Web Panels with TFT Display
User manual
User manual
Web Panels with TFT Display
UM EN WP 4XXXX, Revision 04
2020-04-01
This user manual is valid for:
Order No.
WP 4000
WP 4070W/P US 01
WP 4101W/P US 01
WP 4156W/P US 01
WP 4185W/P US 01
WP 4070-WXPS
WP 4070-WVRS
WP 4101-WXPS
WP 4120-WXPS
WP 4156-WHPS
WP 4185-WHPS
1065546
1094819
1094818
1104387
1104395
1148693
1148694
1148687
1148689
1148691
1148690
108594_en_04
Designation
PHOENIX CONTACT GmbH & Co. KG • Flachsmarktstraße 8 • 32825 Blomberg • Germany
phoenixcontact.com
How to contact us
Internet
Up-to-date information on Phoenix Contact products and our Terms and Conditions can be
found on the Internet at:
phoenixcontact.com
Make sure you always use the latest documentation.
It can be downloaded at:
phoenixcontact.net/products
Subsidiaries
If there are any problems that cannot be solved using the documentation, please contact
your Phoenix Contact subsidiary.
Subsidiary contact information is available at phoenixcontact.com.
Published by
PHOENIX CONTACT GmbH & Co. KG
Flachsmarktstraße 8
32825 Blomberg
GERMANY
Should you have any suggestions or recommendations for improvement of the contents and
layout of our manuals, please send your comments to
tecdoc@phoenixcontact.com
General terms and conditions of use for technical documentation
Phoenix Contact reserves the right to alter, correct, and/or improve the technical documentation and the products described in the technical documentation at its own discretion and
without giving prior notice, insofar as this is reasonable for the user. The same applies to any
technical changes that serve the purpose of technical progress.
The receipt of technical documentation (in particular user documentation) does not constitute any further duty on the part of Phoenix Contact to furnish information on modifications
to products and/or technical documentation. You are responsible to verify the suitability and
intended use of the products in your specific application, in particular with regard to observing the applicable standards and regulations. All information made available in the technical
data is supplied without any accompanying guarantee, whether expressly mentioned, implied or tacitly assumed.
In general, the provisions of the current standard Terms and Conditions of Phoenix Contact
apply exclusively, in particular as concerns any warranty liability.
This manual, including all illustrations contained herein, is copyright protected. Any
changes to the contents or the publication of extracts of this document is prohibited.
Phoenix Contact reserves the right to register its own intellectual property rights for the product identifications of Phoenix Contact products that are used here. Registration of such intellectual property rights by third parties is prohibited.
Other product identifications may be afforded legal protection, even where they may not be
indicated as such.
PHOENIX CONTACT
PHOENIX CONTACT
Table of Contents
Table of Contents
1
2
3
4
Important Notes .........................................................................................................................7
1.1
Symbols ................................................................................................................ 7
1.2
Safety Notes.......................................................................................................... 7
1.3
Security in the network .......................................................................................... 8
1.4
Intended Use ......................................................................................................... 8
1.5
Target Group ......................................................................................................... 9
1.6
Licensing information on open source software..................................................... 9
1.7
Retrieving the source code .................................................................................... 9
Installation and Commissioning ...............................................................................................11
2.1
Unpacking the Device.......................................................................................... 11
2.2
Mounting the Device............................................................................................ 12
2.2.1
Front Panel Dimensions ....................................................................... 13
2.2.2
Mounting Cutout .................................................................................. 19
2.2.3
Side View, Mounting Depth .................................................................. 25
2.3
Connecting the Device ........................................................................................ 31
2.3.1
Supply Voltage ..................................................................................... 31
2.3.2
Grounding ............................................................................................ 32
2.4
Switching On ....................................................................................................... 33
2.5
Identification ........................................................................................................ 33
2.5.1
Orderkey .............................................................................................. 33
Control and Display Elements ..................................................................................................35
3.1
Touchscreen ....................................................................................................... 35
3.2
Display................................................................................................................. 35
3.3
Status LEDs......................................................................................................... 36
Interfaces of the Device ...........................................................................................................37
4.1
5
Standard Interfaces ............................................................................................. 37
4.1.1
Ethernet (X5) ........................................................................................ 38
4.1.2
USB (X9, X10) ..................................................................................... 39
4.1.3
Memory Card ....................................................................................... 40
Maintenance and Servicing ......................................................................................................41
108594_en_04
5.1
Front Panel .......................................................................................................... 41
5.2
Fuse .................................................................................................................... 41
PHOENIX CONTACT
5
WP 4000
6
6
Technical Data .........................................................................................................................43
PHOENIX CONTACT
6.1
General................................................................................................................ 43
6.2
7" Display (resistive) ............................................................................................ 45
6.3
7" Display (PCAP) ............................................................................................... 47
6.4
10.1" Display (PCAP) .......................................................................................... 49
6.5
12.1" Display (PCAP) .......................................................................................... 51
6.6
15.6" Display (PCAP) .......................................................................................... 53
6.7
18.5" Display (PCAP) .......................................................................................... 55
108594_en_04
Important Notes
1
Important Notes
1.1
Symbols
The symbols in this manual are used to draw your attention on notes and dangers.
This symbol indicates hazards that could lead to personal injury.
There are three signal words indicating the severity of a potential injury.
DANGER
Indicates a hazard with a high risk level. If this hazardous situation is not avoided, it will
result in death or serious injury.
WARNING
Indicates a hazard with a medium risk level. If this hazardous situation is not avoided, it
could result in death or serious injury.
CAUTION
Indicates a hazard with a low risk level. If this hazardous situation is not avoided, it could
result in minor or moderate injury.
