HEAVYCON contact insert module, connector, 1-pos., for axial screw connection, 200 A, 40-70 mm², for the PE
connection
Key Commercial Data
Packing unit
1 pc
Weight per Piece (excluding packing)
97.6 g
Custom tariff number
85366990
Country of origin
Germany
Technical data
Electrical characteristics
Note
For HEAVYCON HC-B6 to B48 housing (housing height: min. 72 mm), HCM-MHR... hinged retaining frame required, axial connection for 5 mm Allen
key
Rated current
200 A
Number of positions
1
Ambient conditions
Ambient temperature (operation)
-40 °C ... 125 °C
Mechanical characteristics
Conductor cross section
40 mm² ... 70 mm² (The cross section specification refers to the geometric
cross section of the cable used)
Connection cross section AWG
1 ... 00
Stripping length of the individual wire
16 mm
Tightening torque
9 Nm (40 - 50 mm²)
10 Nm (70 mm²)
Wire diameter including insulation
12 mm (40 mm²)
16 mm (70 mm²)
04/06/2016 Page 1 / 4
https://www.phoenixcontact.com/us/products/1636907
Contact insert module - HC-M-HS 200/70-MOD-ST-PE - 1636907
Technical data
Mechanical characteristics
Hexagonal socket
WAF 5
Insertion/withdrawal cycles
≥ 500
Minimum housing height
72 mm
General
Series
HC-M-HS
Number of module slots
2
Connection method
Axial screw connection
Flammability rating according to UL 94
V0
Assembly instructions
- Use only flexible conductors,
- Connection of wires with 5 mm an Allen wrench,
- Housing height h ≥ 72 mm,
- Connectors may only be operated without load/voltage.
Connection
Note on axial connection technology:
Only for stranded wires. The specified conductor cross sections refer to
the geometric cross section of the cable used.
Use of cables with a geometric cross section that differs greatly from the
nominal cross section of the cable should be checked before use.
The wiring space for axial screw technology is designed for fine strand
cables according to VDE 0295 Class 5. Deviating cable structures (e.g.,
Class 6 cables) should be checked before use.
Assembly instructions
Before assembly, ensure that the tapered screw is turned back all the
way (chamber is open). The cables must not be twisted. The wires should
be inserted as far as they will go into the contact chamber (until the
insulation touches the contact). Hold the wires in position and use the
socket wrench to tighten. The used wire end should be cut off before
connecting again. The connection screw may only be retightened once to
prevent the litz wires from breaking. To prevent damage to the contact,
the wire/cable should be mechanically intercepted at an appropriate
distance from the connection point (e.g., by using a plate cutout). DIN VDE
0100-520:2003-06 contains information on how to do this correctly. The
module cannot be used simultaneously with HC-B..-TMB-SD-IP65 and HCB..-TMS-SD-IP65 protective covers.
PE mounting plate
The PE plate must be pressed hard against the swing frame using the 4
screws. First loosen the 4 screws of the PE plate and then tighten them
again once the module is fixed in the swing frame.
Material data
Contact material
Copper alloy
Contact surface material
Ag
Contact carrier material
PC
Standards and Regulations
Connection in acc. with standard
UL
Flammability rating according to UL 94
V0
04/06/2016 Page 2 / 4
https://www.phoenixcontact.com/us/products/1636907
Contact insert module - HC-M-HS 200/70-MOD-ST-PE - 1636907
Classifications
eCl@ss
eCl@ss 4.0
272607xx
eCl@ss 4.1
27260701
eCl@ss 5.0
27143424
eCl@ss 5.1
27143424
eCl@ss 6.0
27143424
eCl@ss 7.0
27440209
eCl@ss 8.0
27440207
ETIM
ETIM 3.0
EC000438
ETIM 4.0
EC000438
ETIM 5.0
EC000438
UNSPSC
UNSPSC 6.01
30211923
UNSPSC 7.0901
39121522
UNSPSC 11
39121522
UNSPSC 12.01
39121522
UNSPSC 13.2
39121522
Approvals
Approvals
Approvals
UL Recognized / EAC
Ex Approvals
Approvals submitted
Approval details
04/06/2016 Page 3 / 4
https://www.phoenixcontact.com/us/products/1636907
Contact insert module - HC-M-HS 200/70-MOD-ST-PE - 1636907
Approvals
UL Recognized
mm²/AWG/kcmil
2
Nominal current IN
200 A
Nominal voltage UN
600 V
EAC
Drawings
Diagram
Dimensional drawing
34,4
29,4
350
300
23
2
250
200
54,5
Operating current [A]
400
150
1
100
1 = 50 mm2
50
2 = 70 mm
0
0
20
2
40
60
80
100
120
Ambient temperature [°C]
Male insert
Schematic diagram
Axial screw connection
Phoenix Contact 2016 © - all rights reserved