PACT Analog Current transformers INTERFACE Data sheet 103359_en_03 1 © PHOENIX CONTACT 2011-04-04 Description The PACT Analog current transformers form a complete range of bus-bar, plug-in and winding current transformers for measuring AC currents with a range of 1 A to 4000 A. Current transformers belong to a group of specialized transformers and are used in those areas where currents cannot be measured directly. Depending on the transformation ratio, the primary current is transmitted to a smaller electrically isolated secondary current. PACT Analog current transformers can be used either as an industrial version or as a transformer that can be officially calibrated. The calibration process involves additional costs, which are specified in accordance with the national table of fees. 1.1 – – – Features Safe isolation as a result of the test voltage of 12 kV (1.2/50 µs) prevents a hazardous operating voltage from being transferred to downstream components Conforms to surge voltage category 3 as a result of the test voltage amplitude Routine test according to EN 50178 Also refer to additional information on "Safe isolation"; see page 28. PACT Analog current transformers are available in the following designs: – Winding current transformer (Ipn: 1 A to 40 A) – Bus-bar current transformer (Ipn: 50 A to 500 A) – Plug-in current transformer (Ipn: 50 A to 4000 A) WARNING: Danger due to damaged current transformers • Before startup, check that the housing of the current transformer is not damaged. • Also before startup, check that there are no electrically conductive connections between the primary conductor and the secondary terminals. • If a built-in current transformer is removed in order to be used in a different system, check the current transformer for damage again. WARNING: Danger due to voltage at open circuit The output of the current transformer is a constant current source. In the event of an increasing load, the output voltage thus increases and reaches its maximum at infinite load (i.e., with open secondary terminals). • Avoid open-circuit operation at all costs. • Note that unloaded transformers must be short circuited. • Only start up the current transformer once the secondary cables are connected on both sides. PACT Analog 2 1 Table of contents Description.................................................................................................................................. 1 1.1 Features ......................................................................................................................................................... 1 2 Table of contents ........................................................................................................................ 2 3 Ordering data.............................................................................................................................. 3 3.1 3.2 3.3 3.4 Current transformers that cannot be calibrated .............................................................................................. 4 Current transformers that can be calibrated ................................................................................................. 16 Standard accessories, supplied as standard................................................................................................ 21 Optional accessories.................................................................................................................................... 21 4 Technical data ...........................................................................................................................22 5 Safety notes...............................................................................................................................23 6 Selecting the optimum transformer ............................................................................................24 7 Installation and connection ........................................................................................................24 7.1 7.2 Installing a current transformer ..................................................................................................................... 25 Connecting a current transformer ................................................................................................................ 27 8 Calibrating the current transformers...........................................................................................27 9 Safe isolation .............................................................................................................................28 9.1 103359_en_03 Application example with safe isolation up to 1 kV ....................................................................................... 28 PHOENIX CONTACT 2 PACT Analog 3 Ordering data Make sure you always use the latest documentation. It can be downloaded at www.phoenixcontact.net/catalog. Explanation of the type designation by means of an example PACT MCR-V2C-3015-60 V1 = Bus-bar current transformer (for assembly with circular conductors) V2 = Plug-in current transformer (for direct or horizontal assembly on power rails) V3 = Winding current transformer C = Transformer that can be calibrated 30 = Maximum width of the power rail in mm 15 = Maximum height of the power rail in mm 60 = Width of the current transformer in mm Information on the type entry in the order key Type PACT MCR-V2-3015-60 Primary current Ipn - 80 Secondary current Isn - 5A Class - 1 Power () - 2.5 VA Order No. - 2277268 For some of the current transformers listed in the following tables, popular types are available from stock. These have their own order Nos. and are labeled separately. For all other types, please complete the order key using the respective selection table. 