This symbol together with the NOTE signal word alerts the reader to a situation which may
cause damage or malfunction to the device, hardware/software, or surrounding property.
Here you will find additional information or detailed sources of information.
1.2
–
–
–
–
–
–
108594_en_04
Safety Notes
Read this manual carefully before using the operating device. Keep this manual in a
place where it is always accessible to all users.
Proper transportation, handling and storage, placement and installation of this product
are prerequisites for its subsequent flawless and safe operation.
This user manual contains the most important information for the safe operation of the
device.
The user manual, in particular the safety notes, must be observed by all personnel
working with the device.
Observe the accident prevention rules and regulations that apply to the operating site.
Installation and operation must only be carried out by qualified and trained personnel.
PHOENIX CONTACT
7
WP 4000
1.3
Security in the network
NOTE: Risk of unauthorized network access
Connecting devices to a network via Ethernet always entails the risk of unauthorized access to the network.
Therefore, please check your application for any option of deactivating active communication channels . Setting passwords to prevent third parties from accessing the controller
without authorization and modifying the system.
Because of the controller's communication interfaces, we advise against using the controller in safety-critical applications without additional security appliances.
Please take additional protective measures according to the IT security requirements and
the standards applicable to your application (for instance virtual networks (VPN) for remote maintenance access, firewalls, etc.) for protection against unauthorized network access.
On first request, you shall release Phoenix Contact and the companies associated with
Phoenix Contact GmbH & Co. KG, Flachsmarktstraße 8, 32825 Blomberg in accordance
with §§ 15 ff. AktG or German Stock Corporation Act (hereinafter collectively referred to
as "Phoenix Contact") from all third-party claims that are made due to improper use.
For the protection of networks for remote maintenance via VPN, Phoenix Contact offers
the mGuard product series security appliances which you can find described in the latest
Phoenix Contact catalog (phoenixcontact.net/products).
Additional measures for protection from unauthorized network access can be found in the
AH EN INDUSTRIAL SECURITY application note. The application note can be downloaded at phoenixcontact.net/products.
1.4
–
–
–
Intended Use
The device is designed for use in the industry.
The device is state-of-the art and has been built to the latest standard safety requirements. However, dangerous situations or damage to the machine itself or other property can arise from the use of this device.
The device fulfills the requirements of the EMC directives and harmonized European
standards. Any modifications to the system can influence the EMC behavior.
NOTICE: Radio Interference
Operation of this device may cause radio interference in residential areas.
8
PHOENIX CONTACT
108594_en_04
Important Notes
1.5
Target Group
The use of products described in this manual is oriented exclusively to:
– Qualified electricians or persons instructed by them. The users must be familiar with the
relevant safety concepts of automation technology as well as applicable standards and
other regulations.
– Qualified application programmers and software engineers. The users must be familiar
with the relevant safety concepts of automation technology as well as applicable standards and other regulations.
1.6
Licensing information on open source software
The operating device works with a Linux operating system. License information for the individual Linux packages can be found in the web-based management of the operating device.
1.7
Retrieving the source code
This product contains software components which are licensed by the rights holder as free
software or Open-source software under the GNU General Public License, version 2. You
may retrieve the source code for these software components from Phoenix Contact using
an appropriate storage medium (CD or DVD-ROM), by contacting After Sales Service at the
address below. This must be carried out no more than three years after delivery of the product. A processing charge of 50 euros will be required in this case.
PHOENIX CONTACT GmbH & Co. KG
After Sales Service
Flachsmarktstraße 8
32825 Blomberg
GERMANY
Subject: Source code WP 4XXXX
108594_en_04
PHOENIX CONTACT
9
WP 4000
10
PHOENIX CONTACT
108594_en_04
Installation and Commissioning
2
Installation and Commissioning
2.1
Unpacking the Device
Unpack all parts carefully and check the contents for any visible damage in transit. Also
check whether the shipment matches the specifications on your delivery note.
If you notice damages in transit or discrepancies, please contact us immediately.
108594_en_04
PHOENIX CONTACT
11
WP 4000
2.2
Mounting the Device
NOTICE: Damage
When installing the device, leave a gap of at least 30 mm (1.181") around the device to
ensure sufficient air circulation.
NOTICE: Damage
When the operating device is installed horizontally, please note that additional sources of
heat beneath the operating device may result in heat accumulation.
Make sure to allow sufficient heat dissipation!
Please observe the permissible temperature range specified in the technical data when
operating the device.
NOTICE: Damage
In order to ensure the degree of protection specified in the technical data, observe the following points:
– A tolerance of ±0.5 mm is maintained for the mounting cutout.
– The seal lies flat against the mounting surface.
– The number of mounting brackets, given in the technical data, is used.
– The material of the mounting surface is sufficiently stable to ensure permanently secure attachment of the operating device.
– The mounting surface and the operating device may not become deformed due to the
effects of the mounting clamps or through the operation of the device.
– The threaded pins of the mounting brackets are tightened uniformly to a maximum
torque of 1 Nm.
The device can be easily and quickly mounted from the rear of the device. A panel thickness
of 1 mm to 6 mm (0.039" to 0.236") is permitted for proper mounting.
1. Cut the mounting cutout in the housing for the device size to be installed.
2. Push the device through the mounting cutout from the front.
B
A
Figure 2-1
3.
4.
5.
12
PHOENIX CONTACT
C
Mounting the device using a mounting bracket
Fix the mounting brackets in the recesses provided (A).
Pull the mounting brackets down until the snap into place (B).
Secure the device using the threaded pins (C).
