PACT Analog
Current transformers
INTERFACE
Data sheet
103359_en_03
1
© PHOENIX CONTACT 2011-04-04
Description
The PACT Analog current transformers form a complete
range of bus-bar, plug-in and winding current transformers
for measuring AC currents with a range of 1 A to 4000 A.
Current transformers belong to a group of specialized
transformers and are used in those areas where currents
cannot be measured directly. Depending on the
transformation ratio, the primary current is transmitted to a
smaller electrically isolated secondary current.
PACT Analog current transformers can be used either as an
industrial version or as a transformer that can be officially
calibrated.
The calibration process involves additional costs,
which are specified in accordance with the
national table of fees.
1.1
–
–
–
Features
Safe isolation as a result of the test voltage of 12 kV
(1.2/50 µs) prevents a hazardous operating voltage
from being transferred to downstream components
Conforms to surge voltage category 3 as a result of the
test voltage amplitude
Routine test according to EN 50178
Also refer to additional information on "Safe
isolation"; see page 28.
PACT Analog current transformers are available in the
following designs:
– Winding current transformer (Ipn: 1 A to 40 A)
– Bus-bar current transformer (Ipn: 50 A to 500 A)
– Plug-in current transformer (Ipn: 50 A to 4000 A)
WARNING: Danger due to damaged current transformers
•
Before startup, check that the housing of the current transformer is not damaged.
•
Also before startup, check that there are no electrically conductive connections between the primary
conductor and the secondary terminals.
•
If a built-in current transformer is removed in order to be used in a different system, check the current
transformer for damage again.
WARNING: Danger due to voltage at open circuit
The output of the current transformer is a constant current source. In the event of an increasing load, the output
voltage thus increases and reaches its maximum at infinite load (i.e., with open secondary terminals).
•
Avoid open-circuit operation at all costs.
•
Note that unloaded transformers must be short circuited.
•
Only start up the current transformer once the secondary cables are connected on both sides.
PACT Analog
2
1
Table of contents
Description.................................................................................................................................. 1
1.1
Features ......................................................................................................................................................... 1
2
Table of contents ........................................................................................................................ 2
3
Ordering data.............................................................................................................................. 3
3.1
3.2
3.3
3.4
Current transformers that cannot be calibrated .............................................................................................. 4
Current transformers that can be calibrated ................................................................................................. 16
Standard accessories, supplied as standard................................................................................................ 21
Optional accessories.................................................................................................................................... 21
4
Technical data ...........................................................................................................................22
5
Safety notes...............................................................................................................................23
6
Selecting the optimum transformer ............................................................................................24
7
Installation and connection ........................................................................................................24
7.1
7.2
Installing a current transformer ..................................................................................................................... 25
Connecting a current transformer ................................................................................................................ 27
8
Calibrating the current transformers...........................................................................................27
9
Safe isolation .............................................................................................................................28
9.1
103359_en_03
Application example with safe isolation up to 1 kV ....................................................................................... 28
PHOENIX CONTACT
2
PACT Analog
3
Ordering data
Make sure you always use the latest documentation.
It can be downloaded at www.phoenixcontact.net/catalog.
Explanation of the type designation by means of an example
PACT MCR-V2C-3015-60
V1 = Bus-bar current transformer (for assembly with circular conductors)
V2 = Plug-in current transformer (for direct or horizontal assembly on power rails)
V3 = Winding current transformer
C = Transformer that can be calibrated
30 = Maximum width of the power rail in mm
15 = Maximum height of the power rail in mm
60 = Width of the current transformer in mm
Information on the type entry in the order key
Type
PACT MCR-V2-3015-60
Primary current Ipn
-
80
Secondary current
Isn
-
5A
Class
-
1
Power ()
-
2.5 VA
Order No.
-
2277268
For some of the current transformers listed in the following tables, popular types are available from stock. These
have their own order Nos. and are labeled separately.
For all other types, please complete the order key using the respective selection table.
103359_en_03
PHOENIX CONTACT
3
PACT Analog
3.1
Current transformers that cannot be calibrated
Bus-bar current transformers with a primary current of 50 A to 500 A, for circular conductors
Description
Type
Order No.
Pcs. /
Pkt.
Bus-bar current transformer with a primary current of 50 A to 500 A, for circular
conductors
PACT MCR-V1-21-44-...
2277268
1
PACT MCR-V1-21-44-50-5A-1
2277019
1
Transformation ratio 50 A:5 A; 1.25 VA
PACT MCR-V1-21-44-75-5A-1
2277611
1
Transformation ratio 75 A:5 A; 2.5 VA
PACT MCR-V1-21-44-100-5A-1
2277022
1
Transformation ratio 100 A:5 A; 2.5 VA
PACT MCR-V1-21-44-125-5A-1
2277763
1
Transformation ratio 125 A:5 A; 3.75 VA
PACT MCR-V1-21-44-150-5A-1
2277035
1
Transformation ratio 150 A:5 A; 5 VA
PACT MCR-V1-21-44-200-5A-1
2277776
1
Transformation ratio 200 A:5 A; 5 VA
PACT MCR-V1-21-44-250-5A-1
2277048
1
Transformation ratio 250 A:5 A; 5 VA
PACT MCR-V1-21-44-300-5A-1
2277789
1
Transformation ratio 300 A:5 A; 10 VA
PACT MCR-V1-21-44-400-5A-1
2277051
1
Transformation ratio 400 A:5 A; 5 VA
PACT MCR-V1-21-44-500-5A-1
2277792
1
Transformation ratio 500 A:5 A; 10 VA
Selection table
Primary rated current strength Ipn
Isn
Cl.
50
60
75
80
100
1.25
125
2.5
150
2.5
3.75
200
2.5
5
250
2.5
5
7.5
300
2.5
5
400
2.5
5
7.5
500
2.5
5
10
1.25
1.25
2.5
2.5
2.5
2.5
3.75
2.5
5
2.5
5
2.5
5
7.5
2.5
5
2.5
5
7.5
2.5
5
10
1.25
1.5
1.25
2.0
1.25
2.5
2.5
3.75
2.5
5
7.5
2.5
5
10
2.5
5
7.5
2.5
5
7.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
7.5
2.5
2.5
7.5
2.5
5
10
2.5
5
7.5
2.5
5
10
0.5
1
0.5
Rated power Sn [VA]
1A
5A
1.25
1
103359_en_03
1.25
1.5
2.5
2.5
PHOENIX CONTACT
4
PACT Analog
Plug-in current transformers with a primary current of 50 A to 750 A, for rails and circular conductors
Description
Type
Order No.
Pcs. /
Pkt.
Plug-in current transformer with a primary current of 50 A to 750 A, for rails and
circular conductors
PACT MCR-V2-3015-60-...
