 13
16
Commercial Data................................................................................................................... 14
REF
PHOENIX CONTACT 2 / 14
© PHOENIX CONTACT 2021
3
2021-02-23
Product version 00
1119820 LPT 16/ 4-15,0-ZB
3D model in PDF can be activated (Acrobat Reader only)
© PHOENIX CONTACT 2021
4
Document revision 00
REF
PHOENIX CONTACT 3 / 14
2021-02-23
Product version 00
1119820 LPT 16/ 4-15,0-ZB
5
General Technical Data
5.1
item properties
Document revision 00
Order No.
1119820
Type
LPT 16/ 4-15,0-ZB
Product type
PCB terminal block
Range of articles
LPT 16/
Pitch
15 mm
Number of positions
4
Number of levels
1
Number of connections
4
Number of potentials
4
Connection method
Lever Push-in connection
Wave soldering
Connection direction of the conductor to the PCB
0°
Pin layout
Zigzag pinning W
© PHOENIX CONTACT 2021
Mounting type
REF
PHOENIX CONTACT 4 / 14
2021-02-23
Product version 00
1119820 LPT 16/ 4-15,0-ZB
6
Conductor connection
6.1
Connection capacity
Conductor cross section, rigid
Document revision 00
0.75 mm² ... 16 mm² (Conductor connection with open terminal point)
Conductor cross section, rigid
1.5 mm² ... 16 mm² (Push-in connection)
Conductor cross section, multi-stranded
0.75 mm² ... 16 mm²
Conductor cross section, flexible
0.75 mm² ... 25 mm²
Conductor cross section flexible, with ferrule without plastic sleeve
0.75 mm² ... 16 mm²
Conductor cross section flexible, with ferrule with plastic sleeve
0.75 mm² ... 16 mm²
2 conductors with the same cross section flexible with TWIN ferrule and
plastic sleeve
4 mm² ... 6 mm²
Stripping length
18 mm ... 20 mm
Connection capacity AWG
Conductor cross section AWG
7
Material properties
7.1
Material of metal parts
18 ... 4
WEEE/RoHS-compliant, whisker-free acc. to IEC 60068-2-82/JEDEC JESD 201
Contact material
Cu alloy
Terminal point surface
Tin (10 - 16 µm Sn)
Soldering area surface
Tin (10 - 16 µm Sn)
Surface characteristics
Tin-plated
7.2
Note
Material of plastic parts
Housing
Actuation element
green (6021)
orange (2003)
Insulating material
PA
PA GF
Insulating material group
I
I
CTI according to IEC 60112
600
600
Flammability rating according to UL 94
V0
V0
850
Glow wire ignition temperature GWIT according to EN 60695-2-13
775
Temperature for the ball pressure test according to EN 60695-10-2
125 °C
© PHOENIX CONTACT 2021
Glow wire flammability index GWFI according to EN 60695-2-12
Color
6.2
REF
PHOENIX CONTACT 5 / 14
2021-02-23
Product version 00
1119820 LPT 16/ 4-15,0-ZB
8
Dimensions
8.1
Dimensions for the product
Document revision 00
Length
32 mm
Width
56.9 mm
36 mm
Total height
39.6 mm
Solder pin [P]
3.6 mm
© PHOENIX CONTACT 2021
Height (without solder pin)
REF
PHOENIX CONTACT 6 / 14
2021-02-23
Product version 00
1119820 LPT 16/ 4-15,0-ZB
Series drawing
© PHOENIX CONTACT 2021
9
Document revision 00
REF
PHOENIX CONTACT 7 / 14
2021-02-23
Product version 00
1119820 LPT 16/ 4-15,0-ZB
10
Application
11
Packaging information
Document revision 00
Type of packaging
packed in cardboard
Pieces per package
25
11.1
Temperature limit values
-40 °C ... 70 °C
Ambient temperature (assembly)
-5 °C ... 100 °C
Ambient temperature (operation)
-40 °C ... 105 °C (Depending on the current carrying capacity/derating curve)
© PHOENIX CONTACT 2021
Ambient temperature (storage/transport)
REF
PHOENIX CONTACT 8 / 14
2021-02-23
Product version 00
1119820 LPT 16/ 4-15,0-ZB
12
Mechanical tests
12.1
Pull-out test
Document revision 00
Specification
IEC 60999-1:1999-11
Result
Test passed
Conductor cross section/conductor type/tractive force actual value
0.75 mm² / solid / > 30 N
Conductor cross section/conductor type/tractive force actual value
0.75 mm² / flexible / > 30 N
Conductor cross section/conductor type/tractive force actual value
16 mm² / solid / > 100 N
Conductor cross section/conductor type/tractive force actual value
25 mm² / flexible / > 135 N
12.2
Check for damage to conductor or loosening
IEC 60999-1:1999-11
Result
Test passed
© PHOENIX CONTACT 2021
Specification
REF
PHOENIX CONTACT 9 / 14
2021-02-23
Product version 00
1119820 LPT 16/ 4-15,0-ZB
13
Electrical tests