108594_en_04
Installation and Commissioning
Front Panel Dimensions
2.2.1.1
7" Display (resistive)
147
2.2.1
203
Figure 2-2
108594_en_04
Front panel (dimensions in mm)
PHOENIX CONTACT
13
WP 4000
7" Display (PCAP)
146,2
2.2.1.2
185,5
Figure 2-3
14
PHOENIX CONTACT
Front panel (dimensions in mm)
108594_en_04
Installation and Commissioning
10.1" Display (PCAP)
199,3
2.2.1.3
262,7
Figure 2-4
108594_en_04
Front panel (dimensions in mm)
PHOENIX CONTACT
15
WP 4000
12.1" Display (PCAP)
229
2.2.1.4
302
Figure 2-5
16
PHOENIX CONTACT
Front panel (dimensions in mm)
108594_en_04
Installation and Commissioning
15.6" Display (PCAP)
278
2.2.1.5
436
Figure 2-6
108594_en_04
Front panel (dimensions in mm)
PHOENIX CONTACT
17
WP 4000
18.5" Display (PCAP)
329
2.2.1.6
485
Figure 2-7
18
PHOENIX CONTACT
Front panel (dimensions in mm)
108594_en_04
Installation and Commissioning
2.2.2
Mounting Cutout
2.2.2.1
7" Display (resistive)
147
139 ±0,5
A
B
195 ±0,5
203
Figure 2-8
A
B
108594_en_04
Mounting cutout (dimensions in mm)
Mounting Cutout
Front Panel
PHOENIX CONTACT
19
WP 4000
2.2.2.2
7" Display (PCAP)
136
146,2
A
B
175
185,5
Figure 2-9
A
B
20
PHOENIX CONTACT
Mounting cutout (dimensions in mm)
Mounting Cutout
Front Panel
108594_en_04
Installation and Commissioning
2.2.2.3
10.1" Display (PCAP)
199,3
189
A
B
252
262,7
Figure 2-10
A
B
108594_en_04
Mounting cutout (dimensions in mm)
Mounting Cutout
Front Panel
PHOENIX CONTACT
21
WP 4000
2.2.2.4
12.1" Display (PCAP)
219
229
A
B
292
302
Figure 2-11
A
B
22
PHOENIX CONTACT
Mounting cutout (dimensions in mm)
Mounting Cutout
Front Panel
108594_en_04
Installation and Commissioning
2.2.2.5
15.6" Display (PCAP)
278
260 ±0,5
A
B
425 ±0,5
436
Figure 2-12
A
B
108594_en_04
Mounting cutout (dimensions in mm)
Mounting Cutout
Front Panel
PHOENIX CONTACT
23
WP 4000
2.2.2.6
18.5" Display (PCAP)
329
311 ±0,5
A
B
475 ±0,5
485
Figure 2-13
A
B
24
PHOENIX CONTACT
Mounting cutout (dimensions in mm)
Mounting Cutout
Front Panel
108594_en_04
Installation and Commissioning
2.2.3
Side View, Mounting Depth
2.2.3.1
7" Display (resistive)
43
1
2
3
4
5
Figure 2-14
1
2
3
4
5
108594_en_04
Side view, mounting depth (dimensions in mm)
Mounting Bracket
Threaded Pin
Mounting Surface Thickness 1 mm to 6 mm
Circumferential Seal
Front Panel
PHOENIX CONTACT
25
WP 4000
2.2.3.2
7" Display (PCAP)
45
1
2
3
4
5
Figure 2-15
1
2
3
4
5
26
PHOENIX CONTACT
Side view, mounting depth (dimensions in mm)
Mounting Bracket
Threaded Pin
Mounting Surface Thickness 1 mm to 6 mm
Circumferential Seal
Front Panel
108594_en_04
Installation and Commissioning
2.2.3.3
10.1" Display (PCAP)
45
1
2
3
4
5
Figure 2-16
1
2
3
4
5
108594_en_04
Side view, mounting depth (dimensions in mm)
Mounting Bracket
Threaded Pin
Mounting Surface Thickness 1 mm to 6 mm
Circumferential Seal
Front Panel
PHOENIX CONTACT
27
WP 4000
2.2.3.4
12.1" Display (PCAP)
45
1
2
3
4
5
Figure 2-17
1
2
3
4
5
28
PHOENIX CONTACT
Side view, mounting depth (dimensions in mm)
Mounting Bracket
Threaded Pin
Mounting Surface Thickness 1 mm to 6 mm
Circumferential Seal
Front Panel
108594_en_04
Installation and Commissioning
2.2.3.5
15.6" Display (PCAP)
53
1
2
3
4
5
Figure 2-18
1
2
3
4
5
108594_en_04
Side view, mounting depth (dimensions in mm)
Mounting Bracket
Threaded Pin
Mounting Surface Thickness 1 mm to 6 mm
Circumferential Seal
Front Panel
PHOENIX CONTACT
29
WP 4000
2.2.3.6
18.5" Display (PCAP)
53
1
2
3
4
5
Figure 2-19
1
2
3
4
5
30
PHOENIX CONTACT
Side view, mounting depth (dimensions in mm)
Mounting Bracket
Threaded Pin
Mounting Surface Thickness 1 mm to 6 mm
Circumferential Seal
Front Panel
108594_en_04
Installation and Commissioning
2.3
Connecting the Device
2.3.1
Supply Voltage
The supply voltage is supplied via pin strip X1. A suitable socket strip is supplied.
Refer to the technical data for the permissible supply voltage of the operating device.
NOTICE: Damage
The operating device has to be supplied by a power source, which meets the requirements for SELV / Limited energy circuit in accordance with EN 61010-1 / IEC 61010-1 or
Class 2 in accordance with UL 1310 or Limited Power Source (LPS) in accordance with
EN 60950-1 / IEC 60950-1.