103359_en_03 PHOENIX CONTACT 3 PACT Analog 3.1 Current transformers that cannot be calibrated Bus-bar current transformers with a primary current of 50 A to 500 A, for circular conductors Description Type Order No. Pcs. / Pkt. Bus-bar current transformer with a primary current of 50 A to 500 A, for circular conductors PACT MCR-V1-21-44-... 2277268 1 PACT MCR-V1-21-44-50-5A-1 2277019 1 Transformation ratio 50 A:5 A; 1.25 VA PACT MCR-V1-21-44-75-5A-1 2277611 1 Transformation ratio 75 A:5 A; 2.5 VA PACT MCR-V1-21-44-100-5A-1 2277022 1 Transformation ratio 100 A:5 A; 2.5 VA PACT MCR-V1-21-44-125-5A-1 2277763 1 Transformation ratio 125 A:5 A; 3.75 VA PACT MCR-V1-21-44-150-5A-1 2277035 1 Transformation ratio 150 A:5 A; 5 VA PACT MCR-V1-21-44-200-5A-1 2277776 1 Transformation ratio 200 A:5 A; 5 VA PACT MCR-V1-21-44-250-5A-1 2277048 1 Transformation ratio 250 A:5 A; 5 VA PACT MCR-V1-21-44-300-5A-1 2277789 1 Transformation ratio 300 A:5 A; 10 VA PACT MCR-V1-21-44-400-5A-1 2277051 1 Transformation ratio 400 A:5 A; 5 VA PACT MCR-V1-21-44-500-5A-1 2277792 1 Transformation ratio 500 A:5 A; 10 VA Selection table Primary rated current strength Ipn Isn Cl. 50 60 75 80 100 1.25 125 2.5 150 2.5 3.75 200 2.5 5 250 2.5 5 7.5 300 2.5 5 400 2.5 5 7.5 500 2.5 5 10 1.25 1.25 2.5 2.5 2.5 2.5 3.75 2.5 5 2.5 5 2.5 5 7.5 2.5 5 2.5 5 7.5 2.5 5 10 1.25 1.5 1.25 2.0 1.25 2.5 2.5 3.75 2.5 5 7.5 2.5 5 10 2.5 5 7.5 2.5 5 7.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 7.5 2.5 2.5 7.5 2.5 5 10 2.5 5 7.5 2.5 5 10 0.5 1 0.5 Rated power Sn [VA] 1A 5A 1.25 1 103359_en_03 1.25 1.5 2.5 2.5 PHOENIX CONTACT 4 PACT Analog Plug-in current transformers with a primary current of 50 A to 750 A, for rails and circular conductors Description Type Order No. Pcs. / Pkt. Plug-in current transformer with a primary current of 50 A to 750 A, for rails and circular conductors PACT MCR-V2-3015-60-... 2277271 1 Transformation ratio 60 A:5 A; 1.25 VA PACT MCR-V2-3015-60-60-5A-1 2277815 1 Transformation ratio 75 A:5 A; 1.25 VA PACT MCR-V2-3015-60-75-5A-1 2277828 1 Transformation ratio 75 A:5 A; 1.5 VA PACT MCR-V2-3015-60-75-5A-1 2276502 1 Transformation ratio 80 A:5 A; 1.25 VA PACT MCR-V2-3015-60-80-5A-1 2277831 1 Transformation ratio 100 A:5 A; 2.5 VA PACT MCR-V2-3015-60-100-5A-1 2277064 1 Transformation ratio 125 A:5 A; 3.75 VA PACT MCR-V2-3015-60-125-5A-1 2277624 1 Transformation ratio 150 A:5 A; 3.75 VA PACT MCR-V2-3015-60-150-5A-1 2277844 1 Transformation ratio 150 A:5 A; 5 VA PACT MCR-V2-3015-60-150-5A-1 2277077 1 Transformation ratio 200 A:5 A; 5 VA PACT MCR-V2-3015-60-200-5A-1 2277637 1 Transformation ratio 200 A:5 A; 7.5 VA PACT MCR-V2-3015-60-200-5A-1 2277857 1 Transformation ratio 250 A:5 A; 5 VA PACT MCR-V2-3015-60-250-5A-1 2276544 1 Transformation ratio 250 A:5 A; 7.5 VA PACT MCR-V2-3015-60-250-5A-1 2277860 1 Transformation ratio 250 A:5 A; 10 VA PACT MCR-V2-3015-60-250-5A-1 2277080 1 Transformation ratio 300 A:5 A; 7.5 VA PACT MCR-V2-3015-60-300-5A-1 2277640 1 Transformation ratio 400 A:5 A; 10 VA PACT MCR-V2-3015-60-400-5A-1 2277093 1 Transformation ratio 500 A:5 A; 10 VA PACT MCR-V2-3015-60-500-5A-1 2277653 1 Transformation ratio 600 A:5 A; 10 VA PACT MCR-V2-3015-60-600-5A-1 2277103 1 Transformation ratio 750 A:5 A; 10 VA PACT MCR-V2-3015-60-750-5A-1 2277666 1 Selection table Isn Cl. 50 60 75 80 100 1.25 125 1.25 150 2.5 200 2.5 3.75 250 2.5 5 300 2.5 5 7.5 400 2.5 5 10 500 2.5 5 10 1.25 1.25 2.5 2.5 2.5 2.5 3.75 2.5 5 2.5 5 2.5 5 7.5 2.5 5 10 2.5 5 10 2.5 5 10 2.5 3.75 2.5 5 2.5 5 7.5 2.5 5 10 2.5 5 7.5 2.5 5 7.5 10 2.5 5 7.5 10 2.5 5 10 15 0.5 2.5 5 10 600 2.5 5 10 15 2.5 5 10 15 2.5 5 10 750 2.5 5 10 15 5 10 10 20 2.5 5 10 2.5 5 10 2.5 5 10 2.5 5 10 15 1A 1 0.5 Rated power Sn [VA] Primary rated current strength Ipn 5A 1.25 1 103359_en_03 1.25 1.5 1.25 2 2.5 2.5 3.75 2.5 3.75 5 PHOENIX CONTACT 5 PACT Analog Plug-in current transformers with a primary current of 75 A to 1000 A, for rails Description Type Order No. Pcs. / Pkt. Plug-in current transformer with a primary current of 75 A to 1000 A, for rails PACT MCR-V2-4012-70-... 2277284 1 Transformation ratio 250 A:5 A; 5 VA PACT MCR-V2-4012-70-250-5A-1 2277116 1 Transformation ratio 300 A:5 A; 7.5 VA PACT MCR-V2-4012-70-300-5A-1 2277679 1 Transformation ratio 400 A:5 A; 7.5 VA PACT MCR-V2-4012-70-400-5A-1 2277129 1 Transformation ratio 500 A:5 A; 10 VA PACT MCR-V2-4012-70-500-5A-1 2277682 1 Transformation ratio 600 A:5 A; 10 VA PACT MCR-V2-4012-70-600-5A-1 2277132 1 Transformation ratio 750 A:5 A; 10 VA PACT MCR-V2-4012-70-750-5A-1 2277695 1 Transformation ratio 800 A:5 A; 10 VA PACT MCR-V2-4012-70-800-5A-1 2277145 1 Transformation ratio 1000 A:5 A; 10 VA PACT MCR-V2-4012-70-1000-5A-1 2277158 1 Selection table Primary rated current strength Ipn Cl. 50 60 75 80 100 125 1.25 150 2.5 200 2.5 3.75 250 2.5 5 300 2.5 5 400 2.5 5 7.5 500 2.5 5 10 600 2.5 5 10 750 2.5 5 10 1.25 1.25 2.5 2.5 3.75 2.5 5 2.5 5 2.5 5 7.5 2.5 5 7.5 2.5 5 7.5 2.5 5 10 2.5 5 10 1.25 2.5 2.5 3.75 2.5 5 2.5 5 2.5 5 7.5 2.5 5 10 2.5 5 10 2.5 5 10 15 2.5 5 10 2.5 3.75 2.5 5 2.5 5 2.5 5 7.5 2.5 5 7.5 2.5 5 7.5 2.5 5 10 2.5 5 10 0.5 1A 1 0.5 5A 1.25 1 103359_en_03 1.25 2.5 2.5 5 10 15 800 2.5 5 10 15 2.5 5 10 15 2.5 5 10 15 2.5 5 10 15 1000 2.5 5 10 2.5 5 10 2.5 5 10 Rated power Sn [VA] Isn 2.5 5 10 PHOENIX CONTACT 6 PACT Analog Plug-in current transformers with a primary current of 100 A to 1500 A, for rails and circular conductors Description Type Order No. Pcs. / Pkt. Plug-in current transformer with a primary current of 100 A to 1500 A, for rails and circular conductors PACT MCR-V2-5012-85-... 