2-channel electronic circuit breaker module for protecting 12 V DC and 24 V DC loads against overload and short circuit. Nominal
current adjustable from 2 A to 10 A via step switch. EX e approval for zone 2. For DIN rail installation via the CAPAROC current rails.
Your advantages
• The customizable standard, thanks to individual combinations of the future-proof modular system
• Easy operation for everyone through tool-free assembly, uninterrupted installation, and transparent operating state
• Strikingly simple design-in with extensive support from the selection up to digital services
Commercial data
Item number
1344364
Packing unit
1 pc
Minimum order quantity
1 pc
Sales key
CL11
Product key
CLA233
GTIN
4063151658120
Weight per piece (including packing)
96.7 g
Weight per piece (excluding packing)
89.55 g
Customs tariff number
85363010
Country of origin
DE
Jan 8, 2024, 9:55 AM
Page 1 (15)
CAPAROC E2 12-24DC/2-10A EX - Electronic circuit
breaker
1344364
https://www.phoenixcontact.com/us/products/1344364
Technical data
Notes
General
Note
LABS release – in accordance with test specification VW PV 3.
10.7:2005-0
When connecting the conductor, make sure that the CAPAROC
modules are not pulled apart due to tensile force. Gaps must not
be created between the modules.
Observe the specified conditions for use in potentially explosive
areas. Install the device in a suitable approved housing with at
least IP54 degree of protection that meets the requirements of
IEC/EN 60079-0. Also observe the requirements of
IEC/EN 60079-14.
Product properties
Type
Plug-in module
Product type
Device circuit breakers
Product family
CAPAROC
Number of positions
1
No. of channels
2
Number of slots
2
Insulation characteristics
Protection class
III
Pollution degree
2
Electrical properties
No. of channels
2
General
Operating voltage
10 V DC ... 30 V DC
Rated voltage
12 V DC
24 V DC
Rated current IN
10 A DC (per channel)
Rated current IN
2 / 4 / 6 / 8 / 10 A DC (Adjustable via rotary coding switches)
1 / 2 / 3 / 4 / 5 / 6 / 7 / 8 / 9 / 10 A DC (can be set, in RC mode via
power module with communication interface)
Rated current (pre-adjusted)
2A
Rated surge voltage
0.5 kV
Tripping method
E (electronic)
Feedback resistance
max. 35 V DC
Switch-on delay
50 ms (each channel preset by default)
can be adapted with CAPAROC PM IOL and CAPAROC PM PN
power modules
Required backup fuse
Only required if Imax of the power supply > the short-circuit
switching capacity. Integrated failsafe element.
Jan 8, 2024, 9:55 AM
Page 2 (15)
CAPAROC E2 12-24DC/2-10A EX - Electronic circuit
breaker
1344364
https://www.phoenixcontact.com/us/products/1344364
Short-circuit switching capacity
300 A
Dielectric strength
35 V DC (Load circuit)
Active current limitation
typ. 2.0 x IN at IN ≤ 3 A
typ. 1.5 x IN at IN ≥ 4 A
Fuse
electronic
Efficiency
> 99 %
Closed circuit current I0
typ. 25 mA (no load at 24 V)
Power dissipation
typ. 0.6 W (no load at 24 V)
< 3.3 W (in nominal operation at 24 V and 10 A)
Measuring tolerance I
± 10 % (typ.)