NOTICE: Damage
For UL 61010, an 4 A (or smaller) fuse, either standard or electronic, or circuit breaker
must be installed between the 24 V DC external power supply and the operating device.
The fuse / circuit breaker must be rated at 30 V DC and be a UL listed component.
The device has reverse polarity protection. In case of wrong polarity, the device will not
operate.
Connector in the operating device: 3 pin pin strip
Table 2-1
Pin
Pin assignment supply voltage
Designation
1
Function
Functional earth ground (FE)
2
0V
Supply voltage 0 V (GND)
3
24 V
Supply voltage 24 V
DANGER: Hazardous voltages
Hazardous voltages can exist inside electrical installations that can pose a danger to humans. Coming in contact with live parts may result in electric shock!
NOTICE: Damage
Cables with finely stranded copper conductors with a minimum cross-section of 0.75 mm²
(18 AWG) and a maximum cross-section of 2.5 mm² (14 AWG) must be used for the supply voltage.
You must adhere to the following torques at the connector:
Screw connection of terminal blocks: 0.22 Nm (minimal) to 0.25 Nm (maximum)
Screw flange: 0.3 Nm (maximum)
Use the following procedure to connect the device to the supply voltage:
1. Strip approx. 30 mm (1.181") off the outer cable sheath and approx. 5 mm (0.197") off
the wires.
Figure 2-20
108594_en_04
Preparing the cable
PHOENIX CONTACT
31
WP 4000
2.
3.
4.
Fit the wires with wire end ferrules and connect the wires to the socket strip.
Plug the socket strip onto pin strip X1.
Secure the socket strip in place with a screw-type locking to prevent it from slipping out.
2.3.2
Grounding
The grounding is performed with a slip-on sleeve (noiseless ground / functional earth
ground).
NOTICE: Damage
A separate copper conductor must always be provided for the grounding. The conductor
must have a minimum cross-section of 1.5 mm² (16 AWG) and must be kept as short as
possible.
1.
2.
3.
Strip approx. 5 mm (0.197") off the wires.
Fit the stripped wires with a slip-on sleeve.
Plug the slip-on sleeve on the flat tab.
Figure 2-21
32
PHOENIX CONTACT
Noiseless ground
108594_en_04
Installation and Commissioning
2.4
Switching On
When switching on the operating system loads. The interface for microSDHC cards is available for applications and other data.
Please also pay attention to the further information in the user manual of your software option at phoenixcontact.net/products.
2.5
Identification
The operating device can be identified using the nameplate on the rear of the device.
Ord. No. 1065546
Type: WP 4000
1
3
5
2
4
1067721-00
1065546/P29/R34/M76/O00/D31
MAC 00-AA-00-00-00-00
Un:
6
SNR: 201800000000
15
PHOENIX CONTACT GmbH & Co. KG
Flachsmarktstraße 8, 32825 Blomberg, Germany
Figure 2-22
1
2
3
4
5
6
24 V In: 0.4 A
Nameplate (example)
Article Number, Device Type
Version Software (at time of delivery)
Orderkey
MAC Address(es)
Voltage and Current
Serial Number
2.5.1
Orderkey
The configuration of the operating device can be read from the options in the orderkey on
the nameplate.
Table 2-2
108594_en_04
Orderkey
Key
Option
Configuration
D31
Display
7" LCD projected capacitive
D36
Display
7" LCD resistive
D35
Display
10,1" LCD projected capacitive
D33
Display
12,1" LCD projected capacitive
D28
Display
15.6" LCD projected capacitive
D29
Display
18.5" LCD projected capacitive
PHOENIX CONTACT
33
WP 4000
Table 2-2
34
PHOENIX CONTACT
Orderkey
Key
Option
Configuration
P29
Processor
ARM Cortex-A53, 4x 1.2 GHz
P31
Processor
ARM Cortex-A53, 4x 1.2 GHz TPM
R34
Main memory
1 GB LPDDR3
M76
Master storage
8 GB eMMC Flash
O00
Options
No options
108594_en_04
Control and Display Elements
3
Control and Display Elements
3.1
Touchscreen
The device is equipped with a touch screen. You operate the device using this touch screen.
Note the following for devices equipped with a resistive 4-wire touch screen:
NOTICE: Damage
Pointed or sharp objects, such as pens or fingernails, can lead to irreparable damages of
the touch screen. Exclusively therefore use the fingertips or the aids indicated in the technical data for the operation.
3.2
Display
DANGER: Toxic
If the display is damaged, avoid touching, swallowing or breathing in the liquids or gases
which may leak out!
DANGER: Corrosive
If the display is damaged, avoid touching, swallowing or breathing in the liquids or gases
which may leak out!
Pixel failures, which can occur with TFT displays, are due to production and no complaint
reason!
The operating device is equipped with different displays (see technical data) depending on
variant.
108594_en_04
PHOENIX CONTACT
35
WP 4000
3.3
Status LEDs
Next to the slot for the microSD / microSDHC memory card there are status LEDs.
1 2
Figure 3-1
Position of the status LEDs
The status LEDs have the following functions:
Table 3-1
Status LEDs
LED
Color
State
Designation
Function
1
Green
Flashing
Heartbeat
The bootloader and the image has been started
Off
2
Green
On
Off
36
PHOENIX CONTACT
The operating device could
not be started properly
Power
Supply voltage available
Supply voltage not available
108594_en_04
Interfaces of the Device
4
Interfaces of the Device
4.1
Standard Interfaces
1
Figure 4-1
1
2
3
4
5
6
7
108594_en_04
2
3 4
5
6
7
Rear view Ethernet
Female Connector X5 (Ethernet)
Female Connector X9, X10 (USB Host - Type A)
Status LED LD1 (Heartbeat)
Status LED LD2 (Power)
Slot for microSD- / microSDHC Memory Card
Connector X1 (Supply Voltage)
Flat Push-on Connection for Noiseless Grounding
PHOENIX CONTACT
37
WP 4000
4.1.1
Ethernet (X5)
A 10/100Base-T Ethernet interface is located at the operating device.