2277271
1
Transformation ratio 60 A:5 A; 1.25 VA
PACT MCR-V2-3015-60-60-5A-1
2277815
1
Transformation ratio 75 A:5 A; 1.25 VA
PACT MCR-V2-3015-60-75-5A-1
2277828
1
Transformation ratio 75 A:5 A; 1.5 VA
PACT MCR-V2-3015-60-75-5A-1
2276502
1
Transformation ratio 80 A:5 A; 1.25 VA
PACT MCR-V2-3015-60-80-5A-1
2277831
1
Transformation ratio 100 A:5 A; 2.5 VA
PACT MCR-V2-3015-60-100-5A-1
2277064
1
Transformation ratio 125 A:5 A; 3.75 VA
PACT MCR-V2-3015-60-125-5A-1
2277624
1
Transformation ratio 150 A:5 A; 3.75 VA
PACT MCR-V2-3015-60-150-5A-1
2277844
1
Transformation ratio 150 A:5 A; 5 VA
PACT MCR-V2-3015-60-150-5A-1
2277077
1
Transformation ratio 200 A:5 A; 5 VA
PACT MCR-V2-3015-60-200-5A-1
2277637
1
Transformation ratio 200 A:5 A; 7.5 VA
PACT MCR-V2-3015-60-200-5A-1
2277857
1
Transformation ratio 250 A:5 A; 5 VA
PACT MCR-V2-3015-60-250-5A-1
2276544
1
Transformation ratio 250 A:5 A; 7.5 VA
PACT MCR-V2-3015-60-250-5A-1
2277860
1
Transformation ratio 250 A:5 A; 10 VA
PACT MCR-V2-3015-60-250-5A-1
2277080
1
Transformation ratio 300 A:5 A; 7.5 VA
PACT MCR-V2-3015-60-300-5A-1
2277640
1
Transformation ratio 400 A:5 A; 10 VA
PACT MCR-V2-3015-60-400-5A-1
2277093
1
Transformation ratio 500 A:5 A; 10 VA
PACT MCR-V2-3015-60-500-5A-1
2277653
1
Transformation ratio 600 A:5 A; 10 VA
PACT MCR-V2-3015-60-600-5A-1
2277103
1
Transformation ratio 750 A:5 A; 10 VA
PACT MCR-V2-3015-60-750-5A-1
2277666
1
Selection table
Isn
Cl.
50
60
75
80
100
1.25
125
1.25
150
2.5
200
2.5
3.75
250
2.5
5
300
2.5
5
7.5
400
2.5
5
10
500
2.5
5
10
1.25
1.25
2.5
2.5
2.5
2.5
3.75
2.5
5
2.5
5
2.5
5
7.5
2.5
5
10
2.5
5
10
2.5
5
10
2.5
3.75
2.5
5
2.5
5
7.5
2.5
5
10
2.5
5
7.5
2.5
5
7.5
10
2.5
5
7.5
10
2.5
5
10
15
0.5
2.5
5
10
600
2.5
5
10
15
2.5
5
10
15
2.5
5
10
750
2.5
5
10
15
5
10
10
20
2.5
5
10
2.5
5
10
2.5
5
10
2.5
5
10
15
1A
1
0.5
Rated power Sn [VA]
Primary rated current strength Ipn
5A
1.25
1
103359_en_03
1.25
1.5
1.25
2
2.5
2.5
3.75
2.5
3.75
5
PHOENIX CONTACT
5
PACT Analog
Plug-in current transformers with a primary current of 75 A to 1000 A, for rails
Description
Type
Order No.
Pcs. /
Pkt.
Plug-in current transformer with a primary current of 75 A to 1000 A, for rails
PACT MCR-V2-4012-70-...
2277284
1
Transformation ratio 250 A:5 A; 5 VA
PACT MCR-V2-4012-70-250-5A-1
2277116
1
Transformation ratio 300 A:5 A; 7.5 VA
PACT MCR-V2-4012-70-300-5A-1
2277679
1
Transformation ratio 400 A:5 A; 7.5 VA
PACT MCR-V2-4012-70-400-5A-1
2277129
1
Transformation ratio 500 A:5 A; 10 VA
PACT MCR-V2-4012-70-500-5A-1
2277682
1
Transformation ratio 600 A:5 A; 10 VA
PACT MCR-V2-4012-70-600-5A-1
2277132
1
Transformation ratio 750 A:5 A; 10 VA
PACT MCR-V2-4012-70-750-5A-1
2277695
1
Transformation ratio 800 A:5 A; 10 VA
PACT MCR-V2-4012-70-800-5A-1
2277145
1
Transformation ratio 1000 A:5 A; 10 VA
PACT MCR-V2-4012-70-1000-5A-1
2277158
1
Selection table
Primary rated current strength Ipn
Cl.
50
60
75
80
100
125
1.25
150
2.5
200
2.5
3.75
250
2.5
5
300
2.5
5
400
2.5
5
7.5
500
2.5
5
10
600
2.5
5
10
750
2.5
5
10
1.25
1.25
2.5
2.5
3.75
2.5
5
2.5
5
2.5
5
7.5
2.5
5
7.5
2.5
5
7.5
2.5
5
10
2.5
5
10
1.25
2.5
2.5
3.75
2.5
5
2.5
5
2.5
5
7.5
2.5
5
10
2.5
5
10
2.5
5
10
15
2.5
5
10
2.5
3.75
2.5
5
2.5
5
2.5
5
7.5
2.5
5
7.5
2.5
5
7.5
2.5
5
10
2.5
5
10
0.5
1A
1
0.5
5A
1.25
1
103359_en_03
1.25
2.5
2.5
5
10
15
800
2.5
5
10
15
2.5
5
10
15
2.5
5
10
15
2.5
5
10
15
1000
2.5
5
10
2.5
5
10
2.5
5
10
Rated power Sn [VA]
Isn
2.5
5
10
PHOENIX CONTACT
6
PACT Analog
Plug-in current transformers with a primary current of 100 A to 1500 A, for rails and circular conductors
Description
Type
Order No.
Pcs. /
Pkt.
Plug-in current transformer with a primary current of 100 A to 1500 A, for rails
and circular conductors
PACT MCR-V2-5012-85-...
2277297
1
Transformation ratio 150 A:5 A; 3.75 VA
PACT MCR-V2-5012-85-150-5A-1
2276117
1
Transformation ratio 200 A:5 A; 5 VA
PACT MCR-V2-5012-85-200-5A-1
2276120
1
Transformation ratio 250 A:5 A; 7.5 VA
PACT MCR-V2-5012-85-250-5A-1
2276133
1
Transformation ratio 300 A:5 A; 10 VA
PACT MCR-V2-5012-85-300-5A-1
2276146
1
Transformation ratio 400 A:5 A; 10 VA
PACT MCR-V2-5012-85-400-5A-1
2277161
1
Transformation ratio 500 A:5 A; 15 VA
PACT MCR-V2-5012-85-500-5A-1
2276159
1
Transformation ratio 600 A:5 A; 10 VA
PACT MCR-V2-5012-85-600-5A-1
2277174
1
Transformation ratio 600 A:5 A; 15 VA
PACT MCR-V2-5012-85-600-5A-1
2276162
1
Transformation ratio 750 A:5 A; 10 VA
PACT MCR-V2-5012-85-750-5A-1
2276175
1
Transformation ratio 800 A:5 A; 10 VA
PACT MCR-V2-5012-85-800-5A-1
2277187
1
Transformation ratio 1000 A:5 A; 10 VA
PACT MCR-V2-5012-85-1000-5A-1
2276463
1
Transformation ratio 1000 A:5 A; 15 VA
PACT MCR-V2-5012-85-1000-5A-1
2277190
1
Transformation ratio 1250 A:5 A; 15 VA
PACT MCR-V2-5012-85-1250-5A-1
2277200
1
Transformation ratio 1500 A:5 A; 15 VA
PACT MCR-V2-5012-85-1500-5A-1
2276188
1
Selection table
Isn
Cl.