13.1
Electrical data
Rated current / conductor cross section
Document revision 00
76 A / 16 mm²
Rated insulation voltage (III/2)
1000 V
Rated surge voltage (III/2)
8 kV
Contact resistance
0.38 mΩ
Degree of pollution
2
13.2
Air and creepage distances
Component
PCB terminal block
Specification
IEC 60947-7-4:2019-01
Mains type
unearthed mains
Insulating material group
I
Comparative tracking index (IEC 60112:2003-01)
CTI 600
Rated insulation voltage
1000 V
1000 V
1000 V
Rated surge voltage
8 kV
8 kV
6 kV
Degree of pollution
3
2
2
Overvoltage category
III
III
II
Minimum clearance case A (inhomogeneous field)
8 mm
8 mm
5.5 mm
Minimum value of the creepage path requirement in acc. with table
12.5 mm
8 mm
5.5 mm
Short-time withstand current test
13.3
IEC 60947-7-4:2019-01
Result
Test passed
Conductor cross section/short-time current
16 mm² / 360 A
Specification
Specification
IEC 60947-7-4:2019-01
Result
Test passed
Contact resistance R1
0.38 mΩ / 16 mm²
Test sequence 1: low temperature storage
-40 °C / 2 h
Test sequence 2: heat storage
168 h/105 °C
Test sequence 3: noxious gas storage
(ISO 6988)
KFW 0.2 S/1 cycle
Contact resistance R2
0.2 mΩ / 16 mm²
Rated impulse voltage at sea level
Voltage waveform ≥ (1.2/50 μs)
9.8 kV
Power-frequency withstand voltage
Voltage waveform ≥ (50/60 Hz)
4.2 kV
13.5
REF
Aging test (climatic impact and corrosion testing)
© PHOENIX CONTACT 2021
13.4
Insulation resistance
PHOENIX CONTACT 10 / 14
2021-02-23
Product version 00
1119820 LPT 16/ 4-15,0-ZB
Document revision 00
Specification
IEC 60512-3-1:2002-02
Result
Test passed
Insulation resistance, neighboring positions
> 5 MΩ
13.6
Mechanical connection test for the PCB terminal block
Specification
IEC 60947-7-4:2019-01
Result
Test passed
13.7
Temperature rise test
Specification
IEC 60947-7-4:2019-01
Result
Test passed
Requirement temperature-rise test
The sum of ambient temperature and temperature rise of the PCB terminal block
shall not exceed the upper limiting temperature.
16 mm² / 76 A / 41.7 K
10 mm² / 57 A / 33.7 K
Conductor cross section/test current/temperature rise
6 mm² / 41 A / 30.2 K
© PHOENIX CONTACT 2021
Conductor cross section/test current/temperature rise
Conductor cross section/test current/temperature rise
REF
PHOENIX CONTACT 11 / 14
2021-02-23
Product version 00
1119820 LPT 16/ 4-15,0-ZB
14
Document revision 00
Current carrying capacity/derating curves
Specification
IEC 60947-7-4:2019-01
Note
Representation based on IEC 60512-5-2:2002-02
Reduction factor
1
Number of positions
4
Conductor cross section
16 mm²
I [A]
Type: LPT 16/...-15,0-ZB
130
120
110
100
90
80
70
60
50
40
30
20
10
0
1
2
3
2
= 16 mm
2
= 10 mm
2
= 6 mm
1
2
3
0
10
20
30
40
50
60
70
80
90 100 110
© PHOENIX CONTACT 2021
ă [°C]
REF
PHOENIX CONTACT 12 / 14
2021-02-23
Product version 00
1119820 LPT 16/ 4-15,0-ZB
15
Environmental and durability tests
15.1
Vibration test
Document revision 00
Specification
IEC 60068-2-6:2007-12
Result
Test passed
Frequency
10 - 150 - 10 Hz
Sweep speed
1 octave/min
Amplitude
0.35 mm (10 - 60.1 Hz)
Acceleration
50 m/s2 (60.1 - 150 Hz)
Test duration per axis
2.5 h
Test directions
X-, Y- and Z-axis
Note
15.2
Assessment of fire risk (glow wire test)
Specification
IEC 60695-2-10:2013-04
Result
Test passed
Temperature
850 °C
Time of exposure
5s
15.3
Shock protection
Following IEC 60529:1989-11 + AMD 1:1999-11 + AMD 2:2013-08
Back of the hand protection (Ball ø 50)
conditional guaranteed
Finger protection (movable test finger)
conditional guaranteed
Note
Contact protection above the PCB is only assured when a conductor with a crosssection of 6 mm² is connected.
© PHOENIX CONTACT 2021
Specification
REF
PHOENIX CONTACT 13 / 14
2021-02-23
Product version 00
1119820 LPT 16/ 4-15,0-ZB
16
Document revision 00
Commercial Data
Order No.
1119820
Type
LPT 16/ 4-15,0-ZB
Pieces per package
25
Net weight
2.22 g
GTIN
4063151065676
Information that applies locally, see link on page 1
Information that applies locally, see link on page 1
© PHOENIX CONTACT 2021
Country of origin
REF
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany
phoenixcontact.com
PHOENIX CONTACT 14 / 14