4.1.1.1
Pin Assignment
Connector in the operating device: RJ45 female connector.
Table 4-1
Pin
Assignment of the Ethernet interface
Designation
Function
1
Tx+
Transmitted Data, Positive Polarity
2
Tx-
Transmitted Data, Negative Polarity
3
Rx+
Received Data, Positive Polarity
4
n.c.
Not Connected
5
n.c.
Not Connected
6
Rx-
Received Data, Negative Polarity
7
n.c.
Not Connected
8
n.c.
Not Connected
4.1.1.2
Cable
NOTICE
Use a twisted pair cable of category 5 (CAT 5). The maximum cable length is 100 m
(328.084 feet).
See the IEEE 802.3 standard for further information.
38
PHOENIX CONTACT
108594_en_04
Interfaces of the Device
4.1.1.3
Diagnostics
Ethernet diagnostics LEDs are located at the operating device.
Figure 4-2
Position of the ethernet diagnostics LEDs
Table 4-2
Ethernet diagnostics LEDs
LED
Color
State
Designation
Function
1
Green
On
ACT/LNK
Connected
Flashing
2
Yellow
On
Off
4.1.2
Sending / receiving ethernet
data telegram
SPD 10/100
Operation in 100 MBit/s mode
Operation in 10 MBit/s mode
or disconnected
USB (X9, X10)
Two host interfaces are available on the operating device.
NOTICE:
Using hardware not suitable for industrial use (for example keyboard, mouse, memory
card) in industrial environments may decrease safety of operation. This includes hardware intended for home and office use.
4.1.2.1
Cable
For the specification of a suitable cable, please refer to the „Universal Serial Bus Specification“.
NOTICE:
Use industrial-suited USB cables with a length of maximally 2.5 m (8.202 feet).
108594_en_04
PHOENIX CONTACT
39
WP 4000
4.1.3
Memory Card
At the underside of the operating device you can plug in an microSD / microSDHC card.
NOTICE:
Using hardware not suitable for industrial use (for example keyboard, mouse, memory
card) in industrial environments may decrease safety of operation. This includes hardware intended for home and office use.
4.1.3.1
Inserting the memory card
When you insert the memory card, make sure the front side (side with contacts is below) of
the memory card is visible. Insert the memory card until it snaps into place.
Figure 4-3
4.1.3.2
Inserting the memory card
Ejecting the memory card
To remove, push the memory card into the operating device until it clicks. The memory card
bounces when released automatically out of the operating device. Now you can remove the
memory card.
40
PHOENIX CONTACT
108594_en_04
Maintenance and Servicing
5
Maintenance and Servicing
5.1
Front Panel
Use a damp cloth to remove any dirt from the front panel. You also can use Isopropanol for
stronger pollutions.
5.2
Fuse
NOTICE: Damage
The semiconductor fuse cannot be replaced!
A semiconductor fuse is used to protect the device. Once the fuse has been tripped, the device must be disconnected from the supply voltage to allow the semiconductor fuse to regenerate. At an ambient temperature of 20 °C (68 °F), the regeneration takes approximately
20 seconds. The higher the ambient temperature, the longer the regeneration takes.
108594_en_04
PHOENIX CONTACT
41
WP 4000
42
PHOENIX CONTACT
108594_en_04
Technical Data
6
Technical Data
6.1
General
Ethernet
X5 Ethernet
10/100Base-T
USB
Corresponds to the „Universal serial bus specification Rev. 2.0“
X9, X10 Host
Min.: 1.5 Mbit/s
Max.: 12 Mbit/s
Max. output current 100 mA per output
Beeper
Sound pressure level
At most 85 db at a distance of 10 (3.937“) cm without shielding.
The sound pressure level of the mounted operating device is dependent on the shielding at the mounting place.
Central Processing Unit
Central processing unit
ARM Cortex™-A53
Clock frequency
1,2 GHz quad-core
Other features
Real-time clock (typical deviation is approx. 2 minutes per month)
Real-time Clock
The real-time clock is buffered with a capacitor.
The capacitor reaches its maximum capacity after approximately 30 minutes of continuous charging.
After a maximum charge, the real-time clock can be buffered approximately 10 days.
Memory
RAM
1 GByte LPDDR3
Mass storage
8 GByte eMMC
microSD/microSDHC interface
2 GByte / 32 GByte maximum
Connection System
Male connector strip Phoenix MINI-COMBICON, 3 pin (Art.-No. 1847068)
RJ45 male connector
USB male connector type A
108594_en_04
PHOENIX CONTACT
43
WP 4000
Standards and Guidelines
Interference immunity
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
EN 61000-4-6
EN 61000-6-2
Emitted interference
EN 55011 limit value class A
EN 55032 limit value class A
EN 61000-6-4
Equipment requirements
EN 61131-2
Storage and
transportation
EN 61131-2
Power supply
EN 61131-2
Electromagnetic
compatibility
2014/30/EU
Degrees of protection
EN 60529
Impact load, shocks
EN 60068-2-27
Sinusoidal vibrations
EN 60068-2-6
NOTICE: Radio Interference
Operation of this device may cause radio interference in residential areas.