100
125
150
1.25
200
2.5
5
250
2.5
5
300
2.5
5
7.5
1.25
2.5
2.5
3.75
2.5
5
7.5
2.5
5
10
1.25
2.5
5
2.5
5
7.5
10
2.5
5
2.5
3.75
2.5
5
7.5
2.5
5
7.5
10
2.5
5
10
0.5
1A
1
0.5
2.5
5
7.5
5A
1.25
1
103359_en_03
2.5
400
2.5
5
10
15
2.5
5
10
15
2.5
5
10
15
2.5
5
10
15
500
2.5
5
10
15
2.5
5
10
20
2.5
5
10
15
5
10
15
20
600
2.5
5
10
15
2.5
5
10
20
2.5
5
20
15
5
10
15
20
750
2.5
5
10
800
2.5
5
10
2.5
5
10
2.5
5
10
15
2.5
5
10
2.5
5
10
2.5
5
10
2.5
5
10
15
1000
2.5
5
10
15
5
10
15
20
2.5
5
10
15
5
10
15
20
1250
2.5
5
10
15
5
10
15
20
2.5
5
10
15
5
10
15
20
1500
2.5
5
10
15
5
10
15
30
2.5
5
10
15
5
10
15
20
PHOENIX CONTACT
Rated power Sn [VA]
Primary rated current strength Ipn
7
PACT Analog
Plug-in current transformers with a primary current of 200 A to 1600 A, for rails and circular conductors
Description
Type
Order No.
Pcs. /
Pkt.
Plug-in current transformer with a primary current of 200 A to 1600 A, for rails
and circular conductors
PACT MCR-V2-6015-85-...
2277336
1
Transformation ratio 200 A:5 A; 2.5 VA
PACT MCR-V2-6015-85-200-5A-1
2277873
1
Transformation ratio 250 A:5A; 2.5 VA
PACT MCR-V2-6015-85-250-5A-1
2277886
1
Transformation ratio 300 A:5 A; 2.5 VA
PACT MCR-V2-6015-85-300-5A-1
2277899
1
Transformation ratio 400 A:5 A; 2.5 VA
PACT MCR-V2-6015-85-400-5A-1
2277909
1
Transformation ratio 500 A:5 A; 5 VA
PACT MCR-V2-6015-85-500-5A-1
2277912
1
Transformation ratio 600 A:5 A; 10 VA
PACT MCR-V2-6015-85-600-5A-1
2277925
1
Transformation ratio 750 A:5 A; 10 VA
PACT MCR-V2-6015-85-750-5A-1
2277938
1
Transformation ratio 800 A:5 A; 10 VA
PACT MCR-V2-6015-85-800-5A-1
2277941
1
Transformation ratio 1000 A:5 A; 15 VA
PACT MCR-V2-6015-85-1000-5A-1
2277954
1
Transformation ratio 1250 A:5 A; 15 VA
PACT MCR-V2-6015-85-1250-5A-1
2277967
1
Transformation ratio 1500 A:5 A; 15 VA
PACT MCR-V2-6015-85-1500-5A-1
2277970
1
Transformation ratio 1600 A:5 A; 15 VA
PACT MCR-V2-6015-85-1600-5A-1
2277983
1
Selection table
Primary rated current strength Ipn
Isn
Cl.
100
125
150
200
250
1.25
300
1.25
400
1.25
500
2.5
600
2.5
750
2.5
5
800
2.5
1000
2.5
1250
2.5
5
2.5
2.5
2.5
2.5
2.5
3.75
2.5
2.5
5
2.5
3.75
2.5
3.75
2.5
5
1.25
1.25
1.25
2.5
2.5
5
2.5
5
10
2.5
5
10
2.5
2.5
2.5
2.5
5
2.5
5
10
2.5
5
10
2.5
5
10
15
2.5
5
10
15
2.5
5
10
15
5
10
15
5
10
15
20
5
10
15
20
1500
2.5
1600
5
10
15
20
5
10
15
30
5
10
15
0.5
1
0.5
5A
2.5
1
103359_en_03
Rated power Sn [VA]
1A
5
10
15
PHOENIX CONTACT
8
PACT Analog
Plug-in current transformers with a primary current of 200 A to 2500 A, for rails and circular conductors
Description
Type
Order No.
Pcs. /
Pkt.
Plug-in current transformer with a primary current of 200 A to 2500 A, for rails
and circular conductors
PACT MCR-V2-6315-95-...
2277307
1
Transformation ratio 600 A:5 A; 10 VA
PACT MCR-V2-6315-95-600-5A-1
2276191
1
Transformation ratio 750 A:5 A; 10 VA
PACT MCR-V2-6315-95-750-5A-1
2276201
1
Transformation ratio 800 A:5 A; 10 VA
PACT MCR-V2-6315-95-800-5A-1
2277213
1
Transformation ratio 1000 A:5 A; 10 VA
PACT MCR-V2-6315-95-1000-5A-1
2277226
1
Transformation ratio 1250 A:5 A; 10 VA
PACT MCR-V2-6315-95-1250-5A-1
2277239
1
Transformation ratio 1500 A:5 A; 10 VA
PACT MCR-V2-6315-95-1500-5A-1
2277242
1
Transformation ratio 1600 A:5 A; 10 VA
PACT MCR-V2-6315-95-1600-5A-1
2277255
1
Transformation ratio 2000 A:5 A; 15 VA
PACT MCR-V2-6315-95-2000-5A-1
2276243
1
Selection table
Isn
Cl.
200
2.5
250
2.5
300
2.5
5
400
2.5
5
7.5
500
2.5
5
10
600
2.5
5
10
750
5
10
15
800
5
10
15
1000
5
10
1250
5
10
1500
5
10
15
1600
5
10
15
2.5
3.75
2.5
5
2.5
5
7.5
2.5
5
10
2.5
5
10
5
10
15
5
10
5
10
15
5
10
15
2.5
3.75
2.5
5
7.5
2.5
5
10
2.5
3.75
2.5
5
2.5
5
10
2.5
5
10
15
2.5
5
10
15
5
10
15
20
5
10
15
20
5
10
15
20
5
10
15
30
5
10
2.5
2.5
5
10
15
2.5
5
10
15
5
10
15
20
5
10
15
30
10
15
30
5
10
15
20
5
10
15
30
5
10
15
30
5
10
15
30
5
10
15
30
10
10
30
45
0.5
1A
1
0.5
5A
1
103359_en_03
5
10
15
20
5
10
15
30
2000
5
10
15
20
10
15
20
2500
5
10
15
30
10
15
30
5
10
15
30
10
15
30
PHOENIX CONTACT
Rated power Sn [VA]
Primary rated current strength Ipn
9
PACT Analog
Plug-in current transformers with a primary current of 200 A to 2000 A, for rails and circular conductors
Description
Type
Order No.
Pcs. /
Pkt.
Plug-in current transformer with a primary current of 200 A to 2000 A, for rails
and circular conductors
PACT MCR-V2-6040-96-...