2277297 1 Transformation ratio 150 A:5 A; 3.75 VA PACT MCR-V2-5012-85-150-5A-1 2276117 1 Transformation ratio 200 A:5 A; 5 VA PACT MCR-V2-5012-85-200-5A-1 2276120 1 Transformation ratio 250 A:5 A; 7.5 VA PACT MCR-V2-5012-85-250-5A-1 2276133 1 Transformation ratio 300 A:5 A; 10 VA PACT MCR-V2-5012-85-300-5A-1 2276146 1 Transformation ratio 400 A:5 A; 10 VA PACT MCR-V2-5012-85-400-5A-1 2277161 1 Transformation ratio 500 A:5 A; 15 VA PACT MCR-V2-5012-85-500-5A-1 2276159 1 Transformation ratio 600 A:5 A; 10 VA PACT MCR-V2-5012-85-600-5A-1 2277174 1 Transformation ratio 600 A:5 A; 15 VA PACT MCR-V2-5012-85-600-5A-1 2276162 1 Transformation ratio 750 A:5 A; 10 VA PACT MCR-V2-5012-85-750-5A-1 2276175 1 Transformation ratio 800 A:5 A; 10 VA PACT MCR-V2-5012-85-800-5A-1 2277187 1 Transformation ratio 1000 A:5 A; 10 VA PACT MCR-V2-5012-85-1000-5A-1 2276463 1 Transformation ratio 1000 A:5 A; 15 VA PACT MCR-V2-5012-85-1000-5A-1 2277190 1 Transformation ratio 1250 A:5 A; 15 VA PACT MCR-V2-5012-85-1250-5A-1 2277200 1 Transformation ratio 1500 A:5 A; 15 VA PACT MCR-V2-5012-85-1500-5A-1 2276188 1 Selection table Isn Cl. 100 125 150 1.25 200 2.5 5 250 2.5 5 300 2.5 5 7.5 1.25 2.5 2.5 3.75 2.5 5 7.5 2.5 5 10 1.25 2.5 5 2.5 5 7.5 10 2.5 5 2.5 3.75 2.5 5 7.5 2.5 5 7.5 10 2.5 5 10 0.5 1A 1 0.5 2.5 5 7.5 5A 1.25 1 103359_en_03 2.5 400 2.5 5 10 15 2.5 5 10 15 2.5 5 10 15 2.5 5 10 15 500 2.5 5 10 15 2.5 5 10 20 2.5 5 10 15 5 10 15 20 600 2.5 5 10 15 2.5 5 10 20 2.5 5 20 15 5 10 15 20 750 2.5 5 10 800 2.5 5 10 2.5 5 10 2.5 5 10 15 2.5 5 10 2.5 5 10 2.5 5 10 2.5 5 10 15 1000 2.5 5 10 15 5 10 15 20 2.5 5 10 15 5 10 15 20 1250 2.5 5 10 15 5 10 15 20 2.5 5 10 15 5 10 15 20 1500 2.5 5 10 15 5 10 15 30 2.5 5 10 15 5 10 15 20 PHOENIX CONTACT Rated power Sn [VA] Primary rated current strength Ipn 7 PACT Analog Plug-in current transformers with a primary current of 200 A to 1600 A, for rails and circular conductors Description Type Order No. Pcs. / Pkt. Plug-in current transformer with a primary current of 200 A to 1600 A, for rails and circular conductors PACT MCR-V2-6015-85-... 2277336 1 Transformation ratio 200 A:5 A; 2.5 VA PACT MCR-V2-6015-85-200-5A-1 2277873 1 Transformation ratio 250 A:5A; 2.5 VA PACT MCR-V2-6015-85-250-5A-1 2277886 1 Transformation ratio 300 A:5 A; 2.5 VA PACT MCR-V2-6015-85-300-5A-1 2277899 1 Transformation ratio 400 A:5 A; 2.5 VA PACT MCR-V2-6015-85-400-5A-1 2277909 1 Transformation ratio 500 A:5 A; 5 VA PACT MCR-V2-6015-85-500-5A-1 2277912 1 Transformation ratio 600 A:5 A; 10 VA PACT MCR-V2-6015-85-600-5A-1 2277925 1 Transformation ratio 750 A:5 A; 10 VA PACT MCR-V2-6015-85-750-5A-1 2277938 1 Transformation ratio 800 A:5 A; 10 VA PACT MCR-V2-6015-85-800-5A-1 2277941 1 Transformation ratio 1000 A:5 A; 15 VA PACT MCR-V2-6015-85-1000-5A-1 2277954 1 Transformation ratio 1250 A:5 A; 15 VA PACT MCR-V2-6015-85-1250-5A-1 2277967 1 Transformation ratio 1500 A:5 A; 15 VA PACT MCR-V2-6015-85-1500-5A-1 2277970 1 Transformation ratio 1600 A:5 A; 15 VA PACT MCR-V2-6015-85-1600-5A-1 2277983 1 Selection table Primary rated current strength Ipn Isn Cl. 100 125 150 200 250 1.25 300 1.25 400 1.25 500 2.5 600 2.5 750 2.5 5 800 2.5 1000 2.5 1250 2.5 5 2.5 2.5 2.5 2.5 2.5 3.75 2.5 2.5 5 2.5 3.75 2.5 3.75 2.5 5 1.25 1.25 1.25 2.5 2.5 5 2.5 5 10 2.5 5 10 2.5 2.5 2.5 2.5 5 2.5 5 10 2.5 5 10 2.5 5 10 15 2.5 5 10 15 2.5 5 10 15 5 10 15 5 10 15 20 5 10 15 20 1500 2.5 1600 5 10 15 20 5 10 15 30 5 10 15 0.5 1 0.5 5A 2.5 1 103359_en_03 Rated power Sn [VA] 1A 5 10 15 PHOENIX CONTACT 8 PACT Analog Plug-in current transformers with a primary current of 200 A to 2500 A, for rails and circular conductors Description Type Order No. Pcs. / Pkt. Plug-in current transformer with a primary current of 200 A to 2500 A, for rails and circular conductors PACT MCR-V2-6315-95-... 2277307 1 Transformation ratio 600 A:5 A; 10 VA PACT MCR-V2-6315-95-600-5A-1 2276191 1 Transformation ratio 750 A:5 A; 10 VA PACT MCR-V2-6315-95-750-5A-1 2276201 1 Transformation ratio 800 A:5 A; 10 VA PACT MCR-V2-6315-95-800-5A-1 2277213 1 Transformation ratio 1000 A:5 A; 10 VA PACT MCR-V2-6315-95-1000-5A-1 2277226 1 Transformation ratio 1250 A:5 A; 10 VA PACT MCR-V2-6315-95-1250-5A-1 2277239 1 Transformation ratio 1500 A:5 A; 10 VA PACT MCR-V2-6315-95-1500-5A-1 2277242 1 Transformation ratio 1600 A:5 A; 10 VA PACT MCR-V2-6315-95-1600-5A-1 2277255 1 Transformation ratio 2000 A:5 A; 15 VA PACT MCR-V2-6315-95-2000-5A-1 2276243 1 Selection table Isn Cl. 200 2.5 250 2.5 300 2.5 5 400 2.5 5 7.5 500 2.5 5 10 600 2.5 5 10 750 5 10 15 800 5 10 15 1000 5 10 1250 5 10 1500 5 10 15 1600 5 10 15 2.5 3.75 2.5 5 2.5 5 7.5 2.5 5 10 2.5 5 10 5 10 15 5 10 5 10 15 5 10 15 2.5 3.75 2.5 5 7.5 2.5 5 10 2.5 3.75 2.5 5 2.5 5 10 2.5 5 10 15 2.5 5 10 15 5 10 15 20 5 10 15 20 5 10 15 20 5 10 15 30 5 10 2.5 2.5 5 10 15 2.5 5 10 15 5 10 15 20 5 10 15 30 10 15 30 5 10 15 20 5 10 15 30 5 10 15 30 5 10 15 30 5 10 15 30 10 10 30 45 0.5 1A 1 0.5 5A 1 103359_en_03 5 10 15 20 5 10 15 30 2000 5 10 15 20 10 15 20 2500 5 10 15 30 10 15 30 5 10 15 30 10 15 30 PHOENIX CONTACT Rated power Sn [VA] Primary rated current strength Ipn 9 PACT Analog Plug-in current transformers with a primary current of 200 A to 2000 A, for rails and circular conductors Description Type Order No. Pcs. / Pkt. Plug-in current transformer with a primary current of 200 A to 2000 A, for rails and circular conductors PACT MCR-V2-6040-96-... 