44
PHOENIX CONTACT
108594_en_04
Technical Data
6.2
7" Display (resistive)
Touch Screen
Type
Analog resistive, 4 wire technology
Activation force
15 g (Standard)
With R8 HS60 silicon rubber
Durability
No damages or malfunctions after 3 million keystrokes as the following:
Keystroke element: R8, HS40 silicon rubber
Keystroke load: 150 g
Keystroke frequency: 3 Hz
Display
Size (diagonal) in cm (inch)
17.78 (7)
Type
TFT (color)
Resolution (pixels)
800 x 480
Colors
262144
Viewing angle (left / right / up / down)
in °
70 / 70 / 65 / 65
Half-life backlighting
40,000 h
Brightness in cd/m2
350
Display area (H x W) in mm (Inch)
91.4 x 152.4 (3.598 x 6.0)
Environmental Conditions
Temperature during
operation
0 °C to 50 °C (32 °F to 122 °F) - (with order key option P29 / P31)
Temperature during
storage, transport
- 25 °C to + 70 °C (- 13°F to + 158 °F)
Relative air humidity for operation and
storage
20 % to 85 %, no condensation
Application area
Degree of pollution 2, overvoltage category II
No direct solar radiation
Electrical Data
Supply voltage
24 V DC (SELV / Limited energy circuit in accordance with EN 61010-1 / IEC 61010-1 or Class 2 in accordance with
UL 1310 or Limited Power Source (LPS) in accordance with EN 60950-1 / IEC 60950-1)
Residual ripple
10 % maximum
Minimum voltage
18 V
Maximum voltage
30 V
Power consumption (typical at 24 V)
0.4 A
Connected load
9.6 W
Fuse
Semiconductor fuse, self-resetting
Protection against
polarity reversal
Integrated
108594_en_04
PHOENIX CONTACT
45
WP 4000
Front Panel and Enclosure
Enclosure
Steel sheet, galvanized
Front panel material
Aluminium, brushed, anodized natural finish
Front panel (H x W x D) in mm (Inch)
147 x 203 x 5 (5.787 x 7.992 x 0.197)
Seal
Circumferential rubber seal on the rear
Mounting cutout (H x W) in mm (Inch)
139 x 195 (5.7472 x 7.677)
Mounting brackets
6
Mounting depth in mm (Inch)
About 43 mm (1.692)
Degree of protection
Front: IP65 / NEMA Enclosure Type 1 (indoor use only)
Rear: IP20
Total weight
About 750 g
Approvals
CE approval
CE
UL approval
UL / cUL
46
PHOENIX CONTACT
108594_en_04
Technical Data
6.3
7" Display (PCAP)
Touch Screen
Type
Projected capacitive
Operation
With the finger
Display
Size (diagonal) in cm (inch)
17.78 (7)
Type
TFT (color)
Resolution (pixels)
1280 x 800
Colors
16.77 million
Viewing angle (left / right / up / down)
in °
85 / 85 / 85 / 85
Half-life backlighting
50,000 h
Brightness in cd/m2
500
Display area (H x W) in mm (Inch)
91.4 x 152.4 (3.598 x 6.0)
Environmental Conditions
Temperature during
operation
0 °C to 50 °C (32 °F to 122 °F) - (with order key option P29 / P31)
Temperature during
storage, transport
- 20 °C to + 60 °C (- 4 °F to 140 °F)
Relative air humidity for operation and
storage
Front: 5 % to 95 %, no condensation
Rear: 20 % to 85 %, no condensation
Application area
Degree of pollution 2, overvoltage category II
No direct solar radiation
Electrical Data
Supply voltage
24 V DC (SELV / Limited energy circuit in accordance with EN 61010-1 / IEC 61010-1 or Class 2 in accordance with
UL 1310 or Limited Power Source (LPS) in accordance with EN 60950-1 / IEC 60950-1)
Residual ripple
10 % maximum
Minimum voltage
18 V
Maximum voltage
30 V
Power consumption (typical at 24 V)
0.4 A
Connected load
9.6 W
Fuse
Semiconductor fuse, self-resetting
Protection against
polarity reversal
Integrated
Front Panel and Enclosure
Enclosure
Steel sheet, galvanized
Front panel material
Aluminium, brushed, anodized natural finish
Front panel (H x W x D) in mm (Inch)
146.2 x 185.5 x 6 (5.755 x 7.303 x 0.236)
Seal
Flat gasket on the rear
Mounting cutout (H x W) in mm (Inch)
136 x 175 (5.354 x 6.889)
108594_en_04
PHOENIX CONTACT
47
WP 4000
Front Panel and Enclosure
Mounting brackets
6
Mounting depth in mm (Inch)
About 45 (1.771)
Degree of protection
Front: IP65 / NEMA Enclosure Type 4 (indoor use only)
Rear: IP20
Total weight
About 760 g
Approvals
CE approval
CE
UL approval
UL / cUL
48
PHOENIX CONTACT
108594_en_04
Technical Data
6.4
10.1" Display (PCAP)
Touch Screen
Type
Projected capacitive
Operation
With the finger
Display
Size (diagonal) in cm (inch)
25.65 (10.1)
Type
TFT (color)
Resolution (pixels)
1280 x 800
Colors
16.77 million
Viewing angle (left / right / up / down)
in °
85 / 85 / 85 / 85
Half-life backlighting
50,000 h
Brightness in cd/m2
850
Display area (H x W) in mm (Inch)
217 x 136 (8.543 x 5.354)
Environmental Conditions
Temperature during
operation
0 °C to 50 °C (32 °F to 122 °F) - (with order key option P29 / P31)
Temperature during
storage, transport
- 20 °C to + 60 °C (- 4 °F to 140 °F)
Relative air humidity for operation and
storage
Front: 5 % to 95 %, no condensation
Rear: 20 % to 85 %, no condensation
Application area
Degree of pollution 2, overvoltage category II
No direct solar radiation
Electrical Data
Supply voltage
24 V DC (SELV / Limited energy circuit in accordance with EN 61010-1 / IEC 61010-1 or Class 2 in accordance with
UL 1310 or Limited Power Source (LPS) in accordance with EN 60950-1 / IEC 60950-1)
Residual ripple
10 % maximum
Minimum voltage
18 V
Maximum voltage
30 V
Power consumption (typical at 24 V)
0.6 A
Connected load
14.4 W
Fuse
Semiconductor fuse, self-resetting
Protection against
polarity reversal
Integrated
Front Panel and Enclosure
Enclosure
Steel sheet, galvanized
Front panel material
Aluminium, brushed, anodized natural finish
Front panel (H x W x D) in mm (Inch)