Temperature derating
20 A (Total current at 40°C)
10 A (Total current at 65 °C)
MTBF (IEC 61709, SN 29500)
11140621 h (at 25 °C with 21 % load)
4699883 h (at 40°C with 34.25% load)
534110 h (at 40°C with 100% load)
Voltage drop
0.14 V (at 10 A)
Fail-safe element
15 A DC (per output channel)
Load circuit
Shutdown time
5 s (for overload 1.1…1.3 x IN at IN ≥ 4 A)
5 s (for overload 1.1…1.7 x IN at IN < 4 A)
typ. 400 ms (max. 450 ms for high starting currents)
typ. 20 ms (for short circuit > 1,5 x IN)
Undervoltage switch-off
≤ 8.5 V DC (active)
≥ 9.2 V DC (inactive)
Overvoltage switch-off
≥ 32.5 V DC (active)
≤ 30.5 V DC (inactive)
Max. capacitive load
≤ 75000 µF (Depending on the current setting and the shortcircuit current available)
Connection data
Fuse-protected output
Connection method
Push-in connection
Stripping length
10 mm
Conductor cross section flexible
0.2 mm² ... 4 mm²
Conductor cross section rigid
0.2 mm² ... 4 mm²
Conductor cross section AWG
24 ... 12
Conductor cross section, flexible, with ferrule, with plastic sleeve
0.25 mm² ... 4 mm²
Conductor cross section flexible, with ferrule without plastic
sleeve
0.25 mm² ... 4 mm²
Signaling
Channel LED off
off (Channel switched off)
Channel LED yellow
lit (Channel switched on, channel load > 80% )
two flashes (Check the installation, no communication to power
Jan 8, 2024, 9:55 AM
Page 3 (15)
CAPAROC E2 12-24DC/2-10A EX - Electronic circuit
breaker
1344364
https://www.phoenixcontact.com/us/products/1344364
module)
Channel LED green
lit (Channel switched on)
flashing (Channel switched on, coding switch position is not
equal to set value)
Channel LED red
lit (Channel switched off, over- or undervoltage active)
ON temporarily (Channel switched off, 5 s cool-down phase,
overload or short-circuit release)
flashing (Channel switched off, ready to be switched back on,
overload or short-circuit release)
two flashes (Channel switched off, system total current limit
exceeded)
Channel LED red-yellow
flashing (Channel is overloaded and is switched off)
Channel LED red-green
flashing (Channel switched off, programming mode active,
current adjustment after overload or short-circuit release)
Dimensions
Dimensional drawing
Width
12.4 mm
Height
132.4 mm
Depth
111.3 mm (incl. DIN rail 7.5 mm)
Material specifications
Material
PA 6
PA 6
PA 6
PC
Flammability rating according to UL 94
V-0
Environmental and real-life conditions
Ambient conditions
Degree of protection
IP20
Ambient temperature (operation)
-30 °C ... 65 °C (The temperature range of the power module
must be taken into consideration)
Ambient temperature (storage/transport)
-40 °C ... 70 °C
Altitude
≤ 4000 m (amsl)
Humidity test
96 h, 95 % RH, 40 °C
Shock (operation)
30g (11 ms period, half-sine shock pulse, according to IEC
60068-2-27)
25g (6 ms duration, half-sine shock pulse in accordance with
IEC 60068-2-27, continuous shock)
Vibration (operation)
5g (10 ... 150 Hz / 10 cycles / axis / X, Y, Z)
Approvals
UL approval
Identification
UL/C-UL Listed UL 508
UL Recognized UL 2367
Jan 8, 2024, 9:55 AM
Page 4 (15)
CAPAROC E2 12-24DC/2-10A EX - Electronic circuit
breaker
1344364
https://www.phoenixcontact.com/us/products/1344364
UL 121201 Class I, Division 2, Groups A, B, C, D, T4A
ATEX
Identification
TÜV 22 ATEX 8874 X
II 3G Ex ec IIC T4 Gc
IECEx
Identification
IECEx TUR 22.0049X
II 3G Ex ec IIC T4 Gc
UKCA Ex (UKEX)
Identification
TÜV 22 UKEX 7109 X
II 3G Ex ec IIC T4 Gc
Standards and regulations
Standards/specifications
EN 61000-6-2
Note
EMC – Immunity for industrial areas