2277349 1 Transformation ratio 600 A:5 A; 10 VA PACT MCR-V2-6040-96-600-5A-1 2276191 1 Transformation ratio 750 A:5 A; 10 VA PACT MCR-V2-6040-96-750-5A-1 2276201 1 Transformation ratio 800 A:5 A; 10 VA PACT MCR-V2-6040-96-800-5A-1 2276214 1 Transformation ratio 1000 A:5 A; 10 VA PACT MCR-V2-6040-96-1000-5A-1 2277705 1 Transformation ratio 1250 A:5 A; 15 VA PACT MCR-V2-6040-96-1250-5A-1 2276227 1 Transformation ratio 1500 A:5 A; 10 VA PACT MCR-V2-6040-96-1500-5A-1 2277718 1 Transformation ratio 1600 A:5 A; 15 VA PACT MCR-V2-6040-96-1600-5A-1 2276230 1 Transformation ratio 2000 A:5 A; 15 VA PACT MCR-V2-6040-96-2000-5A-1 2276243 1 Selection table Primary rated current strength Ipn Isn Cl. 200 250 2.5 300 2.5 400 2.5 5 500 2.5 5 7.5 600 2.5 5 750 2.5 5 7.5 800 2.5 5 7.5 1000 2.5 5 10 1250 2.5 5 10 1500 2.5 2.5 3.75 2.5 5 2.5 5 2.5 5 7.5 2.5 5 7.5 2.5 5 2.5 5 7.5 2.5 5 7.5 2.5 5 10 2.5 5 10 2.5 5 2.5 2.5 2.5 5 2.5 5 7.5 2.5 5 7.5 2.5 5 10 2.5 5 10 2.5 5 7.5 2.5 5 10 2.5 5 10 2.5 3.75 2.5 5 2.5 5 7.5 2.5 5 7.5 2.5 5 10 2.5 5 10 2.5 5 10 15 2.5 5 10 5 10 15 2.5 5 10 0.5 1600 2000 2.5 5 10 15 5 10 15 5 10 15 1 0.5 5A 2.5 3.75 1 103359_en_03 Rated power Sn [VA] 1A 5 10 15 PHOENIX CONTACT 10 PACT Analog Plug-in current transformers with a primary current of 400 A to 2500 A, for rails and circular conductors Description Type Order No. Pcs. / Pkt. Plug-in current transformer with a primary current of 400 A to 2500 A, for rails and circular conductors PACT MCR-V2-8015-105-... 2277352 1 Transformation ratio 400 A:5 A; 7.5 VA PACT MCR-V2-8015-105-400-5A-1 2276256 1 Transformation ratio 500 A:5 A; 10 VA PACT MCR-V2-8015-105-500-5A-1 2276269 1 Transformation ratio 600 A:5 A; 10 VA PACT MCR-V2-8015-105-600-5A-1 2276272 1 Transformation ratio 750 A:5 A; 10 VA PACT MCR-V2-8015-105-750-5A-1 2276285 1 Transformation ratio 800 A:5 A; 15 VA PACT MCR-V2-8015-105-800-5A-1 2276298 1 Transformation ratio 1000 A:5 A; 10 VA PACT MCR-V2-8015-105-1000-5A-1 2277721 1 Transformation ratio 1000 A:5 A; 15 VA PACT MCR-V2-8015-105-1000-5A-1 2276308 1 Transformation ratio 1250 A:5 A; 10 VA PACT MCR-V2-8015-105-1250-5A-1 2276311 1 Transformation ratio 1500 A:5 A; 15 VA PACT MCR-V2-8015-105-1500-5A-1 2277734 1 Transformation ratio 1600 A:5 A; 15 VA PACT MCR-V2-8015-105-1600-5A-1 2276324 1 Transformation ratio 2000 A:5 A; 20 VA PACT MCR-V2-8015-105-2000-5A-1 2276337 1 Transformation ratio 2500 A:5 A; 20 VA PACT MCR-V2-8015-105-2500-5A-1 2276340 1 Selection table Primary rated current strength Ipn Cl. 400 2.5 500 2.5 5 600 2.5 5 10 750 2.5 5 800 2.5 5 10 1000 2.5 5 7.5 1250 2.5 5 10 2.5 5 7.5 2.5 5 10 2.5 5 10 2.5 5 10 2.5 5 10 2.5 5 2.5 5 2.5 5 10 2.5 5 10 2.5 5 10 2.5 5 10 15 5 10 15 2.5 5 10 15 2.5 5 10 2.5 5 7.5 2.5 5 10 15 2.5 5 10 15 2.5 5 10 15 5 10 15 20 5 10 15 20 0.5 1A 1 0.5 5A 1 103359_en_03 2.5 5 10 1500 2.5 5 10 15 5 10 15 20 2.5 5 10 2.5 5 10 15 1600 2.5 5 10 15 5 10 15 20 2.5 5 10 15 5 10 15 2000 5 10 15 20 10 15 20 25 2.5 5 10 15 5 10 15 20 2500 Rated power Sn [VA] Isn 5 10 15 20 10 15 20 30 PHOENIX CONTACT 11 PACT Analog Plug-in current transformers with a primary current of 500 A to 2000 A, for rails and circular conductors Description Type Order No. Pcs. / Pkt. Plug-in current transformer with a primary current of 500 A to 2000 A, for rails and circular conductors PACT MCR-V2-8020-105-... 2277365 1 Transformation ratio 1000 A:5 A; 10 VA PACT MCR-V2-8020-105-1000-5A-1 2277747 1 Transformation ratio 1500 A:5 A; 15 VA PACT MCR-V2-8020-105-1500-5A-1 2277750 1 Transformation ratio 2000 A:5 A; 10 VA PACT MCR-V2-8020-105-2000-5A-1 2276382 1 Selection table Primary rated current strength Ipn Isn Cl. 500 2.5 600 2.5 5 750 2.5 5 800 2.5 5 1000 2.5 5 10 1250 2.5 1500 2.5 5 1600 2.5 5 2.5 5 2.5 5 7.5 2.5 5 7.5 2.5 5 7.5 2.5 5 2.5 5 2.5 5 2.5 5 2.5 5 7.5 2.5 5 7.5 2.5 5 7.5 2.5 5 10 15 2.5 5 10 2.5 5 10 2.5 5 10 2.5 5 2.5 5 7.5 2.5 5 7.5 2.5 5 10 2.5 5 10 5 10 10 2.5 5 10 15 2.5 5 10 15 5 10 15 0.5 2000 1 0.5 5A 1 103359_en_03 Rated power Sn [VA] 1A 2.5 5 10 5 10 PHOENIX CONTACT 12 PACT Analog Plug-in current transformers with a primary current of 400 A to 4000 A, for rails and circular conductors Description Type Order No. Pcs. / Pkt. Plug-in current transformer with a primary current of 400 A to 4000 A, for rails and circular conductors PACT MCR-V2-10020-129-... 2277378 1 PACT MCR-V2-10020-129-2500-5A-1 2276395 1 Transformation ratio 2500 A:5 A; 15 VA Selection table Primary rated current strength Ipn Cl. 400 500 2.5 5 600 5 10 750 5 10 800 5 10 1000 5 10 1250 5 10 15 1500 5 10 15 1600 5 10 15 2000 5 10 15 2.5 5 2.5 5 5 10 5 10 5 10 5 10 5 10 15 5 10 15 5 10 15 5 10 15 2.5 5 5 5 5 10 5 10 5 10 5 10 15 5 10 15 5 10 15 2.5 5 5 10 5 10 5 10 5 10 15 5 10 15 5 10 15 5 10 15 20 5 10 15 20 5 10 15 25 0.5 1A 1 0.5 5A 2.5 5 1 2500 5 10 15 20 5 10 15 25 5 10 15 20 5 10 15 30 3000 5 10 15 20 5 10 15 30 5 10 15 25 5 10 15 30 4000 Rated power Sn [VA] Isn 5 10 15 25 5 10 15 30 Plug-in current transformers with a primary current of 400 A to 4000 A, for rails Description Type Order No. Pcs. / Pkt. Plug-in current transformer with a primary current of 400 A to 4000 A, for rails PACT MCR-V2-10036-129-... 