https://www.phoenixcontact.com/us/products/1507528
Bus system cable - SAC-5P-M12MS/ 0,3-920/M12FS - 1507528
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
®
Bus system cable, CANopen , DeviceNet™, 5-position, PUR halogen-free, violet RAL 4001, shielded, Plug
straight M12, A-coded, on Socket straight M12, A-coded, Cable length: 0.3 m
Key Commercial Data
Packing unit
1 STK
GTIN
GTIN
4017918900311
Weight per Piece (excluding packing)
54.400 g
Custom tariff number
85444290
Country of origin
Poland
Technical data
Dimensions
Length of cable
0.3 m
Ambient conditions
Ambient temperature (operation)
-25 °C ... 90 °C (Plug / socket)
Degree of protection
IP65
IP67
General
Rated current at 40°C
4A
Rated voltage
60 V
Number of positions
5
Insulation resistance
≥ 100 MΩ
12/01/2016 Page 1 / 5
https://www.phoenixcontact.com/us/products/1507528
Bus system cable - SAC-5P-M12MS/ 0,3-920/M12FS - 1507528
Technical data
General
Coding
A - standard
Signal type/category
CANopen
®
DeviceNet™
Status display
No
Overvoltage category
II
Degree of pollution
3
Insertion/withdrawal cycles
≥ 100
Torque
0.4 Nm (M12 connector)
Material
Flammability rating according to UL 94
HB
Contact material
CuSn
Contact surface material
Ni/Au
Contact carrier material
TPU GF
Material of grip body
TPU, hardly inflammable, self-extinguishing
Material, knurls
Zinc die-cast, nickel-plated
Sealing material
NBR
Pin assignment
Position = wire color (signal) = position (optional)
1 (Plug) = SR (shield) = 1 (Socket)
2 (Plug) = RD (V+) = 2 (Socket)
3 (Plug) = BK (V-) = 3 (Socket)
4 (Plug) = WH (CAN_H) = 4 (Socket)
5 (Plug) = BU (CAN_L) = 5 (Socket)
Standards and Regulations
Flammability rating according to UL 94
HB
Cable
Cable type
CAN Bus/DeviceNet
Cable type (abbreviation)
920
UL AWM style
21198 (80°C/300 V)
Cable structure
2xAWG24/19+2xAWG22/19
Conductor cross section
2x 0.25 mm² (Data cable)
2x 0.34 mm² (Power supply)
1x 0.34 mm² (Drain wire)
AWG signal line
24
AWG power supply
22
Conductor structure signal line
19x 0.13 mm
12/01/2016 Page 2 / 5
https://www.phoenixcontact.com/us/products/1507528
Bus system cable - SAC-5P-M12MS/ 0,3-920/M12FS - 1507528
Technical data
Cable
Conductor structure, voltage supply
19x 0.15 mm
Core diameter including insulation
1.95 mm ±0.05 mm (Data cable)
1.4 mm ±0.05 mm (Power supply)
Wire colors
Red-black, blue-white
Twisted pairs
2 cores to the pair
Type of pair shielding
Plastic-coated aluminum foil, aluminum side outside
Overall twist
2 pairs around a drain wire in the center to the core
Shielding
Tinned copper braided shield
Optical shield covering
80 %
External sheath, color
violet RAL 4001
External cable diameter D
6.7 mm ±0,3 mm
Minimum bending radius, flexible installation
10 x D
Number of bending cycles
5000000
Bending radius
70 mm
Traversing path
4.5 m
Traversing rate
3 m/s
Acceleration
3 m/s²
Cable weight
90 kg/km
Outer sheath, material
PUR
Material conductor insulation
Foamed PE (Data cable)
PE (Power supply)
Conductor material
Tin-plated Cu litz wires
Insulation resistance
≥ 5 GΩ*km (Data cable)
≥ 5 GΩ*km (Power supply)
Conductor resistance
≤ 90.9 Ω/km (Data cable)
≤ 57.4 Ω/km (Power supply)
Cable capacity
nom. 40 pF/m (Data cable)
Wave impedance
120 Ω ±10 % (with 1 MHz)
Wave attenuation
≥ 0.0229 dB/m (with 1 MHz)
Nominal voltage, cable
≤ 300 V (Peak value, not for high-power applications)
Test voltage Core/Core
2000 V (50 Hz, 1 min.)
Test voltage Core/Shield
2000 V (50 Hz, 1 min.)
Flame resistance
UL 1581, Sec. 1060 (FT-1)
IEC 60332-1
in accordance with ISO 6722-1 5.22 (UN ECE-R 118.01)
Halogen-free
in accordance with DIN VDE 0472 part 815
According to IEC 60754-1
12/01/2016 Page 3 / 5
https://www.phoenixcontact.com/us/products/1507528
Bus system cable - SAC-5P-M12MS/ 0,3-920/M12FS - 1507528
Technical data
Cable
Other resistance
Low adhesion
Ambient temperature (operation)
-40 °C ... 80 °C (cable, fixed installation)
-20 °C ... 80 °C (cable, flexible installation)
Environmental Product Compliance
China RoHS
Environmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values
Drawings
Schematic diagram
4
Schematic diagram
3
3
4
5
1
5
2
2
Pin assignment M12 male connector, 5-pos., A-coded, male side
1
Pin assignment M12 socket, 5-pos., A-coded, socket side view
Cable cross section
Circuit diagram
1
1 --- (Drain)
2
2 RD (V+)
3
3 BK (V-)
4
4 WH (CAN_H)
5
5 BU (CAN_L)
CAN Bus/DeviceNet [920]
Plug, M12 x 1, straight, shielded
Ø15
44,5
M12
47,3
Ø12
Dimensional drawing
Ø12
Dimensional drawing
M12
Ø14,8
Contact assignment of the M12 connector and the M12 socket
M12 x 1 socket, straight, shielded
12/01/2016 Page 4 / 5
https://www.phoenixcontact.com/us/products/1507528
Bus system cable - SAC-5P-M12MS/ 0,3-920/M12FS - 1507528
Approvals
Approvals
Approvals
EAC
Ex Approvals
Approval details
EAC EAC-Zulassung
Phoenix Contact 2016 © - all rights reserved
http://www.phoenixcontact.com
12/01/2016 Page 5 / 5