2277349
1
Transformation ratio 600 A:5 A; 10 VA
PACT MCR-V2-6040-96-600-5A-1
2276191
1
Transformation ratio 750 A:5 A; 10 VA
PACT MCR-V2-6040-96-750-5A-1
2276201
1
Transformation ratio 800 A:5 A; 10 VA
PACT MCR-V2-6040-96-800-5A-1
2276214
1
Transformation ratio 1000 A:5 A; 10 VA
PACT MCR-V2-6040-96-1000-5A-1
2277705
1
Transformation ratio 1250 A:5 A; 15 VA
PACT MCR-V2-6040-96-1250-5A-1
2276227
1
Transformation ratio 1500 A:5 A; 10 VA
PACT MCR-V2-6040-96-1500-5A-1
2277718
1
Transformation ratio 1600 A:5 A; 15 VA
PACT MCR-V2-6040-96-1600-5A-1
2276230
1
Transformation ratio 2000 A:5 A; 15 VA
PACT MCR-V2-6040-96-2000-5A-1
2276243
1
Selection table
Primary rated current strength Ipn
Isn
Cl.
200
250
2.5
300
2.5
400
2.5
5
500
2.5
5
7.5
600
2.5
5
750
2.5
5
7.5
800
2.5
5
7.5
1000
2.5
5
10
1250
2.5
5
10
1500
2.5
2.5
3.75
2.5
5
2.5
5
2.5
5
7.5
2.5
5
7.5
2.5
5
2.5
5
7.5
2.5
5
7.5
2.5
5
10
2.5
5
10
2.5
5
2.5
2.5
2.5
5
2.5
5
7.5
2.5
5
7.5
2.5
5
10
2.5
5
10
2.5
5
7.5
2.5
5
10
2.5
5
10
2.5
3.75
2.5
5
2.5
5
7.5
2.5
5
7.5
2.5
5
10
2.5
5
10
2.5
5
10
15
2.5
5
10
5
10
15
2.5
5
10
0.5
1600
2000
2.5
5
10
15
5
10
15
5
10
15
1
0.5
5A
2.5
3.75
1
103359_en_03
Rated power Sn [VA]
1A
5
10
15
PHOENIX CONTACT
10
PACT Analog
Plug-in current transformers with a primary current of 400 A to 2500 A, for rails and circular conductors
Description
Type
Order No.
Pcs. /
Pkt.
Plug-in current transformer with a primary current of 400 A to 2500 A, for rails
and circular conductors
PACT MCR-V2-8015-105-...
2277352
1
Transformation ratio 400 A:5 A; 7.5 VA
PACT MCR-V2-8015-105-400-5A-1
2276256
1
Transformation ratio 500 A:5 A; 10 VA
PACT MCR-V2-8015-105-500-5A-1
2276269
1
Transformation ratio 600 A:5 A; 10 VA
PACT MCR-V2-8015-105-600-5A-1
2276272
1
Transformation ratio 750 A:5 A; 10 VA
PACT MCR-V2-8015-105-750-5A-1
2276285
1
Transformation ratio 800 A:5 A; 15 VA
PACT MCR-V2-8015-105-800-5A-1
2276298
1
Transformation ratio 1000 A:5 A; 10 VA
PACT MCR-V2-8015-105-1000-5A-1
2277721
1
Transformation ratio 1000 A:5 A; 15 VA
PACT MCR-V2-8015-105-1000-5A-1
2276308
1
Transformation ratio 1250 A:5 A; 10 VA
PACT MCR-V2-8015-105-1250-5A-1
2276311
1
Transformation ratio 1500 A:5 A; 15 VA
PACT MCR-V2-8015-105-1500-5A-1
2277734
1
Transformation ratio 1600 A:5 A; 15 VA
PACT MCR-V2-8015-105-1600-5A-1
2276324
1
Transformation ratio 2000 A:5 A; 20 VA
PACT MCR-V2-8015-105-2000-5A-1
2276337
1
Transformation ratio 2500 A:5 A; 20 VA
PACT MCR-V2-8015-105-2500-5A-1
2276340
1
Selection table
Primary rated current strength Ipn
Cl.
400
2.5
500
2.5
5
600
2.5
5
10
750
2.5
5
800
2.5
5
10
1000
2.5
5
7.5
1250
2.5
5
10
2.5
5
7.5
2.5
5
10
2.5
5
10
2.5
5
10
2.5
5
10
2.5
5
2.5
5
2.5
5
10
2.5
5
10
2.5
5
10
2.5
5
10
15
5
10
15
2.5
5
10
15
2.5
5
10
2.5
5
7.5
2.5
5
10
15
2.5
5
10
15
2.5
5
10
15
5
10
15
20
5
10
15
20
0.5
1A
1
0.5
5A
1
103359_en_03
2.5
5
10
1500
2.5
5
10
15
5
10
15
20
2.5
5
10
2.5
5
10
15
1600
2.5
5
10
15
5
10
15
20
2.5
5
10
15
5
10
15
2000
5
10
15
20
10
15
20
25
2.5
5
10
15
5
10
15
20
2500
Rated power Sn [VA]
Isn
5
10
15
20
10
15
20
30
PHOENIX CONTACT
11
PACT Analog
Plug-in current transformers with a primary current of 500 A to 2000 A, for rails and circular conductors
Description
Type
Order No.
Pcs. /
Pkt.
Plug-in current transformer with a primary current of 500 A to 2000 A, for rails
and circular conductors
PACT MCR-V2-8020-105-...
2277365
1
Transformation ratio 1000 A:5 A; 10 VA
PACT MCR-V2-8020-105-1000-5A-1
2277747
1
Transformation ratio 1500 A:5 A; 15 VA
PACT MCR-V2-8020-105-1500-5A-1
2277750
1
Transformation ratio 2000 A:5 A; 10 VA
PACT MCR-V2-8020-105-2000-5A-1
2276382
1
Selection table
Primary rated current strength Ipn
Isn
Cl.
500
2.5
600
2.5
5
750
2.5
5
800
2.5
5
1000
2.5
5
10
1250
2.5
1500
2.5
5
1600
2.5
5
2.5
5
2.5
5
7.5
2.5
5
7.5
2.5
5
7.5
2.5
5
2.5
5
2.5
5
2.5
5
2.5
5
7.5
2.5
5
7.5
2.5
5
7.5
2.5
5
10
15
2.5
5
10
2.5
5
10
2.5
5
10
2.5
5
2.5
5
7.5
2.5
5
7.5
2.5
5
10
2.5
5
10
5
10
10
2.5
5
10
15
2.5
5
10
15
5
10
15
0.5
2000
1
0.5
5A
1
103359_en_03
Rated power Sn [VA]
1A
2.5
5
10
5
10
PHOENIX CONTACT
12
PACT Analog
Plug-in current transformers with a primary current of 400 A to 4000 A, for rails and circular conductors
Description
Type
Order No.
Pcs. /
Pkt.
Plug-in current transformer with a primary current of 400 A to 4000 A, for rails
and circular conductors
PACT MCR-V2-10020-129-...
2277378
1
PACT MCR-V2-10020-129-2500-5A-1
2276395
1
Transformation ratio 2500 A:5 A; 15 VA
Selection table
Primary rated current strength Ipn
Cl.