2277381 1 PACT MCR-V2-10036-129-3000-5A-1 2276405 1 Transformation ratio 3000 A:5 A; 15 VA Selection table Primary rated current strength Ipn Cl. 400 500 2.5 5 600 5 10 750 5 10 800 5 10 1000 5 10 1250 5 10 15 1500 5 10 15 1600 5 10 15 2000 5 10 15 2.5 5 2.5 5 5 10 5 10 5 10 5 10 5 10 15 5 10 15 5 10 15 5 10 15 2.5 5 2.5 5 5 10 5 10 5 10 5 10 15 5 10 15 5 10 15 2.5 5 5 10 5 10 5 10 5 10 15 5 10 15 5 10 15 5 10 15 20 5 10 15 20 5 10 15 25 0.5 1A 1 0.5 5A 2.5 5 1 103359_en_03 2500 5 10 15 20 5 10 15 25 5 10 15 20 5 10 15 30 3000 5 10 15 20 5 10 15 30 5 10 15 25 5 10 15 30 4000 Rated power Sn [VA] Isn 5 10 15 25 5 10 15 30 PHOENIX CONTACT 13 PACT Analog Plug-in current transformers with a primary current of 400 A to 4000 A, for rails and circular conductors Description Type Order No. Pcs. / Pkt. Plug-in current transformer with a primary current of 400 A to 4000 A, for rails and circular conductors PACT MCR-V2-12020-159-... 2277394 1 Order No. Pcs. / Pkt. Plug-in current transformer with a primary current of 400 A to 4000 A, for rails PACT MCR-V2-12040-159-... 2277404 1 Transformation ratio 4000 A:5 A; 15 VA 2276418 1 Selection table Primary rated current strength Ipn Cl. 0.5 400 2.5 5 10 500 2.5 5 10 600 2.5 5 10 750 2.5 5 10 800 2.5 5 10 2.5 5 10 15 2.5 5 10 5 10 15 20 2.5 5 10 5 10 15 20 2.5 5 10 2.5 5 10 2.5 5 10 15 5 10 15 20 5 10 15 20 2.5 5 10 15 2.5 10 10 15 5 10 15 30 1A 1 0.5 5A 1 2.5 10 10 15 5 10 15 20 1000 2.5 5 10 15 5 10 15 20 5 10 15 30 5 10 15 30 1250 5 10 15 20 5 10 15 30 5 10 15 30 5 10 15 30 1500 5 10 15 30 5 10 15 30 10 10 30 45 10 15 30 45 1600 5 10 15 30 5 10 15 30 5 10 15 30 5 10 15 30 2000 5 10 15 30 5 10 15 30 5 10 15 30 5 10 15 30 2500 5 10 15 30 5 10 15 30 5 10 15 30 10 15 30 45 3000 5 10 15 30 10 15 30 45 10 10 30 45 10 15 30 45 4000 10 15 30 45 10 15 30 45 10 10 30 45 10 15 30 45 Rated power Sn [VA] Isn Plug-in current transformers with a primary current of 400 A to 4000 A, for rails Description Type PACT MCR-V2-12040-159-4000-5A-1 Selection table Primary rated current strength Ipn Isn Cl. 400 2.5 5 500 2.5 5 600 2.5 5 750 2.5 5 800 2.5 5 1000 2.5 5 10 1250 5 10 15 1500 5 10 15 1600 5 10 15 2000 5 10 15 2500 5 10 15 3000 5 10 15 4000 10 15 30 2.5 5 10 5 10 15 5 10 15 2.5 5 2.5 5 10 5 10 15 5 10 15 5 10 15 5 10 15 5 10 15 5 10 15 10 15 30 10 15 30 2.5 5 2.5 5 2.5 5 2.5 5 10 2.5 5 10 5 10 15 5 10 15 10 15 30 5 10 15 5 10 15 5 10 15 10 15 30 10 15 30 2.5 5 10 5 10 15 5 10 15 5 10 15 5 10 15 5 10 15 5 10 15 10 15 30 5 10 15 5 10 15 5 10 30 10 15 30 10 15 30 0.5 1 0.5 Rated power Sn [VA] 1A 5A 1 103359_en_03 PHOENIX CONTACT 14 PACT Analog Winding current transformers with a primary current of 1 A to 40 A Description Type Order No. Pcs. / Pkt. Winding current transformer with a primary current of 1 A to 40 A PACT MCR-V3-60-... 2277417 1 Selection table Primary rated current strength Ipn Isn Cl. 1 2.5 5 2 2.5 5 2.5 2.5 5 4 2.5 5 5 2.5 5 6 2.5 5 7.5 2.5 5 10 2.5 5 12.5 2.5 5 15 2.5 5 20 2.5 5 25 2.5 5 30 2.5 5 40 2.5 5 2.5 5 2.5 5 2.5 5 2.5 5 2.5 5 2.5 5 2.5 5 2.5 5 2.5 5 2.5 5 2.5 5 2.5 5 2.5 5 2.5 5 2.5 5 2.5 5 2.5 5 2.5 5 2.5 5 2.5 5 2.5 5 2.5 5 2.5 5 2.5 5 2.5 5 2.5 5 2.5 5 2.5 5 2.5 5 2.5 5 2.5 5 2.5 5 2.5 5 2.5 5 2.5 5 2.5 5 2.5 5 2.5 5 2.5 5 2.5 5 2.5 5 2.5 5 0.5 1 0.5 Rated power Sn [VA] 1A 5A 1 103359_en_03 PHOENIX CONTACT 15 PACT Analog 3.2 Current transformers that can be calibrated Bus-bar current transformers with a primary current of 150 A to 500 A, for circular conductors Description Type Order No. Pcs. / Pkt. Bus-bar current transformer with a primary current of 150 A to 500 A, for circular conductors PACT MCR-V1C-21-44-... 2277420 1 Selection table Primary rated current strength Ipn Isn Cl. 150 200 250 300 400 2.5 500 2.5 5 2.5 5 2.5 5 2.5 5 Rated power Sn [VA] 0.2 S 0.2 5A 2.5 2.5 5 2.5 5 10 2.5 5 2.5 5 10 2.5 5 2.5 5 2.5 5 10 2.5 5 2.5 5 10 0.5 S 2.5 0.5 Plug-in current transformers with a primary current of 200 A to 750 A, for rails and circular conductors Description Type Order No. Pcs. / Pkt. Plug-in current transformer with a primary current of 200 A to 750 A, for rails and circular conductors PACT MCR-V2C-3015-60-... 2277433 1 Selection table Isn Cl. 200 250 300 400 500 600 2.5 5 10 750 2.5 5 10 2.5 2.5 5 2.5 5 10 2.5 5 10 2.5 5 10 15 2.5 5 10 15 0.2 0.2 S Rated power Sn [VA] Primary rated current strength Ipn 5A 2.5 2.5 5 2.5 5 10 2.5 5 10 2.5 5 10 2.5 5 2.5 5 2.5 5 10 2.5 5 10 2.5 5 10 0.5 2.5 0.5 S 103359_en_03 PHOENIX CONTACT 16 PACT Analog Plug-in current transformers with a primary current of 200 A to 1000 A, for rails and circular conductors Description Type Order No. Pcs. / Pkt. Plug-in current transformer with a primary current of 200 A to 1000 A, for rails and circular conductors PACT MCR-V2C-4012-70-... 2277446 1 Selection table Isn Cl. 200 250 300 400 500 600 2.5 5 750 2.5 5 10 800 2.5 5 10 1000 5 10 2.5 5 2.5 5 10 2.5 5 10 5 10 2.5 5 10 5 10 0.2 S 0.2 Rated power Sn [VA] Primary rated current strength Ipn 5A 2.5 2.5 5 2.5 5 10 2.5 5 10 5 10 5 10 2.5 5 10 5 10 2.5 5 2.5 5 2.5 5 10 2.5 5 10 5 10 5 10 2.5 5 10 5 10 0.5 S 2.5 0.5 Plug-in current transformers with a primary current of 200 A to 1200 A, for rails and circular conductors Description Type Order No. Pcs. / Pkt. Plug-in current transformer with a primary current of 200 A to 1200 A, for rails and circular conductors PACT MCR-VC2-5012-85-... 2277459 1 Selection table Primary rated current strength Ipn Cl. 200 250 300 400 500 600 2.5 5 700 2.5 5 10 800 2.5 5 10 2.5 2.5 5 2.5 5 10 2.5 5 10 2.5 5 10 0.2 S 0.2 5A 2.5 2.5 5 2.5 5 2.5 5 10 2.5 5 10 5 10 5 10 5 10 2.5 2.5 5 2.5 5 2.5 5 10 2.5 5 10 5 10 5 10 5 10 0.5 S 0.5 103359_en_03 1000 5 10 15 30 5 10 15 30 5 10 15 30 5 10 15 30 1200 5 10 15 30 5 10 15 30 5 10 15 30 5 10 15 30 Rated power Sn [VA] Isn PHOENIX CONTACT 17 PACT Analog Plug-in current transformers with a primary current of 250 A to 1200 A, for rails and circular conductors Description Type Order No. Pcs. / Pkt. Plug-in current transformer with a primary current of 250 A to 1200 A, for rails and circular conductors PACT MCR-V2C-6015-85-... 