https://www.phoenixcontact.com/us/produkte/1402262
Sensor/Actuator cable - SAC-8P- 1,0-285/FS SH SCO - 1402262
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in
the user's documentation. Our General Terms of Use for Downloads are valid
(http://download.phoenixcontact.com)
Sensor/Actuator cable, 8-position, PUR, Gray RAL 7001, shielded, Free cable end, on Socket
straight M12-SPEEDCON, A-coded, Cable length: 1 m, Twisted pair cables
as in the figure, but with a gray
conductor
Key commercial data
Packing unit
0
Minimum order quantity
25
GTIN
Custom tariff number
85444290
Country of origin
POLAND
Technical data
General data
Rated current at 40°C
2A
Rated voltage
30 V
Number of positions
8
Volume resistance
≤ 5 mΩ
Insulation resistance
≥ 100 MΩ
Length of cable
1m
Stripping length of the free conductor end
50 mm
Ambient temperature (operation)
-25 °C ... 90 °C (Male connector / female connector)
General characteristics
Coding
A - standard
Surge voltage category
II
Pollution degree
3
Degree of protection
IP65/IP67/IP69K
Contact material
CuZn
Contact surface material
Ni/Au
Contact carrier material
TPU GF
Material of grip body
TPU, hardly inflammable, self-extinguishing
Material, knurls
Zinc die-cast, nickel-plated
08.08.2012 Page 1 / 4
https://www.phoenixcontact.com/us/produkte/1402262
Sensor/Actuator cable - SAC-8P- 1,0-285/FS SH SCO - 1402262
Technical data
General characteristics
Sealing material
NBR
Status display
No
Conductor data
Cable type
PUR, gray, shielded
Cable type (abbreviation)
285
Cable abbreviation
Li12YC11Y-HF
Conductor cross section
4 x 2 x 0.25 mm² (signal line)
Conductor cross section
1x 0.25 mm² (Drain wire)
AWG signal line
24
Conductor structure signal line
32x 0.10 mm
External cable diameter
7.6 mm ± 0.2 mm
Wire colors
white-brown, green-yellow, gray-pink, blue-red
External sheath, color
Gray RAL 7001
Insulation resistance
≥ 100 MΩ*km
Nominal voltage, conductor
350 V
Test voltage, conductor
1200 V
Twisted pairs
2 cores to the pair
Overall twist
4 pairs for core
Shielding
Tinned copper braided shield
Optical shield covering
85 %
Outer sheath, material
PUR
Material conductor insulation
PES
Conductor material
Bare Cu litz wires
Smallest bending radius, movable installation
57 mm
Number of bending cycles
3000000
Bending radius
100 mm
Traversing path
1.2 m
Traversing rate
1.4 m/s
Acceleration
2 m/s²
Ambient temperature (operation)
-50 °C ... 80 °C (cable, fixed installation)
Ambient temperature (operation)
-40 °C ... 80 °C (cable, flexible installation)
Special properties
wear-resistant and notch tough
Resistance to oil
very good oil and chemical resistance
Other resistance
ozone and UV resistant
Classifications
eclass
eCl@ss 4.0
27060306
eCl@ss 4.1
27060306
eCl@ss 5.0
27061801
eCl@ss 5.1
27061801
08.08.2012 Page 2 / 4
https://www.phoenixcontact.com/us/produkte/1402262
Sensor/Actuator cable - SAC-8P- 1,0-285/FS SH SCO - 1402262
Classifications
eclass
eCl@ss 6.0
27279218
eCl@ss 7.0
27279218
etim
ETIM 3.0
EC001855
ETIM 4.0
EC001855
unspsc
UNSPSC 6.01
31251501
UNSPSC 7.0901
31251501
UNSPSC 11
31251501
UNSPSC 12.01
31251501
UNSPSC 13.2
31251501
Drawings
Schematic diagram
Cable cross section
5
4
6
8
3
2
7
1
Pin assignment M12 socket, 8-pos., A-coded, view female side
PUR, gray, shielded [285]
Dimensioned drawing
Dimensioned drawing
M12 x 1 female connector, straight, shielded
M12
Ø14,8
Ø12
M12
44,5
Ø14,8
Ø12
44,5
M12 x 1 female connector, straight, shielded
08.08.2012 Page 3 / 4
https://www.phoenixcontact.com/us/produkte/1402262
Sensor/Actuator cable - SAC-8P- 1,0-285/FS SH SCO - 1402262
Circuit diagram
1
WH
2
BN
3
GN
4
YE
5
GY
6
PK
7
BU
8
RD
Contact assignment of the M12 socket
© Phoenix Contact 2012 - all rights reserved
http://www.phoenixcontact.com
08.08.2012 Page 4 / 4