400
500
2.5
5
600
5
10
750
5
10
800
5
10
1000
5
10
1250
5
10
15
1500
5
10
15
1600
5
10
15
2000
5
10
15
2.5
5
2.5
5
5
10
5
10
5
10
5
10
5
10
15
5
10
15
5
10
15
5
10
15
2.5
5
5
5
5
10
5
10
5
10
5
10
15
5
10
15
5
10
15
2.5
5
5
10
5
10
5
10
5
10
15
5
10
15
5
10
15
5
10
15
20
5
10
15
20
5
10
15
25
0.5
1A
1
0.5
5A
2.5
5
1
2500
5
10
15
20
5
10
15
25
5
10
15
20
5
10
15
30
3000
5
10
15
20
5
10
15
30
5
10
15
25
5
10
15
30
4000
Rated power Sn [VA]
Isn
5
10
15
25
5
10
15
30
Plug-in current transformers with a primary current of 400 A to 4000 A, for rails
Description
Type
Order No.
Pcs. / Pkt.
Plug-in current transformer with a primary current of 400 A to 4000 A,
for rails
PACT MCR-V2-10036-129-...
2277381
1
PACT MCR-V2-10036-129-3000-5A-1
2276405
1
Transformation ratio 3000 A:5 A; 15 VA
Selection table
Primary rated current strength Ipn
Cl.
400
500
2.5
5
600
5
10
750
5
10
800
5
10
1000
5
10
1250
5
10
15
1500
5
10
15
1600
5
10
15
2000
5
10
15
2.5
5
2.5
5
5
10
5
10
5
10
5
10
5
10
15
5
10
15
5
10
15
5
10
15
2.5
5
2.5
5
5
10
5
10
5
10
5
10
15
5
10
15
5
10
15
2.5
5
5
10
5
10
5
10
5
10
15
5
10
15
5
10
15
5
10
15
20
5
10
15
20
5
10
15
25
0.5
1A
1
0.5
5A
2.5
5
1
103359_en_03
2500
5
10
15
20
5
10
15
25
5
10
15
20
5
10
15
30
3000
5
10
15
20
5
10
15
30
5
10
15
25
5
10
15
30
4000
Rated power Sn [VA]
Isn
5
10
15
25
5
10
15
30
PHOENIX CONTACT
13
PACT Analog
Plug-in current transformers with a primary current of 400 A to 4000 A, for rails and circular conductors
Description
Type
Order No.
Pcs. /
Pkt.
Plug-in current transformer with a primary current of 400 A to 4000 A, for rails
and circular conductors
PACT MCR-V2-12020-159-...
2277394
1
Order No.
Pcs. /
Pkt.
Plug-in current transformer with a primary current of 400 A to 4000 A, for rails PACT MCR-V2-12040-159-...
2277404
1
Transformation ratio 4000 A:5 A; 15 VA
2276418
1
Selection table
Primary rated current strength Ipn
Cl.
0.5
400
2.5
5
10
500
2.5
5
10
600
2.5
5
10
750
2.5
5
10
800
2.5
5
10
2.5
5
10
15
2.5
5
10
5
10
15
20
2.5
5
10
5
10
15
20
2.5
5
10
2.5
5
10
2.5
5
10
15
5
10
15
20
5
10
15
20
2.5
5
10
15
2.5
10
10
15
5
10
15
30
1A
1
0.5
5A
1
2.5
10
10
15
5
10
15
20
1000
2.5
5
10
15
5
10
15
20
5
10
15
30
5
10
15
30
1250
5
10
15
20
5
10
15
30
5
10
15
30
5
10
15
30
1500
5
10
15
30
5
10
15
30
10
10
30
45
10
15
30
45
1600
5
10
15
30
5
10
15
30
5
10
15
30
5
10
15
30
2000
5
10
15
30
5
10
15
30
5
10
15
30
5
10
15
30
2500
5
10
15
30
5
10
15
30
5
10
15
30
10
15
30
45
3000
5
10
15
30
10
15
30
45
10
10
30
45
10
15
30
45
4000
10
15
30
45
10
15
30
45
10
10
30
45
10
15
30
45
Rated power Sn [VA]
Isn
Plug-in current transformers with a primary current of 400 A to 4000 A, for rails
Description
Type
PACT MCR-V2-12040-159-4000-5A-1
Selection table
Primary rated current strength Ipn
Isn
Cl.
400
2.5
5
500
2.5
5
600
2.5
5
750
2.5
5
800
2.5
5
1000
2.5
5
10
1250
5
10
15
1500
5
10
15
1600
5
10
15
2000
5
10
15
2500
5
10
15
3000
5
10
15
4000
10
15
30
2.5
5
10
5
10
15
5
10
15
2.5
5
2.5
5
10
5
10
15
5
10
15
5
10
15
5
10
15
5
10
15
5
10
15
10
15
30
10
15
30
2.5
5
2.5
5
2.5
5
2.5
5
10
2.5
5
10
5
10
15
5
10
15
10
15
30
5
10
15
5
10
15
5
10
15
10
15
30
10
15
30
2.5
5
10
5
10
15
5
10
15
5
10
15
5
10
15
5
10
15
5
10
15
10
15
30
5
10
15
5
10
15
5
10
30
10
15
30
10
15
30
0.5
1
0.5
Rated power Sn [VA]
1A
5A
1
103359_en_03
PHOENIX CONTACT
14
PACT Analog
Winding current transformers with a primary current of 1 A to 40 A
Description
Type
Order No.
Pcs. /
Pkt.
Winding current transformer with a primary current of 1 A to 40 A
PACT MCR-V3-60-...
2277417
1
Selection table
Primary rated current strength Ipn
Isn
Cl.
1
2.5
5
2
2.5
5
2.5
2.5
5
4
2.5
5
5
2.5
5
6
2.5
5
7.5
2.5
5
10
2.5
5
12.5
2.5
5
15
2.5
5
20
2.5
5
25
2.5
5
30
2.5
5
40
2.5
5
2.5
5
2.5
5
2.5
5
2.5
5
2.5
5
2.5
5
2.5
5
2.5
5
2.5
5
2.5
5
2.5
5
2.5
5
2.5
5
2.5
5
2.5
5
2.5
5
2.5
5
2.5
5
2.5
5
2.5
5
2.5
5
2.5
5
2.5
5
2.5
5
2.5
5
2.5
5
2.5
5
2.5
5
2.5
5
2.5
5
2.5
5
2.5
5
2.5
5
2.5
5
2.5
5
2.5
5
2.5
5
2.5
5
2.5
5
2.5
5
2.5
5
2.5
5
0.5
1
0.5
Rated power Sn [VA]
1A
5A
1
103359_en_03
PHOENIX CONTACT
15
PACT Analog
3.2
Current transformers that can be calibrated
Bus-bar current transformers with a primary current of 150 A to 500 A, for circular conductors
Description
Type
Order No.
Pcs. /
Pkt.
Bus-bar current transformer with a primary current of 150 A to 500 A,
for circular conductors
PACT MCR-V1C-21-44-...
2277420
1
Selection table
Primary rated current strength Ipn
Isn
Cl.
150
200
250
300
400
2.5
500
2.5
5
2.5
5
2.5
5
2.5
5
Rated power Sn [VA]
0.2 S
0.2
5A
2.5
2.5
5
2.5
5
10
2.5
5
2.5
5
10
2.5
5
2.5
5
2.5
5
10
2.5
5
2.5
5
10
0.5 S
2.5
0.5
Plug-in current transformers with a primary current of 200 A to 750 A, for rails and circular conductors
Description
Type
Order No.