2277462 1 Selection table Isn Cl. 200 250 300 400 500 600 750 2.5 5 800 2.5 5 1000 2.5 5 10 1200 2.5 5 10 2.5 2.5 5 2.5 5 2.5 5 10 2.5 5 10 15 2.5 5 10 15 2.5 5 10 15 2.5 5 10 15 2.5 5 10 15 0.2 S 0.2 5A 2.5 2.5 5 2.5 5 2.5 5 10 2.5 5 10 2.5 2.5 5 2.5 5 2.5 5 10 2.5 5 10 0.5 S 2.5 2.5 0.5 Rated power Sn [VA] Primary rated current strength Ipn Plug-in current transformers with a primary current of 200 A to 1500 A, for rails and circular conductors Description Type Order No. Pcs. / Pkt. Plug-in current transformer with a primary current of 200 A to 1500 A, for rails and circular conductors PACT MCR-V2C-6015-95-... 2277475 1 Selection table Primary rated current strength Ipn Cl. 200 250 300 400 500 600 750 800 1000 2.5 5 15 2.5 5 2.5 5 2.5 5 10 2.5 2.5 5 2.5 5 10 2.5 5 10 2.5 5 2.5 5 10 15 2.5 5 10 15 2.5 5 10 15 2.5 5 10 15 5 10 10 15 5 10 15 20 2.5 5 10 15 5 10 15 20 5 10 15 30 5 10 15 20 5 10 15 20 5 10 15 30 0.2 S 0.2 5A 0.5 S 2.5 0.5 103359_en_03 2.5 5 1200 5 10 15 20 5 10 15 20 5 10 15 20 5 10 15 20 1250 5 10 15 20 5 10 15 20 5 10 15 30 5 10 15 30 1500 5 10 15 30 5 10 15 30 5 10 15 30 5 10 15 30 Rated power Sn [VA] Isn PHOENIX CONTACT 18 PACT Analog Plug-in current transformers with a primary current of 500 A to 1500 A, for rails and circular conductors Description Type Order No. Pcs. / Pkt. Plug-in current transformer with a primary current of 500 A to 1500 A, for rails and circular conductors PACT MCR-V2C-6040-96-... 2277488 1 Selection table Primary rated current strength Ipn Cl. 500 600 750 800 1000 1200 2.5 5 2.5 5 2.5 5 2.5 5 2.5 5 10 2.5 5 10 15 2.5 5 10 15 0.2 S 0.2 5A 2.5 2.5 5 2.5 5 2.5 5 10 2.5 5 10 2.5 5 2.5 5 2.5 5 10 2.5 5 10 2.5 5 10 0.5 S 0.5 1250 2.5 5 10 15 2.5 5 10 15 2.5 5 10 15 2.5 5 10 15 1500 2.5 5 2.5 5 Rated power Sn [VA] Isn 2.5 5 10 2.5 5 10 Plug-in current transformers with a primary current of 400 A to 1500 A, for rails and circular conductors Description Type Order No. Pcs. / Pkt. Plug-in current transformer with a primary current of 400 A to 1500 A, for rails and circular conductors PACT MCR-V2C-8015-105-... 2277491 1 Selection table Primary rated current strength Ipn Isn Cl. 400 500 600 750 800 1000 1200 1250 1500 2.5 5 2.5 5 2.5 5 10 2.5 5 10 2.5 5 10 2.5 5 10 2.5 5 10 15 2.5 5 10 15 2.5 5 10 15 5 10 15 20 5 10 15 20 2.5 5 10 2.5 5 10 2.5 5 10 2.5 5 10 2.5 5 10 15 2.5 5 10 15 2.5 5 10 15 0.2 5A 2.5 2.5 2.5 5 2.5 5 10 2.5 5 2.5 5 2.5 5 10 2.5 5 10 15 0.5 S 0.5 103359_en_03 Rated power Sn [VA] 0.2 S PHOENIX CONTACT 19 PACT Analog Plug-in current transformers with a primary current of 400 A to 1500 A, for rails and circular conductors Description Type Order No. Pcs. / Pkt. Plug-in current transformer with a primary current of 400 A to 1500 A, for rails and circular conductors PACT MCR-V2C-8020-105-... 2277501 1 Selection table Primary rated current strength Ipn Isn Cl. 400 500 600 750 800 1000 1200 1250 2.5 5 1500 2.5 5 2.5 2.5 2.5 2.5 5 2.5 5 10 2.5 5 10 2.5 5 10 2.5 2.5 5 2.5 5 2.5 5 10 2.5 5 10 2.5 5 10 2.5 5 10 2.5 5 10 2.5 5 2.5 5 2.5 5 2.5 5 10 2.5 5 10 2.5 5 10 2.5 5 10 2.5 5 10 0.2 Rated power Sn [VA] 0.2 S 5A 0.5 S 2.5 5 0.5 Plug-in current transformers with a primary current of 500 A to 2500 A, for rails and circular conductors Description Type Order No. Pcs. / Pkt. Plug-in current transformer with a primary current of 500 A to 2500 A, for rails and circular conductors PACT MCR-V2C-10020-129-... 2277514 1 Selection table Isn Cl. 500 600 750 800 1000 1200 1250 1500 2.5 5 1600 2.5 5 200 2.5 5 2500 2.5 5 10 2.5 5 10 2.5 5 10 2.5 5 10 15 2.5 5 10 15 2.5 5 10 15 2.5 5 10 15 2.5 5 10 15 2.5 5 10 15 2.5 5 10 15 2.5 5 10 15 2.5 5 10 15 2.5 5 10 15 2.5 5 10 15 2.5 5 10 15 2.5 5 10 15 2.5 5 10 15 2.5 5 10 15 2.5 5 10 15 2.5 5 10 15 0.2 S 0.2 5A 2.5 5 2.5 5 2.5 5 2.5 5 10 2.5 5 10 2.5 5 2.5 5 2.5 5 10 2.5 5 10 15 2.5 5 10 15 0.5 S 0.2 103359_en_03 Rated power Sn [VA] Primary rated current strength Ipn PHOENIX CONTACT 20 PACT Analog Plug-in current transformers with a primary current of 500 A to 2500 A, for rails and circular conductors Description Type Order No. Pcs. / Pkt. Plug-in current transformer with a primary current of 500 A to 2500 A, for rails and circular conductors PACT MCR-V2C-10036-129-... 2277527 1 Type Order No. Pcs. / Pkt. Outside diameter 42 mm, inside diameter 12 mm (for MCR-V2-5012-85-...) PACT MCR-CB-42-12 2277530 1 Outside diameter 28 mm, inside diameter 12 mm (for MCR-V2-3015-60-...) PACT MCR-CB-28-12 2277543 1 Outside diameter 21 mm, inside diameter 12 mm (for MCR-V1-21-44-...) PACT MCR-CB-21-12 2277556 1 Outside diameter 21 mm, inside diameter 8 mm (for MCR-V1-21-44-...) PACT MCR-CB-21-8 2277569 1 Snap-on mounting for DIN rails PACT MCR-RA 2277598 9 Secondary terminal cover to increase air and creepage distances when installed horizontally, length of 60 mm PACT MCR-ETC-60 2277572 9 Secondary terminal cover to increase air and creepage distances when installed horizontally, length of 70 mm PACT MCR-ETC-75 2277585 9 Protective caps for the primary rail mounting screws (for protection against accidental contact) PACT MCR-ICAP 2277608 9 Selection table Isn Cl. 500 600 750 800 1000 1200 1250 1500 2.5 5 1600 2000 2.5 5 2500 2.5 5 10 2.5 5 10 2.5 5 10 2.5 5 10 2.5 5 10 15 2.5 5 10 15 2.5 5 10 15 2.5 5 10 15 2.5 5 10 15 2.5 5 10 15 2.5 5 10 15 2.5 5 10 15 2.5 5 10 15 2.5 5 10 15 2.5 5 10 15 2.5 5 10 15 2.5 5 10 15 2.5 5 10 15 0.2 S 0.2 5A 2.5 2.5 2.5 5 2.5 5 10 2.5 5 10 2.5 5 10 2.5 5 10 2.5 5 10 0.5 S 2.5 5 2.5 5 0.5 3.3 Rated