Standards/specifications
EN 61000-6-3
Note
EMC – Emission for residential, business and commercial
properties and small operations
Standards/specifications
EN 60068-2-78
Note
Environmental influences – Moisture and heat, constant
Standards/specifications
EN 50178
Note
Equipping power installations with electronic equipment
Standards/specifications
EN 60068-2-6
Note
Environmental influences – Vibrations (sinusoidal)
Standards/specifications
EN 60068-2-27
Note
Environmental influences – Shocks
Standards/specifications
IEC 60079-7
Note
Explosive atmospheres – Part 7: Equipment protection by
increased safety “e”
Standards/specifications
IEC 60079-0
Note
Explosive atmospheres – Part 0: Equipment – General
requirements
Mounting
Mounting type
pluggable onto CAPAROC CR… current rail
Jan 8, 2024, 9:55 AM
Page 5 (15)
CAPAROC E2 12-24DC/2-10A EX - Electronic circuit
breaker
1344364
https://www.phoenixcontact.com/us/products/1344364
Drawings
Diagram
t
s
1000
Trigger Point
100
10
1
0,1
0,01
0,6
1 1,1
1,7
2
x IN
Tripping characteristic < 4 A
Jan 8, 2024, 9:55 AM
Page 6 (15)
CAPAROC E2 12-24DC/2-10A EX - Electronic circuit
breaker
1344364
https://www.phoenixcontact.com/us/products/1344364
I [A]
Diagram
25
20
15
10
5
0
-40
-20
0
20
40
60
[°C]
Max. permissible current in relation to the ambient temperature
Jan 8, 2024, 9:55 AM
Page 7 (15)
CAPAROC E2 12-24DC/2-10A EX - Electronic circuit
breaker
1344364
https://www.phoenixcontact.com/us/products/1344364
Diagram
t
s
1000
Trigger Point
100
10
1
0,1
0,01
0,6
1 1,1
1,3
1,5
2
x IN
Tripping characteristic ≥ 4 A
Jan 8, 2024, 9:55 AM
Page 8 (15)
CAPAROC E2 12-24DC/2-10A EX - Electronic circuit
breaker
1344364
https://www.phoenixcontact.com/us/products/1344364
Dimensional drawing
111,3
132,4
12,4
Block diagram
IN+ 5.1
IN- 6.1
µC
Current
limitation
CH1
Current
limitation
CH2
OUT+
1.1
1.2
2.1
2.2
CH1
CH2
Jan 8, 2024, 9:55 AM
Page 9 (15)
CAPAROC E2 12-24DC/2-10A EX - Electronic circuit
breaker
1344364
https://www.phoenixcontact.com/us/products/1344364
Approvals
To download certificates, visit the product detail page: https://www.phoenixcontact.com/us/products/1344364
UL Recognized
Approval ID: FILE E 317172
UL Listed
cUL Listed
Approval ID: FILE E 123528
Approval ID: FILE E 123528
IECEx
Approval ID: IECEx TUR 22.0049X
UL Recognized
Approval ID: FILE E 324415
cUL Listed
UL Listed
Approval ID: FILE E 483407
Approval ID: FILE E 483407
X
ATEX
UKCA-EX
Approval ID: TÜV 22 ATEX 8874 X
Approval ID: TÜV 22 UKEX 7109 X
cULus Listed
cULus Listed
Jan 8, 2024, 9:55 AM
Page 10 (15)
CAPAROC E2 12-24DC/2-10A EX - Electronic circuit
breaker
1344364
https://www.phoenixcontact.com/us/products/1344364
Classifications
ECLASS
ECLASS-11.0
27140401
ECLASS-12.0
27140401
ECLASS-13.0
27140401
ETIM
ETIM 9.0
EC003538
Jan 8, 2024, 9:55 AM
Page 11 (15)
CAPAROC E2 12-24DC/2-10A EX - Electronic circuit
breaker
1344364
https://www.phoenixcontact.com/us/products/1344364
Mandatory accessories
CAPAROC CR 20 - Busbar
1110989
https://www.phoenixcontact.com/us/products/1110989
Busbar for CAPAROC system with 20
slots. For installation on a DIN rail.
CAPAROC CR 8 - Busbar
1115672
https://www.phoenixcontact.com/us/products/1115672
Busbar for the CAPAROC system with
8 slots. For installation on a DIN rail.
CAPAROC PM S-R EX - Power module
1344363
https://www.phoenixcontact.com/us/products/1344363
Power module with status output and
reset input for supplying the
CAPAROC circuit breaker system with
12 V DC or 24 V DC. EX e approval
for zone 2. For DIN rail installation via
the CAPAROC current rails.