Pcs. /
Pkt.
Plug-in current transformer with a primary current of 200 A to 750 A, for rails
and circular conductors
PACT MCR-V2C-3015-60-...
2277433
1
Selection table
Isn
Cl.
200
250
300
400
500
600
2.5
5
10
750
2.5
5
10
2.5
2.5
5
2.5
5
10
2.5
5
10
2.5
5
10
15
2.5
5
10
15
0.2
0.2 S
Rated power Sn [VA]
Primary rated current strength Ipn
5A
2.5
2.5
5
2.5
5
10
2.5
5
10
2.5
5
10
2.5
5
2.5
5
2.5
5
10
2.5
5
10
2.5
5
10
0.5
2.5
0.5 S
103359_en_03
PHOENIX CONTACT
16
PACT Analog
Plug-in current transformers with a primary current of 200 A to 1000 A, for rails and circular conductors
Description
Type
Order No.
Pcs. /
Pkt.
Plug-in current transformer with a primary current of 200 A to 1000 A, for rails
and circular conductors
PACT MCR-V2C-4012-70-...
2277446
1
Selection table
Isn
Cl.
200
250
300
400
500
600
2.5
5
750
2.5
5
10
800
2.5
5
10
1000
5
10
2.5
5
2.5
5
10
2.5
5
10
5
10
2.5
5
10
5
10
0.2 S
0.2
Rated power Sn [VA]
Primary rated current strength Ipn
5A
2.5
2.5
5
2.5
5
10
2.5
5
10
5
10
5
10
2.5
5
10
5
10
2.5
5
2.5
5
2.5
5
10
2.5
5
10
5
10
5
10
2.5
5
10
5
10
0.5 S
2.5
0.5
Plug-in current transformers with a primary current of 200 A to 1200 A, for rails and circular conductors
Description
Type
Order No.
Pcs. /
Pkt.
Plug-in current transformer with a primary current of 200 A to 1200 A, for rails
and circular conductors
PACT MCR-VC2-5012-85-...
2277459
1
Selection table
Primary rated current strength Ipn
Cl.
200
250
300
400
500
600
2.5
5
700
2.5
5
10
800
2.5
5
10
2.5
2.5
5
2.5
5
10
2.5
5
10
2.5
5
10
0.2 S
0.2
5A
2.5
2.5
5
2.5
5
2.5
5
10
2.5
5
10
5
10
5
10
5
10
2.5
2.5
5
2.5
5
2.5
5
10
2.5
5
10
5
10
5
10
5
10
0.5 S
0.5
103359_en_03
1000
5
10
15
30
5
10
15
30
5
10
15
30
5
10
15
30
1200
5
10
15
30
5
10
15
30
5
10
15
30
5
10
15
30
Rated power Sn [VA]
Isn
PHOENIX CONTACT
17
PACT Analog
Plug-in current transformers with a primary current of 250 A to 1200 A, for rails and circular conductors
Description
Type
Order No.
Pcs. /
Pkt.
Plug-in current transformer with a primary current of 250 A to 1200 A, for rails
and circular conductors
PACT MCR-V2C-6015-85-...
2277462
1
Selection table
Isn
Cl.
200
250
300
400
500
600
750
2.5
5
800
2.5
5
1000
2.5
5
10
1200
2.5
5
10
2.5
2.5
5
2.5
5
2.5
5
10
2.5
5
10
15
2.5
5
10
15
2.5
5
10
15
2.5
5
10
15
2.5
5
10
15
0.2 S
0.2
5A
2.5
2.5
5
2.5
5
2.5
5
10
2.5
5
10
2.5
2.5
5
2.5
5
2.5
5
10
2.5
5
10
0.5 S
2.5
2.5
0.5
Rated power Sn [VA]
Primary rated current strength Ipn
Plug-in current transformers with a primary current of 200 A to 1500 A, for rails and circular conductors
Description
Type
Order No.
Pcs. /
Pkt.
Plug-in current transformer with a primary current of 200 A to 1500 A, for rails
and circular conductors
PACT MCR-V2C-6015-95-...
2277475
1
Selection table
Primary rated current strength Ipn
Cl.
200
250
300
400
500
600
750
800
1000
2.5
5
15
2.5
5
2.5
5
2.5
5
10
2.5
2.5
5
2.5
5
10
2.5
5
10
2.5
5
2.5
5
10
15
2.5
5
10
15
2.5
5
10
15
2.5
5
10
15
5
10
10
15
5
10
15
20
2.5
5
10
15
5
10
15
20
5
10
15
30
5
10
15
20
5
10
15
20
5
10
15
30
0.2 S
0.2
5A
0.5 S
2.5
0.5
103359_en_03
2.5
5
1200
5
10
15
20
5
10
15
20
5
10
15
20
5
10
15
20
1250
5
10
15
20
5
10
15
20
5
10
15
30
5
10
15
30
1500
5
10
15
30
5
10
15
30
5
10
15
30
5
10
15
30
Rated power Sn [VA]
Isn
PHOENIX CONTACT
18
PACT Analog
Plug-in current transformers with a primary current of 500 A to 1500 A, for rails and circular conductors
Description
Type
Order No.
Pcs. /
Pkt.
Plug-in current transformer with a primary current of 500 A to 1500 A, for rails
and circular conductors
PACT MCR-V2C-6040-96-...
2277488
1
Selection table
Primary rated current strength Ipn
Cl.
500
600
750
800
1000
1200
2.5
5
2.5
5
2.5
5
2.5
5
2.5
5
10
2.5
5
10
15
2.5
5
10
15
0.2 S
0.2
5A
2.5
2.5
5
2.5
5
2.5
5
10
2.5
5
10
2.5
5
2.5
5
2.5
5
10
2.5
5
10
2.5
5
10
0.5 S
0.5
1250
2.5
5
10
15
2.5
5
10
15
2.5
5
10
15
2.5
5
10
15
1500
2.5
5
2.5
5
Rated power Sn [VA]
Isn
2.5
5
10
2.5
5
10
Plug-in current transformers with a primary current of 400 A to 1500 A, for rails and circular conductors
Description
Type
Order No.
Pcs. /
Pkt.
Plug-in current transformer with a primary current of 400 A to 1500 A, for rails
and circular conductors
PACT MCR-V2C-8015-105-...
2277491
1
Selection table
Primary rated current strength Ipn
Isn
Cl.
400
500
600
750
800
1000
1200
1250
1500
2.5
5
2.5
5
2.5
5
10
2.5
5
10
2.5
5
10
2.5
5
10
2.5
5
10
15
2.5
5
10
15
2.5
5
10
15
5
10
15
20
5
10
15
20
2.5
5
10
2.5
5
10
2.5
5
10
2.5
5
10
2.5
5
10
15
2.5
5
10
15
2.5
5
10
15
0.2
5A
2.5
2.5
2.5
5
2.5
5
10
2.5
5
2.5
5
2.5
5
10
2.5
5
10
15
0.5 S
0.5
103359_en_03
Rated power Sn [VA]
0.2 S
PHOENIX CONTACT
19
PACT Analog
Plug-in current transformers with a primary current of 400 A to 1500 A, for rails and circular conductors
Description
Type
Order No.
Pcs. /
Pkt.
Plug-in current transformer with a primary current of 400 A to 1500 A, for rails
and circular conductors
PACT MCR-V2C-8020-105-...