power Sn [VA] Primary rated current strength Ipn Standard accessories, supplied as standard Description Attachment of the current transformer to the copper rail using the primary rail support (with 2 screws and 2 nuts) Secondary terminal cover (2 green slides for covering the secondary terminals) Plug-in feet which can be inserted into the side for attaching the current transformer to the mounting plate 3.4 Optional accessories Description Copper sleeves for horizontal installation as a connecting piece, e.g., from the power rail to the fuse holder 103359_en_03 PHOENIX CONTACT 21 PACT Analog 4 Technical data General data Rated frequency Transformers that cannot be calibrated 50 Hz to 60 Hz Transformers that can be calibrated 50 Hz Class of insulation E Thermal rated short-time current Ith 60 x IN Rated surge current Idyn 2.5 x Ith Rated insulation voltage according to EN 50178 1 kV Impulse withstand voltage 12 kV (1.2/50 µs) Surge voltage category III Rated power Depends on type, 1.25 VA to 45 VA Primary rated current Ipn Depends on type, 1 A to 4000 A Secondary rated current Isn Depends on type, 1 A or 5 A Accuracy Depends on type, class 0.2; 0.2 S; 0.5; 0.5 S or 1 Surge current limitation factor FS 5 or FS 10 Housing material Polyamide PA glass fiber reinforced, black Connection data Connection capacity of the secondary terminals 2 x (2.5 x 4) mm Ambient conditions Ambient temperature (operation/storage/transport) -25°C to +40°C Permissible humidity Use only indoors; no condensation Conformance/approvals Conformance EN 50178 Standard IEC 60044-1 103359_en_03 PHOENIX CONTACT 22 PACT Analog 5 Safety notes WARNING: Danger due to damaged current transformers • Before startup, check that the housing of the current transformer is not damaged. • Also before startup, check that there are no electrically conductive connections between the primary conductor and the secondary terminals. • If a built-in current transformer is removed in order to be used in a different system, check the current transformer for damage again. WARNING: Danger due to voltage at open circuit The output of the current transformer is a constant current source. In the event of an increasing load, the output voltage thus increases and reaches its maximum at infinite load (i.e., with open secondary terminals). • Avoid open-circuit operation at all costs. • Note that unloaded transformers must be short circuited. • Only start up the current transformer once the secondary cables are connected on both sides. NOTE: Avoid material damage when grounding In accordance with VDE 0414, current transformers and voltage transducers must be secondary grounded from a series voltage of 3.6 kV. At low voltages there is no need for grounding, provided the transformers do not have any large metal surfaces within reach. • Ground the current transformers at the k terminal block. NOTE: Avoid damage due to improper mounting Vibrations can cause the screws on the primary rail to loosen. • During mounting, tighten the screws on the primary rail support so that they cannot loosen as a result of vibrations. Condensation can cause short circuits on the screws of the primary rail. • Only start up the current transformer inside, where there is no condensation. 103359_en_03 PHOENIX CONTACT 23 PACT Analog 6 Selecting the optimum transformer Once the technical specifications for the current transformers required by the application have been defined, the next step is to determine the transformer types. The four main current transformer characteristics are: 1. Primary rated current (primary current Ipn) 2. Secondary rated current (secondary current Isn) 3. Capacity (power) in VA 4. Accuracy (class) Power requirement of copper cables with a different diameter Cable cross Power in VA section in mm2 (consider the supply and return line) at 5 A at 1 A 1.5 0.2917 0.117 2.5 0.175 0.0070 4 0.1094 0.0044 6 0.0729 0.0029 The current transformer is selected first and foremost based on the primary rated current Ipn, which can be up to 4000 A (depending on the type) and the secondary rated current Isn. This is either 1 A AC or 5 A AC at the output. Isn at 5 A AC: The accuracy (class) can be another important criterion for selecting the correct current transformer if certain specifications have to be met. Isn at 1 A AC: Special attention, however, should be paid to the calculation of the rated power (in VA). Here it is important to take into consideration all occurring loads of the measuring circuit for optimum selection of the rated power of the current transformer (see below). 7 Phoenix Contact offers an extensive range of current transformer types. This means that several different types may meet the prescribed technical criteria. The main differences lie in the size and shape of the transformer opening and in the external dimensions of the transformer housing. This allows you to select an optimum current transformer based on the size of the copper rail and the space available in the control cabinet. How do you choose the optimum current transformer? Firstly, add together all occurring loads: – Calculate the power requirement of the copper cable (info: cable length x 2) – Take into account the power requirement of the connected devices – Add the reserve requirement P = 10 m x 2 x 0.175 VA  P = 3.50 VA P = 10 m x 2 x 0.007 VA  P = 0.14 VA Installation and connection Current transformers from Phoenix Contact can be positioned anywhere. Thanks to the primary rail support of the PACT Analog current transformer which can be pulled out, no edges protrude from the