199.3 x 262.7 x 6 (7.846 x 10.342 x 0.236)
Seal
Flat gasket on the rear
Mounting cutout (H x W) in mm (Inch)
189 x 252 (7.44 x 9.921)
108594_en_04
PHOENIX CONTACT
49
WP 4000
Front Panel and Enclosure
Mounting brackets
6
Mounting depth in mm (Inch)
About 45 (1.771)
Degree of protection
Front: IP65 / NEMA Enclosure Type 4 (indoor use only)
Rear: IP20
Total weight
About 1270 g
Approvals
CE approval
CE
UL approval
UL / cUL
50
PHOENIX CONTACT
108594_en_04
Technical Data
6.5
12.1" Display (PCAP)
Touch Screen
Type
Projected capacitive
Operation
With the finger
Display
Size (diagonal) in cm (inch)
30.73 (12.1)
Type
TFT (color)
Resolution (pixels)
1280 x 800
Colors
16.77 million
Viewing angle (left / right / up / down)
in °
85 / 85 / 85 / 85
Half-life backlighting
50,000 h
Brightness in cd/m2
380
Display area (H x W) in mm (Inch)
163.2 x 261.1 (6.425 x 10.28)
Environmental Conditions
Temperature during
operation
0 °C to 50 °C (32 °F to 122 °F) - (with order key option P29 / P31)
Temperature during
storage, transport
- 20 °C to + 60 °C (- 4 °F to 140 °F)
Relative air humidity for operation and
storage
Front: 5 % to 95 %, no condensation
Rear: 20 % to 85 %, no condensation
Application area
Degree of pollution 2, overvoltage category II
No direct solar radiation
Electrical Data
Supply voltage
24 V DC (SELV / Limited energy circuit in accordance with EN 61010-1 / IEC 61010-1 or Class 2 in accordance with
UL 1310 or Limited Power Source (LPS) in accordance with EN 60950-1 / IEC 60950-1)
Residual ripple
10 % maximum
Minimum voltage
18 V
Maximum voltage
30 V
Power consumption (typical at 24 V)
0.7 A
Connected load
16.8 W
Fuse
Semiconductor fuse, self-resetting
Protection against
polarity reversal
Integrated
Front Panel and Enclosure
Enclosure
Steel sheet, galvanized
Front panel material
Aluminium, brushed, anodized natural finish
Front panel (H x W x D) in mm (Inch)
229 x 302 x 6 (9.015 x 11.889 x 0.236)
Seal
Flat gasket on the rear
Mounting cutout (H x W) in mm (Inch)
219 x 292 (8.622 x 11.496)
108594_en_04
PHOENIX CONTACT
51
WP 4000
Front Panel and Enclosure
Mounting brackets
8
Mounting depth in mm (Inch)
About 45 (1.771)
Degree of protection
Front: IP65 / NEMA Enclosure Type 4 (indoor use only)
Rear: IP20
Total weight
About 1650 g
Approvals
CE approval
CE
UL approval
UL / cUL
52
PHOENIX CONTACT
108594_en_04
Technical Data
6.6
15.6" Display (PCAP)
Touch Screen
Type
Projected capacitive
Operation
With the finger
Display
Size (diagonal) in cm (inch)
39.6 (15.6)
Type
TFT (color)
Resolution (pixels)
1366 x 768
Colors
16.77 million
Viewing angle (left / right / up / down)
in °
80 / 80 / 80 / 80
Half-life backlighting
70.000 h
Brightness in cd/m2
320
Display area (H x W) in mm (Inch)
194 x 344 (7.637 x 13.543)
Environmental Conditions
Temperature during
operation
0 °C to 50 °C (32 °F to 122 °F) - (with order key option P29 / P31)
Temperature during
storage, transport
- 25 °C bis + 70 °C (- 13°F to + 158 °F)
Relative air humidity for operation and
storage
Front: 5 % to 95 %, no condensation
Rear: 20 % to 85 %, no condensation
Application area
Degree of pollution 2, overvoltage category II
No direct solar radiation
Electrical Data
Supply voltage
24 V DC (SELV / Limited energy circuit in accordance with EN 61010-1 / IEC 61010-1 or Class 2 in accordance with
UL 1310 or Limited Power Source (LPS) in accordance with EN 60950-1 / IEC 60950-1)
Residual ripple
10 % maximum
Minimum voltage
18 V
Maximum voltage
30 V
Power consumption (typical at 24 V)
1A
Connected load
24 W
Fuse
Semiconductor fuse, self-resetting
Protection against
polarity reversal
Integrated
Front Panel and Enclosure
Enclosure
Steel sheet, galvanized
Front panel material
Aluminium, brushed, anodized natural finish
Front panel (H x W x D) in mm (Inch)
278 x 436 x 6 (10.944 x 17.165 x 0.236)
Seal
Flat gasket on the rear
Mounting cutout (H x W) in mm (Inch)
260 x 425 (10.236 x 16.732)
108594_en_04
PHOENIX CONTACT
53
WP 4000
Front Panel and Enclosure
Mounting brackets
12
Mounting depth in mm (Inch)
About 53 (2.086)
Degree of protection
Front: IP65 / NEMA Enclosure Type 1 (indoor use only)
Rear: IP20
Total weight
About 4000 g
Approvals
CE approval
CE
UL approval
UL / cUL
54
PHOENIX CONTACT
108594_en_04
Technical Data
6.7
18.5" Display (PCAP)
Touch Screen
Type
Projected capacitive
Operation
With the finger
Display
Size (diagonal) in cm (inch)
47 (18.5)
Type
TFT (color)
Resolution (pixels)
1366 x 768
Colors
16.77 million
Viewing angle (left / right / up / down)
in °
85 / 85 / 80 / 80
Half-life backlighting
50,000 h
Brightness in cd/m2
240
Display area (H x W) in mm (Inch)
230 x 410 (9.055 x 16.141)
Environmental Conditions
Temperature during
operation
0 °C to 50 °C (32 °F to 122 °F) - (with order key option P29 / P31)
Temperature during
storage, transport
- 20 °C to + 60 °C (- 4 °F to 140 °F)
Relative air humidity for operation and
storage
Front: 5 % to 95 %, no condensation
Rear: 20 % to 85 %, no condensation
Application area
Degree of pollution 2, overvoltage category II
No direct solar radiation
Electrical Data
Supply voltage
24 V DC (SELV / Limited energy circuit in accordance with EN 61010-1 / IEC 61010-1 or Class 2 in accordance with
UL 1310 or Limited Power Source (LPS) in accordance with EN 60950-1 / IEC 60950-1)
Residual ripple
10 % maximum
Minimum voltage
18 V
Maximum voltage
30 V
Power consumption, typical at 24 V
(standard / field bus)
1.2 A
Connected load
