https://www.phoenixcontact.com/us/products/1414359
Contact insert module - HC-M-03-CT-F - 1414359
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Contact insert module, Number of positions: 3, Socket, Crimp connection, 690 V, 40 A, 1.5 mm² ... 10
mm², Application: Power
Key Commercial Data
Packing unit
1 STK
Minimum order quantity
5 STK
GTIN
GTIN
4055626025025
Weight per Piece (excluding packing)
12.000 g
Custom tariff number
85389099
Country of origin
Poland
Technical data
Dimensions
Height
44.7 mm
Width
34.2 mm
Length
14.6 mm
Electrical characteristics
Note
For HEAVYCON housing type B6 to B48, HC-M-B...MF-... hinged module
carrier frame required, CK4,0...... crimp contacts, crimp contacts not
supplied as standard.
Rated voltage (III/3)
690 V
Rated current
40 A
Rated surge voltage
6 kV
04/11/2017 Page 1 / 4
https://www.phoenixcontact.com/us/products/1414359
Contact insert module - HC-M-03-CT-F - 1414359
Technical data
Electrical characteristics
Connection profile
3
Ambient conditions
Ambient temperature (operation)
-40 °C ... 125 °C
Mechanical characteristics
Conductor cross section
1.5 mm² ... 10 mm²
Connection cross section AWG
16 ... 8
Stripping length of the individual wire
9 mm (for 1.5 - 2.5 mm²)
9.6 mm (for 4 mm² ... 6 mm²)
15 mm (for 10 mm²/conductor ≥ 5 mm diameter)
18 mm (for 10 mm²/conductor ≥ 6.4 mm diameter)
Wire diameter including insulation
7.5 mm
Insertion/withdrawal cycles
≥ 500
Minimum housing height
52 mm
General
Series
HC-M-03
Color
light gray
Number of module slots
1
Connection method
Crimp connection
Connection in acc. with standard
IEC / EN
Flammability rating according to UL 94
V0
Degree of pollution
3
Overvoltage category
III
Assembly instructions
Housing height ≥ 52 mm.
Plug-in connections may only be operated only when there is no load/
voltage.
Connection
The CK4,0-EWZ tool (order no. 1662735) is required for removing the
crimp contacts.
At every "C" contact chamber, the position of the contact retaining springs
is marked with two black markings on the connection side. From the
connection side, the tool is pushed over the contact in a position-oriented
manner, so that it touches both the retaining springs. Then insert it up to
the limit stop. Do not turn the inserted tool. Push the conductor out of the
insulating body along with the tool from the connection side.
Material data
Contact material
Copper alloy
Contact surface material
Ag
Contact carrier material
PC
Standards and Regulations
04/11/2017 Page 2 / 4
https://www.phoenixcontact.com/us/products/1414359
Contact insert module - HC-M-03-CT-F - 1414359
Technical data
Standards and Regulations
Connection in acc. with standard
IEC / EN
Flammability rating according to UL 94
V0
Drawings
Diagram
I [A]
Schematic diagram
60
50
1
!
40
30
2
20
10
0
20
3
= 10 mm
2
! = 6 mm
2
" = 4 mm
30
40
2
"
50
60
70
80
90 100 110 120 130
T [°C]
Connector pin assignment
Derating diagram (6 modules in HC-B 24 housing)
Dimensional drawing
37,5
34,1
14,6
Approvals
Approvals
Approvals
EAC / UL Recognized / CSA
Ex Approvals
Approval details
04/11/2017 Page 3 / 4
https://www.phoenixcontact.com/us/products/1414359
Contact insert module - HC-M-03-CT-F - 1414359
Approvals
EAC
7500651.22.01.00246
UL Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
E118976
mm²/AWG/kcmil
10
Nominal current IN
42 A
Nominal voltage UN
600 V
CSA
http://www.csagroup.org/services/testingand-certification/certified-product-listing/
mm²/AWG/kcmil
10
Nominal current IN
33 A
Nominal voltage UN
600 V
13631
Phoenix Contact 2017 © - all rights reserved
http://www.phoenixcontact.com
04/11/2017 Page 4 / 4
很抱歉,暂时无法提供与“1414359”相匹配的价格&库存,您可以联系我们找货
免费人工找货- 国内价格
- 5+24.16011
- 25+23.43530