housing. Instead all edges are flush. This is the basic prerequisite for the parallel attachment and positioning of the current transformers on the copper rail, which thus enables currents and loads supplied via an electric branch to be measured. To this end, a copper sleeve (accessory) is inserted into the internal opening of the current transformer, which creates a conductive connection between the current-carrying copper rail and, e.g., the securing lug of a downstream fuse. To increase the air and creepage distances, an extended secondary terminal cover (accessory) is placed over the connections of the secondary terminals of the horizontal current transformer. The optimum current transformer is one which can accommodate a maximum of 1.5 times the total load. This is because underloads affect accuracy and impair the overcurrent limiting protection, which protects the secondary circuit from being damaged by excessive currents. 103359_en_03 PHOENIX CONTACT 24 PACT Analog 7.1 Installing a current transformer The current transformers can be installed in the following mounting positions: 1. B C Vertically on the copper rail In most applications, the current transformer is fitted directly onto the copper rail. • Slide the current transformer over the copper rail. • Slide the primary rail support through the inner hole of the current transformer (A). • Insert the two screws on the left and right of the transformer into the holes of the primary rail support until they reach the copper rail and the pressure is such that the current transformer is fixed in place (B). • Attach the protective caps for protection against accidental contact to the screw heads (C). A 103359A003 2. Vertically on the mounting plate Two plug-in feet are included as standard accessories (see page 21). • Insert the plug-in feet underneath the transformer on the right and the left (A). • Place the current transformer on the mounting plate (B). • Insert the screws through the openings of the plug-in feet to secure the current transformer (C). C B A 103359A004 103359_en_03 PHOENIX CONTACT 25 PACT Analog 3. Vertically on the DIN rail The current transformer can also be snapped onto the DIN rail with the optional snap-on mounting (see page 21). • Snap the snap-on mounting into the holes beneath the current transformer (A). • Snap the current transformer onto the DIN rail (B). A B 103359A005 4. Horizontally on the copper rail As a result of their flat shape, the Phoenix Contact current transformers can also be fitted horizontally onto copper rails, e.g., behind fuse rails. A This is possible with the following current transformer types: – MCR-V2-5012-85... (see page 7) – MCR-V2-3015-60... (see page 5) – MCR-V1-21-44... (see page 4) B • 103359A006 • 103359_en_03 Insert a suitable copper sleeve (see page 21) into the inner hole of the current transformer (A) to create a conductive connection between the copper rail and the fuse. Attach the extended secondary terminal cover to the secondary terminals (B) to increase the air and creepage distances when the current transformer is installed horizontally. PHOENIX CONTACT 26 PACT Analog 7.2 Connecting a current transformer The connections of the primary winding are designated as "K" and "L" or "P1" and "P2". The connections of the secondary winding are designated as "k" and "l" or "s1" and "s2". Pole the cables so that the power flows from "K" to "L". A Isn s1 k I pn s2 l K P1 L P2 103359A002 Figure 2 Power flow direction 103359A001 Figure 1 8 Example connection with PACT MCR-V1-2144-... Calibrating the current transformers Calibrated current transformers are identified by a yellow sticker: Consecutive number A PTB (Physikalisch-Technischen Bundesanstalt) approval mark is also applied: Identification of the Calibration regulations, measuring transducer type appendix 20 20.21 Calibration mark of a test center 01.03 Year Approval year Figure 3 Example stamp of a nationally recognized test center Figure 4 Consecutive number Example PTB (Physikalisch-Technischen Bundesanstalt) approval mark Each calibrated current transformer is provided with a corresponding calibration certificate. The calibration process involves additional costs, which are specified in accordance with the national table of fees. These depend on the maximum rated input current of the current transformer. 103359_en_03 PHOENIX CONTACT 27 PACT Analog 9 Safe isolation Operating voltages by comparison EN 60044-11 480 V (L-L) Rated insulation voltage: (operating voltage)     7280 V (L-L) 1000 V (L-L) / EN 501782 277 V (L-L) 416 V (L-L) 577 V (L-L) 1000 V (L-L) Impulse withstand voltage for transformer testing: 3 kV at 277 V (L-N) 6 kV 12 kV 3 kV at 1000 V (L-N) 9.1 – – 1 EN 60044-1: Measuring transducers - Part 1: Current transformer 2 EN 50178: Electronic equipment for use in power installations Application example with safe isolation up to 1 kV The current transformer converts the high current down to 1 A AC or 5 A AC. A downstream current transducer creates a standard signal from the secondary current. SELV = Safety Extra Low Voltage Inline controller Safe isolation according to EN 50178 1 A AC 4 to 20 mA 5 A AC 0 to 10 V EN 60044-1 applies only to here. e.g., Ethernet Motor Rated insulation voltage up to 1000 V (L-N) Figure 5 103359_en_03 Application example PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany • Phone: + 49 5235 3-00 PHOENIX CONTACT • P.O.Box 4100 • Harrisburg • PA 17111-0100 • USA • Phone: +717-944-1300 www.phoenixcontact.com 28
2277048 价格&库存

很抱歉,暂时无法提供与“2277048”相匹配的价格&库存,您可以联系我们找货

免费人工找货