2277501
1
Selection table
Primary rated current strength Ipn
Isn
Cl.
400
500
600
750
800
1000
1200
1250
2.5
5
1500
2.5
5
2.5
2.5
2.5
2.5
5
2.5
5
10
2.5
5
10
2.5
5
10
2.5
2.5
5
2.5
5
2.5
5
10
2.5
5
10
2.5
5
10
2.5
5
10
2.5
5
10
2.5
5
2.5
5
2.5
5
2.5
5
10
2.5
5
10
2.5
5
10
2.5
5
10
2.5
5
10
0.2
Rated power Sn [VA]
0.2 S
5A
0.5 S
2.5
5
0.5
Plug-in current transformers with a primary current of 500 A to 2500 A, for rails and circular conductors
Description
Type
Order No.
Pcs. /
Pkt.
Plug-in current transformer with a primary current of 500 A to 2500 A, for rails
and circular conductors
PACT MCR-V2C-10020-129-...
2277514
1
Selection table
Isn
Cl.
500
600
750
800
1000
1200
1250
1500
2.5
5
1600
2.5
5
200
2.5
5
2500
2.5
5
10
2.5
5
10
2.5
5
10
2.5
5
10
15
2.5
5
10
15
2.5
5
10
15
2.5
5
10
15
2.5
5
10
15
2.5
5
10
15
2.5
5
10
15
2.5
5
10
15
2.5
5
10
15
2.5
5
10
15
2.5
5
10
15
2.5
5
10
15
2.5
5
10
15
2.5
5
10
15
2.5
5
10
15
2.5
5
10
15
2.5
5
10
15
0.2 S
0.2
5A
2.5
5
2.5
5
2.5
5
2.5
5
10
2.5
5
10
2.5
5
2.5
5
2.5
5
10
2.5
5
10
15
2.5
5
10
15
0.5 S
0.2
103359_en_03
Rated power Sn [VA]
Primary rated current strength Ipn
PHOENIX CONTACT
20
PACT Analog
Plug-in current transformers with a primary current of 500 A to 2500 A, for rails and circular conductors
Description
Type
Order No.
Pcs. /
Pkt.
Plug-in current transformer with a primary current of 500 A to 2500 A, for rails
and circular conductors
PACT MCR-V2C-10036-129-...
2277527
1
Type
Order No.
Pcs. /
Pkt.
Outside diameter 42 mm, inside diameter 12 mm
(for MCR-V2-5012-85-...)
PACT MCR-CB-42-12
2277530
1
Outside diameter 28 mm, inside diameter 12 mm
(for MCR-V2-3015-60-...)
PACT MCR-CB-28-12
2277543
1
Outside diameter 21 mm, inside diameter 12 mm
(for MCR-V1-21-44-...)
PACT MCR-CB-21-12
2277556
1
Outside diameter 21 mm, inside diameter 8 mm
(for MCR-V1-21-44-...)
PACT MCR-CB-21-8
2277569
1
Snap-on mounting for DIN rails
PACT MCR-RA
2277598
9
Secondary terminal cover to increase air and creepage distances when
installed horizontally, length of 60 mm
PACT MCR-ETC-60
2277572
9
Secondary terminal cover to increase air and creepage distances when
installed horizontally, length of 70 mm
PACT MCR-ETC-75
2277585
9
Protective caps for the primary rail mounting screws (for protection against
accidental contact)
PACT MCR-ICAP
2277608
9
Selection table
Isn
Cl.
500
600
750
800
1000
1200
1250
1500
2.5
5
1600
2000
2.5
5
2500
2.5
5
10
2.5
5
10
2.5
5
10
2.5
5
10
2.5
5
10
15
2.5
5
10
15
2.5
5
10
15
2.5
5
10
15
2.5
5
10
15
2.5
5
10
15
2.5
5
10
15
2.5
5
10
15
2.5
5
10
15
2.5
5
10
15
2.5
5
10
15
2.5
5
10
15
2.5
5
10
15
2.5
5
10
15
0.2 S
0.2
5A
2.5
2.5
2.5
5
2.5
5
10
2.5
5
10
2.5
5
10
2.5
5
10
2.5
5
10
0.5 S
2.5
5
2.5
5
0.5
3.3
Rated power Sn [VA]
Primary rated current strength Ipn
Standard accessories, supplied as standard
Description
Attachment of the current transformer to the copper rail using the primary rail support (with 2 screws and 2 nuts)
Secondary terminal cover (2 green slides for covering the secondary terminals)
Plug-in feet which can be inserted into the side for attaching the current transformer to the mounting plate
3.4
Optional accessories
Description
Copper sleeves for horizontal installation as a connecting piece, e.g., from the
power rail to the fuse holder
103359_en_03
PHOENIX CONTACT
21
PACT Analog
4
Technical data
General data
Rated frequency
Transformers that cannot be calibrated
50 Hz to 60 Hz
Transformers that can be calibrated
50 Hz
Class of insulation
E
Thermal rated short-time current Ith
60 x IN
Rated surge current Idyn
2.5 x Ith
Rated insulation voltage according to EN 50178
1 kV
Impulse withstand voltage
12 kV (1.2/50 µs)
Surge voltage category
III
Rated power
Depends on type, 1.25 VA to 45 VA
Primary rated current Ipn
Depends on type, 1 A to 4000 A
Secondary rated current Isn
Depends on type, 1 A or 5 A
Accuracy
Depends on type, class 0.2; 0.2 S; 0.5; 0.5 S or 1
Surge current limitation factor
FS 5 or FS 10
Housing material
Polyamide PA glass fiber reinforced, black
Connection data
Connection capacity of the secondary terminals
2 x (2.5 x 4) mm
Ambient conditions
Ambient temperature (operation/storage/transport)
-25°C to +40°C
Permissible humidity
Use only indoors; no condensation
Conformance/approvals
Conformance
EN 50178
Standard
IEC 60044-1
103359_en_03
PHOENIX CONTACT
22
PACT Analog
5
Safety notes
WARNING: Danger due to damaged current transformers
•
Before startup, check that the housing of the current transformer is not damaged.
•
Also before startup, check that there are no electrically conductive connections between the primary
conductor and the secondary terminals.
•
If a built-in current transformer is removed in order to be used in a different system, check the current
transformer for damage again.
WARNING: Danger due to voltage at open circuit
The output of the current transformer is a constant current source. In the event of an increasing load, the output
voltage thus increases and reaches its maximum at infinite load (i.e., with open secondary terminals).
•
Avoid open-circuit operation at all costs.
•
Note that unloaded transformers must be short circuited.
•
Only start up the current transformer once the secondary cables are connected on both sides.
NOTE: Avoid material damage when grounding
In accordance with VDE 0414, current transformers and voltage transducers must be secondary grounded from a
series voltage of 3.6 kV. At low voltages there is no need for grounding, provided the transformers do not have any
large metal surfaces within reach.
•
Ground the current transformers at the k terminal block.
NOTE: Avoid damage due to improper mounting
Vibrations can cause the screws on the primary rail to loosen.
•
During mounting, tighten the screws on the primary rail support so that they cannot loosen as a result of
vibrations.
Condensation can cause short circuits on the screws of the primary rail.
•
Only start up the current transformer inside, where there is no condensation.