Accessories
Jan 8, 2024, 9:55 AM
Page 12 (15)
CAPAROC E2 12-24DC/2-10A EX - Electronic circuit
breaker
1344364
https://www.phoenixcontact.com/us/products/1344364
CAPAROC PD 0V - Potential distributors
1110987
https://www.phoenixcontact.com/us/products/1110987
Potential distributor with Push-in
connections for directly connecting the
0 V return conductor in the CAPAROC
system. For DIN rail installation via
the CAPAROC current rails.
UC-TMF 6 - Marker for terminal blocks
0818140
https://www.phoenixcontact.com/us/products/0818140
Marker for terminal blocks, Sheet, white, unlabeled, can be labeled with:
BLUEMARK ID COLOR, BLUEMARK ID, BLUEMARK CLED, PLOTMARK,
CMS-P1-PLOTTER, mounting type: snapped, for terminal block width: 6.2 mm,
lettering field size: 5.6 x 5.1 mm, Number of individual labels: 80
UCT-TMF 6 - Marker for terminal blocks
0828746
https://www.phoenixcontact.com/us/products/0828746
Marker for terminal blocks, Sheet, white, unlabeled, can be labeled with:
TOPMARK NEO, TOPMARK LASER, BLUEMARK ID COLOR, BLUEMARK ID,
BLUEMARK CLED, THERMOMARK PRIME, THERMOMARK CARD 2.0,
THERMOMARK CARD, mounting type: snapped, for terminal block width: 6.2
mm, lettering field size: 5.4 x 4.7 mm, Number of individual labels: 60
Jan 8, 2024, 9:55 AM
Page 13 (15)
CAPAROC E2 12-24DC/2-10A EX - Electronic circuit
breaker
1344364
https://www.phoenixcontact.com/us/products/1344364
UC-TM 12 - Marker for terminal blocks
0819194
https://www.phoenixcontact.com/us/products/0819194
Marker for terminal blocks, Sheet, white, unlabeled, can be labeled with:
BLUEMARK ID COLOR, BLUEMARK ID, BLUEMARK CLED, PLOTMARK,
CMS-P1-PLOTTER, mounting type: snapped, for terminal block width: 12 mm,
lettering field size: 11.45 x 10.5 mm, Number of individual labels: 40
UCT-TM 12 - Marker for terminal blocks
0829144
https://www.phoenixcontact.com/us/products/0829144
Marker for terminal blocks, Sheet, white, unlabeled, can be labeled with:
TOPMARK NEO, TOPMARK LASER, BLUEMARK ID COLOR, BLUEMARK ID,
BLUEMARK CLED, THERMOMARK PRIME, THERMOMARK CARD 2.0,
THERMOMARK CARD, mounting type: snapped, for terminal block width: 12
mm, lettering field size: 10.8 x 9.6 mm, Number of individual labels: 30
CAPAROC CR EXT20 - Busbar
1115674
https://www.phoenixcontact.com/us/products/1115674
Extension busbar with 20 slots for the
CAPAROC system. For installation on
a DIN rail.
Jan 8, 2024, 9:55 AM
Page 14 (15)
CAPAROC E2 12-24DC/2-10A EX - Electronic circuit
breaker
1344364
https://www.phoenixcontact.com/us/products/1344364
CAPAROC CR EXT8 - Busbar
1110990
https://www.phoenixcontact.com/us/products/1110990
Extension busbar with 8 slots for
CAPAROC system. For installation on
a DIN rail.
CAPAROC CR EXT4 - Busbar
1110991
https://www.phoenixcontact.com/us/products/1110991
Extension busbar with 4 slots for the
CAPAROC system. For installation on
a DIN rail.
CAPAROC CR CON - Metal part
1270955
https://www.phoenixcontact.com/us/products/1270955
Metal extension rails from connecting
CAPAROC initial busbars.
Phoenix Contact 2024 © - all rights reserved
https://www.phoenixcontact.com
Phoenix Contact USA
586 Fulling Mill Road
Middletown, PA 17057, United States
(+717) 944-1300
info@phoenixcon.com
Jan 8, 2024, 9:55 AM
Page 15 (15)