Energy storage - UPS-BAT/PB/24DC/20AH
1348516
https://www.phoenixcontact.com/in/products/1348516
Please be informed that the data shown in this PDF document is generated from our Online Catalog. Please find the complete data in the user
documentation. Our General Terms of Use for Downloads are valid.
Energy storage, VRLA-AGM, 24 V DC, 20 Ah, automatic detection and communication with
QUINT UPS-IQ
Product Description
For continuous monitoring and intelligent management, there is constant communication with the QUINT UPS. Thanks to automatic detection of the
energy storage, and tool-free switching during operation, quick installation is possible. The QUINT UPS with IQ technology energy storage leaves
the warehouse fully charged.
Your advantages
• Maximum buffer times
• Consists of 2 x 12 V battery modules and an electronic monitoring unit
• Lead AGM (Absorbent Glass Mat) technology
May 16, 2022, 6:56 AM
Page 1 (9)
Energy storage - UPS-BAT/PB/24DC/20AH
1348516
https://www.phoenixcontact.com/in/products/1348516
Commercial Data
Item number
1348516
Packing unit
1 pc
Minimum order quantity
1 pc
Product Key
CMUEV3
GTIN
4063151665951
Weight per Piece (including packing)
13.4 kg
Weight per Piece (excluding packing)
13.2 kg
Customs tariff number
85072080
Country of origin
CN
May 16, 2022, 6:56 AM
Page 2 (9)
Energy storage - UPS-BAT/PB/24DC/20AH
1348516
https://www.phoenixcontact.com/in/products/1348516
Technical Data
Energy storage
Input voltage
24 V DC (SELV)
End-of-charge voltage
27.6 V (20 °C)
Output current Imax
45 A
Charge current
6A
Nominal capacity
20 Ah
Buffer time
82 min. (10 A)
22 min. (30 A)
Accumulator module service life (according to Eurobat)
8 (20 °C)
Latest startup date (battery only)
12 Months (0 °C ... 20 °C)
Latest startup (battery only) - range
9 Months ... 12 Months (20 °C ... 30 °C)
6 Months ... 9 Months (30 °C ... 40 °C)
Battery type
BB Battery BP 20-12FR
Battery technology
VRLA-AGM
Storage medium
VRLA-AGM
Size designation
Block
Battery pack
yes
Disposal
Used batteries must not be thrown away with household waste,
they should instead be disposed of in accordance with applicable
national regulations.
Connection in parallel
yes
Connection in series
No
IQ-Technology
yes
Temperature sensor
yes
Suitable for fast charging
yes
Output fuse
2x 25 A
Connection data
Conductor connection
Connection method
Push-in connection
rigid
0.75 mm² ... 16 mm²
flexible
0.75 mm² ... 16 mm²
rigid (AWG)
18 ... 4
Stripping length
18 mm
Product properties
Product type
Battery unit
Disposal
Used batteries must not be thrown away with household waste,
they should instead be disposed of in accordance with applicable
national regulations.
Insulation characteristics
May 16, 2022, 6:56 AM
Page 3 (9)
Energy storage - UPS-BAT/PB/24DC/20AH
1348516
https://www.phoenixcontact.com/in/products/1348516
Protection class
III
Degree of pollution
2
Dimensions
Width
155 mm
Height
168 mm
Depth
183 mm
Installation dimensions
Installation distance right/left
0 mm / 0 mm
Installation distance top/bottom
50 mm / 50 mm
Mounting
Mounting position
horizontal DIN rail NS 35, EN 60715
Material specifications
Housing material
Metal
Type of housing
Galvanized sheet steel, powder-coated
Cable / line
Battery connecting cable: 6 mm² 265 mm red/black (A+/-)
Cable cross section
6 mm²
Cable length
265 mm
Color
red/black
Battery connecting cable: 6 mm² 265 mm red/black (B+/-)
Cable cross section
6 mm²
Cable length
265 mm
Color
red/black
Environmental and real-life conditions
Ambient conditions
Degree of protection
IP20
Ambient temperature (storage/transport)
-20 °C ... 40 °C
Ambient temperature (charge)
0 °C ... 40 °C
Ambient temperature (discharge)
-20 °C ... 50 °C
Max. permissible relative humidity (operation)
≤ 95 %
Ex data
Suited for EX-applications
No
May 16, 2022, 6:56 AM
Page 4 (9)
Energy storage - UPS-BAT/PB/24DC/20AH
1348516
https://www.phoenixcontact.com/in/products/1348516
Approvals
DNV GL
Approval ID: TAA0000265
cULus Listed
cULus Listed
Nominal Voltage UN
Nominal Current IN
Cross Section AWG
Cross Section mm2
500 V
41 A
-
-6
Approval ID: FILE E 123528
Approval ID: FILE E 199827
May 16, 2022, 6:56 AM
Page 5 (9)
Energy storage - UPS-BAT/PB/24DC/20AH
1348516
https://www.phoenixcontact.com/in/products/1348516
Classifications
ECLASS
ECLASS-11.0
27050403
ETIM
ETIM 8.0
EC000357
UNSPSC
UNSPSC 21.0
May 16, 2022, 6:56 AM
Page 6 (9)
Energy storage - UPS-BAT/PB/24DC/20AH
1348516
https://www.phoenixcontact.com/in/products/1348516
Environmental Product Compliance
China RoHS
Environmentally Friendly Use Period = 8
For information on hazardous substances, refer to the
manufacturer’s declaration available under “Downloads”
May 16, 2022, 6:56 AM
Page 7 (9)
Energy storage - UPS-BAT/PB/24DC/20AH
1348516
https://www.phoenixcontact.com/in/products/1348516
Accessories
Fuse
Fuse - FUSE 25A/32V ATOF - 2908366
https://www.phoenixcontact.com/in/products/2908366
Fuse, nominal current: 25 A, length: 19.1 mm, width: 5 mm, height: 18.8 mm
Mounting set for securing the batteries
Mounting set for securing the batteries - BATTERY MOUNTING CASE M - 1134645
https://www.phoenixcontact.com/in/products/1134645
Used for mounting batteries that cannot be mounted on DIN rails.
May 16, 2022, 6:56 AM
Page 8 (9)
Energy storage - UPS-BAT/PB/24DC/20AH
1348516
https://www.phoenixcontact.com/in/products/1348516
Mounting set for securing the batteries
Mounting set for securing the batteries - BATTERY MOUNTING KIT - 2320788
https://www.phoenixcontact.com/in/products/2320788
Used for mounting batteries that cannot be mounted on DIN rails.
Mounting set for securing the batteries
Mounting set for securing the batteries - BATTERY MOUNTING CASE - 2320458
https://www.phoenixcontact.com/in/products/2320458
Used for mounting batteries that cannot be mounted on DIN rails.
Phoenix Contact 2022 © - all rights reserved
https://www.phoenixcontact.com
PHOENIX CONTACT (I) Pvt. Ltd.
A-58/2, Okhla Industrial Area, Phase - II, New Delhi-110 020
+91.1275.71420
info@phoenixcontact.co.in
May 16, 2022, 6:56 AM