(standard / field bus)
28.8 W
Fuse
Semiconductor fuse, self-resetting
Protection against
polarity reversal
Integrated
Front Panel and Enclosure
Enclosure
Steel sheet, galvanized
Front panel material
Aluminium, brushed, anodized natural finish
Front panel (H x W x D) in mm (Inch)
329 x 485 x 8 (12.952 x 19.094 x 0.314)
108594_en_04
PHOENIX CONTACT
55
WP 4000
Front Panel and Enclosure
Seal
Flat gasket on the rear
Mounting cutout (H x W) in mm (Inch)
311 x 475 (12.244 x 18.7)
Mounting brackets
12
Mounting depth in mm (Inch) - (standard / field bus)
About 53 (2.086)
Degree of protection
Front: IP65 / NEMA Enclosure Type 1 (indoor use only)
Rear: IP20
Total weight
About 5500 g
Approvals
CE approval
CE
UL approval
UL / cUL
56
PHOENIX CONTACT
108594_en_04
A1
Index
C
Cable
Ethernet................................................................. 38
USB....................................................................... 39
Connecting.................................................................. 31
D
Diagnostics
Ethernet.................................................................
Dimensions
Cutout....................................................................
Front panel ............................................................
Display ........................................................................
Mounting depth
10.1" Display (PCAP) ............................................
12.1" Display (PCAP) ............................................
15.6" Display (PCAP) ............................................
18.5" Display (PCAP) ............................................
7" Display (PCAP) .................................................
7" Display (resistive)..............................................
27
28
29
30
26
25
N
39
Nameplate .................................................................. 33
19
13
35
P
Pin assignment
Ethernet................................................................. 38
F
Front panel dimensions
10.1" Display (PCAP) ............................................
12.1" Display (PCAP) ............................................
15.6" Display (PCAP) ............................................
18.5" Display (PCAP) ............................................
7" Display (PCAP) .................................................
7" Display (resistive)..............................................
Fuse ............................................................................
R
15
16
17
18
14
13
41
I
Identification................................................................ 33
Intended use ................................................................. 8
Interface
Ethernet................................................................. 38
USB....................................................................... 39
M
Maintenance ...............................................................
Memory card ...............................................................
Mounting .....................................................................
Mounting cutout
10.1" Display (PCAP) ............................................
12.1" Display (PCAP) ............................................
15.6" Display (PCAP) ............................................
18.5" Display (PCAP) ............................................
7" Display (PCAP) .................................................
7" Display (resistive)..............................................
108594_en_04
41
40
12
21
22
23
24
20
19
Rear view
Ethernet................................................................. 37
S
Safety notes .................................................................. 7
Servicing ..................................................................... 41
Side view
10.1" Display (PCAP) ............................................ 27
12.1" Display (PCAP) ............................................ 28
15.6" Display (PCAP) ............................................ 29
18.5" Display (PCAP) ............................................ 30
7" Display (PCAP) ................................................. 26
7" Display (resistive).............................................. 25
Standards ................................................................... 44
Supply Voltage............................................................ 31
Switching on ............................................................... 33
Symbols ........................................................................ 7
T
Target group ................................................................. 9
Technical data ............................................................ 43
10.1" Display (PCAP) ............................................ 49
12.1" Display (PCAP) ............................................ 51
15,6" Display (PCAP) ............................................ 53
18.5" Display (PCAP) ............................................ 55
7" Display (PCAP) ................................................. 47
7" Display (resistive).............................................. 45
PHOENIX CONTACT
57
WP 4000
Touchscreen ............................................................... 35
U
Unpacking................................................................... 11
V
Version........................................................................ 33
58
PHOENIX CONTACT
108594_en_04