103359_en_03
PHOENIX CONTACT
23
PACT Analog
6
Selecting the optimum transformer
Once the technical specifications for the current
transformers required by the application have been defined,
the next step is to determine the transformer types.
The four main current transformer characteristics are:
1. Primary rated current (primary current Ipn)
2. Secondary rated current (secondary current Isn)
3. Capacity (power) in VA
4. Accuracy (class)
Power requirement of copper cables with a different
diameter
Cable cross
Power in VA
section in mm2 (consider the supply and return line)
at 5 A
at 1 A
1.5
0.2917
0.117
2.5
0.175
0.0070
4
0.1094
0.0044
6
0.0729
0.0029
The current transformer is selected first and foremost based
on the primary rated current Ipn, which can be up to 4000 A
(depending on the type) and the secondary rated current Isn.
This is either 1 A AC or 5 A AC at the output.
Isn at 5 A AC:
The accuracy (class) can be another important criterion for
selecting the correct current transformer if certain
specifications have to be met.
Isn at 1 A AC:
Special attention, however, should be paid to the calculation
of the rated power (in VA). Here it is important to take into
consideration all occurring loads of the measuring circuit for
optimum selection of the rated power of the current
transformer (see below).
7
Phoenix Contact offers an extensive range of current
transformer types. This means that several different types
may meet the prescribed technical criteria. The main
differences lie in the size and shape of the transformer
opening and in the external dimensions of the transformer
housing. This allows you to select an optimum current
transformer based on the size of the copper rail and the
space available in the control cabinet.
How do you choose the optimum current transformer?
Firstly, add together all occurring loads:
– Calculate the power requirement of the copper cable
(info: cable length x 2)
– Take into account the power requirement of the
connected devices
– Add the reserve requirement
P = 10 m x 2 x 0.175 VA P = 3.50 VA
P = 10 m x 2 x 0.007 VA P = 0.14 VA
Installation and connection
Current transformers from Phoenix Contact can be
positioned anywhere.
Thanks to the primary rail support of the PACT Analog
current transformer which can be pulled out, no edges
protrude from the housing. Instead all edges are flush. This
is the basic prerequisite for the parallel attachment and
positioning of the current transformers on the copper rail,
which thus enables currents and loads supplied via an
electric branch to be measured. To this end, a copper
sleeve (accessory) is inserted into the internal opening of
the current transformer, which creates a conductive
connection between the current-carrying copper rail and,
e.g., the securing lug of a downstream fuse. To increase the
air and creepage distances, an extended secondary
terminal cover (accessory) is placed over the connections of
the secondary terminals of the horizontal current
transformer.
The optimum current transformer is one which can
accommodate a maximum of 1.5 times the total load.
This is because underloads affect accuracy and impair the
overcurrent limiting protection, which protects the
secondary circuit from being damaged by excessive
currents.
103359_en_03
PHOENIX CONTACT
24
PACT Analog
7.1
Installing a current transformer
The current transformers can be installed in the following mounting positions:
1.
B
C
Vertically on the copper rail
In most applications, the current transformer is fitted directly
onto the copper rail.
• Slide the current transformer over the copper rail.
• Slide the primary rail support through the inner hole of
the current transformer (A).
• Insert the two screws on the left and right of the
transformer into the holes of the primary rail support until
they reach the copper rail and the pressure is such that
the current transformer is fixed in place (B).
• Attach the protective caps for protection against
accidental contact to the screw heads (C).
A
103359A003
2.
Vertically on the mounting plate
Two plug-in feet are included as standard accessories (see
page 21).
• Insert the plug-in feet underneath the transformer on the
right and the left (A).
• Place the current transformer on the mounting plate (B).
• Insert the screws through the openings of the plug-in feet
to secure the current transformer (C).
C
B
A
103359A004
103359_en_03
PHOENIX CONTACT
25
PACT Analog
3.
Vertically on the DIN rail
The current transformer can also be snapped onto the DIN
rail with the optional snap-on mounting (see page 21).
• Snap the snap-on mounting into the holes beneath the
current transformer (A).
• Snap the current transformer onto the DIN rail (B).
A
B
103359A005
4.
Horizontally on the copper rail
As a result of their flat shape, the Phoenix Contact current
transformers can also be fitted horizontally onto copper rails,
e.g., behind fuse rails.
A
This is possible with the following current transformer types:
– MCR-V2-5012-85... (see page 7)
– MCR-V2-3015-60... (see page 5)
– MCR-V1-21-44... (see page 4)
B
•
103359A006
•
103359_en_03
Insert a suitable copper sleeve (see page 21) into the
inner hole of the current transformer (A) to create a
conductive connection between the copper rail and the
fuse.
Attach the extended secondary terminal cover to the
secondary terminals (B) to increase the air and
creepage distances when the current transformer is
installed horizontally.
PHOENIX CONTACT
26
PACT Analog
7.2
Connecting a current transformer
The connections of the primary winding are designated as
"K" and "L" or "P1" and "P2". The connections of the
secondary winding are designated as "k" and "l" or "s1" and
"s2". Pole the cables so that the power flows from "K" to "L".
A
Isn
s1
k
I pn
s2
l
K
P1
L
P2
103359A002
Figure 2
Power flow direction
103359A001
Figure 1
8
Example connection with PACT MCR-V1-2144-...
Calibrating the current transformers
Calibrated current transformers are identified by a yellow
sticker:
Consecutive number
A PTB (Physikalisch-Technischen Bundesanstalt) approval
mark is also applied:
Identification of the
Calibration regulations,
measuring transducer type
appendix 20
20.21
Calibration mark of a test center
01.03
Year
Approval year
Figure 3
Example stamp of a nationally recognized test
center
Figure 4
Consecutive number
Example PTB (Physikalisch-Technischen
Bundesanstalt) approval mark
Each calibrated current transformer is provided with a corresponding calibration certificate.
The calibration process involves additional costs, which are specified in accordance with the national table of fees.
These depend on the maximum rated input current of the current transformer.
103359_en_03
PHOENIX CONTACT
27
PACT Analog
9
Safe isolation
Operating voltages by comparison
EN 60044-11
480 V (L-L)
Rated insulation voltage:
(operating voltage)
7280 V (L-L)
1000 V (L-L)
/
EN 501782
277 V (L-L)
416 V (L-L)
577 V (L-L)
1000 V (L-L)
Impulse withstand voltage for transformer testing:
3 kV
at 277 V (L-N)
6 kV
12 kV
3 kV
at 1000 V (L-N)
9.1
–
–
1
EN 60044-1: Measuring transducers - Part 1: Current transformer
2
EN 50178: Electronic equipment for use in power installations
Application example with safe isolation up to 1 kV
The current transformer converts the high current down
to 1 A AC or 5 A AC.
A downstream current transducer creates a standard
signal from the secondary current.
SELV = Safety Extra Low Voltage
Inline controller
Safe isolation
according to EN 50178
1 A AC
4 to 20 mA
5 A AC
0 to 10 V
EN 60044-1
applies only to here.
e.g.,
Ethernet
Motor
Rated insulation voltage
up to 1000 V (L-N)
Figure 5
103359_en_03
Application example
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany • Phone: + 49 5235 3-00
PHOENIX CONTACT • P.O.Box 4100 • Harrisburg • PA 17111-0100 • USA • Phone: +717-944-1300
www.phoenixcontact.com
28