https://www.phoenixcontact.com/us/products/2290009
Front adapters - FLKM 14-PA/GE/DO - 2290009
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
VARIOFACE front adapter, for GE-FANUC series 90-30, 2 x 8 channels can be connected, digital output
Your advantages
Pre-assembled system cables are connected directly to I/O modules using the front adapters
Key Commercial Data
Packing unit
1 pc
GTIN
GTIN
4017918057909
Weight per Piece (excluding packing)
59.500 g
Custom tariff number
85366990
Country of origin
Germany
Technical data
Note
Note
Do not connect adjacent channels to SELV/ PELV and voltages dangerous
to the touch.
No additional touch protection is required when using a SELV/PELV
voltage (≤ 25 V AC or 60 V DC).
At least one functional insulation against adjacent modules is complied
with (in the support rail direction). If the application has stricter
requirements for the insulation (basic insulation or reinforced insulation),
they must be realized by applying suitable measures (e. g. partition plates).
Ambient conditions
Ambient temperature (operation)
-20 °C ... 50 °C
08/29/2019 Page 1 / 4
https://www.phoenixcontact.com/us/products/2290009
Front adapters - FLKM 14-PA/GE/DO - 2290009
Technical data
Ambient conditions
Ambient temperature (storage/transport)
-20 °C ... 70 °C
Degree of protection
IP00
≥ IP54 (Installation location)
General
Max. permissible operating voltage
25 V AC
60 V DC
Max. permissible current
1 A (per path)
4 A (per connection, supply via separate power supply)
Max. permissible total current
3 A (per Byte, for supply via connector)
Mounting position
any
Assembly instructions
In rows with zero spacing
Nominal operating mode
100% operating factor
Standards and Regulations
Connection in acc. with standard
CUL
Designation
Air clearances and creepage distances
Standards/regulations
DIN EN 50178
Rated insulation voltage
63 V
Rated surge voltage
0.6 kV
Insulation
Functional insulation
Pollution degree
2
Overvoltage category
II
Connection data
Connection name
Controller level
Channels which can be connected
16
Connection data 2
Connection name
Field level
Connection method
IDC/FLK pin strip
Number of connections
2
Number of positions
14
Pitch
2.54 mm
Connection data 3
Connection method
Slip-on connection
Note
2,8 x 0,8
Supported controller
Controller
GE-FANUC 90-30
08/29/2019 Page 2 / 4
https://www.phoenixcontact.com/us/products/2290009
Front adapters - FLKM 14-PA/GE/DO - 2290009
Technical data
Supported controller
- suitable I/O card
IC693 MDL732
IC693 MDL733
IC693 MDL740
IC693 MDL741
IC693 MDL742
IC693 ALG220
IC693 ALG221
IC693 ALG222
IC693 ALG223
IC693 ALG390
IC693 ALG391
IC693 ALG392
IC693 ALG442
Environmental Product Compliance
REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category
“Manufacturer's declaration”
Classifications
eCl@ss
eCl@ss 5.1
27250300
eCl@ss 6.0
27249200
eCl@ss 7.0
27249290
eCl@ss 8.0
27249290
eCl@ss 9.0
27242292
ETIM
ETIM 4.0
EC002584
ETIM 5.0
EC002584
ETIM 6.0
EC002584
ETIM 7.0
EC002584
UNSPSC
UNSPSC 6.01
30211824
UNSPSC 7.0901
39121421
UNSPSC 11
39121421
08/29/2019 Page 3 / 4
https://www.phoenixcontact.com/us/products/2290009
Front adapters - FLKM 14-PA/GE/DO - 2290009
Classifications
UNSPSC
UNSPSC 12.01
39121421
UNSPSC 13.2
32151601
Approvals
Approvals
Approvals
cUL Recognized / EAC
Ex Approvals
Approval details
cUL Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
Nominal voltage UN
125 V
Nominal current IN
2A
EAC
FILE E 238705